You are on page 1of 1

TERRACE

CIRCUIT LOAD NO OF REQUIRED VOLT VOLTS AMP CB SIZE OF WIRE CONDUIT ELECTRICAL NOTES:
NO. DESCRIPTION OUTLET WATTS AMP. PORTECTION
LIGHTING 9 100 900W 220 V 4.09 A 15 A
3
1 OUTLET 1. ALL THE ELECTRICAL WORKS SHALL CONFORM TO THE
LIGHTING 100 1000W 220 V 4.55 A

PANEL-1
10 15 A
2 OUTLET PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE
CONVENIENCE 6 360 2160W 220 V 9.82 A 15 A
3 OUTLET ELECTRICAL CODE (PEC) WITH THE RULES AND REGULATION
2 3000 3000W 220 V 13.64A

SLIDING DOOR
RANGE 1 20 A
GYM 4 OF THE NATIONAL AND LOCAL AUTHORITIES CONCERNED IN
REFRIGERATOR 1 500 500W 220 V 2.27 A 20 A
5
THE ENFORCEMENT OF THE ELECTRICAL LAWS AND WITH
THE REQUIREMENTS OF THE UTILITIES CONCERN.

SLIDING DOOR
TOTAL 27 7560W 220 V 44.34A
2. ELECTRICAL MATERIALS TO BE USED HEREIN SHALL BE
NEW AND OF APPROVED TYPE FOR LOCATION AND

TERRACE
SLIDING DOOR

CIRCUIT LOAD NO OF REQUIRED VOLT VOLTS AMP CB SIZE OF WIRE CONDUIT


DOWN NO. DESCRIPTION OUTLET WATTS AMP. PORTECTION
PANEL NO. TOTAL VA TOTAL AMP PURPOSES.
LIGHTING 8 100 800W 220 V 3.64 A 15 A
DOWN PB 1 OUTLET 1 7560W 44.34 A 3. THERE SHALL BE ONE SERVICE DROP IN THE SYSTEM AND

PANEL-2
ALIGHTING 9 100 900W 220 V 4.09 A 15 A 2 5120W 23.27 A
2 OUTLET
3 5120W 23.27 A IT SHALL BE 220 VOLTS, SINGLE PHASE, 2 WIRES AND 60Hz.
4 LIGHTING 9 100 900W 220 V 4.09 A 15 A
FIXED GLASS

3 OUTLET 4 5080W 23.09 A 4. ALL WIRING METHODS SHALL BE DONE IN PVC PIPES
TERRACE

CONVENIENCE 360 2520W 220 V 11.45A


7 20 A
ZUMBA AREA 1
GYM 4 OUTLET TOTAL 22880W 113.97 A EXCEPT FOR THE MAIN ENTRANCE WHICH SHALL BE RMC
33 5120W 220 V 23.27A
PIPE.
TOTAL
TOTAL CONNECTED LOAD=113.97 AMP AT 80% DEMAND FACTOR 5. ONVENIENCE OUTLET FOR GENERAL USE SHALL BE RATED
MAIN FEEDER=(113.97 AMPX80%)=91.18AMP
CIRCUIT LOAD NO OF REQUIRED VOLT VOLTS AMP CB SIZE OF WIRE CONDUIT
15 AMPS, 250 VOLTS AND APPROVED TYPE. UNLESS
USE=240AMP MAIN CIRCUIT BREAKER AS 10 KAIC
FIXED GLASS SLIDING DOOR
NO. DESCRIPTION OUTLET WATTS AMP. PORTECTION SPECIFIED OTHERWISE.
LIGHTING 8
1 OUTLET
100 800W 220 V 3.64 A 15 A 6. LIGHT CONTROL SWITCHES SHALL BE 10 AMPS, 250 VOLTS

PANEL-3
TERRACE ALIGHTING 9 MAIN PROTECTION:
2 OUTLET
100 900W 220 V 4.09 A 15 A
AND APPROVED TYPE.
LIGHTING 9
USE: 60 AMP, 220V, 32 DIA. RSC
4TH FLOOR PLAN 3 OUTLET
100 900W 220 V 4.09 A 15 A 7. MOUNTING HEIGHT SHALL BE AS FOLLOWS:
CONVENIENCE
4 OUTLET
7 360 2520W 220 V 11.45A 20 A A. LIGHT CONTROL SWITCHES = 1.37 METERS ABOVE
TERRACE FLOOR FINISH FROM THE CENTER OF THE DEVICE.
TOTAL 33 5120W 220 V 23.27A
B. CONVENIENCE OUTLET = 0.33 METER ABOVE FLOOR
3
BEDROOM 3 CIRCUIT LOAD NO OF REQUIRED VOLT VOLTS AMP CB SIZE OF WIRE CONDUIT
FINISH FROM THE CENTER OF DEVICE.
NO. DESCRIPTION OUTLET WATTS AMP. PORTECTION C. AIR CONDITIONING OUTLET = 2 METERS ABOVE
LIGHTING 7 100 700W 220 V 3.18 A 15 A FLOOR LINE
SLIDING DOOR

1 OUTLET
FAMILY ROOM

PANEL-4
CO
LIGHTING 7
CO
2 OUTLET
100 700W 220 V 3.18 A 15 A
D. PANEL BOARD = 1.37 METERS ABOVE FLOOR LINE
LIGHTING 8
BEDROOM 4
3 OUTLET
100 800W 220 V 3.64 A 15 A E.KILOWATT-HOUR METER = 1.85 METER FROM THE
CO CONVENIENCE
4 OUTLET
8 360 2880W 220 V 13.09A 20 A GROUND TO THE CENTER OF METER.
HALL WAY
8. ALL ELECTRICAL WORKS SHALL BE DONE IN
TERRACE

TOTAL 30 5080W 220 V 23.09A


WORKMANLIKE MANNER AND IN GOOD ENGINEERING
SLIDING DOOR

PB

4 UP CO PRACTICE AND SHALL BE UNDER DIRECT SUPERVISION OF


SCHEDULE OF LOADS AN ELECTRICAL ENGINEER, DULY LICENSED FOR THE WORKS
SCALE NTS SPECIFIED.
TERRACE

MASTER'S BEDROOM

CO CO
UP
BEDROOM 1 BEDROOM 2
LANDING CONVENIENCE OUTLET
1 PANEL- 1 PANEL- 2
2
REFRIGERATOR
M 60 A 60 A CONVENIENCE OUTLET
15 A 15 A 15 A 15 A
CKT 01 -LO CKT 01 -LO RANGE OUTLET
CKT 02 -LO CKT 02 - LO
TERRACE
M 20 A 20 A 15 A 20 A
1 HOME RUN TO PANEL BOX
CKT 03 -CO CKT 04 -R CKT 03 -LO CKT 04 -CO
TYPICAL 2ND & 3RD FLOOR PLAN
20 A
LIGHTING LINE
CKT 05 -REF
POWER LINE
SWITCH LINE
COPPER CLAD COPPER CLAD
LIVING ROOM M GROUND ROD GROUND ROD
PIN LIGHT
3
CO

CO
S1 SINGLE GANG SWITCH
M S2
2 TWO GANG SWITCH

SLIDING DOOR
UP CO

SLIDING DOOR
PANEL- 3 PANEL-4 S2W THREE WAY SWITCH
PB
1
BUSBAR 60 A 60 A PANEL BOX
WATER UP
15 A 15 A 15 A 15 A
SLIDING DOOR

REFILLING CO
240A MAIN CKT 01 -LO CKT 02 - LO CKT 01 -LO CKT 02 - LO KILO WATT HOUR METER
STATION M
KITCHEN 15 A 20 A 15 A 20 A
& DINING 4 CKT 03 -LO CKT 03 -LO
CKT 04 -CO CKT 04 -CO SERVICE ENTRANCE
RECEIVING AREA

CO
UP
220 V 15 A
DISPENSING 5
R

SERVICE MAIN FEEDER CIRCUIT BREAKER


REF
ENTRANCE
LIGHTING OUTLET (CENTER
GROUND FLOOR PLAN COPPER CLAD COPPER CLAD LIGHT)
GROUND ROD GROUND ROD

ELECTRICAL LAYOUT PLAN RISER DIAGRAM ELECTRICAL SYMBOLS


SCALE NTS SCALE NTS SCALE NTS

CONSULTANT: RESTRICTION: PROJECT TITLE: DESIGNED &DRAWN BY: REVISIONS: PROJECT OWNER: SHEET CONTENT: SHEET No.
<NAME OF DESIGNER>
CONSTRUCTION OF 4-STOREY RESIDENTIAL DRAWN BY
BUILDING W/ COMMERCIAL E
ELECTRICAL ENGINEER AS SHOWN
PRC NO. (AMENDED PLAN) ISSUED TO
FROILAN S. FLORENDO, JR. 6 7
PTR NO.
DATE ISSUED: PLACE ISSUED: LOCATION: BARIQUIR, NAGUILIAN LA UNION <NAME OF OWNER> LOCATION: BARIQIUR, NAGUILIAN LA UNION

You might also like