Professional Documents
Culture Documents
Overcurrent Relay
Characteristics
Pickup setting
Time-current characteristics
Phase and ground overcurrent relays
Overload vs Overcurrent
protection
Overload protection- related to thermal capability of the element to be protected
11 kV, 10 MVA, 50 Hz
X=10%, Load Load
Load
Note: Since currents are measured through current transformer, both 𝐼 𝑝 𝑖 𝑐 𝑘 𝑢 𝑝 and I should be referred
to either primary or secondary of the CT.
Types of Overcurrent Relays
• Two types:
1. Phase relay - to protect the system for phase faults
2. Ground relay - to protect the system for faults involving ground
3Io Residual
current
Digital Relays -Residual Current
Calculation
Residual current for balanced load or three-phase fault
𝐼𝐴
𝐼𝐶
𝐼𝐶
𝐼𝐴 𝐼→𝐴 + 𝐼→𝐵 + 𝐼→𝐶 = 3𝐼→0
= 𝐼→𝐺 = 0
𝐼𝐵
𝐼𝐵
Residual current for ground fault
𝐼𝐴
𝐼𝐺
𝐼𝐶
2. Pickup current should be below the minimum fault current i.e; Ipickup < IFmin. This
ensure that protection system will operate for low fault current
situations
Zline = 4.7∠34° Ω F2
B
Zline = 4.7∠34° Ω F1
C
ag-Fault at 2s
1190 A
𝐼 𝑝 𝑖 𝑐 𝑘 𝑢 𝑝 (ground relay) = 30 A
Ground and phase relays for a ground fault-another
situation B C
Zline = 4.7∠34° Ω F2
Zline = 4.7∠34° Ω F1
A
11 kV, 10 MVA, 50 Hz
X=10%, Load Load
Load
• The time-current characteristic for computation of trip time for overcurrent relay are:
(a) Instantaneous relay
(b) Time delayed definite time relay
(c ) Inverse definite minimum time (IDMT) relay
i. Moderately inverse
ii. Very inverse
iii. Extremely inverse
Time-current
Characteristics
1. Instantaneous overcurrent relay (50)
• The operating time of an instantaneous relay is of
the order of a few milliseconds.
Instantaneous relay characteristic
• It is used to protect a long feeder from close-in
fault.
(s)
• This characteristic is not suitable for backup
protection.
(s)
change much with the location of the fault across the feeder.
• In coordination of the relays- the relay takes more time for
faults close to the source-not desirable
• The operating time of the relay near the source
-may hit the upper limit of fault clearing time
𝛽
𝑡= 𝛼 + 𝐿 𝑇𝑀𝑆
𝐼 𝑝𝑖𝑐𝑘 −1
𝑢𝑝
𝐼
Given the relay characteristic, for a fault current, it is a straightforward task to calculate
the time response for a given TMS, pickup setting and the other values of the expression.
Likewise, if a particular time response and pickup setting have been determined, the time
dial setting is found by solving TMS from the same equation.
Flexibility with Numerical 51
Relays
t Different Setting Options
*****
**