Professional Documents
Culture Documents
Power System Analysis Lab Manual
Power System Analysis Lab Manual
SUBMITTEDTO:
ENGR.M.JUNAID
SUBMITTEDBY:
ASAD NAEEM
2006-RCET-EE-22
POWERSYSTEMANALYSISLABMANUAL
01
To plot the daily load curve for the given data using MATLAB
02
03
04
05
06
07
ASADNAEEM
2006RCETEE22
To study the Concept of Modifications of an Existing BusImpedance Matrix & Implementing in MATLAB
POWERSYSTEMANALYSISLABMANUAL
08
09
10
11
12
13
14
15
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
EXPERIMENT#01
Toplotthedailyloadcurveforthegivendatausing
MATLAB
Givendata:
Intervalfrom
12A.M
2
6
9
12P.M
2
4
6
8
10
11
To
2A.M
6
9
12
2P.M
4
6
8
10
11
12A.M
Requirements:
1.
2.
3.
4.
Findaveragevalueofload
Findpeakvalueofload
Findtheloadfactor
Plottheloadcurve
ASADNAEEM
2006RCETEE22
LoadMW
6
5
10
15
12
14
16
18
16
12
6
POWERSYSTEMANALYSISLABMANUAL
Theory
Loads:
Loads of power systems are divided into three main categories that are
given below.
1. Industrial Loads
2. Commercial Loads
3. Residential Loads
Very large industrial loads are served through the transmission lines.
Large industrial loads are served directly from the sub-transmission
level. And small industrial loads are served directly from the primary
distribution network. The industrial loads are composite loads and
induction motors from a high proportion of these loads. These
composite loads are functions of voltage and frequency and form a
major part of the system load. Commercial and residential load consist
largely of lighting, heating and cooling. These loads are independent of
frequency and consume negligibly small reactive power.
The real power of loads is expressed in terms of kilowatts or
megawatts. The magnitude of load varies throughout the day and
power must be available to the consumer on demand.
The daily load curve of a utility is a composite of demands made by
various classes of users. The greatest value of load during a twenty
four hours is called the peak or maximum demand. Smaller peaking
generators may be commissioned to meet the peak load that occurs
for only a few hours. In order to asses the usefulness of the generating
plant the load factor is defined.
The load factor is the ratio of average load over a designated period of
time to the peak load occurring in that period. Load factor may be
given for a day, a month or an year. Yearly or annual load factor is the
most useful since a year represents a full cycle of time. The daily load
factor is
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
Matlab code:
data=[0 2 6;
2 6 5;
6 9 10;
9 12 15;
12 14 12;
14 16 14;
16 18 16;
18 20 18;
20 22 16;
22 23 12;
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
23 24 6];
p=data(:,3);
Dt=data(:,2)-data(:,1);
w=p'*Dt;
pavg=w/sum(Dt)
peak=max(p)
LF=pavg/peak*100
L=length(data);
tt = [data(:,1) data(:,2)];
t = sort(reshape(tt, 1, 2*L));
for n = 1:L
pp(2*n-1)=p(n);
pp(2*n)=p(n);
end
plot(t,pp)
xlabel('TIME,Hr'),ylabel('P,MW')
Matlab results:
pavg=11.5417
peak=18
LF=64.1204
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
18
16
14
P,MW
12
10
4
0
10
15
20
25
TIME,Hr
COMMENTS:
In this experiment we learn how to find the daily load curve
for any power system using MATLAB. Load curve is very
important as we can achieve very important information
from it like:
Peak load
Average load
Load factor
These quantities are very helpful for understanding any
power system.
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
EXPERIMENT#02
IntroductiontobasicsofElectricalTransientsAnalyzer
Program(ETAP)
What is ETAP?
ETAP is the most comprehensive analysis platform for the design,
simulation, operation, control, optimization, and automation of
generation, transmission, distribution, and industrial power systems.
Project Toolbar
TheProjectToolbarcontainsiconsthatallowyoutoperformshortcutsofmany
commonlyusedfunctionsinPowerStation.
Create
Createanewprojectfile
Open
Openanexistingprojectfile
Save
Savetheprojectfile
PrinttheonelinediagramorU/Gracewaysystem
Cut
CuttheselectedelementsfromtheonelinediagramorU/Graceway
systemtotheDumpster
Copy
CopytheselectedelementsfromtheonelinediagramorU/Graceway
systemtotheDumpster
Paste
raceway
PasteelementsfromaDumpsterCelltotheonelinediagramorU/G
system
ZoomIn
MagnifytheonelinediagramorU/Gracewaysystem
ZoomOut
ReducetheonelinediagramorU/Gracewaysystem
ZoomtoFitPage
Resizetheonelinediagramtofitthewindow
CheckContinuity
Checkthesystemcontinuityfornonenergizedelements
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
PowerCalculator
Help
ActivatePowerStationCalculatorthatrelatesMW,MVAR,MVA,
kV,Amp,andPFtogetherwitheitherkVAorMVAunits
PointtoaspecificareatolearnmoreaboutPowerStation
Mode Toolbar
ETAPoffersasuiteoffullyintegratedsoftwaresolutionsincludingarcflash,loadflow,
shortcircuit,transientstability,relaycoordination,cableampacity,optimalpowerflow,
andmore.Itsmodularfunctionalitycanbecustomizedtofittheneedsofanycompany,
fromsmalltolargepowersystems.
EditMode
Editmodeenablesyoutobuildyouronelinediagram,changesystemconnections,edit
engineeringproperties,saveyourproject,andgenerateschedulereportsinCrystal
Reportsformats.TheEditToolbarsforbothACandDCelementswillbedisplayedtothe
rightofthescreenwhenthismodeisactive.Thismodeprovidesawidevarietyoftasks
including:
Drag&DropElements
ConnectElements
ChangeIDs
Cut,Copy,&PasteElements
MovefromDumpster
InsertOLEObjects
Cut,Copy&OLEObjects
MergePowerStationProject
Hide/ShowGroupsofProtectiveDevices
RotateElements
SizeElements
ChangeSymbols
EditProperties
RunScheduleReportManager
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
Example implementation:
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
EXPERIMENT#03
Evaluatethevalueofvoltagesfora4BUSsystemusing
nodeequationsinMATLAB
REACTANCE DIAGRAM
In the first step, we draw the reactance diagram of the given
one-line diagram as shown below:
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
SOURCE TRANSFORM
After making the reactance diagram, we apply source
transformation on the given network by replacing the
voltage sources with current sources
Replace all the reactance by admittances using the
relation:
Y=1/X
The resultant diagram now can be shown as:
NODE EQUATIONS
Now, using the above figure write the node equations of the
system:
Applying KCL at node-1:
I1= (V1-0) y10 + (V1-V4) y14+ (V1-V3) y13
I1= (y10+y14+y13) V1 + 0V2 + (-y13) V3+ (-y14) V4
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
Where:
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
CALCULATIONS
MATLAB CODE
YBUS=
[0-9.80i
0+4.00i
0+5.00i;
0-8.30i
0+2.50i
0+5.00i;
0+4.00i
0+2.50i
0-15.30i
0+8.00i;
0+5.00i
0+5.00i
0+8.00i
0-18.00i];
MATLAB RESULTS
V=
1.4111 - 0.2668i
1.3831 - 0.3508i
1.4059 - 0.2824i
1.4010 - 0.2971i
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
COMMENTS:
In this experiment we learn that using the bus impedance or
admittance matrix we can find the voltages and currents for
all buses of a given power system.
Moreover, we use MATLAB for the calculation of these
quantities by just entering the bus impedance matrix and
one given quantity (current or voltage) and MATLAB gives
the results of very complex networks within no time.
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
EXPERIMENT#04
ModelingandLoadflowanalysisofRCETpower
distributionnetworkusingETAP
INTRODUCTION:
POWERSYSTEMANALYSISLABMANUAL
Report Manager
STEPS
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
OLD BUILDING:
NEW BUILDING:
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
HOSTEL-A,B:
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
HOSTEL-E:
COMMENTS:
In this experiment we learn how to:
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
EXPERIMENT#05
Buseliminationofa4BUSsystemusingMATLAB
REACTANCE DIAGRAM
It is given that the transformer and generator at bus-3 are
disconnected, so the reactance diagram now becomes:
SOURCE TRANSFORM
After making the reactance diagram, we apply source
transformation on the given network by replacing the
voltage sources with current sources
Replace all the reactance by admittances using the
relation:
Y=1/X
The resultant diagram now can be shown as:
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
Part1:EliminationofBus3&4
MATRIX FORM
Where:
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
MATLAB CODE
>>YBUS= [0-9.80i 0
0+4.00i
0+5.00i;
0-8.30i
0+2.50i
0+5.00i;
0+4.00i
0+2.50i
0-14.5i
0+8.00i;
0+5.00i
0+5.00i
0+8.00i
0-18.00i];
MATLAB RESULTS
Ybus =
0 - 4.8736i
0 + 4.0736i
0 + 4.0736i
0 - 4.8736i
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
MATLAB CODE:
>>Ybus=[-9.8i
4.0i
5i;
-8.3i
2.5i
5i;
4i
2.5i
-14.5i
8i;
5i
5i
8i
-18i];
MATLAB RESULTS
A=
0 -11.1889i
0 - 1.3889i
0 + 1.7778i
0 - 1.3889i
0 - 9.6889i
0 + 0.2778i
0 + 1.7778i
0 + 0.2778i
0 -18.0556i
MATLAB CODE:
>>P=[-11.1889i -1.3889i;-1.3889i -9.6889i];
>>Q=[1.7778i;0.2778i];
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
>>R=[-18.0556i];
>>S=Q';
>>T=inv(R);
>>B=P-Q*T*S
MATLAB RESULTS
B=
0 -11.3639i
0 - 1.4163i
0 - 1.4163i
0 - 9.6932i
COMMENTS:
Bus impedance matrix is a very important tool for the
calculation of voltages and currents at all the buses of a
given network. Suppose that any fault occurs in the power
system then we can get a task to modify the bus impedance
matrix by eliminating the faulty node which will reduce the
order of matrix by eliminating the faulty node.
In this experiment we learn how to:
Eliminate last two nodes together
Eliminate only one last node
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
EXPERIMENT#06
TostudytheConceptofModificationsofanExistingBus
ImpedanceMatrix&ImplementinginMATLAB
IMPEDANCE MATRIX
Impedance matrix is a very important tool in power system
analysis. Using this matrix we can find:
Voltages at all buses when currents are given
Currents at all buses when voltages are given
So it is very important that how to modify the bus
impedance matrix when any new impedance is add into the
original system.
Suppose a power system with n-buses having the
impedances matrix of order n*n:
There are four cases that can take place while adding a new
impedance Zb in the system:
Adding
Adding
Adding
Adding
ASADNAEEM
2006RCETEE22
Zb
Zb
Zb
Zb
POWERSYSTEMANALYSISLABMANUAL
MODIFICATION CASES
CASE1:ADDINGZbFROMANEWBUSTOREFERENCEBUS
This condition is explained in the following diagram:
Clearly,
Vp-0=Ib*Zb
Vp=Ib*Zb
Hence the modified matrix will take the form as:
MATLAB CODE
function [Z]=Case1(Zorg,Zb)
Zorg=[1 2 3 4;2 5 6 7;3 6 8 9;4 7 9 10]
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
Zb=17;
l=length(Zorg);
for i=1:l+1
for j=1:l+1
if i<=l && j<=l
Znew(i,j)=Zorg(i,j);
elseif i==l+1 && j==l+1
Znew(i,j)=Zb;
else
Znew(i,j)=0;
end
end
end
Znew
MATLAB RESULTS
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
CASE2:ADDINGZbFROMANEWBUSPTOANEXISTINGBUSK
This condition is explained in the following diagram:
Clearly,
Vp-Vk,new=Ip*Zb
Vp=Vk,new+Ip*Zb
Where,
Vk,new=Vk,org+Ip*Zkk
Vp= Vk,org+Ip(Zkk+Zb)
Hence the modified matrix will take the form as:
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
MATLAB CODE:
function [Z]=CASE2(Zorg,Zb)
Zorg=[1 2 3 4;2 5 6 7;3 6 8 9;4 7 9 10]
Zb=5;
l=length(Zorg);
row =Zorg(l,:);
column =Zorg(:,l);
for i=1:l+1
for j=1:l+1
if i<=l && j<=l
Znew(i,j)=Zorg(i,j);
elseif i==l+1
for p=1:l
Znew(i,p)=row(p);
end
elseif j==l+1
for q=1:l
Znew(q,j)=column(q);
end
end
if i==l+1 && j==l+1
Znew(i,j)=Zb+Zorg(l,l);
end
end
end
Znew
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
MATLAB RESULTS
CASE3:ADDINGZbFROMANEXISTINGBUSKTOREFERENCE
BUS
This condition is explained in the following diagram:
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
Here we can apply the same case as in case-2 and then put
Vp=0. This task can be achieved by eliminating the last row
and column of the Znew matrix.
MATLAB CODE:
function [Z]=CASE3(Zorg,Zb)
Zorg=[1 2 3 4;2 5 6 7;3 6 8 9;4 7 9 10]
Zb=5;
l=length(Zorg);
row =Zorg(l,:);
column =Zorg(:,l);
for i=1:l+1
for j=1:l+1
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
POWERSYSTEMANALYSISLABMANUAL
end
for a=1:l
L(a,1)=Znew(a,5);
end
M=Znew(l+1,l+1);
P=L';
T=inv(M);
Zwithnewbusrefferenced=K-L*T*P
MATLAB RESULTS
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
CASE4:ADDINGZbBETWEENTWOEXISTINGBUSES
This condition is explained in the following diagram:
In this case,
Zbb=Zb+Zjj+Zkk-2Zjk
Hence the modified matrix will take the form as:
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
MATLAB CODE:
function [Z]=CASE4(Zorg,Zb)
Zorg=[1 2 3 4;2 5 6 7;3 6 8 9;4 7 9 10]
Zb=5;
l=length(Zorg);
R1 =Zorg(l,:);
C1 =Zorg(:,l);
R2 =Zorg(l-1,:);
C2 =Zorg(:,l-1);
for i=1:l+1
for j=1:l+1
if i<=l && j<=l
Znew(i,j)=Zorg(i,j);
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
elseif i==l+1
for p=1:l
Znew(i,p)=R1(p)-R2(p);
End
elseif j==l+1
for q=1:l
Znew(q,j)=C1(q)-C2(q);
End
End
if i==l+1 && j==l+1
Znew(i,j)=Zb+Zorg(l,l)+Zorg(l-1,l-1)-(2*Zorg(l,l-1));
end
end
end
Znew
for a=1:l
for b=1:l
K(a,b)=Znew(a,b);
end
end
for a=1:l
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
L(a,1)=Znew(a,5);
end
M=Znew(l+1,l+1);
P=L';
T=inv(M);
Zfinal=K-L*T*P
MATLAB RESULTS
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
COMMENTS:
Bus impedance matrix is a very important tool for the
calculation of voltages and currents at all the buses of a
given network. Suppose that any improvement occurs in the
power system then we can get a task to modify the bus
impedance matrix by adding the new impedance in the
system. The new impedance can be added in four different
conditions:
Addition of new
bus
Addition of new
bus
Addition of new
reference bus
Addition of new
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
EXPERIMENT#07
ApplicationofGaussSiedalandNewtonRaphsonmethodforload
flowstudiesonathreebussystemusingMATLAB(Implimentation
ofexample#6.7,6.8&6.10fromPOWERSYSTEMANALYSISbyHadi
Saadat)
EXAMPLE 6.7
Given figure shows the one line diagram of a simple three
bus system with generation at bus-1. The magnitude of
voltage at bus-1 is adjusted to 1.05 per unit. The scheduled
loads at buses-2 and 3 are as marked on the diagram. Line
impedances are marked in per unit on a 100-MVA base and
the line charging susceptances are neglected.
POWERSYSTEMANALYSISLABMANUAL
SOLUTION
Line impedances are converted to admittances:
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
GAUSS-SIEDEL FARMULA
SLACK1=conj(V1)*[V1*(y12+y13)-( y12*V2+y13*V3)]
Sij=Vi*conj(Iij)
Iij=yij*(Vi-Vj)
MATLAB CODE
y12=10-j*20;
y13=10-j*30;
y23=16-j*32;
V1=1.05+j*0;
%CODE FOR PART-A
iter=0;
s2=-2.566-j*1.102;
s3=-1.386-j*0.452;
V2=1+j*0.0;
V3=1+j*0.0;
for I=1:10;
iter=iter+1;
V2=(conj(s2)/conj(V2)+y12*V1+y23*V3)/(y12+y23);
V3=(conj(s3)/conj(V3)+y13*V1+y23*V2)/(y13+y23);
end
V2
V3
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
MATLAB RESULTS
PART-A RESULTS
V2 =
0.9800 - 0.0600i
V3 =
1.0000 - 0.0500i
PART-B RESULTS
SLACK-BUS POWER
Pslack = 4.0949 - 1.8900i
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
PART-C RESULTS
I12 =
1.9000 - 0.8000i
2.0000 - 1.0000i
0.6400 - 0.4800i
LINE FLOWS
s12 =
1.9950 + 0.8400i
2.1000 + 1.0500i
0.6640 + 0.4480i
LINE LOSSES
SL12 =
0.0850 + 0.1700i
SL13 =
0.0500 + 0.1500i
SL23 =
0.0080 + 0.0160i
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
EXAMPLE 6.8
Given figure shows the one line diagram of a simple three
bus system with generators at buses-1 and 3. The
magnitude of voltage at bus-1 is adjusted to 1.05pu. voltage
magnitude at bus-3 is fixed at 1.04 pu with a real power
generation of 200MW. A load consisting of 400MW and
250MVAR is taken from bus-2. Line impedances are marked
in per unit on a 100MVA base, and the line charging
susceptances are neglected. Obtain the power flow solution
by the Gauss-Siedal method including line flows and line
losses.
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
FARMULAS
S3=conj(V3)*(y33*V3-y13*V1-y23*V2)
Q3=-imag(conj(V3)*(y33*V3-y13*V1-y23*V2))
MATLAB CODE
y12=10-j*20;
y13=10-j*30;
y23=16-j*32;
y33=y13+y23;
V1=1.05+j*0;
format long
iter=0;
s2=-4.0-j*2.5;
p3=2;
V2=1+j*0.0;
Vm3=1.04;
V3=1.04+j*0;
for I=1:10;
iter=iter+1;
E2=V2;
E3=V3;
V2=(conj(s2)/conj(V2)+y12*V1+y23*V3)/(y12+y23)
DV2=V2-E2;
Q3=-imag(conj(V3)*(y33*V3-y13*V1-y23*V2))
s3=p3+j*Q3;
Vc3=(conj(s3)/conj(V3)+y13*V1+y23*V2)/(y13+y23);
Vi3=imag(Vc3);
Vr3=sqrt(Vm3^2-Vi3^2);
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
V3=Vr3+j*Vi3
DV3=V3-E3;
end
V2
V3
Q3
format short
I12=y12*(V1-V2);
I21=-I12;
I13=y13*(V1-V3);
I31=-I13;
I23=y23*(V2-V3);
I32=-I23;
s12=V1*conj(I12);
s21=V2*conj(I21);
s13=V1*conj(I13);
s31=V3*conj(I31);
s23=V2*conj(I23);
s32=V3*conj(I32);
I1221=[I12,I21];
I1331=[I13,I31];
I2332=[I23,I32];
SL12=s12+s21
SL13=s13+s31
SL23=s23+s32
S1=(s12+s13)
S2=(s23+s21)
S3=(s31+s32)
S12=s12
S21=s21
S13=s13
S31=s31
S23=s23
S32=s32
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
MATLAB RESULTS
ITERATIONRESULTS:
1STITERATION
V2 = 0.974615384615385 - 0.042307692307692i
Q3 = 1.160000000000002
V3 = 1.039987148574197 - 0.005170183798502i
2NDITERATION
V2 = 0.971057059512953 - 0.043431876337850i
Q3 = 1.387957731052817
V3 = 1.039974378708180 - 0.007300111679686i
3RDITERATION
V2 = 0.970733708554698 - 0.044791724463619i
Q3 = 1.429040300785471
V3 = 1.039966679445820 - 0.008325001047174i
4THITERATION
V2 = 0.970652437281433 - 0.045329920732880i
Q3 = 1.448333275594840
V3 = 1.039963173621928 - 0.008752000354604i
5THITERATION
V2 = 0.970623655331095 - 0.045554240372625i
Q3 = 1.456209166612119
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
V3 = 1.039961668920058 - 0.008929007616053i
6THITERATION
V2 = 0.970612037114234 - 0.045646940090561i
Q3 = 1.459469889628077
V3 = 1.039961037734205 - 0.009002221658867i
7THITERATION
V2 = 0.970607253520093 - 0.045685276728252i
Q3 = 1.460818201396914
V3 = 1.039960775170297 - 0.009032502820155i
8THITERATION
V2 = 0.970605276281561 - 0.045701131870879i
Q3 = 1.461375872168914
V3 = 1.039960666313617 - 0.009045027392915i
9THITERATION
V2 = 0.970604458527297 - 0.045707689707255i
Q3 = 1.461606535170454
V3 = 1.039960621244008 - 0.009050207830587i
10THITERATION
V2 = 0.970604120282796 - 0.045710402176455i
Q3 = 1.461701943643423
V3 = 1.039960602594413 - 0.009052350604469i
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
FINALRESULTS:
V2 = 0.970604120282796 - 0.045710402176455i
V3 = 1.039960602594413 - 0.009052350604469i
Q3 = 1.461701943643423
SL12 = 0.0839 + 0.1679i
SL13 = 0.0018 + 0.0055i
SL23 = 0.0985 + 0.1969i
S1 = 2.1841 + 1.4085i
S2 = -3.9999 - 2.5000i
S3 = 2.0000 + 1.4618i
S12 = 1.7936 + 1.1874i
S21 = -1.7096 - 1.0195i
S13 = 0.3906 + 0.2212i
S31 = -0.3887 - 0.2157i
S23 = -2.2903 - 1.4805i
S32 = 2.3888 + 1.6775i
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
EXAMPLE 6.10
Given figure shows the one line diagram of a simple three
bus system with generators at buses-1 and 3. The
magnitude of voltage at bus-1 is adjusted to 1.05pu. voltage
magnitude at bus-3 is fixed at 1.04 pu with a real power
generation of 200MW. A load consisting of 400MW and
250MVAR is taken from bus-2. Line impedances are marked
in per unit on a 100MVA base, and the line charging
susceptances are neglected. Obtain the power flow solution
by the Newton-Raphson method including line flows and line
losses.
-10+j20
-10+j30
POWERSYSTEMANALYSISLABMANUAL
-10+j20
26-j52
-10+j30
-16+j32
-16+j32
26-j62];
FARMULAS
P1=V1^2*Y11*cos(11)+V1*V2*Y12*cos(12-d1+d2)+...
V1*V3*Y13*cos(13-d1+d3)
Q1=-V1^2*Y11*sin(11)-V1*V2*Y12*sin(12-d1+d2)-...
V1*V3*Y13*sin(13-d1+d3)
Q3=-V3*V1*Y31*sin(31)-d3+d1)-V3*V2*Y32*...
sin(32-d3+d2)-V3^2*Y33*sin33
MATLAB CODE
V=[1.05;1.0;1.04];
d=[0;0;0];
Ps=[-4;2.0];
Qs=-2.5;
YB=[20-j*50 -10+j*20 -10+j*30
-10+j*20 26-j*52 -16+j*32
-10+j*30 -16+j*32 26-j*62];
Y=abs(YB);
t=angle(YB);
iter=0;
pwracur=0.00025;
%power accuracy
DC=10;
%set the maximun power residue to a high value
while max(abs(DC))>pwracur
iter=iter+1
P=[V(2)*V(1)*Y(2,1)*cos(t(2,1)d(2)+d(1))+V(2)^2*Y(2,2)*cos(t(2,2))+...
V(2)*V(3)*Y(2,3)*cos(t(2,3)-d(2)+d(3));
V(3)*V(1)*Y(3,1)*cos(t(3,1)d(3)+d(1))+V(3)^2*Y(3,3)*cos(t(3,3))+...
V(3)*V(2)*Y(3,2)*cos(t(3,2)-d(3)+d(2))];
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
Q=-V(2)*V(1)*Y(2,1)*sin(t(2,1)-d(2)+d(1))V(2)^2*Y(2,2)*sin(t(2,2))-...
V(2)*V(3)*Y(2,3)*sin(t(2,3)-d(2)+d(3));
J(1,1)=V(2)*V(1)*Y(2,1)*sin(t(2,1)-d(2)+d(1))+...
V(2)*V(3)*Y(2,3)*sin(t(2,3)-d(2)+d(3));
J(1,2)=-V(2)*V(3)*Y(2,3)*sin(t(2,3)-d(2)+d(3));
J(1,3)=V(1)*Y(2,1)*cos(t(2,1)d(2)+d(1))+2*V(2)*Y(2,2)*cos(t(2,2))+...
V(3)*Y(2,3)*cos(t(2,3)-d(2)+d(3));
J(2,1)=-V(3)*V(2)*Y(3,2)*sin(t(3,2)-d(3)+d(2));
J(2,2)=V(3)*V(1)*Y(3,1)*sin(t(3,1)-d(3)+d(1))+...
V(3)*V(2)*Y(3,2)*sin(t(3,2)-d(3)+d(2));
J(2,3)=V(3)*Y(2,3)*cos(t(3,2)-d(3)+d(2));
J(3,1)=V(2)*V(1)*Y(2,1)*cos(t(2,1)-d(2)+d(1))+...
V(2)*V(3)*Y(2,3)*cos(t(2,3)-d(2)+d(3));
J(3,2)=-V(2)*V(3)*Y(2,3)*cos(t(2,3)-d(2)+d(3));
J(3,3)=-V(1)*Y(2,1)*sin(t(2,1)-d(2)+d(1))-2*V(2)*Y(2,2)
*sin(t(2,2)) ...
V(3)*Y(2,3)*sin(t(2,3)-d(2)+d(3));
DP=Ps-P;
DQ=Qs-Q;
DC=[DP;DQ]
J
DX=J\DC
d(2)=d(2)+DX(1);
d(3)=d(3)+DX(2);
V(2)=V(2)+DX(3);
V, d, delta=180/pi*d;
end
P1=V(1)^2*Y(1,1)*cos(t(1,1))+V(1)*V(2)*Y(1,2)*cos(t(1,2)d(1)+d(2))+...
V(1)*V(3)*Y(1,3)*cos(t(1,3)-d(1)+d(3))
Q1=-V(1)^2*Y(1,1)*sin(t(1,1))-V(1)*V(2)*Y(1,2)*sin(t(1,2)d(1)+d(2))-...
V(1)*V(3)*Y(1,3)*sin(t(1,3)-d(1)+d(3))
Q3=-V(3)*V(1)*Y(3,1)*sin(t(3,1)-d(3)+d(1))-V(3)*V(2)*Y(3,2)*...
sin(t(3,2)-d(3)+d(2))-V(3)^2*Y(3,3)*sin(t(3,3))
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
MATLAB RESULTS
1STITERATION
DC =
-2.8600
1.4384
-0.2200
J=
54.2800 -33.2800
24.8600
-33.2800
66.0400 -16.6400
-27.1400
16.6400
DX =
-0.0453
-0.0077
-0.0265
V=
1.0500
0.9735
1.0400
d=
-0.0453
-0.0077
ASADNAEEM
2006RCETEE22
49.7200
POWERSYSTEMANALYSISLABMANUAL
2NDITERATION
DC =
-0.0992
0.0217
-0.0509
J=
51.7247 -31.7656
21.3026
-32.9816
65.6564 -15.3791
-28.5386
17.4028
DX =
-0.0018
-0.0010
-0.0018
V=
1.0500
0.9717
1.0400
d=
0
-0.0471
-0.0087
ASADNAEEM
2006RCETEE22
48.1036
POWERSYSTEMANALYSISLABMANUAL
3RDITERATION
DC =
1.0e-003 *
-0.2166
0.0382
-0.1430
J=
51.5967 -31.6939
21.1474
-32.9339
65.5976 -15.3516
-28.5482
17.3969
DX =
1.0e-005 *
-0.3856
-0.2386
-0.4412
V=
1.0500
0.9717
1.0400
d=
-0.0471
-0.0087
ASADNAEEM
2006RCETEE22
47.9549
POWERSYSTEMANALYSISLABMANUAL
FINALRESULTS:
P1 =
2.1842
Q1 =
1.4085
Q3 =
1.4618
COMMENTS:
Power system calculations are mostly very complex for large
power systems. To analyze such power systems, there are
two very important iterative methods:
Gauss Siedel Method
Newton Raphson method
In this experiment we learn how to apply these two methods
using MATLAB.
Gauss-Seidel iteration has two advantages:
While Newton Raphson method is readily applied to nonlinear equations, and can use finite-difference estimates
of the derivatives to evaluate the gradients.
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
EXPERIMENT#08
HarmonicLoadModelingusingbuiltinanduserdefined
modelsofETAP
HARMONIC ANALYSIS
Becauseofthewideandeverincreasingapplicationsofpower
electronicdevices,suchasvariablespeeddrives,uninterruptible
powersupplies(UPS),staticpowerconverters,etc.,powersystem
voltageandcurrentqualityhasbeenseverelyaffectedinsome
areas.Intheseareascomponentsotherthanthatoffundamental
frequencycanbefoundtoexistinthedistortedvoltageand
currentwaveforms.Thesecomponentsusuallyaretheinteger
multipliersofthefundamentalfrequency,calledharmonics.In
additiontoelectronicdevices,someothernonlinearloads,or
devicesincludingsaturatedtransformers,arcfurnaces,
fluorescentlights,andcycloconvertersarealsoresponsibleforthe
deteriorationinpowersystemquality.
HARMONIC SOURCES
Thefollowingcomponentscanbemodeledasaharmonicvoltage
sourceinPowerStation:
PowerGrid
SynchronousGenerator
Inverter
Charger/Converter
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
StaticLoad
IMPORTANT DEFINITIONS
Transients
Thetermtransienthaslongbeenusedintheanalysisofpower
systemvariationstodenoteaneventthatisundesirableand
momentaryinnature.Transientisthatpartofthechangeina
variablethatdisappearsduringtransitionfromonesteadystate
operatingconditiontoanother.
Impulsive transient
Animpulsivetransientisasudden;nonpowerfrequencychange
inthesteadystateconditionofvoltage,current,orboththatis
unidirectionalinpolarity(primarilyeitherpositiveornegative).
Oscillatory transient
Anoscillatorytransientisasudden,nonpowerfrequencychange
inthesteadystateconditionofvoltage,current,orboth,that
includesbothpositiveandnegativepolarityvalues.
Long-Duration Voltage Variations
Longdurationvariationsencompassrootmeansquare(rms)
deviationsatpowerfrequenciesforlongerthan1minute.
Overvoltage
Anovervoltageisanincreaseinthermsacvoltagegreaterthan
110percentatthepowerfrequencyfordurationlongerthan1
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
min.Overvoltagesareusuallytheresultsofloadswitching(e.g.,
switchingoffalargeloadorenergizingacapacitorbank).
Under voltage
Anundervoltageisadecreaseinthermsacvoltagetolessthan
90percentatthepowerfrequencyforadurationlongerthan1
min.Undervoltagesaretheresultsofswitchingeventsthatare
theoppositeoftheeventsthatcauseovervoltages.
Short-Duration Voltage Variations
ThiscategoryencompassestheIECcategoryofvoltagedipsand
shortinterruptions.Eachtypeofvariationcanbedesignatedas
instantaneous,momentary,ortemporary,dependingonits
duration.
Shortdurationvoltagevariationsarecausedbyfaultconditions,
theenergizationoflargeloadswhichrequirehighstarting
currents,orintermittentlooseconnectionsinpowerwiring.
Interruption
Aninterruptionoccurswhenthesupplyvoltageorloadcurrent
decreasestolessthan0.1puforaperiodoftimenotexceeding1
min.
Sags (dips)
Sagisadecreasetobetween0.1and0.9puinrmsvoltageor
currentatthepowerfrequencyfordurationsfrom0.5cycleto1
min.
Swells
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
Aswellisdefinedasanincreasetobetween1.1and1.8puinrms
voltageorcurrentatthepowerfrequencyfordurationsfrom0.5
cycleto1min.
Voltage Imbalance
Voltageimbalance(alsocalledvoltageunbalance)issometimes
definedasthemaximumdeviationfromtheaverageofthethree
phasevoltagesorcurrents,dividedbytheaverageofthethree
phasevoltagesorcurrents,expressedinpercent.
Waveform Distortion
Waveformdistortionisdefinedasasteadystatedeviationfrom
anidealsinewaveofpowerfrequencyprincipallycharacterized
bythespectralcontentofthedeviation.
Harmonics
Harmonicsaresinusoidalvoltagesorcurrentshavingfrequencies
thatareintegermultiplesofthefrequencyatwhichthesupply
systemisdesignedtooperate(termedthefundamental
frequencyusually50or60Hz).
Interharmonics
Voltagesorcurrentshavingfrequencycomponentsthatarenot
integermultiplesofthefrequencyatwhichthesupplysystemis
designedtooperate(e.g.,50or60Hz)arecalledInterharmonics.
Odd harmonics
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
Voltagesorcurrentshavingfrequencycomponentsthatareodd
integermultiplesofthefrequencyatwhichthesupplysystemis
designedtooperate(e.g.,50or60Hz)arecalledoddharmonics.
Even harmonics
Voltagesorcurrentshavingfrequencycomponentsthatareeven
integermultiplesofthefrequencyatwhichthesupplysystemis
designedtooperate(e.g.,50or60Hz)arecalledevenharmonics.
Voltage Fluctuation
Voltagefluctuationsaresystematicvariationsofthevoltage
envelopeoraseriesofrandomvoltagechanges,themagnitudeof
whichdoesnotnormallyexceedthevoltagerangesspecifiedby
ANSIC84.1of0.9to1.1pu.
Power Frequency Variations
Powerfrequencyvariationsaredefinedasthedeviationofthe
powersystemfundamentalfrequencyfromitspecifiednominal
value(e.g.,50or60Hz).
Power factor, displacement
Thepowerfactorofthefundamentalfrequencycomponentsof
thevoltageandcurrentwaveforms
Power factor (true)
Theratioofactivepower(watts)toapparentpower(volt
amperes)
Total harmonic distortion (THD)
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
Theratiooftherootmeansquareoftheharmoniccontenttothe
rmsvalueofthefundamentalquantity,expressedasapercentof
thefundamental.
Triplen harmonics
Atermfrequentlyusedtorefertotheoddmultiplesofthethird
harmonic,whichdeservespecialattentionbecauseoftheir
naturaltendencytobezerosequence.
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ROCKWELL (12-Pulse-VFD)
ROCKWELL (18-Pulse-VFD)
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ROCKWELL (6-Pulse-VFD)
TOSHIBA (PWM-ASD)
TYPICAL (LCI)
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
TYPICAL-IEEE (12-Pulse1)
TYPICAL-IEEE (12-Pulse2)
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
TYPICAL-IEEE (18-Pulse-CT)
TYPICAL-IEEE (18-Pulse-VT)
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
TYPICAL-IEEE (6-Pulse1)
TYPICAL-IEEE (6-Pulse2)
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
TYPICAL-IEEE (Fluorescent)
TYPICAL-IEEE (Large-ASD)
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
TYPICAL-IEEE (SPC)
TYPICAL-IEEE (XFMR-Magnet)
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
COMMENTS
In this experiment, we learnt:
How to model a harmonic load using built-in models
How to built a user-defined harmonic model
How to model a harmonic load using user-defined
models
So, ETAP is a very powerful tool for harmonic analysis of any
power distribution network.
EXPERIMENT#09
Impactofpersonalcomputerloadonpowerdistribution
networkofRCET
Harmonics
Harmonicsaresinusoidalvoltagesorcurrentshavingfrequencies
thatareintegermultiplesofthefrequencyatwhichthesupply
systemisdesignedtooperate(termedthefundamental
frequencyusually50or60Hz).
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
PC LOAD THDS
Harmonic No.
rd
%THD
91.63
5th
86.61
7th
69.87
th
44.76
11th
54.81
13th
46.44
15th
46.44
th
17
33.05
19th
24.70
23rd
11.74
th
25
7.900
29th
5.120
%THD
178.97
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
POWERSYSTEMANALYSISLABMANUAL
BUS-5:
BUS-11:
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
BUS-27:
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
BUS-33:
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
POWERSYSTEMANALYSISLABMANUAL
CABLE-2:
CABLE-7:
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
CABLE-11:
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
CABLE-18:
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
COMMENTS
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
EXPERIMENT#10
Flowoftriplenharmonics(zerosequenceharmonics)
during5differentschemesofconnectionfora3phase
transformerwithpresenceoflargenonlinearloadusing
ETAP
Harmonic No.
3rd
ASADNAEEM
2006RCETEE22
%THD
91.63
POWERSYSTEMANALYSISLABMANUAL
5th
86.61
7th
69.87
9th
44.76
11th
54.81
th
13
46.44
15th
46.44
17th
33.05
th
19
24.70
23rd
11.74
25th
7.900
th
5.120
29
%THD
178.97
SECONDARY SIDE
Y-Grounded
Y-Grounded
Y-Grounded
Y-Ungrounded
Delta
Y-Ungrounded
Y-Grounded
Delta
Delta
Delta
1
2
3
4
5
POWERSYSTEMANALYSISLABMANUAL
CASE-1:
Transformer primary side Y-Grounded and
secondary Y-Ungrounded
VOLTAGE SPECTRA ON LT-SIDE
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
OBSERVATIONS:
Harmonic source is connected on the LT side of transformer,
so the triplen harmonics are blocked due to ungrounded Yconnection. The magnitude of remaining harmonic
components is reduced on the HT side of transformer.
CASE-2:
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
OBSERVATIONS:
Harmonic source is connected on the LT side of transformer,
so the triplen harmonics are not blocked due to grounded Yconnection. The triplen harmonics are also present on the HT
side of transformer as that is also Y-grounded.
CASE-3:
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
OBSERVATIONS:
Harmonic source is connected on the LT side of transformer,
so the triplen harmonics are blocked due to deltaconnection. The triplen harmonics are also blocked on the
HT side of transformer as there are no triplen harmonics on
secondary side of transformer.
CASE-4:
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
OBSERVATIONS:
Harmonic source is connected on the LT side of transformer,
so the triplen harmonics are blocked due to deltaconnection. The triplen harmonics are also blocked on the
HT side of transformer as there are no triplen harmonics on
secondary side of transformer.
CASE-5:
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
OBSERVATIONS:
Harmonic source is connected on the LT side of transformer,
so the triplen harmonics are blocked due to deltaconnection. The triplen harmonics are also blocked on the
HT side of transformer as there are no triplen harmonics on
secondary side of transformer. Moreover, primary side is
also delta-connected.
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
EXPERIMENT#11
Threephaseshortcircuitanalysis(3phasefaultsdevice
duty)foragivenpowersystemusingETAP
Short-Circuit Toolbar
This toolbar is active when you are in Short-Circuit mode and
the standard is set to ANSI in the Short-Circuit Study Case
Editor.
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
POWERSYSTEMANALYSISLABMANUAL
FAULTY POINT
BUS-15
There is a short circuit fault on bus-15.
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
COMMENTS:
In this experiment, we use three phase fault-device duty
analysis to analyze the effect of fault on the system.
Following results are obtained in this experiment:
At bus-15:
Current
Power flow
Before fault
568A
345KW
After fault
4.8KA
3.6KW
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
EXPERIMENT#12
Threephaseshortcircuitanalysis(3phasefaults30cycle
network)foragivenpowersystemusingETAP
FAULTY POINT
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
BUS-15
There is a short circuit fault on bus-15.
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
COMMENTS:
In this experiment, we use three phase fault-device duty
analysis to analyze the effect of fault on the system.
Following results are obtained in this experiment:
At bus-15:
Current
Power flow
ASADNAEEM
2006RCETEE22
Before fault
568A
345KW
After fault
3.6KA
3.6KW
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
EXPERIMENT#13
Threephaseshortcircuitanalysis(LG,LL,LLG,&3Phase
FaultsCycle)foragivenpowersystemusingETAP
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
FAULTY POINT
BUS-15
There is a short circuit fault on bus-15.
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
COMMENTS:
In this experiment, we use three phase fault-device duty
analysis to analyze the effect of fault on the system.
Following results are obtained in this experiment:
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
At bus-15:
Current
Power flow
Before fault
568A
345KW
After fault
6.2KA
5.1KW
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
EXPERIMENT#14
Threephaseshortcircuitanalysis(LG,LL,LLG,&3Phase
Faults1.5to4Cycle)foragivenpowersystemusing
ETAP
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
FAULTY POINT
BUS-15
There is a short circuit fault on bus-15.
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
COMMENTS:
In this experiment, we use three phase fault-device duty
analysis to analyze the effect of fault on the system.
Following results are obtained in this experiment:
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
At bus-15:
Current
Power flow
Before fault
568A
345KW
After fault
5.7KA
5KW
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
EXPERIMENT#15
Threephaseshortcircuitanalysis(LG,LL,LLG,&3Phase
Faults30Cycle)foragivenpowersystemusingETAP
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
FAULTY POINT
BUS-15
There is a short circuit fault on bus-15.
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
COMMENTS:
In this experiment, we use three phase fault-device duty
analysis to analyze the effect of fault on the system.
Following results are obtained in this experiment:
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
At bus-15:
Current
Power flow
Before fault
568A
345KW
After fault
4.8KA
4.8KW
ASADNAEEM
2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
3phasefaults
deviceduty
3phasefaults30
cyclenetwork
LG,LL,LLG,&3
PhaseFaults
Cycle
LG,LL,LLG,&3
PhaseFaults1.5to
4Cycle
LG,LL,LLG,&3
PhaseFaults30
Cycle
ASADNAEEM
2006RCETEE22
CURRENT
POWER
4.8
3.6
3.6
3.6
6.2
5.1
5.7
4.8
4.8