You are on page 1of 13

DNIT / SCHEDULE OF QUANTITY Estimated Cost : 101250 /---

NAME OF WORK:- Replacement of old Pumping Machienery of LWSSto group pf Vill.Lamian Chourian Nawan Shahar Gheta etc.Earnest Money:- 2025 /---
Distt.Kangra H.P. Time:- 3Month
SUB HEAD:- S/E of Centrifugal pumping machinery with allied accessories
S.NO. DESCRIPTION SPECIFICATIOS QUANTITY RATE UNIT AMOUNT
(To be specified by In Figures In Words
(the tenderer)
1. Supply of horizontal spindle,horizontal/radial split casing and suction (backpull out arrangement) single/ 2 Sets of 3375 Each 101250.00
double / multistage centrifugal pumps or combination of pumps in series /parallel of KSB / Mather & Platt/ 15 HP each
Jyoti /Kirloskar /BE /Maxflow /Beaconweir make conforming to BIS: 1520-1980 (latestwith upto date a) Pump:-
ammendments) read with BIS: 9137-1978 (latest edition) suitable for lifting water of under mentioned
charactristics with impellers of bronze/suitable alloy, priming funnels,casing ring & shaft sleeves of bron b) Motor
suitable alloy, shaft of sutable steel grade with cast iron casing coupled directly through a flexible coupling
on a common C.I. / Cast steel base plate (base plate to be from the principle manufacturer of pumping sec) Coupling
to slippering/squirrel cage screen protected drip proof electric induction motor of Kirlokar / NGEF /
Crompton / Siemen /Jyoti /BHEL /GEC /ABB conforming to BIS: 325-1978 read read with BIS: 900-1968d) Base plate
(latest with upto date ammendments) It should include the cost of bearings, nuts & bolts,painting etc. and
shall be suitable for operation as per data given below.
i) Location of site The Site is located at a distance of _10___ KMs from
_____ Railway station by road and ___ KM by head load
ii) The altitude of place in which Altitude of place is _450_ m above MSL
pumping set is intended to work
iii) Type of current AC three phase with frequency of 50cycles/second
iv) Rated Voltage 415V ± 10%
v) Type of water (Raw/Treated) _______
vi) Charactrstics of water a) Temperature __ °C e) Total solids __ mg/litre
b) Turbidity __ NTU f) Others ____
c) pH ____
d) Hardness __ Mg/Litre(as CaCO3)
vii) Depth of Tank/ P.well _10_ mts.
viii) L.W.L in Tank/sump well __mts.
ix) Centre line Level of Pump __ mts.
x) Suction head _4.5_ mts.
xi) Discharge Level of highest point __mts.
xii) Nos of pumps reqd. _2_ Nos. pumps
xiii) Capacity 3.52 lps for each pump
xiv) Static Head in meters 110.90__ mts.
xv) Total head in Mts. 148.37_mts
xvi) Length of R/Main __mts
xvii) Dia of R/Main 80_ mm
xviii) Pumping hours per day _8_ hours
xix) Limits of pump operation (-) 25% to (+) 10% of Total head at duty point
xx) HP of motor /Drive unit Required BHP of pump at (+) 10% & (-) 25% of total head or BHP
with following margins/multiplying factor at duty point, whichever is higher
a) Upto 2 HP = 1.5 d) 10 to 20 HP = 1.2
b) 2 to 5 HP = 1.4 e) 20 to100 HP = 1.15
c) 5 to 10 HP = 1.3 f) Above 100 HP=1.10
xxi) R.P.M.of Pump (2900/1450rpm) _2900__r.p.m.
xxii) Test Run 16 hours continueously for 7 days
xxiii) NPSH available _3.20__mts.
2 Supply of suitable oil immersed star delta /auto tranformer /stator rotor starter of standard make such as MEI/ __ Nos Each
Kilburn/Jyoti/L&T/S&S conforming to BIS:8544-1979 latest with up to date ammendments for squirrel cage/
slippering motor (make to be specified by the tenderers) mounted on panel board with magnetic type over load
release & dashpot,time lag,under voltage release with initial oil filling .
Note:- Star delta starter upto 37.5 KW, Auto Transformer Stareter between 37.5 KW to 75 KW and Stator Rotor Starter with slippering motor.
3 Providing M S sheet 16 SWG steel fabricated floor mounted closed almirah type switch board __ No. Each
including angale iron post of suitable height and size ISA 65x65x6mm duly painted comprising and
capable of mounting the following accessaries with all internal electric connections.
Note:- The drawing of panel board shall be subject to approval of Engineer in charge.
a) Ammeter AC supply,100 mm circular/square dial Auto electric/AE/IMP/Havells make of suitable range for __ Nos. Each
above motor with selector switches conforming to BIS: 1248-1983 latest with up to date ammendments.
b) Voltmeter AC supply,100 mm circular/square dial Auto electric/AE/IMP/Havells make of suitable range for __ No. Each
above motor with selector switches conforming to BIS: 8044-1978 with up to date ammendments.
c) ICTP switches with HRC fuses Kilburn/L&T/Standard/Siemen's/Havell's make and having capacity 30% __ Nos. Each
extra of the operational rating of motor as per BIS: 4064-1978 with upto date ammendments immediatly
after the power meter of HPSEB.
d) Busbar chamber having 3 copper bars of suitable rating for full length of 3 live phases and one copper bar __ No. Each
of half rating of full length for neutral conforming to BIS: 8084-1976 and BIS;11353-1985 read with
BIS;5578-1985 all latest with upto date ammendments.
e) MCB/OCB of suitable capacity of Kilburn/L&T/MEI/Standard/GEC make on in comming __ No. Each
feeder for motors offered by the tenderer conforming to BIS: 2516-1985 latest with upto date
ammendments with neutral linked under voltage release.
f) Three phase indicating lamps complete with toggle switches for individual motors conforming to BIS: 3452 __ Sets Each
( part I & II) latest with up to date ammendments.
g) Earth leakage circuit breaker (ELCB) of Standard/ Havell's make as per BIS: 2516-1977 with upto date __ No. Each
ammendments and of suitaible range with which should have control box, operating handel and trip/reset
bush button, on/ off indicators, re-indicating off spring condition of the circuit breaker for over current
protection. The circuit should be equipped with magnetic thermal release with metallic tape CTs.It should
also be fitted with earth fault for tripping of breaker on occurance of earth fault on/off breaker load side.
h) Hour run meter of approved make of four digit capacity conforming to BIS: 722 (latest edition) __ Nos. Each
i) Change over Switch of reputed make & suitable capacity conforming to relevant BIS code __ No. Each
j) Single phase preventor of reputed make & suitable capacity conforming to relevant BIS code __ No. Each
4 (a) Providing C.I. / Cast steel double flanged sluice valve of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/ __ Nos. Each
Leader make of size___mm & class____ having one size higher to delivery size of pump and capable of
with standing nominal seat pressure of ____ kg/cm^2
NOTE:-The C.I. sluice valve shall conform to BIS:780-1984 for 50 to 300mm dia & BIS:2906-1984 for 350 to 1200mm dia ( latest
edition). However if seat pressure exceeds the limits prescribed in above mentioned BIS, then it shall be of cast steel conforming to
class ASA-150 for seat pressure upto 21 Kg/cm² or class ASA-300 for seat pressure 52 Kg/cm² as per BS 1414 (API 600) .
(b) Supply of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader make C.I/ Cast steel double flanged __ Nos. Each
swing check type reflux valve having bye pass arrangement and one size higher to delivery size of pump
( size___mm & class ____ ) and shall be suitable for withstanding nominal seat pressure of ____ kg/cm^2
(c) Supply of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader make C.I/ Cast steel double flanged __ Nos. Each
swing check type reflux valve having bye pass arrangement and of size equal to dia of Rising main
i.e ___ mm & of class_____ and shall be suitable for withstanding nominal seat pressure of ____ kg/cm^2
NOTE:- The C.I. reflux valve shall conform to BIS: 5312-1984- Part-I ( latest edition). However if the seat pressure exceeds the
limits prescribed in BIS 5312 then it shall be of cast steel conforming to class ASA-150 for seat pressure upto 21 Kg/cm² or
class ASA-300 for seat pressure 52 Kg/cm² as per BS 1868 (API 600) .
(d) Supply of Kirloskar/Jyoti/Standard/KilburnKartar make cast iron double flanged sluice valve or foot valve on
suction side of pump having size one step higher than the suction size of pump
NOTE:-TheC.I. sluice valve shall conform to BIS: 780-1984 & the foot valve shall conform to BIS 4838-1986 (latest edition) .
5 (a) Providing & laying PVC insulated armoured power copper cable of Siemens/Finolex/Grandlay/
Gloster make conforming to BIS:1554 (Part I) -1988 or latest with up to date ammendments of suitable
size for the pump sets offered(one cable carrying all three phases) including all other electrical equipment
/accessories such as thimbles,flexible pipe, solder, nuts & bolts cable glands etc. laid in pipes or
trenches under floor .The type,size & make will be subject to approval of HPSEB authorities.In case
of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
a) On supply side of 3½ core( From HPSEB Meter to Switch &Starter) = __mts of Size _____ mm². __ mts. Per Metre
b) On motor side 3 core ( From Switch & Starter to Motor) = __ mts. of Size _____ mm². __ mts. Per Metre

(b) Providing & laying double loop earthing with copper plate 600x600x3mm thick electrode complete with material __ Job L.S.
such as charcoal, common salt ,GI pipes,thimbles,nuts & bolts,digging of pits,GI wiring & copper strips of suitable
size conforming to BIS:3043-1978 (latest edition) for above motors & other electrical equipments.
NOTE:-The strip size shall be 20x3 upto 18.5 KW, 25x3 for 18.5 to 37 KW, 25x5 for 37 to 55 KW & 32x5 beyond 55 KW.
(c) Supply & errection of floor/wall mounted power factor shunt capacitor conforming to BIS 2834-1986 __ Nos. Each
latest with upto date ammendments of BHEL/GEC/Machneil/ Mager/Bajaj make to raise the prevailing
power factor at site to 0.95 for direct connection to induction motor individually,of required KVAR
according to HP of motor offered including cable of Siemens/Gloster/ICC make from busbar chamber
chamber to capacitor & also including ICTP switches Kilburn/L&T/Standard/Siemen's/Havell's of conforming to
4064-1978 or latest with HRC fuses (Range to be specified by the tenderer.)
6(a) Supply of 100mm dia circular/square dial pressure gaugeof suitable rangeof Fiebeg/Bourden/ Precision/PREGA __ Nos. Each
make with all accessories such as stop cock,copper tubing etc. conforming to BIS:3624-1987 latest
with up to date ammendments.
(b) Supply of 100mm dia circular/square dial vacuum gauge of suitable range of Fiebeg//Bourden/ Precision/PREGA __ Nos. Each
make with all accessories such as stop cock,copper tubing etc. conforming to BIS: 3624-1987 latest
with up to date ammendments.
7 Prov. & laying MSERW pipes conforming to BIS; 1978-82 of suitable size for suction,delivery and common
header considering site requirements & NPSH required / available.The pipe sizes for suction & delivery shall as
per the requirement of offered pump and common header shall be equal to dia of R/main including cost of tapers,
flanges (conforming to relevant table of BIS:6392-1971), bends, rubber gaskets,3mm thick nuts & bolts and
specials up to 5 mtrs.away from the outer wall of pump house as per layout drawing approved by Engineer-in-
Charg. Pipe & material shall be capable of withstanding field test pressure equal to 1.5 times the operating pressure
The complete arrangement shall comprise of ; a) Suction pipe _____mm dia __ mm thick ( to be mentioned by tenederer) __ mts. Per Metre
b) Delivery pipe _____mm dia __mm thick ( -----do--- ) __ mts. Per Metre
c) Common header _____mm dia __mm thick __ mts. Per Metre
8 Errection of all equipments from S.No. 1 to 4, & 6 i/c cost of tees,bends tapers & any other fittings __ Job L.S.
required as per site conditions & as per directions of Engineer-in-Charge
TOTAL AMOUNT Rs. 101250.00

Terms & Conditions:


1 Pumping machinery and all other equipments or allied accessories shall be guaranteed for 12 months from the date of
commissioning.
2 All the equipments or accessories to be supplied shall be of of suitable capacity /rating and shall be only of the make as
specified in NIT . Nothing extra shall be paid for any change in capacity / rating of the equipments offered if the
same does not fulfil the requirements as per NIT
3 Original Charachstric curve /selection chart of the offered pumpset duly marked with discharge, total head, efficiency,
BHP and NPSH required at duty point and (-) 25% & (+)10% of total head , must accompany with the tender, otherwise the
same will be summarily rejected. The Ch. curve shall be legible and must be signed by the tendering contractor/firms
4 In case the efficiency of the offered pump is less than 60%, the offer of the contractor shall be rejected straightway
5 The respective class & sizes of refluxe valves/sluice valves (for delivery & suction side) shall be mentioned clearly and shall
carry a guarantee of minimum two years. The make of valve shall be either engraved or cast inside the body of the valve.

Executive Engineer,
I&PH Division Nurpur.
SUB HEAD: - SUPPLY & ERRECTION OF CENTRIFUGAL PUMPING MACHINARY WITH ALLIED ACCESSORIES Stage -2nd. )
===== ======================================================================= ======== ========= =========================== =========

S.NO. DESCRIPTION RATE QTY UNIT


In Figure In words
===== ======================================================================= ======== ========= =========================== =========

1. Supply of horizontal spindle,horizontal split casing Single/Multistage centrifugal pumps of


standarad make such as KSB/Mather & Platt/Jyoti/Kirloskar conforming to BIS 1520-1980 (latest 2 2625.00 ( Rupees Two Thousand Each
with upto date ammendments) read with BIS 9137-1978 or latest to handle Raw water having sets of 25 HP Six Hundred & Twenty
turbidity 500 ppm. with impelleres,casing ring & shaft sleeves of bronze, shaft of steel with cast each Five Only
iron casing of suitable capacity coupled directly through a flexible coupling on a common base
plate to Kirlokar/NGEF/Crompton/ Siemen/Jyoti/ABB, squirrel cage screen protected drip proof
induction electric motor suitable for operation on the data given below.

A) SITE CONDITIONS
=======================================================================
i) Location of Site Site is located at 80 KM from Pathankot by Road
& 200 Meters by head load
ii) The altitude of place in which 600 Mts above MSL
the motor is intended to work
in ordinary service if it exceeds
1000 mt.

iii) Humidity Weather generally remains humid during


monsoon season.
iv) Nature of atmosphere As normally encounterd in Shivalik Range

v) Detail of quality of water Rawr water of Manjhi Khad

vi) Water free from sand or not Not

vii) Water corosive or not Not

viii) Turbidity (if any) 500 PPM

ix) NPSH available Positive suction


x) Any other information or requirement

B) OPERATING CONDITIONS
=======================================================================

i) Type of current AC three/single phase

ii) Operating frequency 50 HZ

iii) Rated voltage 400 (+/-) 10% volts

iv) System of earthing if any to Double loop earthing as per BIS 3043-1987
to be adopted. latest with upto date ammendments

v) No. of working hours per day 16 hours

vi) Speed of revolution in RPM To be quoted by tenderer

vii) Direction of rotation To be quoted by tenderer

viii) The max. Temp. of cooling air 35 degree Centigrade


& water in the place in which
the motor is intented to work
in ordinary service.

C) MOTOR
===== ===========

i) Ref to BIS code BIS 325-1978 read with BIS 900-1992


(latest)with upto date ammendments

ii) Type of enclosure of motor SPDP(as per BIS 4691-1985 (latest)

iii) Type of duty Continuous

iv) Mechanical out put in KW Suitable for driving centrifugal pumps


required for duties specified against
pumps.To avoid overloading of motor a
margin of about 15-20% may be kept in
the rated out put of prime mover.
v) Class of insulation Class ~B~

vi) Max.permissible temp.rise of ---


motor reqd. if different from
given in B(viii) above

vii) Particulars of test reqd. & As per terms & conditions


where they are to be conducted.

viii) Particulars as to whether voltage Star delta starter


limiting device will be employed oil immersed,fully automatic to
be installed between bus bar & motor.
Shunt capacitor is also proposed to be
installed for improving the power factor
at site.
NOTE:- Star delta starter upto 37.5 KW,
ATS between 37.5 KW to 50 KW & Stator rotor
starter with slip ring motor beyond 50 KW

ix) Motor whether squirrel cage or Squirrel cage


slipring Note:- Squirrel cage upto 65HP and
slipring above 65HP
x) Details of shaft extension reqd. Just sufficient to provide direct drive
by flexible coupling to pump.

xi) Type of slip ring gear whether Continouslly rated for Squirrel cage/
continouly rated or for starting Slipring motor
purposes only & whether to be fitted
with brush lifting or short circuiting
arrangements or both if interlocks
are rquired.

xii) Breakway torque in terms of rated Breakway torque to be given by the tenderer
load torque & the corresponding but the starting current should not exceed
breakway starting current which 2.5 times of the full load current.
may be taken from the supply with
the starting apparatus in circuit.

xiii) Nature of load & any information To work the pump offered
regarding the driven machine which
has a bearing upon the torque reqd.
during the accelerated period, the
kinetic energy of the moving parts
to be accelrated & No.of starts
during a specified period.

xiv) Where possible fault capacity of The motor should be able to withstand
the system to which the motor is initial current of 2.5 times the rated
connected. current for two minutes without suffering
damages or permanent deformations.

D) PUMP (BIS 1520-1980 ) read with BIS 9137-1978 both latest with up to date ammendments
======================================================================= ========

a) Nos of pumps reqd. 2 no. pumps to work at a time independently

b) Spare parts required For Two years normal maintenance as


recommended by manufacturer.

c) Optional fittings reqd. Air cock for exahausting air from each
stage.
E) PUMP OPERATING CONDITIONS
============================

i) Capacity 12.83 lps for each pump

ii) Total head in Mts. 84.35 mts

If total head is not known then


following details be provided:-

i) Static head 77.83 mts


ii) Minimum depth of water Positive suction
iii) Variation in water level _ ___ mts
iv) Ground level to max. water level ____ mts
v) Ground level to delivery point ____ mts
vi) Pressure in the suction tank ____ Kg/cm^2
vii) Pressure in the delivery tank ....... Kg/cm^2

iii) Length of R/Main 1335 mts


iv) Dia of R/Main 250 mm

v) Drive arrangement Direct through flexible coupling on a


common base plate

vi) Drive type Electric driven

vii) NPSH reqd. To be quoted by the tenderer

viii) Limits of total head in which (-) 25% to (+) 10% of total head.
the pump is reqd. to operate.

ix) Suction/delivery size of pump To be specified by the tenderer

x) Efficiency of pump at To be specified by the tenderer


a) duty head
b) (+)10 % head
c) (-)25 % head

xi) Material of construction To be specified by the tenderer


(manufacturer~s certficate to be appended)
============

AMOUNT

============

131250.00
QUANTITY RATE UNIT AMOUNT
S.NO. DESCRIPTION
--------------- --------------------------------------- ---------------------------- -------------------------------------------------- --------------- --------------- --------------- --------------- ---------------
2 Supply of suitable oil immersed star delta starter of standarad
make such as MEI/Kilburn/Jyoti/ Siemen's conforming to
BIS-8544-1979 latest with up to date ammendments for squirrel
cage/slipriing motor (make to be specified by the tenderers) mounted on panel board with
magnetic type over load release & dashpot,time lag,under voltage release with initial 2 each
oil filling . Nos
Note:- Star - delta - starter upto 37.5 KW , ATS between 37.5 KW to 50 KW and stater rotor
starter with slipring motor beyond 50 KW.

3 Providing M S sheet 16 SWG steel fabricated floor mounted closed almirah type switch
board including angale iron post of suitable height and size ISA 40x40x6mm duly painted
comprising and capable of mounting the following accessaries with all internal 1 Each
electric connections. The drawing of panel board shall be subject to approval of No.
Engineer in charge.

a) Ammeter AC supply,100 mm circular dial Auto electric/AE/IMP/Havells make of suitable


range for above motor with selector switches conforming to BIS 1248-1983 latest with 2 Each
up to date ammendments. No.

b) Voltmeter AC supply,100 mm circular dial Auto electric/AE/IMP/Havells make of suitable 1 Each


range for above motor with selector switches conforming to BIS 4064-1978 with No.
up to date ammendments.

c) ICTP switches with HRC fuses Kilburn/Larsen & turbo/Standard/Siemen make and having 2 Each
capacity 30% extra of the operational rating of motor as per BIS 4064-1978 with upto date Sets
ammendments immediatly after the power meter of HPSEB.

d) Busbar chamber having 3 copper bars of suitable rating for full length equal to wirdth 1 Each
of board of 3 live phases and one copper bar of half reating of full length for neutral No
conforming to BIS 8084-1976 and 11353-1985 read with 5578-1985 all latest with upto
date ammendments.

e) MCB/Oil circuit breaker of suitable capacity of Kilburn/LT/LK/MEI/Standard make on in


comming feeder for motors offered by the tenderer conforming to BIS 2516-1985 latest 1 Each
with upto date ammendments with neutral linked under voltage release. No.

f) 3 phase indicating lamps complete with toggle switches for individual motors 2 Each
conforming to BIS 3452 part I & II latest with up to date ammendments. Sets

g) Earth leakage circuit breaker of requcemended (Kilburn/L&T/MET/GEC as per BIS-2516-1977 1 Each


with upto date ammendments and of suitaible range with which should have control box, No.
oprating handel and trip/reset bush button on/ off indicators, re-indicating off spring condition
of the circut breaker for over current protection. The circuit should be equipped with magnet
thermal release with metallic tap CTS. It should also be fitted earth fault for tripping of breaker
on occurance of earth fault on/ of breaker load side.

h) Hour run meter of reputed make of four digit capacity conforming to BIS-722(latest edition)/ 2 Each
recommendations. No.
I) Change over Switch of reputed make & suitable capacity Not Required Each

j) Single phase preventor of reputed make & suitable capacity 1 Each


No.
k) Suitable three phase voltage monitor relay with all protections & usual indicators with electrical 1 Each
sirens against single phasing,no voltage,high voltage & overloading & phase voltage difference No.

4 (a) Supply of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader/Bir of reputed make of suitable


size cast iron double flanged sluice valve having size equal to delivery pipe of pump
and capable of with standing nominal seat pressure of 10 kg/cm^2 2 Each
NOTE:- The sluice valve shall conform to BIS 780-1984 latest with up to date ammend- No.
-ments.However if the seat pressure exceeds the limits prescribed in BIS 780 then the
sluice valves shall be of cast steel conforming to class 150 ASA (Seat pressure
21 Kg/cm^2) or class 300 ASA (seat pressure 52 Kg/cm^2) as per BS 1414(API 600) .

(b) Supply of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader of suitable size cast iron


double flanged swing check type reflux valve having bye pass arrangement &
size equal to delivery pipe of pump for withstanding nominal seat pressure of 10 kg/cm^2 2 Each
NOTE:- The reflux valve shall conform to BIS 5312-1984 (part I)latest with up to date No.
ammendments.However if the seat pressure exceeds the limits prescribed in BIS 5312
then the reflux valves shall be of cast steel conforming to class 150 ASA (Seat
pressure 21 Kg/cm^2) or class 300ASA (seat pressure 52 Kg/cm^2) as per BS1868 (API 6D) .

(c) Supply of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader of suitable size cast iron/Cast Steel


double flanged swing check type reflux valve having bye pass arrangement & 1 Each
size equal to dia of R/main i.e 250mm for withstanding nominal seat pressure of 10 kg/cm^2 No.
NOTE:- The reflux valve shall conform to BIS 5312-1984 (part I)latest with up to date ammend-
-ments.However if the seat pressure exceeds the limits prescribed in BIS 5312 then the
reflux valves shall be of cast steel conforming to class 150 ASA (Seat pressure
21 Kg/cm^2) or class 300 ASA (seat pressure 52 Kg/cm^2) as per BS 1868(API 6D) .

(d) Supply of Kirloskar/Jyoti/Standard/Kilburn make cast iron double flanged Sluice valve 2 Each
on suction side of pump of dia equal to suction pipe conforming to BIS 780-1984 No.
or latest with up to date ammendments.

5 (a) P/L suitable size copper PVC insulated armoured power 3 1/2 core cable conforming
to BIS 1554 (Part I) -1988 or latest with up to date ammendments Siemen/Gloster/ICC
make from meter of HPSEB to MCB & from MCB to Busbar switch & starter (one cable
carrying all three phases) including all other electrical equipment/accessories such
as thimbles,flexible pipe,solder,nuts & bolts,cable glands etc. laid in pipes or 1 LS
trenches under floor .The type,size & make will be subject to approval of HPSEB Job
authorities.In case of non acceptance by HPSEB authorities it shall have to be
replaced by the tenderer free of cost..

(b) P/L suitable size copper PVC insulated armoured power three core cable conforming
to BIS 1554(part I)-1988 or latest with up to date ammendments Siemen/Gloster/ICC
make from switch to starter & starter to motor (one cable for carrying all three phases)
including all other electrical equipment /accesories such as thimbles,flexible pipes, 1 LS
solder,nuts & bolts,cable glands etc. laid in pipes or trenches under floor. Job
The type,size & make will be subject to approval of HPSEB authorities.In case of non
acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.

(c) P/L double loop earthing with copper plate 600x600x3mm thick electrode complete with
material such as charcoal, common salt ,GI pipes,thimbles,nuts & bolts,digging of pits,GI wiring 1 LS
& 25x5mm copper strips of required capacity conforming to BIS 3043-1987 latest with up to date Job
ammendments for above motors & other electrical equipment.

(d) Supply & errection of floor/wall mounted power factor shunt capacitor conforming to BIS 2834-
1986 latest with upto date ammendments BHEL/GEC/Machneil/ Mager/Bajaj make to raise the
prevailing power factor at site to 0.95 for direct connection to induction motor 2 Each
individually,of required KVAR according to HP of motor offered including cable Siemens/ No.
Gloster/ICC make from busbar chamber to capacitor & also including LT/LK/Kilburn
make ICTP switches conforming to BIS 4064-1978 or latest with HRC fuses (Range to be
specified by the tenderer.

6(a) Supply of standarad make 100mm dia circular dial pressure gauge of suitable range Fiebeg/ 2 Each
Bourden/ Precision make with all accessories such as stop cock,copper tubing etc. conforming No.
to BIS 3624-1987 latest with up to date ammendments.

(b) Supply of standarad make 100mm dia circular dial vacuum gauge of suitable range Fiebeg/ Not Required Each
Bourden/Precision make with all accessories such as stop cock,copper tubing etc. conforming
to BIS 3624-1987 latest with up to date ammendments.

7 P/L suction,delivery pipe considering site requirements,NPSH required & available


& common header having area equal to two times the area of delivery branch of pump 1 LS
including tapers,flanges,rubber gaskets,3mm thick as per BIS-2712-1978 nuts & bolts as per Job
1364-1983 & special up to 5 mtrs. away from the outer wall of pump house as per layout drawings
approved by Engineer-in-Charge The pipes shall be capable of withstanding 1.5 times the
total presure indicated in item no. 1e(ii).
NOTE:- Actual laying to be done as per final drawings to be approved by the Engineer in charge

8 Supply of antivibration pads conforming to BIS 6337-1971 or latest with upto date 2 Each
ammendmentsof suitable size for above machinery. Sets

9 Supply & fixing of 4 mm thick rubber matting for floor Job LS

10 Errection of all equipments from S.No. 1 to 4, 6 & 8 i/c cost of tees,bends 1 LS


tapers & any other fittings required as per site conditions & as per directions of Job
Engineer-in-Charge.

TOTAL 131250.00