Professional Documents
Culture Documents
FAULT
Short circuit produced by failure of insulation.
PROTECTION IS INSTALLED TO :
Detect fault occurrence and isolate the faulted equipment.
SO THAT :
Damage to the faulted equipment is limited;
Disruption of supplies to adjacent equipment is minimized.
Danger to staff or the public is avoided
Faults Are Mainly Caused By Insulation Failure
Underground Cables
Diggers
Overloading
Oil Leakage
Ageing
Faults Are Mainly Caused By Insulation
Failure
Overhead Lines
Lightning
Kites
Trees
Moisture
Salt
Birds
Failure of discs
Broken Conductors
Faults Are Mainly Caused By Insulation
Failure
Machines
Mechanical Damage
Unbalanced Load
Types of Fault
a
b
Phase to Earth Fault
c
a
b
Phase/Phase/Earth
c
e
a
Phase/Phase b
c
a a
b b
c 3 Phase/Earth c
3 Pase Fault
e
Breaker
Equipment /
Feeder
Instrument
Relay Transformers
Battery
Types Of Protection - Principles
Dc Shunt
Battery Trip coil
E/F OC OC OC E/F OC OC
51 A I2 C 51 LOAD
51 B D 51
Relays ‘C’ and ‘D’ see the same fault current (I2). As ‘C’
and ‘D’ have similar settings both feeders will be tripped.
Parallel Feeders
Solution:- Directional Control at ‘C’ and ‘D’
I1 + I2
I1
C
51 A I2 67 LOAD
51 B D 67
Relay ‘D’ does not operate due to current flow in the reverse
direction.
Establishing Direction:- Polarising Voltage
The DIRECTION of Alternating Current may only be
determined with respect to a COMMON REFERENCE.
VC VB
A
B
C
VRES
Application of Overcurrent Protection
Overcurrent & Earth fault Protection is used.
HT lines
Transformers
Generators
Reactors
Capacitor Banks
Motors
Neutral displacement relays in capacitor banks
EHT lines (Directional overcurrent &E/F)
Breaker failure Protection
2. Differential Principle
Protected object
Relay
Differential Protection Principale (1)
P1 C.T P2 P2 C.T
Protected P1
Circuit
S1 S2
S2 S1
R Differential Relay
R Differential Relay
Transformers
Generators
Busbars.
Lines (with pilot wires)
Restricted Earthfault Protection
Uses differential principle
Increased sensitivity for earth faults
REF elements for each transformer winding
CTs may be shared with differential element
64
64
64
Restricted Earthfault Protection
P1 S1
P2 S2
External earth fault - Current circulates between the phase & neutral CTs;
no current thro’ the relay
So, No Operation
Restricted Earthfault Protection
For an internal earth fault the unbalanced current flows thro’ the relay
F1
Relaying Relaying
Point Point
R R
Trip A Trip B
Relay at End ‘B’ measures current and transmits the value to Relay at end
‘A’ thru optical fibre cable. Relay ‘A’ compares measured value and the
value recived from ‘B’.
If both values are same, relay keeps restraint state.
If there is difference in values. Relays operates.
Pilot wire protection
Used for
EHT cables
Short distance EHT transmission lines
4.Distance Protection
. Distance
For : Transmission Lines. and Sub-Transmission
Circuits
Also used as Back-up Protection for Transformers
and Generators
Impedance Relay
jIX
IF zF
IZ
V2 V1
VF V3
IR
Relay
ZS PT. IR ZL
VR
Impedance measured ZR Z L Z LOAD
R
The relay is set based on the line impedance.
The measured ZR is more than the relay setting Z , hence relay restrains
Basic Principle of Distance Protection
ZL
ZS IR ZF
VS VR ZLOAD Fault
jX
D Z3A
C Z2A
B
Z1A
A
R
Zones of Protection
Time
Z3A
T3
Z2A
T2
Z1A
A Z1B B C D
T2
Z2B
Time
Z3A Z3C
T3
Z2A Z2C
T2
Z1A Z1C
A Z1B B C D
T2
Z2B
VT SUPERVISION
Blocks tripping of Distance Relay when VT supply fails.
AUTORECLOSING
Maintains stability of the system by fast reclosing
after trip on fault.
CARRIER INTERTRIPS
Are provided for fast clearance of faults for entire line.
Distance Relay Applications
Transmission lines
Under ground Cables as backup
Sub transmission line
Backup protection for generators
Other type of relays used in substation
1.Under / Over Voltage Relays
Causes of Overfluxing
Low frequency
High voltage
Geomagnetic disturbances
Over fluxing Relay (V/Hz)
Effects of Over fluxing
Over flux relay measures V/f ratio and in it gives alarm in stage-1
(usually set at 110%)
It gives trip signal in stage-2 (set at 120%)
6.Master Trip Relay
It will transfer the actuation of trip signal from relays to
the circuit breaker
A circuit breaker normally open (52a) contact is used to
interrupt trip coil current. This saves trip coil from
burning out due to continuous current flow.
Burning of trip coil may happen if this contact is faulty.
7.Trip circuit supervision
NO
TRIP
BACK-UP
BREAKERS
10.Low SF6 Alarm/Lockout
It is dangerous to operate Circuit
Breaker without adequate SF6
Pressure. So a relay is provided in side
CB to monitor SF6 gas pressure . 2
stages are provided.
Stage-1 : Alarm
Alarm stage indicates the
inadequate gas pressure inside CB.
Which alerts the operator.
Stage-2 :Lockout.
Lock out stage blocks the
operation of CB. No tripping or
closing will happen then.
11.Control Relays
Auto-Reclose Relay
Used to auto reclosing of EHT feeders
Temperature indica
Sensing device
S1=alarm S2=trip
S4=cooler control 2
S3=cooler control 1
Pressure Relief Device (PRD)
Oil conservator
3 minimum
Transformer
Buchholtz Relay arrangement.
MAGNETIC OIL LEVEL GAUGE
(MOLG)
Mounting 15 0 Inclination.
The movement of the float is
transmitted to the pointer by
using a magnetic coupling.
The follower magnet follows the
driving magnet.
The driving magnet remains
inside the conservator and the
other magnet out side the
conservator.
1/2
1/4 3/
4
FU
BEARING
PTY
LL
EM
FLOATING MEMBER
MOLG
PERMANENT MAGNET