You are on page 1of 11

NAME OF WORK:- C/O 08 Nos.

T/WELLS IN INDORA AREA (C/O OF T/WELL AT BARI KANDORI)

NOTE:- ( * )INDICATES DATA TO BE FILLED SUBMERSIBLE PUMP


DATA FOR ECONOMICAL DIA. STATEMENT DESIGN OF PUMPING MACHINERY

*1 Peak Daily Water Requirement for 24 hrs. 17.29 LPS 1 Peak Daily Water Requirement 17.29 LPS 13 Losses in Column pipe:-

*2 Maximum Daily Pumping Hours 16.00 HRS. 2 Maximum Daily Pumping Hours 16.00 HRS. a)Losses in Column Pipe 2.78 MTS.

*3 Length of Rising Main 320 MTS. 3 Peak Daily Design Water Requirement 25.935 LPS b)Losses in Reflux Valve,Sluice Valve,

*4 Highest Point of Discharge 103.00 MTS. 4 Length of Rising Main 320 MTS. Bend & Exit (2.3+0.2+2.2+1.0)v^2/2G 0.20 MTS.

*5 Reduced Level of Pump House 100.00 MTS. 5 Economical Dia. Of Rising Main 200.00 MM 14 Frictional Losses in Rising Main Including

6 Centre Line Level of Pump/P.W.L. 54.42 MTS. 6 Frictional Losses Per 1000 mts. 6.19 MTS. 10% for Bends & Specials 2.18 MTS.

*7 Value of "C" 100.00 7 Delivery Head 48.58 MTS. 15 Total Head 56.74 MTS.

*8 Rate of Electric Charges Per Unit in Rs. 3.10 Rs. *8 Residual Head 3.00 MTS. 16 B.H.P. OF PUMP I/C 15% OVERLOADING 37.60 H.P.

*9 Rate of Pumping Machinery in Per H.P. in Rs. 4500.00 Rs. *9 Dia of Column Pipe 125.00 MM 17 Say B.H.P. 40.00 H.P.

*10 Exact Hours Of Pumping In a Year 2802.30 HRS. *10 Length of Column Pipe 45.58 MTS. *18 Hence Provide 1 Set of 40H.P. Each

11 Peak Daily Design Water Requirement 25.94 LPS 11 Frictional Losses Per 1000 mts. In Column pipe 61.02 MTS.

12 Delivery Head 48.58 MTS.

13 Length of Column Pipe 45.58 MTS. Velocity 0.83 M/SEC.

14 Hence Economical Dia. Of Rising Main 200 MM Value of V^2/2g 0.03


15 Dia of Column assembly 125 MM
NAME OF WORK:- C/O 08 Nos. T/WELLS IN INDORA AREA (C/O OF T/WELL AT BARI KANDORI)

DESIGN OF WALL THICKNESS AS PER IS-1978-1982

DIA OF LENGTH STATIC DISCHARGE LOSSES TOTAL NORMAL MAXIMUM VELOCITY WATER FIELD TEST PRESSURE
PIPE OF PIPE HEAD PER 1000 LOSSES VELOCITY OPERATING OF HAMMER SHALL BE GREATEST
I/C 10% PRESSURE PRESSURE EFFECT 1.5xCOL.3 1.5xCOL.8
FOR BENDS WAVE

(MM) (MTS.) (MTS.) (LPS) (MTS.) (MTS.) (M/SEC.) (MTS.) (M/SEC.) (MTS.) (MTS.) (MTS.)
1 2 3 4 5 6 7 8 9 10 11 12

AT RD = 0 RL = 1100
200 320 48.58 25.94 61.02 2.18 0.83 50.76 1225.52 103.10 72.87 76.14

AT RD = 90 RL = 1152
200 230 -3.42 25.94 61.02 15.44 0.83 12.02 1199.76 100.93 -5.13 18.03

AT RD = 240 RL = 1221.8
200 80 -73.22 25.94 61.02 5.37 0.83 -67.85 1166.29 98.12 -109.83 -101.78

TENSILE DIA OF OUTSIDE STRESS TEST WALL CORROSION WALL SUMMERY :- PROVIDE
STRENGTH PIPE DIA OF PIPE PRESSURE THICKNESS OR EROSION THICKNESS
* ALLOWANCES I/C 10% MILL RD
"D" "Do" "S" "P" "t" "C" TOLERANCE FROM TO
(Mpa) (MM) (MM) (Mpa) (Mpa) (MM) (MM) tm = t+c(MM)
17 18 19 20 21 22 23 24

210 200 273.10 124.00 1.54 1.99 1.65 3.84 0 90

210 200 273.10 124.00 1.13 1.46 1.65 3.26 90 240

210 200 273.10 124.00 0.30 0.39 1.65 2.08 240 320

Value of "C" taken from t

CALCULATION FOR WATER HAMMER EFFECT

Hmax.=C Vo/g
Where
Hmax.=maximum pressure rise in the closed conduit above the normal pressure in mts.
C =velocity of pressure wave travel in m.sec.
Vo =normal velocity in the pipeline before sudden closure in m/sec.
g =acceleration due to gravity in sq.m/sec.
C =1425/sqrt.(1+(kd/Ect))
Where
k =bulk modulous of water (2.07*10^8 kg/sq.m)
d =diameter of pipe in mts.
Ct =wall thickness in mts.
E =modulous of elasticity of material in kg/sq.m (for steel pipes E=2.1*10^10)

P =2st/Do
Where
P =test pressure in Mpa
S =stress in Mpa which shall be taken as 40% of the
specified minimum tesile strength
t =specified thickness in mm
Do =outside diameter in mm
or t =PDo/2s
FIELD TEST PRESSURE WHICH MAX.FTP GRADE APP. WALL
SHALL BE GREATEST OF OF COLUMN OF THICKNESS
MAX. PRESSURE 11,12,13 STEEL AS PER
+ CODE TAB.
WATER HAMMER *
(MTS.) (MTS.) (MM)
13 14 15 16

153.86 153.86 Yst-210 5.6

112.95 112.95 Yst-210 4.8

30.27 30.27 Yst-210 4

UMMERY :- PROVIDE

PIPE STEEL FLANGES


THICKNESS GRADE TABLE
(MM) IS 1978-1982 IS 6392-1971

6.40 Yst 210 28

5.60 Yst 210 23

4.00 Yst 210 17

alue of "C" taken from table 186 of G.S. Bajwa book


NAME OF WORK:- C/O 08 Nos. T/WELLS IN INDORA AREA (C/O OF T/WELL AT BARI KANDORI)

DESIGN OF WALL THICKNESS AS PER IS - 3589-1991

DIA OF LENGTH STATIC DISCHARGE LOSSES TOTAL NORMAL MAXIMUM VELOCITY


PIPE OF PIPE HEAD PER 1000 LOSSES VELOCITY OPERATING OF
I/C 10% PRESSURE PRESSURE
FOR BENDS WAVE

(MM) (MTS.) (MTS.) (LPS) (MTS.) (MTS.) (M/SEC.) (MTS.) (M/SEC.)


1 2 3 4 5 6 7 8 9

AT RD = 0 RL = 1100
200 320 48.58 25.94 61.02 2.18 0.83 50.76 1225.52

AT RD = 90 RL = 1152
200 230 -3.42 25.94 61.02 15.44 0.83 12.02 1199.76

AT RD = 240 RL = 1221.8
200 80 -73.22 25.94 61.02 5.37 0.83 -67.85 1166.29

TENSILE DIA OF OUTSIDE STRESS TEST WALL CORROSION WALL


STRENGTH PIPE DIA OF PIPE PRESSURE THICKNESS OR EROSION THICKNESS
* ALLOWANCES I/C 10% MILL
"D" "Do" "S" "P" "t" "C" TOLERANCE
(Mpa) (MM) (MM) (Mpa) (Mpa) (MM) (MM) tm = t+c(MM)
17 18 19 20 21 22 23 24

330 200 273.10 132.00 1.54 1.87 1.65 3.71

330 200 273.10 132.00 1.13 1.37 1.65 3.16

330 200 273.10 132.00 0.30 0.37 1.65 2.06

Value of "C" taken from table 186 of G.S. Bajwa book


ELL AT BARI KANDORI)

WATER FIELD TEST PRESSURE WHICH MAX.FTP GRADE ASSUMED


HAMMER SHALL BE GREATEST OF OF COLUMN OF WALL
EFFECT 1.5xCOL.3 1.5xCOL.8 MAX. PRESSUR 11,12,13 STEEL THICKNESS
+
WATER HAMMER *
(MTS.) (MTS.) (MTS.) (MTS.) (MTS.) (MM)
10 11 12 13 14 15 16

103.10 72.87 76.14 153.86 153.86 Fe330 5.6

100.93 -5.13 18.03 112.95 112.95 Fe330 4.8

98.12 -109.83 -101.78 30.27 30.27 Fe330 4

SUMMERY :- PROVIDE

RD PIPE STEEL FLANGES


FROM TO THICKNESS GRADE TABLE
(MM) IS 3589-1991 IS 6392-1971

0 90 6.40 Fe 330 28

90 240 5.60 Fe 330 23

240 320 4.00 Fe 330 17


Pressure strained by GI pipes
Diameter Light Medium Heavy
(mm) (kg/cm²) (kg/cm²) (kg/cm²)
15 10.55 21.09 24.61
20 10.55 21.09 24.61
25 10.55 21.09 24.61
32 8.8 17.58 21.09
40 8.8 17.58 21.09
50 7.03 14.06 17.58
65 7.03 14.06 17.58
80 7.03 14.06 17.58
100 7.03 12.02 16.03
125 - 12.02 14.79
150 - 9.98 12.02

DESIGN OF VARIOUS CIVIL COMPONENTS AND RISING MAIN ECT.

RISING MAIN

Water requirement =
Carring capacity of R/ main in the year =
Economical dia of rising main. =
Total length of the rising main. =
Working Head Heavy class =
Medium class =
Rate of frictinal losses/1000 8.41
Top Rd. of rising main = 300 And RL= 1332.50

i) At RD = 0 And RL = 1200.00
Frictional lossesin the Rising main = 2.52
Add 10 % for other losses. = 0.25
Static Head. = 132.50
Residual Head. = 3.00

Total head. = 138.28

ii) At Rd. 0 And RL. 1200.00

Frictional lossesin the Rising main = 2.52


Add 10 % for other losses. = 0.25
Static Head. = 132.50
Residual Head. = 3.00

Total head. = 138.28 <

Hence provide MSERW 125 mm dia pipes from Rd 0


i.e. total length. = 0 metres

iii) At Rd. 30 And RL. 1218.31

Frictional lossesin the Rising main = 2.27


Add 10 % for other losses. = 0.23
Static Head. = 114.19
Residual Head. = 3.00

Total head. = 119.69 <

Hence provide GMS Heavy Class 125 mm dia. pipes from


0 to 30 i.e. total length. = 30

Hence provide GMS Medium Class 125 mm dia. pipes from


Rd. 30 to 300 i.e. total length. =
ABSTRACT OF PIPES :-
MSERW 125 mm dia. 0 Rmts.
HEAVY CLASS 125 mm dia. 30 Rmts.
MEDIUM CLASS 125 mm dia. 270 Rmts.

Total 300 Rmts.

FLANGES AS PER TABLE - 17 OF IS - 6392-1971


8.9 LPS
768960 litres/day
125 mm
300 Mtrs.
148 Mtrs.
120 Mtrs.
Mtrs.

> 148
148

TO 0

120

Rd.
metres

es from
270 metres