High Pot Test of 11KV Vacuum C.B Applied Voltage= 18 KV.DC
Test Mode R (uA) Y(uA) B(uA) Up side VCB to G 5.00 5.00 6.00 Down side VCB to G 5.00 5.00 5.00
High Pot Test of 11KV Bus Bar Applied Voltage = 18KV. DC
Phase Applied Voltage DC L/Current (uA) R 18 KV 0.8 Y 0.7 B 0.7
Contact Resistance test of 11KV C.B
C.B Phase Applied Current Resistance ( O/G ) R 100A 23.6 Y 27.5 B 24.8
11 KV Circuit Breaker Opening Time Test
Pole Opening Time (ms) Closing Time (ms)
Red 36.3 68.2 Yellow 37.4 69.2 Blue 36.5 69.8 CT Ratio Test of 11KV Panels: Connected CT Applied R Measured Y Measured B Measured Ratio Current Current (A) Current (A) Current (A) (A) 600/5 40 0.33 0.33 0.33 80 0.66 0.66 0.66
PT Ratio Test of 11KV Panels:
Connected CT Applied R Measured Y Measured B Measured Ratio Voltage Voltage Voltage Voltage (V) (V) (V) (V) 11500/110 243 2.32 2.33 2.33
1. CT and PT Circuit checked and found OK for all panels.
2. Trip through Over Current Relay checked and found OK for panels.