Meuang Nan - Naphia

500kV T/L 2cct, ACSR1272MCM x 4, OPGW x 2


Design Load Calculation for Tower Type DQS [ Unit : N ]
Case -1, 19(L), 20(R): Extreme Condition (Transverse Wind Condition)
Vertical Loads (Dead Weight Loads)
V1 =(OPGW weight) x (Vertical Span) 0.4894 x 830 x 9.80665 3,983
V2 =(Arrester Wire weight) x (Vertical Span) 0.4265 x 830 x 9.80665 3,472
V3 = (Conductor weight) x (Vertical Span) x (No. of Cond.) 2.0400 x 690 x 4 x 9.80665 55,215
+ (Insulator strings weight) 728 x 9.80665 7,139
V3 (Total) 62,354

Transverse Load (Wind Loads + Line Angle Loads)


T1 = (Diameter of OPGW) x (Wind Span) x (Wind pressure) 0.01180 x 550 x 1128 7,321
+ 2 x (tension) x sin ( q / 2 ) 2 x 8816 x 0.0262 462
T1 (Total) 7,783
T2 = (Diameter of Arrester wire) x (Wind Span) x (Wind pressure) 0.01050 x 550 x 1128 6,514
+ 2 x (tension) x sin ( q / 2 ) 2 x 7672 x 0.0262 402
T2 (Total) 6,916
T3 = (Dia. of cond.) x (Wind Span) x (Wind pressure ) x (no. of Cond.) 0.03391 x 460 x 932 x 4 58,152
+ 2 x (tension) x sin q / 2 x (No. of Cond.) 2 x 27556 x 0.0262 x 4 5,776
+ (Insulator Project Area) x (Number of Insulator) x (Wind pressure) 0.0210 x 104 x 3776 8,247
T3 (Total) 72,175

Longitudinal Load (Pulling Load)


Longitudinal Load = 0 0

Case -2, 21(L), 22(R): Extreme Condition ( 45゜ Wind Condition)


Vertical Loads (Dead Weight Loads)
V1 =(OPGW weight) x (Vertical Span) 0.4894 x 830 x 9.80665 3,983
V2 =(Arrester Wire weight) x (Vertical Span) 0.4265 x 830 x 9.80665 3,472
V3 = (Conductor weight) x (Vertical Span) x (No. of Cond.) 2.0400 x 690 x 4 x 9.80665 55,215
+ (Insulator strings weight) 728 x 9.80665 7,139
V3 (Total) 62,354

Transverse Load (Wind Loads 45 degree oblique + Line Angle Loads)


T1 = (Diameter of OPGW) x (Wind Span) x (Wind pressure) 0.01180 x 550 x 1128 x 0.707 5,177
+ 2 x (tension) x sin ( q / 2 ) 2 x 8816 x 0.0262 462
T1 (Total) 5,639
T2 = (Diameter of Arrester wire) x (Wind Span) x (Wind pressure) 0.01050 x 550 x 1128 x 0.707 4,606
+ 2 x (tension) x sin ( q / 2 ) 2 x 7672 x 0.0262 402
T2 (Total) 5,008
T3 = (Dia. of cond.) x (Wind Span) x (Wind pressure) x (no. of Cond.) 0.03391 x 460 x 932 x 4 x 0.707 41,119
+ 2 x (tension) x sin q / 2 x (No. of Cond.) 2 x 27556 x 0.0262 x 4 5,776
+ (Insulator Project Area) x (Number of Insulator) x (Wind pressure) 0.0210 x 104 x 3776 x 0.707 5,831
T3 (Total) 52,726

Longitudinal Load (Pulling Load)


Longitudinal Load = 0 0

Case -3, 23(L), 24(R): Extreme Condition ( 60゜ Wind Condition)


Vertical Loads (Dead Weight Loads)
V1 =(OPGW weight) x (Vertical Span) 0.4894 x 830 x 9.80665 3,983
V2 =(Arrester Wire weight) x (Vertical Span) 0.4265 x 830 x 9.80665 3,472
V3 = (Conductor weight) x (Vertical Span) x (No. of Cond.) 2.0400 x 690 x 4 x 9.80665 55,215
+ (Insulator strings weight) 728 x 9.80665 7,139
V3 (Total) 62,354

Transverse Load (Wind Loads 60 degree oblique + Line Angle Loads)


T1 = (Diameter of OPGW) x (Wind Span) x (Wind pressure) 0.01180 x 550 x 1128 x 0.866 6,340
+ 2 x (tension) x sin ( q / 2 ) 2 x 8816 x 0.0262 462
T1 (Total) 6,802
T2 = (Diameter of Arrester wire) x (Wind Span) x (Wind pressure) 0.01050 x 550 x 1128 x 0.866 5,641
+ 2 x (tension) x sin ( q / 2 ) 2 x 7672 x 0.0262 402
T2 (Total) 6,043
T3 = (Dia. of cond.) x (Wind Span) x (Wind pressure) x (no. of Cond.) 0.03391 x 460 x 932 x 4 x 0.866 50,361
+ 2 x (tension) x sin q / 2 x (No. of Cond.) 2 x 27556 x 0.0262 x 4 5,776
+ (Insulator Project Area) x (Number of Insulator) x (Wind pressure) 0.0210 x 104 x 3776 x 0.866 7,142
T3 (Total) 63,279

Longitudinal Load (Pulling Load)


Longitudinal Load = 0 0

Case -4, 25(L), 26(R): Extreme Condition ( Longitudinal Wind Condition)


Vertical Loads (Dead Weight Loads)
V1 =(OPGW weight) x (Vertical Span) 0.4894 x 830 x 9.80665 3,983
V2 =(Arrester Wire weight) x (Vertical Span) 0.4265 x 830 x 9.80665 3,472
V3 = (Conductor weight) x (Vertical Span) x (No. of Cond.) 2.0400 x 690 x 4 x 9.80665 55,215
+ (Insulator strings weight) 728 x 9.80665 7,139
V3 (Total) 62,354

Transverse Load (Wind Loads + Line Angle Loads)


T1 = (Diameter of OPGW) x (Wind Span) x (Wind pressure) 0.01180 x 550 x 1128 x 0 -
+ 2 x (tension) x sin ( q / 2 ) 2 x 8816 x 0.0262 462
T1 (Total) 462
T2 = (Diameter of Arrester wire) x (Wind Span) x (Wind pressure) 0.01050 x 550 x 1128 x 0 -
+ 2 x (tension) x sin ( q / 2 ) 2 x 7672 x 0.0262 402
T2 (Total) 402
T3 = (Dia. of cond.) x (Wind Span) x (Wind pressure) x (no. of Cond.) 0.03391 x 460 x 932 x 4 x 0 -
+ 2 x (tension) x sin q / 2 x (No. of Cond.) 2 x 27556 x 0.0262 x 4 5,776
+ (Insulator Project Area) x (Number of Insulator) x (Wind pressure) 0.0210 x 104 x 3776 x 0 -
T3 (Total) 5,776

Longitudinal Load (Pulling Load)


Longitudinal Load = 0 0
Design Load Calculation for Tower Type DQS [ Unit : N ]
Case -5, 6, 27(L), 28(R), 29(L), 30(R): Broken Condition (Transverse Wind Condition)
Vertical Loads (Dead Weight Loads)
V1 =(OPGW weight) x (Vertical Span) 0.4894 x 830 x 9.80665 3,983
V2 =(Arrester Wire weight) x (Vertical Span) 0.4265 x 830 x 9.80665 3,472
V3 = (Conductor weight) x (Vertical Span) x (No. of Cond.) 2.0400 x 690 x 4 x 9.80665 55,215
+ (Insulator Strings weight) 728 x 9.80665 7,139
V3 (Total) 62,354

Transverse Load (Wind Loads + Line Angle Loads)


T1 = (Diameter of OPGW) x (Wind Span) x (Wind pressure) 0.01180 x 550 x 746 4,842
+ 2 x (tension) x sin ( q / 2 ) 2 x 8816 x 0.0262 462
T1 (Total) 5,304
T2 = (Diameter of Arrester wire) x (Wind Span) x (Wind pressure) 0.01050 x 550 x 746 4,308
+ 2 x (tension) x sin ( q / 2 ) 2 x 7672 x 0.0262 402
T2 (Total) 4,710
T3 = (Dia. of cond.) x (Wind Span) x (Wind pressure 2) x (no. of Cond.) 0.03391 x 460 x 618 x 4 38,560
+ 2 x (tension) x sin q / 2 x (No. of Cond.) 2 x 27556 x 0.0262 x 4 5,776
+ (Insulator Project Area) x (Number of Insulator) x (Wind pressure) 0.0210 x 104 x 2452 5,355
T3 (Total) 49,691

Longitudinal Load (Pulling Load)


Longitudinal Load = (maximum tension) x (No. of Cond.)
OPGW 16217 x 1.0 16,217
Arrester Wire 14340 x 1.0 14,340
Conductor 38770 x 0.7 x 4 108,556

Case -7, 8, 31(L), 32(R), 33(L), 34(R): Broken Condition ( Longitudinal Wind Condition )
Vertical Loads (Dead Weight Loads)
V1 =(OPGW weight) x (Vertical Span) 0.4894 x 830 x 9.80665 3,983
V2 =(Arrester Wire weight) x (Vertical Span) 0.4265 x 830 x 9.80665 3,472
V3 = (Conductor weight) x (Vertical Span) x (No. of Cond.) 2.0400 x 690 x 4 x 9.80665 55,215
+ (Insulator weight) 728 x 9.80665 7,139
V3 (Total) 62,354

Transverse Load (Wind Loads + Line Angle Loads)


T1 = (Diameter of OPGW) x (Wind Span) x (Wind pressure) 0.01180 x 550 x 746 x 0 0
+ 2 x (tension) x sin ( q / 2 ) 2 x 8816 x 0.0262 462
T1 (Total) 462
T2 = (Diameter of Arrester wire) x (Wind Span) x (Wind pressure) 0.01050 x 550 x 746 x 0 0
+ 2 x (tension) x sin ( q / 2 ) 2 x 7672 x 0.0262 402
T2 (Total) 402
T3 = (Dia. of cond.) x (Wind Span) x (Wind pressure 2) x (no. of Cond.) 0.03391 x 460 x 618 x 4 x 0 0
+ 2 x (tension) x sin q / 2 x (No. of Cond.) 2 x 27556 x 0.0262 x 4 5776
+ (Insulator Project Area) x (Number of Insulator) x (Wind pressure) 0.0210 x 104 x 2452 x 0 0
T3 (Total) 5,776

Longitudinal Load (Pulling Load)


Longitudinal Load = (maximum tension) x (No. of Cond.)
OPGW 16217 x 1.0 16,217
Arrester Wire 14340 x 1.0 14,340
Conductor 38770 x 0.7 x 4 108,556
Design Load Calculation for Tower Type DQS [ Unit : N ]
Case -9, 10, 11, 35(L), 36(R), 37(L), 38(R), 39(L), 40(R): Construction and Maintenance Condition (Transverse Wind Condition)
Vertical Loads (Dead Weight Loads)
V1 =(OPGW weight) x (Vertical Span) 0.4894 x 830 x 9.80665 3,983
V2 =(Arrester Wire weight) x (Vertical Span) 0.4265 x 830 x 9.80665 3,472
V3 = (Conductor weight) x (Vertical Span) x (No. of Cond.) 2.0400 x 690 x 4 x 9.80665 55,215
+ (Insulator Strings weight) 728 x 9.80665 7,139
V3 (Total) 62,354

Transverse Load (Wind Loads + Line Angle Loads)


T1 = (Diameter of OPGW) x (Wind Span) x (Wind pressure) 0.01180 x 550 x 245 1,590
+ 2 x (tension) x sin ( q / 2 ) 2 x 8816 x 0.0262 462
T1 (Total) 2,052
T2 = (Diameter of Arrester wire) x (Wind Span) x (Wind pressure) 0.01050 x 550 x 245 1,415
+ 2 x (tension) x sin ( q / 2 ) 2 x 7672 x 0.0262 402
T2 (Total) 1,817
T3 = (Dia. of cond.) x (Wind Span) x (Wind pressure 2) x (no. of Cond.) 0.03391 x 460 x 196 x 4 12,229
+ 2 x (tension) x sin q / 2 x (No. of Cond.) 2 x 27556 x 0.0262 x 4 5,776
+ (Insulator Project Area) x (Number of Insulator) x (Wind pressure) 0.0210 x 104 x 755 1,649
T3 (Total) 19,654

Longitudinal Load (Pulling Load)


Longitudinal Load = (maximum tension) x (No. of Cond.)
OPGW 10599 x 0.5 5,300
Arrester Wire 9246 x 0.5 4,623
Conductor 30517 x 0.5 x 4 61,034

Case -12, 13, 14, 41(L), 42(R), 43(L), 44(R), 45(L), 46(R): Construction and Maintenance Condition ( Longitudinal Wind Condition )
Vertical Loads (Dead Weight Loads)
V1 =(OPGW weight) x (Vertical Span) 0.4894 x 830 x 9.80665 3,983
V2 =(Arrester Wire weight) x (Vertical Span) 0.4265 x 830 x 9.80665 3,472
V3 = (Conductor weight) x (Vertical Span) x (No. of Cond.) 2.0400 x 690 x 4 x 9.80665 55,215
+ (Insulator weight) 728 x 9.80665 7,139
V3 (Total) 62,354

Transverse Load (Wind Loads + Line Angle Loads)


T1 = (Diameter of OPGW) x (Wind Span) x (Wind pressure) 0.01180 x 550 x 245 x 0 0
+ 2 x (tension) x sin ( q / 2 ) 2 x 8816 x 0.0262 462
T1 (Total) 462
T2 = (Diameter of Arrester wire) x (Wind Span) x (Wind pressure) 0.01050 x 550 x 245 x 0 0
+ 2 x (tension) x sin ( q / 2 ) 2 x 7672 x 0.0262 402
T2 (Total) 402
T3 = (Dia. of cond.) x (Wind Span) x (Wind pressure 2) x (no. of Cond.) 0.03391 x 460 x 196 x 4 x 0 0
+ 2 x (tension) x sin q / 2 x (No. of Cond.) 2 x 27556 x 0.0262 x 4 5776
+ (Insulator Project Area) x (Number of Insulator) x (Wind pressure) 0.0210 x 104 x 755 x 0 0
T3 (Total) 5,776

Longitudinal Load (Pulling Load)


Longitudinal Load = (maximum tension) x (No. of Cond.)
OPGW 10599 x 0.5 5,300
Arrester Wire 9246 x 0.5 4,623
Conductor 30517 x 0.5 x 4 61,034
Design Load Calculation for Tower Type DQS [ Unit : N ]
Case -15, 47(L), 48(R): High Intensity Condition (Transverse Wind Condition)
Vertical Loads (Dead Weight Loads)
V1 =(OPGW weight) x (Vertical Span) 0.4894 x 830 x 9.80665 3,983
V2 =(Arrester Wire weight) x (Vertical Span) 0.4265 x 830 x 9.80665 3,472
V3 = (Conductor weight) x (Vertical Span) x (No. of Cond.) 2.0400 x 690 x 4 x 9.80665 55,215
+ (Insulator strings weight) 728 x 9.80665 7,139
V3 (Total) 62,354

Transverse Load (Wind Loads + Line Angle Loads)


T1 = (Diameter of OPGW) x (Wind Span) x (Wind pressure) 0.01180 x 550 x 0 -
+ 2 x (tension) x sin ( q / 2 ) 2 x 8816 x 0.0262 462
T1 (Total) 462
T2 = (Diameter of Arrester wire) x (Wind Span) x (Wind pressure) 0.01050 x 550 x 0 -
+ 2 x (tension) x sin ( q / 2 ) 2 x 7672 x 0.0262 402
T2 (Total) 402
T3 = (Dia. of cond.) x (Wind Span) x (Wind pressure ) x (no. of Cond.) 0.03391 x 460 x 0 x 4 -
+ 2 x (tension) x sin q / 2 x (No. of Cond.) 2 x 27556 x 0.0262 x 4 5,776
+ (Insulator Project Area) x (Number of Insulator) x (Wind pressure) 0.0210 x 104 x 8090 17,669
T3 (Total) 23,445

Longitudinal Load (Pulling Load)


Longitudinal Load = 0 0

Case -16, 49(L), 50(R): High Intensity Condition ( 45゜ Wind Condition)
Vertical Loads (Dead Weight Loads)
V1 =(OPGW weight) x (Vertical Span) 0.4894 x 830 x 9.80665 3,983
V2 =(Arrester Wire weight) x (Vertical Span) 0.4265 x 830 x 9.80665 3,472
V3 = (Conductor weight) x (Vertical Span) x (No. of Cond.) 2.0400 x 690 x 4 x 9.80665 55,215
+ (Insulator strings weight) 728 x 9.80665 7,139
V3 (Total) 62,354

Transverse Load (Wind Loads 45 degree oblique + Line Angle Loads)


T1 = (Diameter of OPGW) x (Wind Span) x (Wind pressure) 0.01180 x 550 x 0 x 0.707 -
+ 2 x (tension) x sin ( q / 2 ) 2 x 8816 x 0.0262 462
T1 (Total) 462
T2 = (Diameter of Arrester wire) x (Wind Span) x (Wind pressure) 0.01050 x 550 x 0 x 0.707 -
+ 2 x (tension) x sin ( q / 2 ) 2 x 7672 x 0.0262 402
T2 (Total) 402
T3 = (Dia. of cond.) x (Wind Span) x (Wind pressure) x (no. of Cond.) 0.03391 x 460 x 0 x 4 x 0.707 -
+ 2 x (tension) x sin q / 2 x (No. of Cond.) 2 x 27556 x 0.0262 x 4 5,776
+ (Insulator Project Area) x (Number of Insulator) x (Wind pressure) 0.0210 x 104 x 8090 x 0.707 12,494
T3 (Total) 18,270

Longitudinal Load (Pulling Load)


Longitudinal Load = 0 0

Case -17, 51(L), 52(R): High Intensity Condition ( 60゜ Wind Condition)
Vertical Loads (Dead Weight Loads)
V1 =(OPGW weight) x (Vertical Span) 0.4894 x 830 x 9.80665 3,983
V2 =(Arrester Wire weight) x (Vertical Span) 0.4265 x 830 x 9.80665 3,472
V3 = (Conductor weight) x (Vertical Span) x (No. of Cond.) 2.0400 x 690 x 4 x 9.80665 55,215
+ (Insulator strings weight) 728 x 9.80665 7,139
V3 (Total) 62,354

Transverse Load (Wind Loads 60 degree oblique + Line Angle Loads)


T1 = (Diameter of OPGW) x (Wind Span) x (Wind pressure) 0.01180 x 550 x 0 x 0.866 -
+ 2 x (tension) x sin ( q / 2 ) 2 x 8816 x 0.0262 462
T1 (Total) 462
T2 = (Diameter of Arrester wire) x (Wind Span) x (Wind pressure) 0.01050 x 550 x 0 x 0.866 -
+ 2 x (tension) x sin ( q / 2 ) 2 x 7672 x 0.0262 402
T2 (Total) 402
T3 = (Dia. of cond.) x (Wind Span) x (Wind pressure) x (no. of Cond.) 0.03391 x 460 x 0 x 4 x 0.866 -
+ 2 x (tension) x sin q / 2 x (No. of Cond.) 2 x 27556 x 0.0262 x 4 5,776
+ (Insulator Project Area) x (Number of Insulator) x (Wind pressure) 0.0210 x 104 x 8090 x 0.866 15,301
T3 (Total) 21,077

Longitudinal Load (Pulling Load)


Longitudinal Load = 0 0

Case -18, 53(L), 54(R): High Intensity Condition ( Longitudinal Wind Condition)
Vertical Loads (Dead Weight Loads)
V1 =(OPGW weight) x (Vertical Span) 0.4894 x 830 x 9.80665 3,983
V2 =(Arrester Wire weight) x (Vertical Span) 0.4265 x 830 x 9.80665 3,472
V3 = (Conductor weight) x (Vertical Span) x (No. of Cond.) 2.0400 x 690 x 4 x 9.80665 55,215
+ (Insulator strings weight) 728 x 9.80665 7,139
V3 (Total) 62,354

Transverse Load (Wind Loads + Line Angle Loads)


T1 = (Diameter of OPGW) x (Wind Span) x (Wind pressure) 0.01180 x 550 x 0 x 0 -
+ 2 x (tension) x sin ( q / 2 ) 2 x 8816 x 0.0262 462
T1 (Total) 462
T2 = (Diameter of Arrester wire) x (Wind Span) x (Wind pressure) 0.01050 x 550 x 0 x 0 -
+ 2 x (tension) x sin ( q / 2 ) 2 x 7672 x 0.0262 402
T2 (Total) 402
T3 = (Dia. of cond.) x (Wind Span) x (Wind pressure) x (no. of Cond.) 0.03391 x 460 x 0 x 4 x 0 -
+ 2 x (tension) x sin q / 2 x (No. of Cond.) 2 x 27556 x 0.0262 x 4 5,776
+ (Insulator Project Area) x (Number of Insulator) x (Wind pressure) 0.0210 x 104 x 8090 x 0 -
T3 (Total) 5,776

Longitudinal Load (Pulling Load)


Longitudinal Load = 0 0
3.983 3.983 3.983 3.983 3.983 3.983

7.783 7.783 5.639 5.639 6.802 6.802

72.175 72.175 52.726 52.726 63.279 63.279

62.354 62.354 62.354 62.354 62.354 62.354

72.175 72.175 52.726 52.726 63.279 63.279

62.354 62.354 62.354 62.354 62.354 62.354

72.175 72.175 52.726 52.726 63.279 63.279

62.354 62.354 62.354 62.354 62.354 62.354

DW
DW

DW
Case 1 Case 2 Case 3
Extreme Condition Extreme Condition Extreme Condition
Transverse Wind 45° Wind 60° Wind
O.L.F=1.15 O.L.F=1.15 O.L.F=1.15
Note
All Loads are in kN
All longitudinal loads are in the same direction
Factor of safety are not included
DW : Dead weight of tower Design Load Diagram for Tower Type DQS (1/16)
2
Wind Pressure of 3.776kN/m shall be considered.
3.983 3.983

0.462 0.462

5.776 5.776

62.354 62.354

5.776 5.776

62.354 62.354

5.776 5.776

62.354 62.354
DW

Case 4
Extreme Condition
Longitudinal Wind
O.L.F=1.15
Note
All Loads are in kN
All longitudinal loads are in the same direction
Factor of safety are not included
DW : Dead weight of tower Design Load Diagram for Tower Type DQS (2/16)
2
Wind Pressure of 3.776kN/m shall be considered.
3.983 3.983 3.983 3.983

5.304 5.304 5.304 5.304

16.217

49.691 49.691 49.691 49.691

108.556

62.354 62.354 62.354 62.354

49.691 49.691 49.691 49.691

62.354 62.354 62.354 62.354

49.691 49.691 49.691 49.691

62.354 62.354 62.354 62.354


DW

Case 5 DW
Case 6
Broken Condition(any one earthwire) Broken Condition(any one conductor )
Transverse Wind Transverse Wind
O.L.F=1.0 O.L.F=1.0
Note
All Loads are in kN
All longitudinal loads are in the same direction
Factor of safety are not included
DW : Dead weight of tower Design Load Diagram for Tower Type DQS (3/16)
2
Wind Pressure of 2.452kN/m shall be considered.
3.983 3.983 3.983 3.983

0.462 0.462 0.462 0.462

16.217

5.776 5.776 5.776 5.776

108.556
62.354 62.354 62.354 62.354

5.776 5.776 5.776 5.776

62.354 62.354 62.354 62.354

5.776 5.776 5.776 5.776

62.354 62.354 62.354 62.354


DW

DW

Case 7 Case 8
Broken Condition(any one earthwire) Broken Condition(any one conductor )
Longitudinal wind Longitudinal wind
O.L.F=1.0 O.L.F=1.0
Note
All Loads are in kN
All longitudinal loads are in the same direction
Factor of safety are not included
DW : Dead weight of tower Design Load Diagram for Tower Type DQS (4/16)
Wind Pressure of 2.452kN/m2 shall be considered.
7.966 7.966 3.983 3.983 7.966 3.983

2.052 2.052 2.052 2.052 2.052 2.052

5.300 5.300 5.300

19.654 19.654 19.654 19.654 19.654 19.654

61.034 61.034

62.354 62.354 124.708 62.354 124.708 62.354

19.654 19.654 19.654 19.654 19.654 19.654

61.034

62.354 62.354 124.708 62.354 62.354 62.354

19.654 19.654 19.654 19.654 19.654 19.654

62.354 62.354 62.354 62.354 62.354 62.354

DW
DW

DW
Case 9 Case 10 Case 11
Construction and Mainetnance
Construction and Mainetnance Construction and Mainetnance
Condition (Combination of any
Condition(any Two earthwire) Condition(any Two conductors)
one earth wire and conductor)
Transverse Wind Transverse Wind Transverse Wind
O.L.F=1.0 O.L.F=1.0 O.L.F=1.0
Note
All Loads are in kN
All longitudinal loads are in the same direction
Factor of safety are not included
DW : Dead weight of tower Design Load Diagram for Tower Type DQS (5/16)
2
Wind Pressure of 0.755kN/m shall be considered.
7.966 7.966 3.983 3.983 7.966 3.983

0.462 0.462 0.462 0.462 0.462 0.462

5.300 5.300 5.300

5.776 5.776 5.776 5.776 5.776 5.776

61.034 61.034

62.354 62.354 124.708 62.354 124.708 62.354

5.776 5.776 5.776 5.776 5.776 5.776

61.034

62.354 62.354 124.708 62.354 62.354 62.354

5.776 5.776 5.776 5.776 5.776 5.776

62.354 62.354 62.354 62.354 62.354 62.354

DW

DW
DW

Case 12 Case 13 Case 14


Construction and Mainetnance
Construction and Mainetnance Construction and Mainetnance
Condition(Combination of any
Condition(any Two earthwire) Condition(any Two conductors)
one earth wire and conductor)
Longitudinal Wind Longitudinal Wind Longitudinal Wind
O.L.F=1.0 O.L.F=1.0 O.L.F=1.0
Note
All Loads are in kN
All longitudinal loads are in the same direction
Factor of safety are not included
DW : Dead weight of tower
Design Load Diagram for Tower Type DQS (6/16)
2
Wind Pressure of 0.755kN/m shall be considered.
3.983 3.983 3.983 3.983 3.983 3.983

0.462 0.462 0.462 0.462 0.462 0.462

23.445 23.445 18.270 18.270 21.077 21.077

62.354 62.354 62.354 62.354 62.354 62.354

23.445 23.445 18.270 18.270 21.077 21.077

62.354 62.354 62.354 62.354 62.354 62.354

23.445 23.445 18.270 18.270 21.077 21.077

62.354 62.354 62.354 62.354 62.354 62.354

DW
DW

DW
Case 15 Case 16 Case 17
High Intensity Condition High Intensity Condition High Intensity Condition
Transverse Wind 45° Wind 60° Wind
O.L.F=1.0 O.L.F=1.0 O.L.F=1.0
Note
All Loads are in kN
All longitudinal loads are in the same direction
Factor of safety are not included
DW : Dead weight of tower Design Load Diagram for Tower Type DQS (7/16)
Wind Pressure of 8.090kN/m2 shall be considered.
3.983 3.983

0.462 0.462

5.776 5.776

62.354 62.354

5.776 5.776

62.354 62.354

5.776 5.776

62.354 62.354
DW

Case 18
High Intensity Condition
Longitudinal Wind
O.L.F=1.0
Note
All Loads are in kN
All longitudinal loads are in the same direction
Factor of safety are not included
DW : Dead weight of tower
Design Load Diagram for Tower Type DQS (8/16)
Wind Pressure of 8.090kN/m2 shall be considered.
3.983 ( 3.983 ) 3.983 ( 3.983 ) 3.983 ( 3.983 )

7.783 ( 7.783 ) 5.639 ( 5.639 ) 6.802 ( 6.802 )

72.175 ( 72.175 ) 52.726 ( 52.726 ) 63.279 ( 63.279 )

62.354 ( 62.354 ) 62.354 ( 62.354 ) 62.354 ( 62.354 )

72.175 ( 72.175 ) 52.726 ( 52.726 ) 63.279 ( 63.279 )

62.354 ( 62.354 ) 62.354 ( 62.354 ) 62.354 ( 62.354 )

72.175 ( 72.175 ) 52.726 ( 52.726 ) 63.279 ( 63.279 )

62.354 ( 62.354 ) 62.354 ( 52.726 ) 62.354 ( 62.354 )


DW

DW

DW
Case 19(L) & 20 ( R) Case 21 (L) & 22 ( R) Case 23 (L) & 24 ( R)
Extreme Condition Extreme Condition Extreme Condition
Transverse Wind 45° Wind 60° Wind
O.L.F=1.15 O.L.F=1.15 O.L.F=1.15
Note
All Loads are in kN
All longitudinal loads are in the same direction
Factor of safety are not included
DW : Dead weight of tower Design Load Diagram for Tower Type DQS (9/16)
2
Wind Pressure of 3.776kN/m shall be considered.
3.983 ( 3.983 )

0.462 ( 0.462 )

5.776 ( 5.776 )

62.354 ( 62.354 )

5.776 ( 5.776 )

62.354 ( 62.354 )

5.776 ( 5.776 )

62.354 ( 62.354 )
DW

Case 25(L) & 26 ( R)


Extreme Condition
Longitudinal Wind
O.L.F=1.15
Note
All Loads are in kN
All longitudinal loads are in the same direction
Factor of safety are not included
DW : Dead weight of tower Design Load Diagram for Tower Type DQS (10/16)
2
Wind Pressure of 3.776kN/m shall be considered.
3.983 ( 3.983 ) 3.983 ( 3.983 )

5.304 ( 5.304 ) 5.304 ( 5.304 )

16.217

49.691 ( 49.691 ) 49.691 ( 49.691 )

108.556

62.354 ( 62.354 ) 62.354 ( 62.354 )

49.691 ( 49.691 ) 49.691 ( 49.691 )

62.354 ( 62.354 ) 62.354 ( 62.354 )

49.691 ( 49.691 ) 49.691 ( 49.691 )

62.354 ( 62.354 ) 62.354 ( 62.354 )


DW

Case 27 (L) & 28 ( R) DW


Case 29 (L) & 30 ( R)
Broken Condition(any one earthwire) Broken Condition(any one conductor )
Transverse Wind Transverse Wind
O.L.F=1.0 O.L.F=1.0
Note
All Loads are in kN
All longitudinal loads are in the same direction
Factor of safety are not included
DW : Dead weight of tower Design Load Diagram for Tower Type DQS (11/16)
2
Wind Pressure of 2.452kN/m shall be considered.
3.983 ( 3.983 ) 3.983

0.462 ( 0.462 ) 0.462 ( 0.462 )

16.217

5.776 ( 5.776 ) 5.776 ( 5.776 )

108.556
62.354 ( 62.354 ) 62.354 ( 62.354 )

5.776 ( 5.776 ) 5.776 ( 5.776 )

62.354 ( 62.354 ) 62.354 ( 62.354 )

5.776 ( 5.776 ) 5.776 ( 5.776 )

62.354 ( 62.354 ) 62.354 ( 62.354 )


DW

DW

Case 31 (L) & 32 ( R) Case 33 (L) & 34 ( R)


Broken Condition(any one earthwire) Broken Condition(any one conductor )
Longitudinal wind Longitudinal wind
O.L.F=1.0 O.L.F=1.0
Note
All Loads are in kN
All longitudinal loads are in the same direction
Factor of safety are not included
DW : Dead weight of tower Design Load Diagram for Tower Type DQS (12/16)
Wind Pressure of 2.452kN/m2 shall be considered.
7.966 ( 3.983 ) 3.983 ( 3.983 ) 3.983 ( 3.983 )

2.052 ( 2.052 ) 2.052 ( 2.052 ) 2.052 ( 2.052 )

5.300 5.300

19.654 ( 19.654 ) 19.654 ( 19.654 ) 19.654 ( 19.654 )

61.034 61.034

62.354 ( 62.354 ) 124.708 ( 62.354 ) 124.708 ( 62.354 )

19.654 ( 19.654 ) 19.654 ( 19.654 ) 19.654 ( 19.654 )

61.034

62.354 ( 62.354 ) 124.708 ( 62.354 ) 62.354 ( 62.354 )

19.654 ( 19.654 ) 19.654 ( 19.654 ) 19.654 ( 19.654 )

62.354 ( 62.354 ) 62.354 ( 62.354 ) 62.354 ( 62.354 )

DW
DW

DW
Case 35 (L) & 36 ( R) Case 37 (L) & 38 ( R) Case 39 (L) & 40 ( R)
Construction and Mainetnance
Construction and Mainetnance Construction and Mainetnance
Condition (Combination of any
Condition(any One earthwire) Condition(any Two conductors)
one earth wire and conductor)
Transverse Wind Transverse Wind Transverse Wind
O.L.F=1.0 O.L.F=1.0 O.L.F=1.0
Note
All Loads are in kN
All longitudinal loads are in the same direction
Factor of safety are not included
DW : Dead weight of tower Design Load Diagram for Tower Type DQS (13/16)
Wind Pressure of 0.755kN/m2 shall be considered.
7.966 ( 7.966 ) 3.983 ( 3.983 ) 7.966 ( 3.983 )

0.462 ( 0.462 ) 0.462 ( 0.462 ) 0.462 ( 0.462 )

5.300 5.300

5.776 ( 5.776 ) 5.776 ( 5.776 ) 5.776 ( 5.776 )

61.034 61.034

62.354 ( 62.354 ) 124.708 ( 62.354 ) 124.708 ( 62.354 )

5.776 ( 5.776 ) 5.776 5.776 ) 5.776 ( 5.776 )

61.034

62.354 ( 62.354 ) 124.708 ( 62.354 ) 62.354 ( 62.354 )

5.776 ( 5.776 ) 5.776 ( 5.776 ) 5.776 ( 5.776 )

62.354 ( 62.354 ) 62.354 ( 62.354 ) 62.354 ( 62.354 )


DW

DW

DW
Case 41 (L) & 42 ( R) Case 43 (L) & 44 ( R) Case 45 (L) & 46 ( R)
Construction and Mainetnance
Construction and Mainetnance Construction and Mainetnance
Condition(Combination of any one
Condition(any One earthwire) Condition(any Two conductors)
earth wire and conductor)
Longitudinal Wind Longitudinal Wind Longitudinal Wind
O.L.F=1.0 O.L.F=1.0 O.L.F=1.0
Note
All Loads are in kN
All longitudinal loads are in the same direction
Factor of safety are not included
DW : Dead weight of tower
Design Load Diagram for Tower Type DQS (14/16)
2
Wind Pressure of 0.755kN/m shall be considered.
3.983 ( 3.983 ) 3.983 ( 3.983 ) 3.983 ( 3.983 )

0.462 ( 0.462 ) 0.462 ( 0.462 ) 0.462 ( 0.462 )

23.445 ( 23.445 ) 18.270 ( 18.270 ) 21.077 ( 21.077 )

62.354 ( 62.354 ) 62.354 ( 62.354 ) 62.354 ( 62.354 )

23.445 ( 23.445 ) 18.270 ( 18.270 ) 21.077 ( 21.077 )

62.354 ( 62.354 ) 62.354 ( 62.354 ) 62.354 ( 62.354 )

23.445 ( 23.445 ) 18.270 ( 18.270 ) 21.077 ( 21.077 )

62.354 ( 62.354 ) 62.354 ( 62.354 ) 62.354 ( 62.354 )

DW
DW

DW
Case 47 (L) & 48 ( R) Case 49 (L) & 50 ( R) Case 51 (L) & 52 ( R)
High Intensity Condition High Intensity Condition High Intensity Condition
Transverse Wind 45° Wind 60° Wind
O.L.F=1.0 O.L.F=1.0 O.L.F=1.0
Note
All Loads are in kN
All longitudinal loads are in the same direction
Factor of safety are not included
DW : Dead weight of tower Design Load Diagram for Tower Type DQS (15/16)
Wind Pressure of 8.090kN/m2 shall be considered.
3.983 ( 3.983 )

0.462 ( 0.462 )

5.776 ( 5.776 )

62.354 ( 62.354 )

5.776 ( 5.776 )

62.354 ( 62.354 )

5.776 ( 5.776 )

62.354 ( 62.354 )
DW

Case 53 (L) & 54 ( R)


High Intensity Condition
Longitudinal Wind
O.L.F=1.0
Note
All Loads are in kN
All longitudinal loads are in the same direction
Factor of safety are not included
DW : Dead weight of tower
Design Load Diagram for Tower Type DQS (16/16)
Wind Pressure of 8.090kN/m2 shall be considered.