You are on page 1of 38

Institute of Integrated Electrical Engineers of the Philippines, Inc.

41 Monte de Piedad St., Cubao, Quezon City

A Technical Report on

Differences in ANSI/IEEE and IEC


Short Circuit Calculations and Their Implications

___________________________________________________________________

Prepared by:

Institute of Integrated Electrical


Engineers, Inc. (IIEE) Standards Committee 2011
Differences in ANSI/IEEE and IEC
Short Circuit Calculations
and Their Implications

Prepared by:
IIEE Standards Committee
March 19, 2011

i
Disclaimer

It is not the intention of this paper to endorse over another the compared short-circuit
calculations and standards.

All discussions in this report are based on the featured system one line diagram only. The
same parameters were considered for the American National Standards Institute/Institute of
Electrical and Electronics Engineers (ANSI/IEEE) and the International Electro-technical
Commission (IEC) calculations for result comparison. The values of these parameters,
however, may vary from every project in terms of available utility short circuit levels, power
system configuration, wiring method and all applicable factors to consider.

IIEE and this Committee will not be responsible for any disputes that may arise out of
referencing from this paper.

ii
Preface

This technical report focuses on two of the most widely used short circuit calculation
methods and standards/guidelines namely: American National Standards Institute/Institute of
Electrical and Electronics Engineers (ANSI/C37/IEEE std 551) and the International Electro-
technical Commission (IEC 60909). To fully understand the analytical techniques of short
circuit current analysis in industrial and commercial power system using both methods, a
representative network model was exemplified and a comprehensive comparison between the
two calculation methods was presented. For expediency, a short circuit calculating software
was employed and the results were presented and evaluated at the end of the analysis.

This technical report provides information and inculcates awareness to electrical practitioners
in the country on the difference in the procedure of short circuit calculations and its
implication between the standards cited. It is not intended to show the detailed short circuit
current calculation for both methods. The reader is still recommended to consult technical
books for reference on a complete and accurate calculation procedure.

This paper starts off with a brief introduction on the current scenario in the Philippines and
the importance of short circuit calculation in Chapter I and expounds on its basic principle in
Chapter II. The equivalent short circuit schematic diagram is also available for analysis in
simple calculation.

Chapter III discusses the asymmetry current application focusing on the importance of
determining the total available short circuit current in the design of electrical equipment such
as circuit breakers, switches, transformers and fuses that are subjected to fault current.

Chapter IV shows the different components in determining the short circuit calculation based
on the two standard/guidelines, the ANSI/IEEE and the IEC. This is followed by Chapter V
presenting the comparative matrix on both standards Calculation Method and Multiplying
Factors with reference to the X/R ratio.

Chapter VI clearly tabulates a comparison between the standards parameters particularly the
device type, device capability and the calculated short circuit duty.

In Chapter VII, an illustration of a sample network was configured consisting of two power
transformers connected to a 13.2 kV bus wherein two different results from the ANSI/IEEE
and IEC calculations were generated with the aid of short circuit calculating software.

Chapter VIII presents the protective devices selection and evaluation focusing on the X/R
ratio for breaker evaluation and on the short circuit test parameters while Chapter IX
discusses the findings and results of the ETAP Total Bus Fault Short Circuit Study. The
tables on the short circuit calculation clearly show the difference in values for the same
parameters between ANSI/IEEE and IEC.

This technical report was developed through the initiative of the IIEE Standards Committee.
Any concern or contention as to its applicability, accuracy and completeness shall be
addressed to the Institute of Integrated Electrical Engineers of the Philippines, Inc. for further
validation and interpretation.

iii
Participants
The following are the working group members of the Institute of Integrated Electrical Engineers of the
Philippines, Inc. (IIEE) under the Standards Committee:

Chairman:

Gem J. Tan
Fuji-Haya Audit Inspection and Maintenance Corporation

Members:
Arjun G. Ansay Jesus C. Santos
Technological University of the Philippines Manila JC Santos and Associates

Arturo M. Zabala Marites R. Pangilinan


AC-DC-KV and Associates LJ Industrial Fabrication, Inc.

Edwin V. Pangilinan Roderick T. Khu


Total Power Box Solution, Inc. Airnergy and Renewables, Inc.

Frumencio T. Tan Samson D. Paden


Safety Consultant Department of Trade and Industry-
Bureau of Product Standards
Genesis A. Ramos
Department of Energy Vincent E. Jimenez
Delta Power Engineering and Consulting
Gideon S. Tan
Yu Eng Kao Electrical Supply and Hardware, Inc. Wilson T. Yu
Standards Committee Member
Jaime S. Jimenez
Meralco

Advisers:

Arthur A. Lopez
Private Consultant
IIEE former president - year 2000

Willington K.K.C. Tan


Columbia Wire and Cable Corporation
IIEE former president - year 1990

Approved by the members of the IIEE Board of Governors on March 19, 2011:

Armando R. Diaz, President Virgilio S. Luzares, Region II


Jules S. Alcantara, VP- Internal Affairs Roselyn C. Rocio, Region IV
Gregorio R. Cayetano, VP- External Affairs Ronaldo D. Ebrada, Region V
Alex C. Cabugao, VP- Technical Affairs Marlon T. Marcuelo, Region VI
Ma. Sheila C. Cabaraban, Secretary Lelanie T. Mirambel, Region VII
Larry C. Cruz, Treasurer Rey G. Paduganan, Region VIII
Florigo, C. Varona, Auditor Victorianito E. Teofilo, Region IX
Francis R. Calanio, Region I Gregorio Y. Guevarra, Immediate former President

iv
Table of Contents

Chapter
Title Page
I. Introduction 1

II. Basic Short-Circuit Discussion 1


Figure 1 : Current Model for Asymmetry 1
Figure 2 : Maximum Peak Asymmetrical Short Circuit Current 2

III. Asymmetry Current Application 2

IV. Short-Circuit Current Calculation Standard/Guideline 3

V. Calculation Comparison 3
Table 1 : Comparison Matrix of ANSI/IEEE and IEC 4

VI. Comparison of Device Duty Rating and Short-Circuit Duty 5


Table 2 : ANSI/IEEE Parameter 5
Table 3 : IEC Parameter 5
Table 4 : ANSI/IEEE vs. IEC Parameter 5

VII. Sample Calculation using ANSI/IEEE and IEC 6


Figure 3 : Single Line Diagram of the Sample Network 6
Figure 4 : Single Line Diagram to consider IEC SC Result 7
Figure 5 : Single Line Diagram to consider ANSI SC Result 16
Figure 6 : Impedance Diagram for ANSI/IEEE SC Method 23

VIII. Protective Devices Selection and Evaluation 26


Table 5 : Circuit Breakers Short Circuit Breaking Capacity 26
Table 6 : Circuit Breakers Interrupting Capacity 27

IX. Findings and Results 27


Table 7 : IEC Short Circuit Calculation 27
Table 8 : ANSI Short Circuit Calculation 27

X. Conclusion and Recommendation 28

XI. References 29

Appendix
ABB MCB S200 Technical Features 30

v
I. Introduction
In the emerging world market place, Electrical Engineers should be familiar with the basic differences between the
American National Standards Institute (ANSI) and the International Electro-technical Commission (IEC) with
regards to short circuit current calculation procedures. Both the ANSI and the IEC Standards developed these
procedures to provide rating for electrical equipment. These two standards are currently being applied by the
electrical practitioners in the Philippines and it is important to determine the differences between these standards
so that a more logical evaluation and breaker rating selection can be appropriated. IEC procedure requires
significantly more detailed modeling of the power system short circuit contribution than ANSI.

A short circuit calculation is an important task undertaken by a professional in power systems planning and
operation. Circuit breaker and switchgear selection, protection settings and coordination require a comprehensive,
detailed and accurate short-circuit calculation. The report focuses on the guidelines found in the following short-
circuit standards: the North American ANSI/IEEE standard and its European counterpart, IEC.

II. Basic Short Circuit Discussion


To come up with a precise short circuit calculation requires a very complex computation. What is important is that
whatever the short circuit calculation method used, it should be compared with the assigned (tested) fault current
rating of the protective devices.

The final equivalent short circuit schematic diagram is shown below.

R L

i(t)

~ 2 Esin(t + )

Figure 1: Current Model for Asymmetry

The circuit constitutes a series of resistance, inductance, and a switch connected to an ideal sinusoidal voltage
source. The fault is simulated by closing the switch and the magnitude of the rms symmetrical short circuit
current, I, is determined by the equation below.

E
I
Z

where:
I = short circuit current (rms symmetrical)
E = driving voltage (rms)
Z = Thevenins equivalent system impedance from the fault point back to and including
the source or sources of short-circuit currents for the distribution system.

The duration and magnitude of the asymmetrical current depends on the following parameters:
a) The X/R ratio of the faulted circuit
b) The phase angle of the voltage waveform at the time the short circuit occur

1
The asymmetrical fault current decay time is longer when X/R ratio is greater at the fault point. For specific X/R
ratio, the angle of the applied voltage at the time of short-circuits initiation determines the degree of fault current
asymmetry that will exist for that X/R ratio. The maximum asymmetrical short-circuit current occurs at the fault
inception when the voltage sine wave is at zero point and not necessarily at the highest dc component.

Figure 2: Maximum Peak Asymmetrical Short Circuit Current

III. Asymmetry Current Application


From the equipment design and application point of view, the phase with the largest fault peak current should be
of major interest. This current subjects the equipment to the most severe magnetic force. The maximum magnetic
force produced on a circuit element, such as a breaker, occurs at the instant the fault current through the circuit
element is at a maximum. The largest fault peak typically occurs in the first cycle when the initiation of the short-
circuit current is near or coincident with the applied voltage passing through zero. This condition is called the
condition of maximum asymmetry.

Electrical equipment such as circuit breakers, switches, transformers and fuses that are subjected to carry fault
current, the total available short circuit current must be determined. For correct equipment application, knowledge
of the minimum test X/R ratio or maximum power factor of the applied fault current used in the acceptance test by
ANSI, NEMA, UL and IEC is also required. Knowledge of peak fault current magnitudes are significant for some
devices, such as low voltage breakers, while asymmetrical rms current magnitudes are equally significant for high
voltage circuit breakers. This leads to the need to develop an X/R ratio dependent short circuit calculation for
proper comparison to the equipment being applied. To determine the maximum peak or rms current magnitude
that can occur in a circuit, every fault current calculation must consider the symmetrical ac component and the
transient dc component of the calculated fault current. When the calculated fault X/R ratio is greater than the
equipment X/R ratio, the higher X/R ratio must also be considered when evaluating or selecting the equipment.

2
IV. Short Circuit Calculation Standard / Guideline
ANSI C37/IEEE Std. 551

The ANSI/IEEE method calls for determining the momentary network fault impedance which makes it possible to
calculate the close and latch rating of the breaker. It also calls for identifying the interrupting network fault
impedance which makes it possible to calculate the interrupting duty of the breaker. The interrupting network fault
impedance value differs from the momentary network in that the impedance increases from the sub-transient to
transient level. The IEEE standard permits the exclusion of 3 phase induction motors below 50 hp and all single
phase motors. Hence no reactance adjustment is required for these sizes of motors. For detailed calculation
requirements please refer to the applicable standards.

IEC60909

The IEC method calls for the adjusted network impedance in calculating the symmetrical three phase fault (I k) at
a voltage higher than the nominal rating by a factor (c). The result is further manipulated to calculate peak current
ip which is then compared to the breakers making capacity (I cm). Also, further manipulation of the calculated
three-phase fault current Ik will result to the interrupting rating requirement that is compared to the selected
breakers interrupting capacity (Ib). For detailed calculation requirements please refer to the applicable standards.

V. Calculation Comparison
Table 1 presents a brief comparison of the ANSI/IEEE and IEC with regards to short circuit current calculation
method and multiplying factors.

3
Table 1: Comparison of ANSI/IEEE and IEC
ANSI/IEEE IEC
Standard North America Europe Predominant
Calculation Method 1. Voltage Source is equivalent 1. Pre-fault voltage is automatically
to the pre-fault voltage at the adjusted by a factor ( c )
location 2. Machines are represented by their
internal impedances
2. Machines are represented by 3. Line capacitance of transmission
their internal impedances lines and static loads are considered
for unbalanced ground faults
3. Line capacitance and static following a Shunt Admittance Model
loads are neglected 4. System impedances are assumed
balanced 3-phase
4. Bolted Fault is assumed hence 5. Uses symmetrical components for
arc resistance is neglected unbalanced fault calculations
6. (Ik) Initial RMS Symmetrical SCC
5. System impedances are calculates through adjusted
assumed balanced 3-phase impedance network of synchronous
machine Zk
6. Uses symmetrical components
for unbalanced fault 7. (ip) Peak Short circuit current =
calculations k1*sqrt 2* Ik where k is determined
by Method A, B or C
7. Momentary calculates through
8. (Ib) Symmetrical Short-Circuit
sub-transient impedance
network at half cycle Breaking Current = Ik for near
generator faults and = u*Ik for synch
8. Interrupting calculates through
machines = u*q*Ik for asynch.
transient impedance network
at 1.5 4 cycles machines
9. Asymmetrical SC Breaking Current =
9. Steady-State calculates Ik + Idc component current
through steady-state 10.Steady State SC current (Ik)
impedance network at and accounts for power grid, generator and
beyond 30 cycles synch machine contributions
(ip) Peak Short circuit current = k1*sqrt.
2 * Ik
Multiplying Factors
1. MF(m) Momentary 1. C pre-fault voltage factor (taken
multiplying factor I mom. from IEC)
rms asym = I mom. rms sym *
MF(m) 2. k factors determined by IEC
method A, B or C
2. MF(p) Peak multiplying factor
I mom. peak = I mom. rms.
Sym * MF(p)

4
VI. Comparison of Device Duty Rating and Short-Circuit Duty
The tables below show the different parameters used in evaluating a protective device in terms of calculated short
circuit duty of the ANSI/IEEE and IEC Standards.

Table 2: ANSI/IEEE Parameter


CALCULATED SHORT-
CIRCUIT DUTY
DEVICE TYPE DEVICE CAPABILITY
(Momentary Duty)
Asymm. KA rms Asymm. KA rms
HV BUS BRACING
Symm. KA rms Symm. KA rms
Symm. KA rms Symm. KA rms
LV BUS BRACING
Asymm. KA rms Asymm. KA rms
C and L Capability KA rms Asymm. KA rms
HVCB C and L Capability KA Crest Asymm. KA Crest
Interrupting KA Adjusted KA
LVCB Rated Interrupting KA Adjusted KA

Table 3: IEC Parameter


CALCULATED
SHORT-CIRCUIT
DEVICE TYPE DEVICE CAPABILITY DUTY (Momentary
Duty)
Making ip
MVCB
AC Breaking Ib ,symm
Making ip
LVCB
Breaking Ib ,symm
Fuse Breaking Ib ,symm

Table 4: The ANSI/IEEE vs. IEC


DEVICE TYPE DEVICE CAPABILITY CALCULATED SHORT
CIRCUIT DUTY
ANSI IEC ANSI IEC ANSI IEC
Asymm. KA
HVCB MVCB C and L cap. KA rms Making (ip) ip
rms
Asymm. KA
C and L cap. KA rest n/a
rest
Interrupting KA AC breaking (Isc) Adjusted KA Ib symm
Ib asymm Ib asymm
Idc
Iohm Ish
Breaking (Ib symm) Ib symm
LVCB LVCB Rated interrupting KA
ICU or Ik
Making peak (ICM) ip
Ib asymm Ib asymm
Ish Ish

5
VII. Sample Calculation using ANSI/IEEE and IEC
Description of Sample network

The sample network consists of two power transformers connected to a 13.2 KV bus. One of the transformers feeds
a bus at a nominal voltage of 240 V, while the other transformer feeds a bus at a nominal voltage of 2.3 KV. The
data of the transformer and other equipment and their principal characteristics are presented in Fig. 3. For the
purpose of presenting a discussion on fault calculation, points B l and B2 are selected to have experienced a 3
phase bolted fault.

Figure 3: Single Line Diagram of the Sample Network

6
A. IEC SHORT CIRCUIT RESULT

Figure 4: Single Line Diagram to consider IEC SC Result

7
Project: ETAP Page: 1
6.0.0C
Location: Date: 10-19-2010
Contract: SN: FUJIHAYAPH
Engineer: Revision: Base
Study Case: SC
Filename: sample Config.: Normal

Electrical Transient Analyzer Program

Short-Circuit Analysis

IEC 60909 Standard


3-Phase Fault Currents
Maximum Short-Circuit Current

Swing V-Control Load Total


Number of Buses: 1 0 7 8

XFMR2 XFMR3 Reactor Line/Cable Impedance Tie PD Total


Number of 2 0 0 0 0 5 7
Branches:

Synchronous Power Synchronous Induction Lumped


Generator Grid Motor Machines Load Total
Number of 0 1 0 5 1 7
Machines:

System Frequency: 60 Hz

Unit System: English

Project Filename: sample

Output Filename: D:\Etap6.0 Projects\SC sample attachments_2010_10_18\Untitled.SI1

8
Adjustments

Apply Individual
Tolerance Percent
Adjustment /Global
Transformer Impedance: Yes Individual
Reactor Impedance: Yes Individual
Overload Heater Resistance: No
Transmission Line Length: No
Cable Length: No

Apply Individual
Temperature Correction Degree C
Adjustment /Global
Transformer Resistance: Yes Global 20
Cable Resistance: Yes Global 20

Bus Input Data

Bus Initial Voltage


ID Type Nom. kV Base kV Sub-sys %Mag. Ang.
B1 Load 0.240 0.240 1 100.00 0.00
B2 Load 2.300 2.300 1 100.00 0.00
Bus4 Load 0.240 0.240 1 100.00 0.00
Bus5 Load 2.300 2.300 1 100.00 0.00
Bus6 Load 2.300 2.300 1 100.00 0.00
Bus7 Load 2.300 2.300 1 100.00 0.00
Bus8 Load 2.300 2.300 1 100.00 0.00
UB SWNG 13.200 13.200 1 100.00 0.00

8 Buses Total
All voltages reported by ETAP are in % of bus Nominal kV.
Base kV values of buses are calculated and used internally by ETAP

2-Winding Transformer Input Data

Transformer Rating Z Variation % Tap Setting Adjusted Phase Shift


Prim.
ID MVA Sec. kV %Z X/R +5% -5% %Tol. Prim. Sec. %Z Type Angle
kV
T1 1.500 13.200 0.240 5.75 7.10 0 0 0 0 0 5.7500 Std Pos. Seq. 0.0

T2 5.000 13.200 2.300 7.15 12.14 0 0 0 0 0 7.1500 Std Pos. Seq. 0.0

Branch Connections

CKT/Branch Connected Bus ID % Impedance, Pos. Seq., 100 MVAb


ID Type From Bus To Bus R X Z Y
T1 2W XFMR UB B1 51.58 366.13 369.74
T2 2W XFMR UB B2 11.76 142.82 143.31
CB6 Tie Breaker B1 Bus4
CB7 Tie Breaker B2 Bus5
CB8 Tie Breaker B2 Bus6
CB9 Tie Breaker B2 Bus7
CB10 Tie Breaker B2 Bus8

9
Power Grid Input Data

% Impedance 100
Power Grid Connected Bus Rating
MVA Base
ID ID MVAsc kV R X" R/X

U1 UB 720.000 13.200 0.00014 13.88889 0.00

Total Connected Power Grids ( = 1 ): 720.000 MVA

Induction Machine Input Data

% Impedance
Induction Machine Connected Bus Rating mFact.
(Motor Base)
ID Type Qty ID HP/kW kVA kV Amp PF R X" R/X" MW/PP
M2 Motor 1 Bus5 500.00 440.28 2.300 110.52 90.82 2.96 15.41 0.19 0.19
M3 Motor 1 Bus6 500.00 440.28 2.300 110.52 90.82 2.96 15.41 0.19 0.19
M4 Motor 1 Bus7 500.00 440.28 2.300 110.52 90.82 2.96 15.41 0.19 0.19
M5 Motor 1 Bus8 500.00 440.28 2.300 110.52 90.82 2.96 15.41 0.19 0.19
M1 Motor 1 Bus4 125.00 110.12 0.240 264.91 91.51 4.62 16.01 0.29 0.05

Total Connected Induction Machines ( = 5 ): 1871.3 kVA

Lumped Load Input Data

Lumped Load Motor Loads


% Impedance
Lumped Load Connected Bus Rating % Load Loading m Fact.
Machine Base
ID ID kVA kV Amp % PF MTR STAT kW kvar R X" R/X" MW/PP
L1 B1 1000.0 0.240 2405.63 85.00 60 40 510.0 316.1 6.46 15.37 0.42 0.51

Total Connected Lumped Loads ( = 1 ): 1000.0 kVA

10
SHORT - CIRCUIT REPORT

3-Phase fault at bus: B1

Nomimal kV = 0.240
Voltage c Factor = 1.10 (Maximum If)
Peak Value = 181.348 kA Method A
Steady State = 68.754 kA rms

Contribution Voltage and Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
From
ID ID Real Imaginary Ratio Magnitude
Bus
B1 Total 0.00 13.406 -78.631 5.9 79.766
UB B1 96.12 9.232 -68.170 7.4 68.792
L1 B1 100.00 3.690 -8.782 2.4 9.526
M1 Bus4 100.00 0.485 -1.680 3.5 1.748
Bus4 B1 0.00 0.485 -1.680 3.5 1.748

Breaking and DC Fault Current (kA)

Based on Total Bus Fault Current


TD (S) Ib sym Ib asym Idc
0.01 78.916 101.347 63.588
0.02 78.315 86.941 37.756
0.03 77.529 80.547 21.843
0.04 76.761 77.794 12.637
0.05 76.017 76.406 7.704
0.06 75.656 75.79 4.504
0.07 75.301 75.347 2.633
0.08 74.952 74.968 1.539
0.09 74.610 74.616 0.939
0.10 74.275 74.277 0.551
0.15 73.582 73.582 0.039
0.20 72.918 72.918 0.003
0.25 72.285 72.285 0.000
0.30 72.260 72.260 0.000

11
3-Phase fault at bus: B2

Nomimal kV = 2.300
Voltage c Factor = 1.10 (Maximum If)
Peak Value = 51.136 kA Method A
Steady State = 17.417 kA rms

Contribution Voltage and Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude
B2 Total 0.00 1.882 -20.420 10.9 20.506

UB B2 90.44 1.297 -17.377 13.4 17.425


M5 Bus8 100.00 0.146 -0.761 5.2 0.775
M4 Bus7 100.00 0.146 -0.761 5.2 0.775
M3 Bus6 100.00 0.146 -0.761 5.2 0.775
M2 Bus5 100.00 0.146 -0.761 5.2 0.775

Bus5 B2 0.00 0.146 -0.761 5.2 0.775


Bus6 B2 0.00 0.146 -0.761 5.2 0.775
Bus7 B2 0.00 0.146 -0.761 5.2 0.775
Bus8 B2 0.00 0.146 -0.761 5.2 0.775

Breaking and DC Fault Current (kA)

Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 20.014 28.877 20.816

0.02 19.722 25.04 15.429

0.03 19.441 22.464 11.254

0.04 19.174 20.857 8.208

0.05 18.921 19.955 6.342

0.06 18.799 19.373 4.679

0.07 18.681 18.997 3.453

0.08 18.566 18.74 2.548

0.09 18.456 18.564 2.001

0.10 18.349 18.409 1.486

0.15 18.145 18.148 0.336

0.20 17.954 17.954 0.076

0.25 17.775 17.775 0.017

0.30 17.769 17.769 0.004

12
3-Phase fault at bus: Bus4

Nomimal kV = 0.240
Voltage c Factor = 1.10 (Maximum If)
Peak Value = 181.348 kA Method A
Steady State = 68.754 kA rms

Contribution Voltage and Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude
Bus4 Total 0.00 13.406 -78.631 5.9 79.766

M1 Bus4 100.00 0.485 -1.680 3.5 1.748

UB B1 96.12 9.232 -68.170 7.4 68.792

L1 B1 100.00 3.690 -8.782 2.4 9.526

B1 Bus4 0.00 12.921 -76.952 6.0 78.029

Breaking and DC Fault Current (kA)

Based on Total Bus Fault Current


TD (S) Ib sym Ib asym Idc

0.01 78.916 101.347 63.588


0.02 78.315 86.941 37.756
0.03 77.529 80.547 21.843
0.04 76.761 77.794 12.637
0.05 76.017 76.406 7.704
0.06 75.656 75.790 4.504
0.07 75.301 75.347 2.633
0.08 74.952 74.968 1.539
0.09 74.61 74.616 0.939
0.10 74.275 74.277 0.551
0.15 73.582 73.582 0.039
0.20 72.918 72.918 0.003
0.25 72.285 72.285 0.000
0.30 72.26 72.260 0.000

13
3-Phase fault at bus: UB

Nomimal kV = 13.200
Voltage c Factor = 1.10 (Maximum If)
Peak Value = 90.256 kA Method A
Steady State = 31.492 kA rms

Contribution Voltage and Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude
UB Total 0.00 0.142 -32.117 226.5 32.117

B1 UB 13.64 0.060 -0.167 2.8 0.178

B2 UB 13.86 0.081 -0.458 5.7 0.465

U1 UB 100.00 0.000 -31.492 99999.0 31.492

Breaking and DC Fault Current (kA)

Based on Total Bus Fault Current


TD
Ib sym Ib asym Idc
(S)
0.01 32.048 55.226 44.977

0.02 32.004 55.166 44.934

0.03 31.959 54.943 44.692

0.04 31.915 54.723 44.452

0.05 31.874 54.998 44.82

0.06 31.853 54.889 44.701

0.07 31.833 54.781 44.583

0.08 31.814 54.674 44.464

0.09 31.795 55.076 44.971

0.10 31.777 55.024 44.921

0.15 31.74 54.801 44.674

0.20 31.706 54.581 44.427

0.25 31.673 54.362 44.182

0.30 31.672 54.164 43.939

14
Short Circuit Summary Report

3-Phase FaultCurrent

Bus Device Device Capacity (kA) Short-Circuit Current (kA)


Making
ID kV ID Type Peak Ib sym Ib asym Idc I"k ip Ib sym Ib asym Idc Ik
B1 0.240 B1 Bus 79.766 181.348 68.754
0.240 CB2 CB 220.000 100.000 102.111 79.766 181.348 77.920 83.044 28.718
0.240 CB6 CB 176.000 80.000 80.426 79.766 181.348* 77.219 77.219 17.549
B2 2.300 B2 Bus 20.506 51.136 17.417
Bus4 0.240 Bus4 Bus 79.766 181.348 68.754
0.240 CB6 CB 176.000 80.000 80.426 79.766 181.348* 77.219 79.188 17.549
UB 13.200 UB Bus 32.117 90.256 31.492

ip is calculated using method A


Ib does not include decay of non-terminal faulted induction motors
Ik is the maximum steady state fault current
Idc is based on X/R from Method C and Ib as specified above

LV CB duty determined based on ultimate rating.


Total through current is used for device duty.
*Indicates a device with calculated duty exceeding the device capability.
# Indicates a device with calculated duty exceeding the device marginal limit ( 95 % times device capability)

Short Circuit Summary Report

3-Phase
Short-Circuit
Device Capacity Current
Bus ID Device ID 1thr (kA) Tkr (sec.) Ith (kA)

B1 CB2 100.000 1.00 75.613

B1 CB6 65.000 1.00 75.613*

Bus4 CB6 65.000 1.00 75.613*

1thr = Rated short-circuit withstand current


Tkr = Rated short-time
Ith = thermal equivalent short-time current

*Indicates a device with calculated duty exceeding the device capability.


# Indicates a device with calculated duty exceeding the device marginal limit ( 95 % times device capability )

15
B. ANSI SHORT CIRCUIT RESULT

FIGURE 5: Single Line Diagram to consider ANSI SC Result

16
Project: ANSI Calc Total Bus Fault Peak Current ETAP Page: 1
6.0.0C
Location: Date: 10-19-2010
Contract: SN: FUJIHAYAPH
Engineer: Revision: Ansi Breaker
Study Case: SC
Filename: sample Config.: Normal

Electrical Transient Analyzer


Program
Short-Circuit Analysis

ANSI Standard
3-Phase Fault Currents

Swing V-Control Load Total


Number of Buses: 1 0 7 8

XFMR2 XFMR3 Reactor Line/Cable Impedance Tie PD Total


Number of 2 0 0 0 0 5 7
Branches:

Synchronous Power Synchronous Induction Lumped


Generator Grid Motor Machines Load Total

Number of 0 1 0 5 1 7
Machines:

System Frequency: 60 Hz

Unit System: English

Project Filename: sample

Output Filename: D:\Etap6.0 Projects\SC sample attachments_2010_10_18\Untitled.SA1

17
Adjustments
Apply Individual
Tolerance Percent
Adjustment /Global
Transformer Impedance: Yes Individual
Reactor Impedance: Yes Individual
Overload Heater Resistance: No
Transmission Line Length: No
Cable Length: No

Apply Individual
Temperature Correction Degree C
Adjustment /Global
Transformer Resistance: Yes Global 20
Cable Resistance: Yes Global 20

Bus Input Data


Bus Initial Voltage
ID Type Nom. kV Base kV Sub-sys %Mag. Ang.
B1 Load 0.240 0.240 1 100.00 0.00
B2 Load 2.300 2.300 1 100.00 0.00
Bus4 Load 0.240 0.240 1 100.00 0.00
Bus5 Load 2.300 2.300 1 100.00 0.00
Bus6 Load 2.300 2.300 1 100.00 0.00
Bus7 Load 2.300 2.300 1 100.00 0.00
Bus8 Load 2.300 2.300 1 100.00 0.00
UB SWNG 13.200 13.200 1 100.00 0.00

8 Buses Total
All voltages reported by ETAP are in % of bus Nominal kV.
Base kV values of buses are calculated and used internally by ETAP

2-Winding Transformer Input Data

Transformer Rating Z Variation % Tap Setting Adjusted Phase Shift


Prim.
ID MVA Sec. kV %Z X/R +5% -5% %Tol. Prim. Sec. %Z Type Angle
kV
T1 1.500 13.200 0.240 5.75 7.10 0 0 0 0 0 5.7500 Std Pos. Seq. 0.0

T2 5.000 13.200 2.300 7.15 12.14 0 0 0 0 0 7.1500 Std Pos. Seq. 0.0

18
Branch Connections

CKT/Branch Connected Bus ID % Impedance, Pos. Seq., 100 MVAb


ID Type From Bus To Bus R X Z Y
T1 2W XFMR UB B1 53.48 379.58 383.33
T2 2W XFMR UB B2 11.74 142.52 143.00
CB6 Tie Breaker B1 Bus4
CB7 Tie Breaker B2 Bus5
CB8 Tie Breaker B2 Bus6
CB9 Tie Breaker B2 Bus7
CB10 Tie Breaker B2 Bus8

Power Grid Input Data


% Impedance
Power Grid Connected Bus Rating
100 MVA Base
ID ID MVASC kV X/R R X
U1 UB 720.000 13.200 99999 0.00014 13.88889
Total Connected Power Grids ( = 1 ): 720.000 MVA

Induction Machine Input Data

Induction % Impedance
Connected Bus Rating X/R Ratio
Machine (Motor Base)

ID Qty ID HP/kW kVA kV RPM X"/R X'/R R X" X'

Motors
M2 1 Bus5 500.00 440.28 2.300 1800 10.89 10.89 2.21 24.05 36.08
M3 1 Bus6 500.00 440.28 2.300 1800 10.89 10.89 2.21 24.05 36.08
M4 1 Bus7 500.00 440.28 2.300 1800 10.89 10.89 2.21 24.05 36.08
M5 1 Bus8 500.00 440.28 2.300 1800 10.89 10.89 2.21 24.05 36.08
M1 1 Bus4 125.00 110.12 0.240 1800 8.71 8.71 2.30 20.00 50.00

Total Connected Induction Machines ( = 5 ): 1871.3 kVA

Lumped Load Input Data

Lumped Load Motor Loads Static Loads


Lumped Load Connected Bus Rating % Load Loading X/R Ratio % Imp. (Machine Base) Loading

ID ID kVA kV MTR STAT kW kvar X"/R X'/R R X" X' kW kvar

L1 B1 1000.0 0.240 60 40 510.00 316.1 2.38 2.38 8.403 20.00 50.00 340.00 210.71

Total Connected Lumped Loads ( = 1 ): 1000.0 kVA

19
SHORT - CIRCUIT REPORT

3-Phase fault at bus: B1


= 100.00% of nominal bus kV ( 0.240
Prefault voltage = 0.240
kV )
100.00% of base ( 0.240
=
kV )

Contribution 1/2 Cycle


kA
From Bus To Bus %V kA kA Imag.
Symm.
From
ID ID Real Imaginary /Real Magnitude
Bus
B1 Total 0.00 10.893 -67.489 6.2 68.362

UB B1 96.57 8.165 -60.047 7.4 60.600


L1 B1 100.00 2.577 -6.134 2.4 6.653
M1 Bus4 100.00 0.150 -1.307 8.7 1.316

*Bus4 B1 0.00 0.150 -1.307 8.7 1316

NACD Ratio = 1.00

# Indicates a fault current contribution from a three-winding transformer


* Indicates a fault current through a tie circuit breaker

If faulted bus is involved in loops formed by protection devices, the short-circuit contribution through these PDs will not be reported

3-Phase fault at bus: B2

Prefault voltage = 2.300 = 100.00% of nominal bus kV ( 2.300 kV )


= 100.00% of base ( 2.300 kV )

Contribution 1/2 Cycle 1.5 to 4 Cycle


kA kA
From Bus To Bus %V kA kA Imag. %V kA kA Imag.
Symm. Symm.
From
ID ID Real Imaginary /Real Magnitude From Bus Real Imaginary /Real Magnitude
Bus
B2 Total 0.00 1.368 -17.787 13.0 17.840 0.00 1.311 -17.177 13.1 17.227

UB B2 91.20 1.201 -15.965 13.3 16.010 91.19 1.199 -15.962 13.3 16.007
M5 Bus8 100.00 0.042 -0.456 10.9 0.458 100.00 0.028 -0.304 10.9 0.305
M4 Bus7 100.00 0.042 -0.456 10.9 0.458 100.00 0.028 -0.304 10.9 0.305
M3 Bus6 100.00 0.042 -0.456 10.9 0.458 100.00 0.028 -0.304 10.9 0.305
M2 Bus5 100.00 0.042 -0.456 10.9 0.458 100.00 0.028 -0.304 10.9 0.305

* Bus5 B2 0.00 0.042 -0.456 10.9 0.458 0.00 0.028 -0.304 10.9 0.305
* Bus6 B2 0.00 0.042 -0.456 10.9 0.458 0.00 0.028 -0.304 10.9 0.305
* Bus7 B2 0.00 0.042 -0.456 10.9 0.458 0.00 0.028 -0.304 10.9 0.305
* Bus8 B2 0.00 0.042 -0.456 10.9 0.458 0.00 0.028 -0.304 10.9 0.305

20
NACD Ratio = 1.00

# Indicates a fault current contribution from a three-winding transformer


* Indicates a fault current through a tie circuit breaker

If faulted bus is involved in loops formed by protection devices, the short-circuit contribution through these PDs will not be reported

3-Phase fault at bus: B4

Prefault voltage = 0.240 = 100.00% of nominal bus kV ( 0.240 kV )


= 100.00% of base ( 0.240 kV )

Contribution 1/2 Cycle


From Bus To Bus %V kA kA Imag. kA Symm.
ID ID From Bus Real Imaginary /Real Magnitude
Bus4 Total 0.00 10.893 -67.489 6.2 68.362

M1 Bus4 100.00 0.150 -1.307 8.7 1.316


UB B1 96.57 8.165 -60.047 7.4 60.6
L1 B1 100.00 2.577 -6.134 2.4 6.653

*B1 Bus4 0.00 10.743 -66.181 6.2 67.048

NACD Ratio = 1.00

# Indicates a fault current contribution from a three-winding transformer


* Indicates a fault current through a tie circuit breaker

If faulted bus is involved in loops formed by protection devices, the short-circuit contribution through these PDs will not be reported

3-Phase fault at bus: UB

Prefault voltage = 13.200 = 100.00% of nominal bus kV ( 13.200 kV )


= 100.00% of base ( 13.200 kV )

Contribution 1/2 Cycle 1.5 to 4 Cycle


From To kA
%V kA kA Imag. kA Symm. %V kA kA Imag.
Bus Bus Symm.
From
ID ID Real Imaginary /Real Magnitude From Bus Real Imaginary /Real Magnitude
Bus
UB Total 0.00 0.068 -31.901 470.9 31.901 0.00 0.037 -31.742 863.6 31.742

B1 UB 11.24 0.041 -0.121 2.9 0.128 4.81 0.018 -0.052 2.8 0.055
B2 UB 9.44 0.026 -0.288 11.0 0.289 6.50 0.018 -0.198 11.0 0.199
U1 UB 100.00 0.000 -31.492 99999.0 31.492 100.00 0.000 -31.492 99999.0 31.492

NACD Ratio = 1.00

# Indicates a fault current contribution from a three-winding transformer


* Indicates a fault current through a tie circuit breaker

If faulted bus is involved in loops formed by protection devices, the short-circuit contribution through these PDs will not be reported

21
Momentary Duty Summary Report

3-Phase Fault Currents: (Prefault


Voltage = 100% of the Bus Nominal
Voltage

Bus Device Momentary Duty Device Capability


Symm Asymm
Symm. X/R Asymm Asymm. Asymm.
ID kV ID Type M.F. kA kA
kA rms Ratio kA rms kA Crest kA rms
rms Crest
B1 0.240 B1 Bus 68.362 6.9 1.342 91.741 157.859

B2 2.300 B2 Bus 17.840 13.1 1.496 26.68 45.067

Bus4 0.240 Bus4 Bus 68.362 6.9 1.342 91.741 157.859

UB 13.200 UB Bus 31.901 999.9 1.728 55.139 90.088

Method : IEEE - X/R is calculated from separate R and X networks.

Protective device duty is calculated based on total fault current

* Indicates a device with momentary duty exceeding the device capability

Interrupting Duty Summary Report

3-Phase Fault Currents: (Prefault Voltage = 100% of the Bus Nominal Voltage

Bus Device Interrupting Duty Device Capability

CPT X/R Adj. Sym. Test Rated Adjusted


ID kV ID Type (Cy) Ratio M.F. kA rms kV PF Int. Int.
Molded
B1 0.240 68.362 6.9 1.070 73.118 0.240 20.00 85.000 85.000
CB6 Case
B2 2.300 17.227 13.1
Molded
Bus4 0.240 68.362 6.9 1.070 73.118 0.240 20.00 85.000 85.000
CB6 Case
UB 13.200 31.742 99184.7

Method: IEEE - X/R is calculated from separate R and X networks.


HV CB interrupting capability is adjusted based on bus nominal voltage
Short-Circuit multiplying factor for LV Molded Case and Insulated Case Circuit Breakers is calculated based on peak current.
Generator protective device duty is calculated based on maximum through fault current. Other protective device duty is calculated
based on total fault current.
* Indicates a device with interrupting duty exceeding the device capability.

22
C. ANSI/IEEE Short Circuit Method (for Manual Calculation)

Impedance Diagram Development @ 100 MVA base

XU

RT1 RT2
where:
B1 B2
XT1 XT2 HP(0.746)
MOTOR (MVA) =
(Eff)(pf)(100)
500(0.746)
RM1 M2 =
RL RM2 RM3 RM4 RM5 (1000)(0.9325)(0.9082)

XL XM4 XM5 M2 = 0.440 MVA


XM1 XM2 XM3

Figure 6: Impedance Diagram

100
1. X U j j 0.13889
720
100
2. R T1 0.575costan 7.1 0.53463
1.5
100
3. X T1 0.575sin tan 7.1 j 3.79587
1.5
100
4. R T2 0.0715costan 12.14 0.11739
5
100
5. X T2 0.0715sin tan 12.14 j1.42157
5
100
6. R M1 0.2costan 8.707 20.74547
0.11
100
7. X M1 0.2sin tan 8.707 j180.63078
0.11
100
8. R L 0.2costan 2.38 12.91214
1.00.6
100
9. X L 0.2sin tan 2.38 j30.73089
1.00.6
100
10. X M2M5 0.24051sin tan 10.888 j54.43227
0.44
100
11. R M2M5 0.24051sin tan 10.888 12.91214
0.44

23
Solving for cycle 3 phase fault at B1

Z T B1 Z T2 Z M2 Z M3 Z M4 Z M5 Z U Z T1 Z M1 Z L
0.56271 j3.44496 3.49062 80.72

100 x 10 6
I T3 B 68.9 kA
1
3 240 3.49062

Solving for cycle, 3phase fault at B2

Z T B2 Z M2 Z M3 Z M4 Z M5 Z M1 Z L Z T1 Z U Z T2
0.10787 j1.40240 1.40655 85.6

100 x 10 6
I T3 B 2 17.85 kA
3 2300 1.40655

IEC Short Circuit Calculation

1. XUK j0.13889
2. RT1K 0.534630.965 0.51592
K 0.965 as per60909IECformula
Cmax
K 0.965 ; ZK ZT K
1 0.6XT
Cmax 1.1 Table1 of 60909 0
3. XT1K j3.795870.965 j3.66301
4. RT2K 0.117391.0 0.11739
5. XT2 j1.425171.0 j1.42517
6. RM1K 20.745470.8 16.596
7. XM1K j180.630780.8 j144.505
8. RLK 12.912140.77 9.942
9. XLK j30.730890.77 j23.66
10. XM2KM5K j54.432270.64 34.837
11. RM2KM5K 4.999290.64 3.199

24
Solving for 3 phase fault at B1 , I "K

Z TK B1 Z T2K Z M2K Z M3 K Z M4K Z M5K Z UK Z T1K Z M1K Z L


0.54641 j3.22821 3.27412 80.39

100 x 10 6 1.1
I"K B 80 kA
1
3 240 3.27412

Solving for 3 phase fault at B2 , I "K

Z TK B 2 Z M2K Z M3K Z M4K Z M5K Z M1K Z LK Z T1K Z UK Z T2K


0.10307 j1.32547 1.32948 85.6

100 x 10 6 1.1
I"K B 17.85 kA
2
3 2300 1.32948

* It is therefore the basic inclusion of factors C m and k that increases the calculated short-circuit of IEC
method when being compared to the result of the ANSI method.

25
VIII. Protective Devices Selection and evaluation
X/R Ratio for Breaker Evaluation

The fault point X/R ratio is a critical factor in the calculation of short circuit current when evaluating breakers.
The X/R ratio determines the amount of dc component in the short circuit current and in the application to the
circuit breaker withstands and interrupting time duties. ANSI/IEEE C37.010-1999 recommends a separate R and
jX network reduction to determine the fault point X/R ratio while IEC 61909 allows several methods to provide a
conservative X/R ratio.

The peak current calculation that yields a very close approximation to the exact peak current and is conservative
for most values of circuit X/R ratios greater than 0.81. The non-conservative errors for circuit X/R ratio around 10
are negligible. Please refer to equation below:



Half cycle I ac peak 1 e X / R or
ANSI / IEEE



2 I ac rms 1 e X / R


3

Half cycle I ac peak 1.02 0.98 e X / R or

IEC 60909

3

2 I ac rms 1.02 0.98 e X / R

Circuit Breaker Short Circuit Test Parameters

Based on IEC 60947-2, the circuit breakers short circuit breaking capacity, power factor and ratio, , between
short circuit making capacity and short circuit breaking capacity should be in accordance with Table 5.

Table 5: Circuit Breakers Short Circuit Breaking Capacity

Short circuit breaking Lagging Minimum value required for


capacity, Power Short-circuit making capacity
= Short-circuit breaking capacity
Ib, kA rms factor X/R
4.5 I 6 0.7 1.02 1.5
6 < I 10 0.5 1.73 1.7
10 < I 20 0.3 3.18 2.0
20 < I 50 0.25 3.87 2.1
50 < I 0.2 4.9 2.2

Ratio between Short-circuit making capacity and Short-circuit breaking capacity and related power factor or X/R
ratio (for ac circuit breaker).

26
Based on NEMA AB1/UL489, the circuit breakers interrupting capacity, lagging power factor should be in
accordance with Table 6.

Table 6: Circuit Breakers Interrupting Capacity

kA lagging pf X/R
MCCB and ICB I 10 0.45 0.5 1.98 1.73
10 < I 20 0.25 0.30 3.87 3.17
20 < I 0.15 0.20 6.59 4.90
Power Circuit Breaker (Unfuse) All 0.15 6.59
Power Circuit Breaker (Fuse) All 0.20 4.90

IX. Findings and Results


From the result of ETAP Total Bus Fault Short Circuit Study, the following results were found:

Table 7: IEC Short Circuit Calculation

Device Capacity (kA) Short Circuit Calculation Result (kA)


Bus
Device Making
ID Ib sym Ib asym I"b ip Ib sym Ib asym
Peak
B1 CB2 176 80 80.426 79.8 181.348* 77.219 79.188
Note: Method A, Total Bus Fault

From the data in Table 7, the calculated short circuit current level of 79.8kA (Ik) is within the circuit breaker
capacity of 80 kA (Ib sym), however, other parameters such as peak short circuit current ( ip) is 181.348 kA
exceeded the circuit breaker rating equivalent to 176 kA (making peak) only. Therefore, the selected IEC rated
circuit breaker is not suitable for this particular application.

The reason for this difference is that the calculated X/R ratio at 3-phase fault at point B1 is 5.9, which is greater
than the device capacity X/R ratio of only 4.9 (see ETAP IEC method result above) applied during the testing of
circuit breaker interrupting capacity or the Icu rating of the circuit breaker.

Table 8: ANSI Short Circuit Calculation

Device Capacity (kA) Short Circuit Calculation Result (kA)


Bus
Device Sym Adj. Sym
ID Rated Int. Adj. Int X/R ratio M.F
rms rms
B1 CB2 85.0 85.0 68.362 6.9 1.07 73.118

From the data in Table 8, the calculated symmetrical rms current of 68.362 kA needs to be adjusted by the
multiplying factor (MF) of 1.070 (see computation below) resulting to 73.118 kA. This is because the calculated
X/R ratio 6.9 is greater than the X/R ratio used in testing the circuit breaker interrupting capacity which is only 4.9
(Table 6). Comparing the adjusted symmetrical rms value of 73.118 kA against the selected NEMA rated device
interrupting capacity of 85kA, the selected circuit breaker is suitable for the particular application.

27
R

X C
1 e
MF R

X T
1 e

1

6 .9 C
1 e
1

4 .9 T
1 e

1.07

R
Where:
X

T
- Break test R/X ratio

R

X C
- Calculated R/X ratio at the point fault

MF - Multiplying factor

X. Conclusion and Recommendation


From the above short circuit calculation examples, IEC method shows a higher value of short circuit current as
compared to ANSI/IEEE calculation method. This is due to the differences in the consideration as mentioned
above. Both methods are being used and internationally acceptable.

In any electrical system, it is important to know the short circuit level of each of the protective equipment.
However, we should not forget to verify the X/R ratio of the faulted bus against the circuit breaker test power
factor or X/R ratio based on their product standard (e.g. UL/NEMA/ANSI or IEC). The example above
illustrates clearly the importance of X/R ratio in evaluating or selecting the circuit breaker. Understanding the
relationship between the product standards and electrical codes is of utmost importance.

It is up to the engineers/designers to decide which method of short circuit calculation they are more comfortable
with provided they have to take note of the different considerations in the selection of the protective equipment.

28
XI. References

1 IEEE Std 551-2006, IEEE Recommended Practice for Calculating Short-Circuit currents in
Industrial and Commercial Power System.

2 IEEE Papers, Simplifying IEEE/ANSI and IEC Fault Point X/R Ratio for Breaker Evaluation
by Ketut Dartawan and Conrad St. Pierre

3 IEC 60497-1:2009, Low-voltage switchgear and control gear - Part 1: General rules

4 IEC 60497-2:2009, Low-voltage switchgear and control gear - Part 2: Circuit-breakers

5 ANSI C37.5-1989, Calculation of Fault Currents for Application of Power Circuit Breakers
Rated on a Total Current Basis

6 UL 489-1986, Molded Case Circuit Breaker and Circuit Breakers Enclosure

7 IEC 60909-0, Corrigendum 1 - Short-circuit currents in three-phase A.C. systems - Part 0:


Calculation of currents

8 Electrical Transient Analyzer Program (ETAP) Software version 6.0

29
Appendix
Courtesy of ABB Phil., Inc.

proM Compact Technical features S 200


of MCBs S 200 series

Series S 200 S 200 M S 200 P S 280


Characteristics B,C,D B,C,D B,C,D B,C,D B,C,D B,C
K,Z K,Z K,Z K,Z K,Z
Rated current [A] 0.5 ln 63 0.5 ln 63 0.2 ln 25 32 ln 40 50 ln 63 80 LN 100
Breaking capacity [kA]
Nr.
Reference standard Poles Ue [V]
IEC 23-3/EN 60898 lcs 230 / 400 6 10 25 15 15 6
1, 1P +
IEC/EN 60947 - 2 lcu N 133 20 25 40 25 25 15
Alternating current 230 10 15 25 15 15 6
2,3,4 230 20 25 40 25 25 10
400 10 15 25 15 15 6
2,3,4 500
690
1, 1P +
lcs N 133 15 18.7 20 18.7 18.7 15

30
(continued )

230 7.5 11.2 12.5 11.2 7.5 6


2,3,4 230 15 18.7 20 18.7 18.7 10
400 7.5 11.2 12.5 11.2 7.5 6
2,3,4 500
690
1, 1P +
IEC/EN 60497 - 2 lcu N 24 20
Direct current 60 10 10 15 10 10 10
T= lR 5ms for all 125
series 250
except S280 UC and 2 48 20
S800S-UC 125 10 10 15 10 10 10
where T = lR <15ms 250
500
600
800
3,4 375
500
750
1000
1200
1, 1P +
lcs N 24 20
60 10 10 15 10 10 10
125
250
2 48 20
125 10 10 15 10 10 10
250
500
600
800
3,4 375

31
(continued )

500
750
1000
1200
1, 1P +
UL 1077 / C22.2 lnt. N 120 10 10 10 10
No 235 cap. 277 6 10 10 10
Alternating current 2,3,4 240 10 10 10 10
480Y /
277 6 10 10 10
1, 1P +
UL 1077 / C22.2 lnt. N 60 10
No 235 cap. 2,3,4 125 10
Direct current
UL 489/ C22.2 lnt. 1 240
No 5 cap. 277
Alternating current 2,3,4 240
480y /
277
IEC / EN 60947 - 3 lcw 2 800
3,4 1200

<50 A

32

You might also like