Size of Beams:
@ Roof Level
300 x 400 mm
@ Second Floor Level
400 x 500 mm
Size of Columns:
@ Roof Level:
350 x 350 mm
@ Second Floor Level
450 x 450 mm
Slab Thickness:
@ Roof Level
130 mm
150 mm
COMPUTATION OF DEAD LOADS:
@ ROOF LEVEL:
Slab kN 3818.75 kN
(
¿ ( 0.130 m ) 23.5
m 3 )
( 1250 m2 ) =¿
Ceiling ¿ ( 1.00 kPa ) ( 1250 m2 ) =¿ 1250.00 kN
Floor Finishes ¿ ( 0.60 kPa ) ( 1250 m 2) =¿ 750.00 kN
Partition 3.5 m 262.50 kN
¿ ( 1.00 kPa ) ( 0.30 m )
2( )
( 500 m )=¿
Beam kN 1410.00 kN
(
¿ ( 0.30 m )( 0.40 m ) 23.5 3 ( 500 m )=¿
m )
Column 3.5 m kN 302.27 kN
¿ ( 0.35 m )( 0.35 m ) ( 2 )( )
23.5 3 ( 60 pcs . )=¿
m
2
Water Proof ¿ ( 0.50 kPa ) ( 1250 m ) =¿ 625.00kN
W roof = 8,418.52 kN
Beam kN 2350.00 kN
¿ ( 0.40 m )( 0.50 m ) 23.5
(m 3 )
( 500 m )=¿
V – Base Shear
C – Numerical Coefficient
T – Fundamental Period of Vibration (in seconds) of the Structure under Construction (Sec. 2.2.5.2.2)
C t - 0.075 for Reinforced Concrete Moment Resisting Space frames and Eccentric Braced Steel Frames
Where:
Z = 0.40 (Zone 4)
I = 1.15
Rw = 8
C = 2.75
FORCE DISTRIBUTION:
( V −F t ) W x hx
F x=
∑ W x hx
( 4517.63−0 )
F Roof = ( 95129.28 )=2060.43 kN
208,577.05
( 4517.63−0 )
F 2nd = ( 41,363.76 )=895.91 kN
208,577.05
@ TRANSVERSAL SECTION:
2060.43
F roof = =228.94 kN ≈ 228.90 kN
9
895.91
F 2nd = =99.546 kN ≈ 99.550 kN
9
@ LONGITUDINAL SECTION:
2060.43
F roof = =228.94 kN ≈ 228.90 kN
9
895.91
F 2nd = =99.546 kN ≈ 99.550 kN
9
COMPUTATION OF STIFFNESS
I
K=
L
Where:
b h3
I=
12
L=length of beams∧columns
FOR COLUMNS:
FOR BEAMS:
@ROOF LEVEL:
3
I 300 ( 400 )
K 31−32=K 39−40= = =27 × 104 mm3
L 12 ( 6000 )
3
I 300 ( 400 )
K 32−33=K 38−39= = =36 ×10 4 mm3
L 12 ( 4500 )
3
I 300 ( 400 )
K 33−34=K 34−35=K 36−37=K 37−38= = =25 ×104 mm3
L 12 ( 6500 )
3
I 300 ( 400 )
K 35−36= = =53 ×10 4 mm3
L 12 (3000 )
COMPUTATION OF GIRDER FACTOR, G FOR EACH JOINT
GIRDER FACTOR=
∑ K COLUMN
∑ K GIRDER
141
G 11−12 ¿ =¿ 0.671
210
141
G 12−11 ¿ =¿ 0.465
303
141
G 12−13 ¿ =¿ 0.465
303
141
G 13−12 ¿ =¿ 0.473
298
141
G 13−14 ¿ =¿ 0.473
298
141
G 14−13 ¿ =¿ 0.524
269
141
G 14−15 ¿ =¿ 0.524
269
141
G 15−14 ¿ =¿ 0.410
344
141
G 15−16 ¿ =¿ 0.410
344
141
G 16−15 ¿ =¿ 0.410
344
141
G 16−17 ¿ =¿ 0.410
344
141
G 17−16 ¿ =¿ 0.524
269
141
G 17−18 ¿ =¿ 0.524
269
141
G 18−17 ¿ =¿ 0.473
298
141
G 18−19 ¿ =¿ 0.473
298
141
G 19−18 ¿ =¿ 0.465
303
141
G19−20 ¿ =¿ 0.465
303
141
G20−19 ¿ =¿ 0.671
210
COMPUTATION OF COLUMN FACTOR, C
COLUMN FACTOR=1−GIRDER FACTOR
C 40−30 ¿ 1−0.571=¿ 0.429
CONSIDER ROOF TOP:
∑ Q=¿ ¿ 821.016
CONSIDER THE GROUND FLOOR:
∑ Q=¿ ¿ 1901.538
COMPUTATION FOR CONSTANT, N X
N X=
∑ H ( h)
∑ QCOLUMN
Where:
2ND
FLOOR
EQ= 821
EH= 402.4
h= 3.8
402.4 X 3.8
N= 821
N= 1.862473
1ST FLOOR
1901.53
EQ= 8
EH= 501.95
h= 4
501.95 X 4
N= 1902
N= 1.055882
J=
∑ M column moment at joint
∑ Q girder at joint
3.513+1.467
@ JOINT 21= =0.124
40.128
5.720+2.304
@ JOINT 22= =0.103
35.640+41.979
5.641+2.276
@ JOINT 23= =0.109
42.185+30.484
5.098+2.074
@ JOINT 24 = =0.116
31.509+30.176
6.335+2.528
@ JOINT 25 = =0.107
27.819+55.269
6.335+2.528
@ JOINT 26= =0.107
27.819+55.269
5.098+2.074
@ JOINT 27= =0.116
31.509+30.176
5.641+2.276
@ JOINT 28= =0.109
42.185+30.484
5.720+2.304
@ JOINT 29= =0.103
35.640+41.979
3.513+1.467
@ JOINT 30= =0.124
40.128
6.231+3.531
@ JOINT 11 = =0.157
62.376
7.780+5.745
@ JOINT 12= =0.112
55.269+ 65.286
7.720+5.663
@ JOINT 13= =0.119
65.658+47.040
7.336+5.116
@ JOINT 14= =0.131
48.704 +46.656
8.193+6.349
@ JOINT 15= =0.113
43.008+85.485
8.193+6.349
@ JOINT 16= =0.113
43.008+ 85.485
7.336+5.116
@ JOINT 17= =0.131
48.704 +46.656
7.720+5.663
@ JOINT 18= =0.119
65.658+47.040
7.780+5.745
@ JOINT 19= =0.112
55.269+65.286
6.231+3.531
@ JOINT 20= =0.157
62.376
SUMMARY TABLE
LONGITUDINAL SECTION – FACTOR METHOD
MOMENT kN-m
JOINT MEMBERS
GIRDER COLUMN
1 1-11 104.514
2 2-12 113.759
3 3-13 113.400
4 4-14 111.110
5 5-15 116.226
6 6-16 116.226
7 7-17 111.110
8 8-18 113.400
9 9-19 113.759
10 10-20 104.514
11-1 74.403
11 11-12 125.625
11-21 51.211
12-2 92.891
12 12-11 80.803
12-13 95.448
12-22 83.334
13-3 92.173
13 13-12 101.573
13-14 72.771
13-23 82.135
14-4 87.596
14 14-13 82.651
14-15 79.175
14-24 74.208
15-5 97.827
15 15-14 63.566
15-16 126.347
15-25 92.096
16-6 97.827
16 16-15 126.347
16-17 63.566
16-26 92.096
17-7 87.596
17 17-16 79.175
17-18 82.651
17-27 74.208
18-8 92.173
18 18-17 72.771
18-19 101.573
18-28 82.135
19-9 92.891
19 19-18 95.448
19-20 80.803
19-29 83.334
20-10 74.403
20 20-19 125.625
20-30 51.211
21-11 50.950
21 21-22 77.648
21-31 26.685
22-12 82.969
22 22-21 57.345
22-23 67.544
22-32 41.923
23-13 81.822
23 23-22 71.546
23-24 51.701
23-33 41.403
24-14 73.948
SEISMIC LOAD – TRANSVERSAL SECTION
(FACTOR METHOD)
COMPUTATION OF STIFFNESS
I
K=
L
Where:
b h3
I=
12
L=length of beams∧columns
FOR COLUMNS:
FOR BEAMS:
@ROOF LEVEL:
3
I 300 ( 400 )
K 31−32=K 39−40= = =27 × 104 mm3
L 12 ( 6000 )
3
I 300 ( 400 )
K 32−33=K 38−39= = =36 ×10 4 mm3
L 12 ( 4500 )
3
I 300 ( 400 )
K 33−34=K 34−35=K 36−37=K 37−38= = =25 ×104 mm3
L 12 ( 6500 )
3
I 300 ( 400 )
K 35−36= = =53 ×10 4 mm3
L 12 (3000 )
GIRDER FACTOR=
∑ K COLUMN
∑ K GIRDER
141
G11−12 ¿ =¿ 0.671
210
141
G12−11 ¿ =¿ 0.465
303
141
G12−13 ¿ =¿ 0.465
303
141
G13−12 ¿ =¿ 0.473
298
141
G13−14 ¿ =¿ 0.473
298
141
G14−13 ¿ =¿ 0.524
269
141
G14−15 ¿ =¿ 0.524
269
141
G15−14 ¿ =¿ 0.410
344
141
G15−16 ¿ =¿ 0.410
344
141
G16−15 ¿ =¿ 0.410
344
141
G16−17 ¿ =¿ 0.410
344
141
G17−16 ¿ =¿ 0.524
269
141
G17−18 ¿ =¿ 0.524
269
141
G18−17 ¿ =¿ 0.473
298
141
G 18−19 ¿ =¿ 0.473
298
141
G 19−18 ¿ =¿ 0.465
303
141
G19−20 ¿ =¿ 0.465
303
141
G20−19 ¿ =¿ 0.671
210
COMPUTATION OF COLUMN FACTOR, C
COLUMN FACTOR=1−GIRDER FACTOR
C 40−30 ¿ 1−0.571=¿ 0.429
CONSIDER ROOF TOP:
∑ Q=¿ ¿ 582.012
CONSIDER THE GROUND FLOOR:
N X=
∑ H ( h)
∑ QCOLUMN
Where:
2ND
FLOOR
EQ= 821
EH= 402.4
h= 3.8
402.4 X 3.8
N= 821
N= 1.862473
1ST FLOOR
1901.53
EQ= 8
EH= 501.95
h= 4
N= 501.95 X 4
1902
N= 1.055882
J=
∑ M column moment at joint
∑ Q girder at joint
1.610
@ JOINT 31= =0.079
20.331
2.451
@ JOINT 32= =0.066
17.550+19.782
2.423
@ JOINT 33= =0.070
19.908+14.513
2.224
@ JOINT 34= =0.075
15.113+14.425
2.661
@ JOINT 35= =0.070
13.138+25.122
2.661
@ JOINT 36= =0.070
13.138+25.122
2.224
@ JOINT 37= =0.075
15.113+14.425
2.423
@ JOINT 38= =0.070
19.908+14.513
2.451
@ JOINT 39= =0.066
17.550+19.782
1.610
@ JOINT 40= =0.079
20.331
CONSIDER THE THIRD FLOOR LEVEL:
3.513+1.467
@ JOINT 21= =0.124
40.128
5.720+2.304
@ JOINT 22= =0.103
35.640+41.979
5.641+2.276
@ JOINT 23= =0.109
42.185+30.484
5.098+2.074
@ JOINT 24 = =0.116
31.509+30.176
6.335+2.528
@ JOINT 25 = =0.107
27.819+55.269
6.335+2.528
@ JOINT 26= =0.107
27.819+55.269
5.098+2.074
@ JOINT 27= =0.116
31.509+30.176
5.641+2.276
@ JOINT 28= =0.109
42.185+30.484
5.720+2.304
@ JOINT 29= =0.103
35.640+41.979
3.513+1.467
@ JOINT 30= =0.124
40.128
6.231+3.531
@ JOINT 11 = =0.157
62.376
7.780+5.745
@ JOINT 12= =0.112
55.269+ 65.286
7.720+5.663
@ JOINT 13= =0.119
65.658+47.040
7.336+5.116
@ JOINT 14= =0.131
48.704 +46.656
8.193+6.349
@ JOINT 15= =0.113
43.008+85.485
8.193+6.349
@ JOINT 16= =0.113
43.008+ 85.485
7.336+5.116
@ JOINT 17= =0.131
48.704 +46.656
7.720+5.663
@ JOINT 18= =0.119
65.658+47.040
7.780+5.745
@ JOINT 19= =0.112
55.269+65.286
6.231+3.531
@ JOINT 20= =0.157
62.376