KONE Error Code Failure Reason
KONE Error Code Failure Reason
0001 driver long time after a period of the position signal 30/B30 running time does not change.
Immediately stop power off
0004 three consecutive synchronous operation failed. Three consecutive synchronous operation of the
system are not receiving proper leveling signal slowdown after three failed to stop at the end of the
station . Off power
0007 Area 308,030 switch stuck after the start time is not detected falling edge 30/B30 signal. Door
zone has been effective operation of the switch to the destination 30/B30
0008 NVRAM damaged or capacity is not enough when the power transmission capacity is not enough
to detect NVRAM . Replace NVRAM
0014 Area check the circuit did not release any of two consecutive .486.443.1.443:2 without (ACO /
ACL) run to the destination floor , shut off electrical service
0015 Area check circuit does not pull any one .486.443.1.443:2 consecutive times without (ACO / ACL)
run to the destination floor , shut off electrical service
0021 safety circuit fails . Safety circuit input a no voltage is immediately stopped. Safety circuit switched
0022 Hall door barrier. 3 no-voltage input safety circuit stop immediately . Hall door turns
0023 car door lock will not work. Safety circuit voltage input 2 no stop immediately . Door sedan turned
0025 start of system failure when the elevator did not stop the main contactor release does not start .
Main contactor failure row
0026 drive system failure . Driven system detects a fault (v3FCK not light ) does not start. Off power or
play overhaul
0039 shorted 77 buttons stuck. Shorted 77 buttons card refuses to start LCEBOPU board. Until the
release button
0042 car lighting monitor lighting no electricity to run the car to the destination floor. From service until
the signal disappears
0044 closed barrier several attempts . Closed door barrier five times but failed . Door opening does not
go off electricity or playing back door opener repair 0048 remain valid reverse signal lasts more than
one minute to open the door to keep the door closed until the signal disappears electricity
0051 start start invalid 5 times unsuccessful , such as landing door may not shut the door and then try
five automatic recovery
0052 down synchronous switching while effectively .77 U and 77N while effectively stop immediately.
RDF can only start at the end of the station automatically restored
0058 ready to run out. Had requested but the elevator did not start running more than 100 seconds to
stop immediately. Attempt to run off after ten seconds or playing electric acceleration signal 0060V3F16
overhaul did not receive accelerated loss of signal -to-end operation of the drive system power off or
play station overhaul
0071 district loss of signal . After several layers 61U / N when the rising edge of the signal can not be
found 30/B30 run to the destination floor. Door shut without electricity or playing overhaul
0072 61U Signal stuck .61 U signal after leaving the gate area is still not released for some time to run
to the destination floor. Then open to the lowest floor as still stuck, then shut off electrical service or
repair 0071 hit area through several layers of signal loss 61U / N can not be found when the rising edge
of the signal to run 30/B30 destination floor . door shut without electricity or playing overhaul
0073 61N signal stuck. Passes through several layers of the door area. 61N can not find the rising edge
of the signal . Off electricity or playing overhaul
0073 61N signal stuck. Passes through several layers of the door area. 61N can not find the rising edge
of the signal . Off electricity or playing overhaul
0074 61N signal stuck .61 N signal after leaving the gate area for some time still not released. Off power
or play overhaul
0075 61U Signal stuck. Passes through several layers of the door area. 61U can not find the rising edge
of the signal . Off electricity or playing overhaul
Automatic recovery after the 0076 area surveillance for the first time not to release without releasing
(ADO / ACL) ( allowed ) to run to the destination floor 15 seconds 486.443:1.443:2 any runtime
0077 open limit fault ( been ineffective ) . Door open , but can not receive a signal
Button stuck in the 0078 car . Buttons stuck inside any car more than 60 seconds to cancel the twist
service until button to return to normal
0079 Outbound button stuck. Arbitrary outbound button stuck more than 60 seconds to cancel the
twisted services back to normal until the button
Monitor automatically restored 0082 area does not pull no first pull (ADO / ACL) ( allowed ) to run to the
destination floor 15 seconds after running either 486.443:1.443:2
0083 to calculate the position of losing the signal does not match with the wells run to the end station
0084 open limit fault ( been effectively ) shut the door open but still received signal
0089 Hall landing door locks open circuit monitoring ( non- car position ) run to the destination floor .
Shut off electrical service or overhaul fight
0101 drivers to stop driving the system detects a fault the elevator stopped to check the drive shaft
failure
0103 braking resistor braking resistor is damaged, check the brake resistor
0107 load bearing device failure signal voltage is less than 0.6V regulator load device
0108 motor / tachometer speed reverse polarity wrong / bad car balance / load allowed / not open brake
/ drive parameters right / overspeed
0109 Position location is lost is lost drive system under investigation deceleration , leveling switch
0111 deck 61: N at 61: Under U 61U / N swapped Chapin layer switching sequence
0113 simultaneous switching error error synchronous switch synchronous switch synchronous switch
failure investigation
0114 floor distance is too short to check the position of the magnet
0116 test runs to learn counting error floor redone floors unsuccessful learning
Network failure
A side door / 3 side
1101 bad circuit board input board is damaged, electrical wiring errors can not be contacted or not
normal deceleration stop layer , close contact does not move again until the
1202 / 2201 first board fault circuit board is damaged , electrical wiring errors can not be contacted or
did not resume normal service until the single staircase contacted again
1202 / 2202 second board fault circuit board is damaged , electrical wiring errors can not be contacted
or did not resume normal service until the single staircase contacted again
1203 / 2203 The third board fault circuit board is damaged , electrical wiring errors can not be contacted
or did not resume normal service until the single staircase contacted again
1301 / 2301 output boards bad circuit board is damaged, electrical wiring errors can not be contacted or
did not reach the target layer , the door does not move again until the contact
1401 / 2401 first board fault circuit board is damaged , electrical wiring errors can not be contacted or
did not resume normal service operation signal is detected by the first xx 14xx/24xx boards fault circuit
board is damaged , electrical wiring errors can not be contacted or did not resume normal service
operation signal detection by
1501 / 2501 first board fault circuit board is damaged , electrical wiring errors can not be contacted or
did not resume normal service operation signal is detected by
15xx/25xx first xx boards fault circuit board is damaged , electrical wiring errors can not be contacted or
did not resume normal service operation signal is detected by
1601 bad circuit board expansion board is damaged, electrical wiring errors can not be contacted or did
not resume normal service until the single staircase contact again on
1701 / 2701 first board fault circuit board is damaged , faulty wiring or no power can not be contacted
again until contact on
17xx/27xx first xx boards fault circuit board is damaged , faulty wiring or no power can not be contacted
again until contact on
The 102 is an over-current,it may happen when you try pulling through the Brake. you may
want to make sure the Brakes are picking. Make sure they pick on a re-level. A 21 will be
thrown almost every time you open the Safety circuit or go on inspection service. It will
also happen when you have an error like a 102.
One other thing that can cause a 102 is a stuck Buffer Test Button. Usually though it is the
.Over-Current error