Professional Documents
Culture Documents
In its final order Supreme Court on 25th August, 2015 modified its
earlier order and ordered real estate barons Ansal brothers will
undergo a two-year rigorous jail term in the Uphaar fire case if they
fail to pay Rs.30 crore each within three months.
This was not the first instance of such fires. After an earlier
transformer caused fire at Gopal Towers, a high-rise in Rajendra
Place, New Delhi in 1983, the licences of 12 cinemas, including that
of Uphaar, had been cancelled. The Deputy Commissioner of Police
(Licensing) who inspected Uphaar, had listed ten serious violations,
however all remained uncorrected until the fire 14 years late On 6
July 1989, a fire had broken out at Uphaar cinema due to a fault in
the sub station.
On the morning of the fire, at around 7 a.m, an explosion had been
heard by the security guard, Sudhir Kumar, who along with his friend
found smoke in the transformer room. The fire brigade and the Delhi
Vidyut Board (DVB) were informed – the fire brigade extinguished this
fire and DVB completed their repairs between 10:30 am and 11 am.
1) Dry-riser system,
2) Wet-riser system,
3) Wet-riser-cum-down-comer system, and
4) Down-comer system.
Components of an Internal Hydrant System
Dry-riser main system could be installed in buildings under Group A (i, ii,
iii, and iv) Residential Buildings where the height of building is above
15 m but not exceeding 24 m up to terrace level and where the water
supply for fire fighting is immediately available either through the
underground water storage tank/tanks or through water mains/town’s
main in lieu of provision given in Table 1. The rising main should have
two-way fire service inlet without non-return valve at ground level, in
front of each such block. It should also be provided with an air-releasing
valve at the top level and drain valve at the bottom. The inlet should be
about 1 m from the ground level, and easily accessible and
unobstructed at all times. Single headed landing valves conforming to
IS 5290: 1983 should be provided at all floor landing/staircase
enclosures or other suitable easily accessible point.
Down-Comer
An arrangement for fire fighting within the building by means of down-
comer mains of not less than 100 mm internal dia, connected to terrace
tank through terrace pump, gate valve and non-return valve and landing
valves on each floor/landing. It is also fitted with inlet connections at
ground. Single headed landing valve, connected to a 100 mm diameter
pipe taken from the terrace pump delivery should be provided at each
floor/landing. A hose reel conforming to IS 884: 1985 and directly
tapped from the down-comer pipe should also be provided on each
floor/landing.
Wet-Riser-cum-Down-Comer
An arrangement for fire fighting within the building by means of vertical
rising mains of not less than 100 mm internal dia with landing valves on
each floor/landing connected to terrace tank for fire fighting purpose,
through a terrace pump, gate valve and non-return valve near the tank
and to a fire pump, gate and non-return valves, over the static tank.
Wet-Riser
k) Where the height of the building exceeds 100 m, multiple wet risers’
zoning system shall be established with pump sets and water tank at the
terrace of 100 m level and at every subsequent 100 m height. Every 100
m height of the building shall be protected in any one of the following
methods:
i) Single pump can be provided with two wet risers – one directly
feeding the upper levels and the other feeding the lower levels through
pressure reducing arrangement
ii) Pump with multi-stage, multi-outlet pump and risers tapped from
different outlets of the pump according to the pressure required at
various heights
iii) Any method other than the above, which shall be acceptable to the
local authorities having jurisdiction.
f) Pump capacity shall be 4 550 lpm (273 m3/hour) and head
shall be 150 m (15 bars).
NOTE - In case, if height of the building beyond 100 m is less
than 75 m in any upper zone(s), provisions of Table 7 can be
applied for the zone(s) concerned (only for hydrant wet risers
and capacity of pumps).
m) Water storage at ground level tank shall be in two separate
but interconnected compartments, having a minimum
capacity of 350 000 litres (350 m3)