Background
Standards
Design
Wind Loading
Page 2
Wind Loading
Page 3
Wind Loading
Page 4
Wind Loading
BS 6399-2:1997
Page 5
Wind Loading - CP3
Exposure
Open Country
City centres
Building Height
Page 6
Wind Loading - BS6399
Exposure
Town
Country
Building height
Page 7
Wind Loading - BS6399
Standard Method
Directional Method
Page 8
Wind Loading - BS6399
Vs = Vb x Sa x Sd x Ss x Sp
Sa – Altitude factor
Sd – Direction factor
Ss – Seasonal factor
Sp – Probability factor
Page 9
Wind Loading - BS6399
Page 10
Wind Loading - BS6399
Altitude factor
Page 11
Wind Loading - BS6399
Page 12
Wind Loading - BS6399
Sd – Direction factor
Page 13
Wind Loading - BS6399
Ss – Seasonal factor = 1
Sp – Probability factor = 1
1 in 50 years storm
Page 14
Example calculation
Vs = Vb x Sa x Sd x Ss x Sp
Sa =1.005
Sd =1
Ss = 1
Sp = 1
Page 15
Wind Loading - BS6399
Page 16
Wind Loading - BS6399
Page 17
Building size:
Example calculation
H = 26.2 m
L = 44.3 m
Ve = Vs x Sb
Page 18
Wind Loading - BS6399
Dynamic Pressure
qs = 0.613 x Ve2
= 0.65 kN/m2
Page 19
Wind Loading - BS6399
Pressure to structure
External pressure
pe = qs x Cpe x Ca
Page 20
Wind Loading - BS6399
Page 21
Page 22
Wind Loading - BS6399
Internal pressure
pi = qs x Cpi x Ca
Page 23
Wind Loading - BS6399
Page 24
Wind Loading - BS6399
Wind Loads
p = pe - pi
Page 25
Wind Loading - BS6399
Page 26
Wind Loading - BS6399
Page 27
Wind Loading - BS6399
Page 28
Wind Loading - BS6399
Page 29
Wind Loading - BS6399
Page 30
Malaysia Wind Map
Page 31
Page 32
Wind speed gust
Page 33
Page 34 *Sources of data: Razali, A.M et al, Mapping of Annual Extreme Wind Speed
Analysis from 12 Stations in Peninsular Malaysia