Mechanical Department
Prepared By : Mohamed ElHarmil Date : 26/2/2012
REVISION :0
PREPARED BY :M EL-HARMEL DATE : ###
One First Riser with (two hose valve) gpm 500 500
The second Riser with (one hose valve) gpm 250 250
Water Spply Duration min 30 60
gallon 22500.0 45000.0
The minmum tank Capacity
m3 85.2 170.3
Notes :
The building classified as ordinary hazard group 2 (for basment)
The building equibed with device for remote alarm signal therefor the design based on minimum water duration
For remote building Water sprinkler duration shall be 90 minutes for ordinary and extra hazard
Conclusion :
Method -1 :As per NFPA 13 requirments is the worst case then select water tank capacity 120
Then The Fire Water Tank Capacity is 140 m3
REVISION :0
PREPARED BY : MOHAMED EL-HARMEL DATE :
Data
Transformer Type Oil Type
Transformer Length 2.12
Transformer Width 1.62
Transformer Height 2.1
Ground Surface Length 4.7
Ground Surface Width 4
Application Rate For Exterior
10.2
Transformer surfaces (l/min/m2) =
Application Rate For ground surfaces
6.1
(l/min/m2) =
Tank Roof
No.Of Nozzles 1
Water Rate Per Nozzle =Water
#VALUE!
Rate/No. Of Nozzles (l/min/nozzle)
Calculated Nozzle k-factor #VALUE!
Selected K-Factor 80.6
Minimum Pressure at nozzles based on #VALUE!
Standard K-Factor
Conclusion
For Tank Shell From GEM SPRINKLER COMPANY Select Nozzles
Model D3 Protectospray Open Spray Nozzle
Size 1/2" NPT
Discharge Angle 110
Orifice Size No. 18
Minimum Dia. 6.35 mm
K-Factor 25.9 ISO/SI 1.8 NFPA
###
###
REVISION :0
PREPARED BY : MOHAMED EL-HARMEL DATE : ###
Network Calculations
Maximum velocity in the pipe = 3.1 m/s 10.17 ft/s
Minimum Pressure at Foam Spray Nozzles = 2.0 bars 29.01 PSI
Area Per Foam Spray Nozzle = 10.0 m2 107.64 ft2
No.of foam spray nozzles = Warehouse area / Area Per Foam Spray Nozzle = 4.0 Nozzles
Foam Solution Quantity per Foam Spray Nozzle = 800.0 Liters 211.4 gallons
Rate of Discharge per Foam Spray Nozzle = 80.00 L/min 21.14 gpm
The Nozzles K-Factor (K) = Q/√P 56.57 ISO/SI 3.92 NFPA
REVISION :0
PREPARED BY :MF B126-May-03
FM-200 CALCULATION
PROJECT NAME
PROJECT NO.
REVISION
PREPARED BY W.ELSweedy
CO2 CALCULATION
REVISION :0
PREPARED BY : MOHAMED EL-HARMEL DATE : ###
From NFPA 11Table 3-2.3.2.1 Number of Fixed Foam Discharge Outlets for Fixed-Roof Tanks
Containing Hydrocarbons or Flammable and Combustible Liquids Requiring Alcohol-Resistant Foams
Tank Diameter (or equivalent area) Minimum
Number of
(ft) (m) Discharge Outlets
Up to 80 Up to 24 1
Application Rate = 4.10 (L/min·m2)
Discharge Times = 30 min
Induction Foam Rate = 0.03
Fuel Surface Area = 3.14*D2/4 = 88.20 m2
Foam Soultion application rate =
Application rate * Fuel Surface Area = 361.6 L/min 95.543107 GPM
Foam Quantity (AFFF 3%) =Foam Soultion application rate * Induction Rate = 10.8 L/min
Water Quantity (H2O 97%)=Foam Soultion application rate * Induction Rate = 350.8 L/min
Total Foam Quantity =Foam Soultion application rate * Discharge Time * Induction Rate = 325.5 Liters
Total Water Quantity = Foam Soultion application rate * Discharge Time * Induction Rate = 10523.5 Liters
The one cubic meter Foam Tank is more enough and safe
According to NFPA 11 with tank diameter 10.6 m .A minimum ONE Foam Chamber is required
Form ANGUS FIRE Catalogue @ 361 l/min Select Foam Chamber ( 3 - 10 bar )
Model TPS - 80
Operating Pressure 5 Bar
Inlet Connection 3"RF Flange
Outlet Connection 6" RF Flange
Form ANGUS FIRE Catalogue @ 361 l/min Select Fixed In-Line Inductors ( 4 - 16 bar )
Model IND 40 /FI
Operating Pressure 8 Bar
Connections 1 1/2" NPT (M)
Foam Inlet Connection 3/4" NPT (M)
REVISION :0
PREPARED BY : MOHAMED EL-HARMEL DATE : ###
From NFPA 11Table 3-2.3.2.1 Number of Fixed Foam Discharge Outlets for Fixed-Roof Tanks
Containing Hydrocarbons or Flammable and Combustible Liquids Requiring Alcohol-Resistant Foams
Tank Diameter (or equivalent area) Minimum
Number of
(ft) (m) Discharge Outlets
Up to 80 Up to 24 1
Application Rate = 4.10 (L/min·m2)
Discharge Times = 30 min
Induction Foam Rate = 0.03
Fuel Surface Area = 3.14*D2/4 = 50.24 m2
Foam Soultion application rate =
Application rate * Fuel Surface Area = 206.0 L/min 54.421136 GPM
Foam Quantity (AFFF 3%) =Foam Soultion application rate * Induction Rate = 6.2 L/min
Water Quantity (H2O 97%)=Foam Soultion application rate * Induction Rate = 199.8 L/min
Total Foam Quantity =Foam Soultion application rate * Discharge Time * Induction Rate = 185.4 Liters
Total Water Quantity = Foam Soultion application rate * Discharge Time * Induction Rate = 5994.1 Liters
The one cubic meter Foam Tank is more enough and safe
According to NFPA 11 with tank diameter 10.6 m .A minimum ONE Foam Chamber is required
Form ANGUS FIRE Catalogue @ 206 l/min Select Foam Chamber
Model TPS - 50
Operating Pressure 5 Bar
Inlet Connection 2"RF Flange
Outlet Connection 4" RF Flange
Form ANGUS FIRE Catalogue @ 206 l/min Select Fixed In-Line Inductors ( 4 - 16 bar )
Model IND 40 /FI
Operating Pressure 8 Bar
Connections 1 1/2" NPT (M)
Foam Inlet Connection 3/4" NPT (M)
REVISION :0
PREPARED BY : MOHAMED EL-HARMEL DATE :
From NFPA 15
1- Application Rate For Tank Shell = 2.00 (l/min/m2)
2- Application Rate For Tank Roof = 2.85 (l/min/m2)
3- Discharge Times = 30 min
4- Minimum Pressure at nozzles = 2 bar
Tank Roof
Spray Angle 95 110 125
No.Of Nozzles 1 1 1
Water Rate Per Nozzle =Water 254.8 254.8 254.8
Rate/No. Of Nozzles (l/min/nozzle)
Calculated Nozzle k-factor 180.2 180.2 180.2
Selected K-Factor 154.4 154.4 154.4
Minimum Pressure at nozzles based 2.72 2.72 2.72
on Standard K-Factor
Conclusion
For Tank Shell Form GEM SPRINKLER COMPANY Select Nozzles
Model D3 Protectospray Open Spray Nozzle
Size 1/2" NPT
Discharge Angle 110
Orifice Size No. 18
Minimum Dia. 6.35 mm
K-Factor 25.9 ISO/SI 1.8 NFPA
###
###
REVISION :0
PREPARED BY : MOHAMED EL-HARMEL DATE :
From NFPA 15
1- Application Rate For Tank Shell = 2.00 (l/min/m2)
2- Application Rate For Tank Roof = 2.85 (l/min/m2)
3- Discharge Times = 30 min
4- Minimum Pressure at nozzles = 2 bar
Tank Roof
Spray Angle 95 110 125
No.Of Nozzles 1 1 1
Water Rate Per Nozzle =Water
145.2 145.2 145.2
Rate/No. Of Nozzles (l/min/nozzle)
Calculated Nozzle k-factor 102.6 102.6 102.6
Selected K-Factor 80.6 80.6 80.6
Minimum Pressure at nozzles based 3.24 3.24 3.24
on Standard K-Factor
Conclusion
For Tank Shell Form GEM SPRINKLER COMPANY Select Nozzles
Model D3 Protectospray Open Spray Nozzle
Size 1/2" NPT
Discharge Angle 110
Orifice Size No. 18
Minimum Dia. 6.35 mm
K-Factor 25.9 ISO/SI 1.8 NFPA
###
###
Data
Dike Dimensions 10m X 7m
Tank DataTwo tanks (2m) diameter, contain diesel fuel oil, Flash Point (38 – 54 C°)
Design Criteria
Minimum Pressure at outdoor Foam Spray Nozzles 2 Bars
Reference Codes
NFPA 11
NFPA 13
NFPA 16
Fuel Classifications
Diesel Fuel Oil, Class II liquid, Flash Point (38 – 54 C°), Do not mix with water.
Type Of Foam
3% AFFF
Select 3 sets each one has 500 gallon PREMIXED SELF-CONTAINED FIRE SUPPRESSION FO
Network Calculations
Foam Spray Nozzles
No. Of Foam Spray Nozzles = Total area/ Area Per Foam Spray Nozzle
= 70 / 9
= 8 Nozzles
Discharge time = 20 minutes
Piping Calculations
charge time
D FIRE SUPPRESSION FOAM UNIT, (as Part No. CPMF 500 based on M/S CHEMGUARD products)
= 718 L (187.5 gallon)
P=6.05*10^5*((q^1.85)/((C^1.85)*(D^4.87))) P=4.52*((q^1.85)/((C^1.85)*(D^4.87)))