System Psychrometrics for CORRIDOR 4

Project Name: 21014 BARKA MALL R4 08/01/2017


Prepared by: Amjaad 07:56AM

July DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 45.8 0.02038 0 400 0 0
Vent - Return Mixing Outlet 24.5 0.00969 6958 3630 - -
Central Cooling Coil Outlet 13.5 0.00898 6958 3630 91977 14605
Supply Fan Outlet 13.6 0.00898 6958 3630 644 -
Cold Supply Duct Outlet 13.6 0.00898 6889 3630 - -
Zone Air - 21.6 0.00970 6889 3631 66148 14603
Return Plenum Outlet 24.6 0.00970 6889 3631 24506 -
Duct Leakage Air Outlet 13.6 0.00898 70 3630 - -
Return Duct Outlet 24.5 0.00969 6958 3630 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.205 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2942.3 W/(L/s)
Site Altitude = 14.9 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (C) (L/s) (ppm) (W) (W)
Zone 1 67891 Cooling 66148 21.6 6889 3631 0 0

Hourly Analysis Program v4.50 Page 1 of 2


System Psychrometrics for CORRIDOR 4
Project Name: 21014 BARKA MALL R4 08/01/2017
Prepared by: Amjaad 07:56AM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 12.0 0.00682 0 400 0 0
Vent - Return Mixing Outlet 18.4 0.01157 6958 800 - -
Central Cooling Coil Outlet 18.3 0.01157 6958 800 0 0
Supply Fan Outlet 18.4 0.01157 6958 800 644 -
Cold Supply Duct Outlet 18.4 0.01157 6889 800 - -
Zone Air - 18.4 0.01157 6889 800 -410 0
Return Plenum Outlet 18.4 0.01157 6889 800 0 -
Duct Leakage Air Outlet 18.4 0.01157 70 800 - -
Return Duct Outlet 18.4 0.01157 6958 800 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.205 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2942.3 W/(L/s)
Site Altitude = 14.9 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (C) (L/s) (ppm) (W) (W)
Zone 1 -6315 Deadband -410 18.4 6889 800 0 0

Hourly Analysis Program v4.50 Page 2 of 2