Professional Documents
Culture Documents
54-69 Loadflow - Utility - Complete Nocapacitor PDF
54-69 Loadflow - Utility - Complete Nocapacitor PDF
Number of Buses: 1 0 32 33
Number of Branches: 16 0 0 12 0 4 32
54 | P a g e
ETAP
Project: Ginebra Cabuyao Plant 14.1.0C Page: 2
Location: Canlubang, Laguna Date: 02-14-2019
Contract: OTI-10125191514 SN: 312114912121
Engineer: JRC Study Case: Load Flow Revision: Base
Filename: ginebra_analysisv2 Config.: Normal
Adjustments
Apply Individual
Tolerance Adjustments /Global Percent
Transformer Impedance: Yes Individual
Cable Length: No
Apply Individual
Temperature Correction Adjustments /Global Degree C
55 | P a g e
ETAP
Project: Ginebra Cabuyao Plant 14.1.0C Page: 3
Location: Canlubang, Laguna Date: 02-14-2019
Contract: OTI-10125191514 SN: 312114912121
Engineer: JRC Study Case: Load Flow Revision: Base
Filename: ginebra_analysisv2 Config.: Normal
Load
Bus Initial Voltage Constant kVA Constant Z Constant I Generic
56 | P a g e
ETAP
Project: Ginebra Cabuyao Plant 14.1.0C Page: 4
Location: Canlubang, Laguna Date: 02-14-2019
Contract: OTI-10125191514 SN: 312114912121
Engineer: JRC Study Case: Load Flow Revision: Base
Filename: ginebra_analysisv2 Config.: Normal
Load
Bus Initial Voltage Constant kVA Constant Z Constant I Generic
Total Number of Buses: 33 1.603 0.994 0.656 0.407 0.000 0.000 0.000 0.000
0.000 0.000
57 | P a g e
ETAP
Project: Ginebra Cabuyao Plant 14.1.0C Page: 5
Location: Canlubang, Laguna Date: 02-14-2019
Contract: OTI-10125191514 SN: 312114912121
Engineer: JRC Study Case: Load Flow Revision: Base
Filename: ginebra_analysisv2 Config.: Normal
58 | P a g e
ETAP
Project: Ginebra Cabuyao Plant 14.1.0C Page: 6
Location: Canlubang, Laguna Date: 02-14-2019
Contract: OTI-10125191514 SN: 312114912121
Engineer: JRC Study Case: Load Flow Revision: Base
Filename: ginebra_analysisv2 Config.: Normal
59 | P a g e
ETAP
Project: Ginebra Cabuyao Plant 14.1.0C Page: 7
Location: Canlubang, Laguna Date: 02-14-2019
Contract: OTI-10125191514 SN: 312114912121
Engineer: JRC Study Case: Load Flow Revision: Base
Filename: ginebra_analysisv2 Config.: Normal
Branch Connections
60 | P a g e
ETAP
Project: Ginebra Cabuyao Plant 14.1.0C Page: 8
Location: Canlubang, Laguna Date: 02-14-2019
Contract: OTI-10125191514 SN: 312114912121
Engineer: JRC Study Case: Load Flow Revision: Base
Filename: ginebra_analysisv2 Config.: Normal
* Bus14 34.500 100.000 0.0 2.247 1.777 0 0 Bus15 2.247 1.777 47.9 78.4
Bus15 0.480 92.761 -4.4 0 0 0 0 Bus16 2.205 1.483 3446.0 83.0
Bus19 0.240 85.483 -6.4 0 0 0.045 0.028 Bus36 -0.045 -0.028 147.8 85.0
Bus20 0.240 87.632 -5.6 0 0 0.011 0.007 Bus37 -0.011 -0.007 36.2 85.0
Bus21 0.240 87.079 -5.9 0 0 0.041 0.026 Bus37 -0.041 -0.026 133.9 85.0
Bus22 0.240 85.368 -7.1 0 0 0.107 0.066 Bus36 -0.107 -0.066 354.6 85.0
Bus23 0.240 85.179 -6.1 0 0 0.042 0.026 Bus38 -0.042 -0.026 140.5 85.0
Bus24 0.240 86.327 -6.7 0 0 0.209 0.130 Bus39 -0.209 -0.130 685.7 85.0
Bus25 0.240 86.958 -6.3 0 0 0.142 0.088 Bus39 -0.142 -0.088 461.9 85.0
Bus26 0.240 85.266 -6.4 0 0 0.056 0.035 Bus40 -0.056 -0.035 187.0 85.0
Bus27 0.240 85.344 -6.4 0 0 0.072 0.045 Bus40 -0.072 -0.045 238.9 85.0
Bus28 0.240 87.154 -6.3 0 0 0.106 0.066 Bus42 -0.106 -0.066 345.0 85.0
Bus29 0.240 82.885 -7.4 0 0 0.081 0.050 Bus43 -0.081 -0.050 278.2 85.0
Bus30 0.240 81.656 -8.3 0 0 0.136 0.085 Bus43 -0.136 -0.085 472.6 85.0
Bus31 0.240 80.493 -9.1 0 0 0.186 0.115 Bus43 -0.186 -0.115 654.1 85.0 61 | P a g e
ETAP
Project: Ginebra Cabuyao Plant 14.1.0C Page: 9
Location: Canlubang, Laguna Date: 02-14-2019
Contract: OTI-10125191514 SN: 312114912121
Engineer: JRC Study Case: Load Flow Revision: Base
Filename: ginebra_analysisv2 Config.: Normal
Bus32 0.240 85.650 -6.6 0 0 0.061 0.038 Bus44 -0.061 -0.038 202.1 85.0
Bus36 0.480 88.326 -5.4 0 0 0.014 0.009 Bus3 -0.221 -0.143 358.4 83.9
Bus38 0.480 87.881 -5.2 0 0 0.147 0.091 Bus3 -0.191 -0.119 307.7 84.8
Bus23 0.043 0.028 70.2 84.1
Bus39 0.480 88.244 -5.4 0 0 0.006 0.003 Bus3 -0.359 -0.232 582.7 84.0
Bus24 0.211 0.137 342.9 83.8
Bus41 0.480 87.991 -5.5 0 0 0.451 0.279 Bus3 -0.451 -0.279 724.9 85.0
Bus42 0.480 88.758 -5.2 0 0 0.004 0.003 Bus3 -0.111 -0.072 179.3 84.0
* Indicates a voltage regulated bus (voltage controlled or swing type machine connected to it)
# Indicates a bus with a load mismatch of more than 0.1 MVA
62 | P a g e
ETAP
Project: Ginebra Cabuyao Plant 14.1.0C Page: 10
Location: Canlubang, Laguna Date: 02-14-2019
Contract: OTI-10125191514 SN: 312114912121
Engineer: JRC Study Case: Load Flow Revision: Base
Filename: ginebra_analysisv2 Config.: Normal
63 | P a g e
ETAP
Project: Ginebra Cabuyao Plant 14.1.0C Page: 11
Location: Canlubang, Laguna Date: 02-14-2019
Contract: OTI-10125191514 SN: 312114912121
Engineer: JRC Study Case: Load Flow Revision: Base
Filename: ginebra_analysisv2 Config.: Normal
* Indicates operating load of a bus exceeds the bus critical limit ( 100.0% of the Continuous Ampere rating).
# Indicates operating load of a bus exceeds the bus marginal limit ( 95.0% of the Continuous Ampere rating).
64 | P a g e
ETAP
Project: Ginebra Cabuyao Plant 14.1.0C Page: 12
Location: Canlubang, Laguna Date: 02-14-2019
Contract: OTI-10125191514 SN: 312114912121
Engineer: JRC Study Case: Load Flow Revision: Base
Filename: ginebra_analysisv2 Config.: Normal
Transformer
CKT / Branch Cable & Reactor
Ampacity Loading Capability Loading (input) Loading (output)
(Amp) Amp (MVA)
ID Type % MVA % MVA %
65 | P a g e
ETAP
Project: Ginebra Cabuyao Plant 14.1.0C Page: 13
Location: Canlubang, Laguna Date: 02-14-2019
Contract: OTI-10125191514 SN: 312114912121
Engineer: JRC Study Case: Load Flow Revision: Base
Filename: ginebra_analysisv2 Config.: Normal
Vd
CKT / Branch From-To Bus Flow To-From Bus Flow Losses % Bus Voltage
% Drop
ID MW Mvar MW Mvar kW kvar From To in Vmag
C10 0.063 0.041 -0.063 -0.041 0.1 0.1 89.3 89.1 0.19
C12 0.083 0.053 -0.083 -0.052 0.5 0.7 89.3 88.6 0.73
T15 0.063 0.041 -0.062 -0.039 0.3 1.5 89.1 87.9 1.26
T10 -0.056 -0.035 0.057 0.037 0.6 2.1 85.3 87.3 2.06
T11 -0.106 -0.066 0.107 0.069 0.7 3.2 87.2 88.8 1.60
T12 -0.081 -0.050 0.082 0.053 0.6 2.8 82.9 84.6 1.73
T13 -0.136 -0.085 0.138 0.093 1.7 8.1 81.7 84.6 2.95
T14 -0.186 -0.115 0.189 0.131 3.3 15.4 80.5 84.6 4.12
C11 -0.061 -0.038 0.062 0.039 1.2 1.6 85.7 87.9 2.22
T16 0.083 0.052 -0.083 -0.051 0.2 1.2 88.6 87.8 0.74
159.3 483.5
66 | P a g e
ETAP
Project: Ginebra Cabuyao Plant 14.1.0C Page: 14
Location: Canlubang, Laguna Date: 02-14-2019
Contract: OTI-10125191514 SN: 312114912121
Engineer: JRC Study Case: Load Flow Revision: Base
Filename: ginebra_analysisv2 Config.: Normal
% Alert Settings
Critical Marginal
Loading
Bus 100.0 95.0
Cable 100.0 95.0
Reactor 100.0 95.0
Line 100.0 95.0
Transformer 100.0 95.0
Panel 100.0 95.0
Protective Device 100.0 95.0
Generator 100.0 95.0
Inverter/Charger 100.0 95.0
Bus Voltage
OverVoltage 105.0 102.0
UnderVoltage 95.0 98.0
Generator Excitation
OverExcited (Q Max.) 100.0 95.0
UnderExcited (Q Min.) 100.0
Critical Report
Critical Report
Marginal Report
68 | P a g e
ETAP
Project: Ginebra Cabuyao Plant 14.1.0C Page: 16
Location: Canlubang, Laguna Date: 02-14-2019
Contract: OTI-10125191514 SN: 312114912121
Engineer: JRC Study Case: Load Flow Revision: Base
Filename: ginebra_analysisv2 Config.: Normal
MW Mvar MVA % PF
Number of Iterations: 1
69 | P a g e