Professional Documents
Culture Documents
AND CONTROL
Dr Mousa Marzband
Faculty of Engineering and Environment
Northumbria University
Newcastle upon Tyne NE1 8ST
E-mail: mousa.marzband@northumbria.ac.uk
Ellison Building E406
Ext 4734
POWER SYSTEMS OPERATION AND
CONTROL
• Introduction
• Active and Reactive Power Flow
• Voltage Control
• Frequency Control
– Turbo-Alternator Control System
– Governor Droop Characteristics
– Division of Load Between Generators
• Optimization of Power System Operation
– Heat Rate Characteristics
– Incremental Fuel Cost
References
1.Weedy, B.M., Cory, B.J., Jenkins, N., Ekanayake, J. and Strbac, G. (2012),
“Electric power systems”, John Wiley & Sons, Ltd.
2.Grainger, J.J. and Stevenson W.D. (1994), ‘Power System Analysis’,
McGraw Hill.
Apparent power, active power and reactive power
Basic Maths-1
A right triangle has three sides, which can be uniquely identified as the
hypotenuse, adjacent to a given angle , or opposite .
opposite side o
sin( )
hypotenuse h
adjacent side a
cos( )
hypotenuse h
opposite side o
tan( )
adjacent side a
Formulas needed in this section
sin( u v) sin( u ) cos(v) cos(u ) sin( v) Subtraction formula
1
sin( t ) cos(t ) sin( 2t )
2
1 cos( 2t ) Double angle formulae
sin (t )
2
0.6
-0.2
It is noted that
-0.4
-0.6
t T
-1
0 1 2 3 4 5 6 7
tt
wt
T
t T
I I p Iq P
Ip
V VI p VI cos
R
V V V VI q VI sin Q
Iq j 90o
jX X X
V V2 V V2
P VI p V Q VI q V
R R X X
Example:
The voltage across and current through a circuit are:
v 339.4 sin(t 10 ) V
o
i 12 sin(t 20 o ) A
Find
1) The r.m.s values of the voltage and current.
2) The phasor expression of the voltage and current (the voltage is taken as reference)
3) The power factor
4) The apparent, active and reactive power
12
I 8.5 A I
2
3) Power factor
P 1766
PI R 2
R 2 2
24.44
I 8.5
Q 1020
QI X 2 X 2 2
14.12
I 8.5
6) If the circuit consists of a parallel resistive and reactive elements R and
X, calculate
R and X.
P VI cos( ) 240 8.5 0.866 1766W
Q VI sin( ) 240 8.5 0.5 1020VAR
12 339.4
I 8.5 A V 240V
2 2
V2 V 2 240 2
P R 32.6
R P 1766
V2 V 2 240 2
Q X 56.47
X Q 1020
,
Complex power
The complex power can be defined as
V
S = P + j Q = V I*
o I
To verify this, let V V I I
V I * V I V I V I
P
= V I cos + j V I sin
=P+jQ Q
S
, ...
P = 3 VL I L cos
Q = 3 VL I L sin
S = 3 VL I L
consumer of P
generator of P and Q generator of Q
~ quadrants
I I
a.c. V
S=P+jQ equivalent P (-)
O (-)
V O (+)
P (+)
circuit
generator of P
I
consumer of Q consumer of P and Q
~
P jQ = V I cos + j V I sin
(a) Q (+)
(b)
Example: Assume a current direction as shown in the circuit given
below:
E2 10030 o
I2 I
E1 E2 1000o 10030o 100 100 cos(30o ) j sin( 30 o )
Z 1 j5 1 j5
13.4 j 50
9.1 j 4.5 10.15206.3o
1 j5
E1 1000o
I Z I 10.15206.3o
Q Q1 Q2 QZ
449.7 65.5 515.2 0
The per-unit System
n1 n2 n3 n4 n5
The main idea of a per unit system is to absorb large differences in absolute
values into base relationships. Thus, representations of elements in
the system with per unit values become more uniform. A per-unit
system provides units for power, voltage, current, impedance, and
admittance.
Actual value
p.u. value
Base value
Simplified calculation.
Two important p.u. parameters:
Rules of selecting:
The base power (MVAbase) is chosen to be the same for all items
in the whole network.
The base voltages MUST be in the ratio of the turns of
transformers. –rating values.
per unit system 3 phase star-connected systems
2
KVbase ( KVbase ) 2 Vbase
Base impedance: Z base or Z base
3KAbase MVAbase S base
Z MVAbase Sbase
p.u. impedance: Z p.u Z or Z p.u Z 2
Z base ( KVbase ) 2 Vbase
Example
Consider now a 415:200 V 3 phase transformer:
1) Calculate the base impedances on both
primary side and secondary side 10kVA
415V
Primary side base impedance:
200V Z=10
VB 415 S B 10 kVA
VB2 4152
ZB 17.22
S B 10 10 3
i.e. they are the same. The transformer turns ratio has
disappeared in the p.u. system. In other words, the turns ratio of
the ideal transformer is 1:1 and can be ignored. The equivalent
circuit of a transformer is now very simple.
If base power and base voltage are both chosen new ones, Z p.u. will change
2
KVbase ( given ) MVAbase (new)
Z p.u (new) Z p.u ( given )
KV base ( new) MVAbase ( given )
2
Vbase ( given ) Sbase (new)
Or Z p.u (new) Z p.u ( given )
V
base ( new) Sbase ( given )
If only base power change, but base voltage stays unchanged, Z p.u. will become
MVAbase (new)
Z p.u (new) Z p.u ( given )
MVAbase ( given )
Sbase (new)
Or Z p.u (new) Z p.u ( given )
Sbase ( given )
Example:
An 11kV, 200MVA alternator has a reactance of 0.25p.u. on rating.
Find the p.u. reactance based on:
(1) 500MVA
(2) 66kV, and 500MVA
Pload 50
I load 1.2028kA
3Vload cos 3 30 0.8
Sbase 50
I base 0.8748kA
3Vbase 3 33
I load 1.2028
I loadp.u. 1.375 p.u.
I base 0.8748
1.375 p.u.
VL
Vsp.u . VL I ( X T 1 X Line X T 2 )
Vs Vsp.u .Vbase
0.90910 1.375 36.87 (0.1 0.287 0.12)90
o o o
1.43922.8o 11
0.90910 o 0.697153.13o 1.3274 j 0.5577
15.83kV22.8o
1.439 p.u.22.8o
Class test:
Z 0.242
Z pu 0.04 pu
ZB 6.05
VB22 (66 10 3 ) 2
b) Secondary side: Z B2 217.8
SB 20 10 6
Backflash when the transmission line tower or one of the ground wires is struck by lighting
can raise the tower potential
Reason to analyse short-cicuit
faults
Make sure that the circuit breakers rating are such that they are capable of interrupting the
fault currents.
Faults calculations
Rf
(a) Balanced faults
Figure (1)
Fault
current
Fault current calculation via p.u. system method
F
22/132 kV 132/11 kV
F T.L.
G1 G2
40 km 80 km
60 MW
100 MW
125 MVA 75 MVA 75 MVA
125 MVA X=j18% Fault
X=j12.5% X=j17.5%
X=j28%
Fault 80 MW 50 MW
0.9 p.f. 0.8 p.f.
lagging lagging
125
X L1 p.u . (40 0.43) 2
0.123 p.u.
132
125
X L 2 p.u . (80 0.43) 2
0.247 p.u.
132
Therefore, the reactance diagram is redrawn as follows:
0.28 0.18 0.123 0.247 0.208 0.292
G1 G2
F 0.583 F F
(b) (c) (d)
1 .0
Fault current: I F . p.u . 3.058 p.u.
0.327
Sbase 125 I F I Fp .u . I B 3.058 0.5467
I base 0.5467 kA
3Vbase 3 132
1.672 kA
Solution:
Base power: 5MVA
1
I fault. p.u . 16.67 p.u.
0.01 0.05
Sbase 5
I base 0.1312kA
3Vbase 322
Solution:
Fault calculation
Power and power flow
Real power or
Apparent power (VA)
active power (W)
Complex power
Q
S
Three phase system
Real power or
active power (W)
Apparent power (VA)
Complex power
Q 3VI sin S VI P jQ
*
Q
S
The per-unit System
n1 n2 n3 n4 n5
Actual value
p.u. value
Base value
Simplified calculation.
Two important p.u. parameters:
Rules of selecting:
The base power (Sbase) is chosen to be the same for all items in the
whole network.
The base voltages MUST be in the ratio of the turns of
transformers. –rating values.
per unit system 3 phase star-connected systems
2
Vbase
Z base
Sbase
Base impedance:
S base
Z p .u Z 2
p.u. impedance: Vbase
If base power and base voltage are both chosen new ones, Z p.u. will change
2
Vbase ( given ) S base (new)
Z p.u (new) Z p.u ( given )
V
base ( new) Sbase ( given )
If only base power change, but base voltage stays unchanged, Z p.u. will become
S base (new)
Z p.u (new) Z p.u ( given )
Sbase ( given )
Faults calculations
Rf
(a) Balanced faults
Figure (1)
Fault
current
Example. Three 11kV, 100MVA generators are connected to common
busbars. Each is connected via a 100MVA inductors and an identical
circuit breakers. The inductors have reactances of 0.15p.u., 0.2p.u. and
0.30p.u.. If the generators each have a transient reactance 0.25p.u.. What
is the minimum circuit-breaker rating to protect the generators against a
fault on the common busbars?
100MVA
G
11kV,
Solution: 100MVA
load
a) Choose XL=0.15p.u.
1 1
I p.u . 2.5 p.u.
0.25 0.15 0.4
I fault 2.5 14kA 35kA
11
VL 0.15 4.125kV
0.25 0.15
S fault 3VL I fault
Sbase 100
I base 14kA 3 4.125 35 250 MVA
3Vbase 34.125
b) Choose XL=0.2p.u.
c) Choose XL=0.3p.u.
1 1
I p.u . 2.22 p.u.
0.25 0.2 0.45 1 1
I p.u . 1.82 p.u.
0.25 0.3 0.55
11
VL 0.2 4.89kV
0.25 0.2 11
VL 0.3 6kV
0.25 0.3
Sbase 100
I base 11 .8kA
3Vbase 34.89 Sbase 100
I base 9.62kA
3Vbase 36
I fault 2.22 11 .8kA 26.2kA
I fault 9.62 1.82 17.5kA
S fault 3VL I fault
S fault 3VL I fault
3 4.89 26.2 222 MVA
3 6 17.5 182 MVA
I fault 35kA I fault 17.5kA
S fault 250 MVA S fault 182 MVA
I fault 35kA
I fault 26.2kA
Solution:
Base power: 5MVA
1
I fault. p.u . 16.67 p.u.
0.01 0.05
Sbase 5
I base 0.1312kA
3Vbase 322
X G1 0.1 p.u. 60
X T 1 0.1 p.u. 0.15 p.u.
40
60 G1
XT2 0.15 p.u. 0.45 p.u.
20
60
X G 2 0.1 p.u. 0.2 p.u.
30
G2
Sbase 60
X Line X 2
126 2
0.434 p.u.
Vbase 132
1.134pu
0.15pu 0.434pu 0.45pu
0.1pu
1p.u.
1p.u.
0.2pu
0.17p.u.
1p.u.
1
I faultp.u . 5.88 p.u.
0.17
Sbase 60
I base 3.15kA
3Vbase 311
1.234p.u.
0.45pu 0.2pu G2
0.1pu 0.15pu 0.434pu
1p.u. 1
I faultp.u . 10.8 p.u.
0.0925p.u. 0.0925
G1
Sbase 60
I base 1.575kA
3Vbase 322
G2
Conflicting Objectives
Therefore, a compromise is sought
Meeting the Objectives
• Long-term and Short-term Load Forecasts
• Plan Network Development
• Power System Operation and Control
– Generation Scheduling (Economic Load Dispatch) and
turbine speed governors
Control of P & f
– Automatic Voltage Regulators (AVR) on alternators,
transformers tap changers and VAr compensators
Control of Q & V
– Optimization of System Operation
Generation Scheduling or Economic Load Dispatch
Minimizing Transmission Losses
Methods of Voltage Control
• Tap changing transformers
– To avoid large voltage disturbances, the voltage change between taps is normally
small; about 1.25 % of the nominal voltage.
– The total range of tapping varies with the transformer usage, a typical figure for
generator transformers is +2% to -16% in 18 steps.
o o
o o
Symbol A o o B
o o o
o o
o
o o o o
o S1 S2
o
o L L o
off-load tap changer on-load tap changer
Methods of Voltage Control
• Automatic Voltage Regulators (AVR) on alternators
– An over-excited machine generates reactive power while an under-excited
machine absorbs it.
– Automatic Voltage Regulators (AVR) on alternators are usually used to control the
terminal voltage, by suitably adjusting the reactive power in response to a control
signal representing the alternator terminal voltage.
– The generator is the main source of supply to the system of both positive and
negative VArs, as reactive power is generated at no cost (i.e. no fuel or additional
capital cost).
• The slope of the line joining any point on the curve to the origin represents the
generation cost for that output power in £/hour per MW, i.e. £/MWh. This is
defined as the heat rate and its reciprocal is defined as the fuel efficiency.
• Maximum fuel efficiency occurs at the point where the slope of the line from
the origin to a point on the curve is a minimum.
Incremental Fuel Cost () in £/MWh
• This is defined as the additional cost in £/hour to increase the output
by 1 MW. It is usually based on the variable generation costs.
• For economical division of load between units (optimum operation),
the incremental fuel cost for all contributing turbine-generator sets
should be the same.
£/MWh £/MWh