WIND LOAD ANALYSIS

A.C.P.R.
A.P.D.
03/27/14


Design Criteria and Specifications
(Wind Analysis)


Wind Direction: Normal to transverse, parallel to longitudinal

Occupancy: Standard Occupancy

Location: Zone II

Exposure: B

Height of Building: 19.00 m

V: 200 kph
Iw: 1.00
kzt: 1.00
kd: 0.85
kz: 0.78

Gust effect factor: 0.85

External Wall Pressure Coefficient, Cp:

Windward walls: 0.80
Leeward walls: -0.50

Internal Wall Pressure Coefficient, Cpi:

Windward walls: 0.55
Leeward walls: -0.55


Velocity Pressure, kPa;

Wind Load, KPa; P = qz (GCp-Gcpi)

Wind Force, KN; F = P (Tributary Area)

L = 60m
B = 32.4m
L/B = 1.85









WIND LOAD ANALYSIS
A.C.P.R.
A.P.D.
03/27/14


LONGITUDINAL SECTION OF FRAME



TRAVERSE SECTION OF FRAME


Windward Leeward Windward Leeward
Base Height Windward Leeward
2nd Floor
1.25 0.85 0.80 -0.50 0.55 -0.55 1.54 -1.22 7.50 5.00 57.86 -45.86 12.00
3rd Floor
1.25 0.85 0.80 -0.50 0.55 -0.55 1.54 -1.22 7.50 3.50 40.50 -32.10 8.40
4th Floor
1.25 0.85 0.80 -0.50 0.55 -0.55 1.54 -1.22 7.50 3.50 40.50 -32.10 8.40
5th Floor
1.25 0.85 0.80 -0.50 0.55 -0.55 1.54 -1.22 7.50 3.50 40.50 -32.10 8.40
Roof Deck
1.25 0.85 0.80 -0.50 0.55 -0.55 1.54 -1.22 7.50 3.50 40.50 -32.10 8.40
FRAME 1,7
qz G
Tribut ary Area
F
TOTAL F
Cp
GCpi
P
Windward Leeward Windward Leeward
Base Height Windward Leeward
2nd Floor
1.25 0.85 0.80 -0.50 0.55 -0.55 1.54 -1.22 5.40 5.00 41.66 -33.02 8.64
3rd Floor
1.25 0.85 0.80 -0.50 0.55 -0.55 1.54 -1.22 5.40 3.50 29.16 -23.12 6.04
4th Floor
1.25 0.85 0.80 -0.50 0.55 -0.55 1.54 -1.22 5.40 3.50 29.16 -23.12 6.04
5th Floor
1.25 0.85 0.80 -0.50 0.55 -0.55 1.54 -1.22 5.40 3.50 29.16 -23.12 6.04
Roof Deck
1.25 0.85 0.80 -0.50 0.55 -0.55 1.54 -1.22 5.40 3.50 29.16 -23.12 6.04
FRAME 1,7
qz G
Tribut ary Area
F
TOTAL F
Cp
GCpi
P