Professional Documents
Culture Documents
ON
“CONTINGENCY ANALYSIS
OF POWER SYSTEM”
Presenters:
Anish Sharma Poudel (073/BEL/204)
Arjun Devkota (073/BEL/206)
Dipendra Gaudel (073/BEL/220)
Nisha Nepal (073/BEL/230)
8/23/20 1
OUTLINES
1. INTRODUCTION
2. TYPE OF VIOLATIONS
3. LOAD FLOW DIAGRAMS
4. RESULT AND DISCUSSIONS
5. FURTHER WORKS
6. CONCLUSION
7. REFERENCES
8/23/20 2
INTRODUCTION
Contingency analysis is a well known function in modern Energy
Management System (EMS).
The goal of this power system analysis function is to give the
operator information about the static security.
Contingency analysis of a power system is a major activity in
power system planning and operation.
In general, an outage of one transmission line ,transformer or
sudden change in load may lead to over loads in other branches
and/or sudden system voltage rise or drop which are also called
violations. Here, contingency analysis is used to calculate violations
and hence tries to maintain stability in the power system.
8/23/20 3
TYPE OF VIOLATIONS
• Line contingency and generator contingency are most common
type of contingency.
• Two types of violations. 1.Low voltage violations
2.Line MVA limits violations
When the MVA rating of the line exceeds given rating , this
violations occurs.
The lines are designed in such a way that they should be able to
withstand 125% of their MVA limit.
8/23/20 5
METHODOLOGY
1.Sensitivity factor method
Generation shift factor(G.S.F)
G.S.F=change in power flow of line/change in
generation of power
Line outage distribution factor(L.O.D.F)
L.O.D.F=change in power flow of line/power flow
in outage line
8/23/20 6
LOAD FLOW DIAGRAM FOR 5 BUS SYSTEM
8/23/20 7
Generator Capacity G1=G2=400MW, 100MVar(Q)
BUS DATA
8/23/20 8
GENERATOR OUTAGE
8/23/20 9
LINE 1-2 OUTAGE
8/23/20 10
RESULTS
Calculation of AND DISCUSSION
GSF when generator 1 is
outage
original final change in change in
Lines flow(MW) flow(MW) flow generation GSF
Line 2-3 168.8 81.2 -87.6 -213.9 0.409537167
Line 1-2 45.1 81.2 36.1 -213.9 -0.168770453
Line 1-5 158 293.1 135.1 -213.9 -0.631603553
Line 4-5 235.5 321.8 86.3 -213.9 -0.403459561
Line 3-4 35.3 119.7 84.4 -213.9 -0.394576905
LOAD DATA
8/23/20 12
FURTHER WORKS
Today, we have analyzed the 5 bus system
using Dig SILENT.
In the next defense, we will enhance
the bus system to 14 bus and we will
determine the performance indices PIp
and PIv and accordance to these data, we
will rank the contingencies.
8/23/20 13
CONCLUSION
Whenever the contingencies arise in the
system, the operator gets notified through
alarm and possible corrective actions can be
done.
8/23/20 15
8/23/20 16