STAATSOLIE MAATSCHAPPIJ SURINAME N.V.

TECHNICAL SERVICES - INSPECTION DEPARTMENT


INSPECTION RECOMMENDATIONS
Equipment Tag: 4"-RW-804-1A2A Unit / AREA: 800 (T-8031 Raw Water Tank)

Reco No.: 007 WO No:

Equipment Name: RW Discharge line from T-8031 to P-8031AB Project:

Inspection Start Date: 12/5/2014 Report Date: 13-05-2014

Last Inspection Date: Inspection Type: VT

FINDINGS :

1. Leakage on CS spool piece from of T-8031 Discharge Line to P-8031AB .

2. 3 small pinhole that are already starting to leak.

RECOMMENDATIONS :
1. Renew this CS spool piece with Galvanised material (as shown in the attached drawing).

2. If the 8" * 4" Concentric Reducer is not available in galvanized material , than a CS can be used. But the
preparation to weld the reducer to the galv. Pipe most be cleaned good.

3. If a CS reducer will be used, the internal of the reducer must be painted with the paint that will be used for
the internal of the tank

4. All weld joints must be cleaned (wirebrushed) and coated with a Zinc Rich Primer (92% Zn)

Attachments :
Drawing of 4"-RW-804-1A2A with remarks on it.

Remarks: