1.0 Introduction:
This calculation report is to document the structural strength verification of existing sewage holding tank
for project of DESIGN AND BUILD OF MODULAR BUILDING SITE FACILITIES.
The finite element analysis (FEA) is used to calculate the maximum axial forces, shear forces and
bending moments of the structural elements. It also analyses the maximum deformations, stability of
structure. The structural calculation presented here to checks the adequacy of the irrigation tank in terms
of strength and serviceability. The loading derivation and structure analysis have been presented in this
calculation report.
2.0 Objective:
The aim of this report is to analyse and design of the proposed Sewage Holding Tank structure accounting
to different acting forces and pressures.
The following codes shall be used in the design of the underground RC structure.
BS 8110-1: 1997 Structural use of concrete —Part 1: Code of practice for design and
Construction.
BS 8004 :1986 Code of practice for foundation.
BS 8007:1987 Code of practice for Design of concrete structures for retaining aqueous liquids.
BS 6399-1 :1996 Loading for buildings —Part 1: Code of practice for dead and imposed loads.
BS 8002 :1994 Code of practice for Earth retaining structure.
BS 4449 :1988 British Standard Specification for Carbon steel bars for reinforcement of concrete.
DMRB Volume 2 Section 1 Part 2 BD 30/87 Backfilled Retaining Walls and Bridge Abutments.
Loads for Highway Bridges BD 37/01, Vol. 1, Section 3, Part 14
General Loadings BS 6399, Part 1 & 3
Early-age thermal crack control in concrete CIRIA Report 91
Qatar National Construction Standards 2010 Section 5 Concrete.
Lusail Particular Technical Specifications.
The following software have been used in the design of the project:
- Staad Pro 8Vi, Prokon, Tedds, Spreadsheet calculation pad & Engineering reference books,
codes.
CLIENT: BL HATBERT INTERNATIONAL PROJECT: DESIGN AND BUILD OF
MODULAR BUILDING SITE
FACILITIES.
COMO
CONSTRUCTION Subject: SEWAGE HOLDING TANK CALCULATION
Prepared: AS Checked :SJ Approved : IG Date: Rev.: 00 Page:
30/04/2018
Concrete:
- Concrete Compressive Strength 40 N/mm2 at 28 days
- Steel reinforcement yield strength 460N/mm2
- Modulus of elasticity E = 205000 N/mm2
- Thermal expansion coefficient = 0.000012/0C
- Concrete Density = 25 kN/m3
3.4.2 Super Imposed dead Load (Vertical): (Cl 3.1.2, BD31/01), (LC 2)
Total uniform load on top slab = 19.60 kN/m2 Say 20.00 kN/m2
Note: For uplift and sliding checks the load on top of roof slab has been considered 19.60 kN/m2 only.
CLIENT: BL HATBERT INTERNATIONAL PROJECT: DESIGN AND BUILD OF
MODULAR BUILDING SITE
FACILITIES.
COMO
CONSTRUCTION Subject: SEWAGE HOLDING TANK CALCULATION
Prepared: AS Checked :SJ Approved : IG Date: Rev.: 00 Page:
30/04/2018
- It is the nominal permanent horizontal soil pressures applied to the side walls at a depth 0.95 m below
from top of roof slab.
The following soil properties are given and listed on item 3.3.
3.4.4 Hydrostatic Loads and Uplift Pressure: (Cl 3.1.4, BD31/01) (LC 4)
- From geotechnical investigation report submitted by COMO, the adopted water table for design is
+0.90m QNHD. (Report 3: Geotechnical Interpretation Report, on April 2005, Section 3.2, provided by
COMO) and uplift considered level -0.55 m QNHD (soffit of base slab).
It should be noted the groundwater levels are prone to fluctuations due to change in tides, dewatering,
rainfall and seasonal variations. Therefore, the highest possible water table is at level +2.50m (for
fluctuation) +0.9m =+ 3.40m QNHD.
Height of water on wall Dw=( 4.6M+0.80m) =5.40 m
The uplift water pressure for base slab Sw= (5.40m)* 10kN/m3 = 54.00 kN/m2
Max. Pressure due to hydrostatic, (max) = ywater* (Dw)=10.15*(5.40)= 54.81 kN/m2 ( @ bottom of wall)
Max. Pressure due to hydrostatic, (max) = ywater* (Dw)=10*(0)= 0 kN/m2 ( @ 4.10m height of wall)
CLIENT: BL HATBERT INTERNATIONAL PROJECT: DESIGN AND BUILD OF
MODULAR BUILDING SITE
FACILITIES.
COMO
CONSTRUCTION Subject: SEWAGE HOLDING TANK CALCULATION
Prepared: AS Checked :SJ Approved : IG Date: Rev.: 00 Page:
30/04/2018
The live load on top of roof slab has been considered as 5.00 kPa (Footpath),as per BS 6399-1-
1996,Table-1.
CLIENT: BL HATBERT INTERNATIONAL PROJECT: DESIGN AND BUILD OF
MODULAR BUILDING SITE
FACILITIES.
COMO
CONSTRUCTION Subject: SEWAGE HOLDING TANK CALCULATION
Prepared: AS Checked :SJ Approved : IG Date: Rev.: 00 Page:
30/04/2018
The load factor for load combination has been considered from Table-1 BD 37/01, also considered one
part of tank full and another empty condition, both part of tank empty, both part of tank full condition and
combination with live load and without live load those are addressed in the STAAD input comment sheet
in Appendix B;
The RC water tank elements have been designed for following characteristics:
1. Should be able to transfer self weight of the structure.
2. Should be able to withstand super imposed dead loads and surcharge loads.
3. Should be able to withstand live load on top of slab and surcharge load.
4. Should be able to withstand lateral loads.
5. Should be able to resist the hydrostatic uplift pressure, sliding and settlement.
According to the UBC 1997, Qatar fall with in Zone 0 , which value is significantly less. So that, Zone 1
with acceleration 0.075g has been considered in this calculation , cause occurrence of nearest seismic
sources along eastern margin of the Zagros Mountains in Iran. Apparently there is very minor seismic
activity north, northeast and west of the state of Qatar.
As per UBC Cl. 1804.5, Peak ground acceleration may be determined based on a site-specific study
taking into account soil amplification effects. In the absence of such a study, peak ground acceleration
may be assumed equal to the seismic zone factor in Table 16-I. There is no faults are mapped on the
geological map of Qatar.
7.2 Evaluating Earth Pressure By Mononobe-Okabe:
CLIENT: BL HATBERT INTERNATIONAL PROJECT: DESIGN AND BUILD OF
MODULAR BUILDING SITE
FACILITIES.
COMO
CONSTRUCTION Subject: SEWAGE HOLDING TANK CALCULATION
Prepared: AS Checked :SJ Approved : IG Date: Rev.: 00 Page:
30/04/2018
The wall seismic stability analyses can be checked by consider as follows, usually earth pressures are
calculated using of the Mononobe-Okabe equation (Mononobe, 1929 and Okabe, 1926). In its complete
form, the equation is written as:
PAE is the combined active static and dynamic thrust, and the other quantities in the equation are:
γ = backfill soil density = 20 kN/m3
H =height of wall = 5.00m
∅=¿ angle of internal friction = 330
CLIENT: BL HATBERT INTERNATIONAL PROJECT: DESIGN AND BUILD OF
MODULAR BUILDING SITE
FACILITIES.
COMO
CONSTRUCTION Subject: SEWAGE HOLDING TANK CALCULATION
Prepared: AS Checked :SJ Approved : IG Date: Rev.: 00 Page:
30/04/2018
φ = tan-1 (Nh/(1-Nv))
According to section 3.4.3 of this calculation, the considered active pressure co-efficient
Ultimate Limit States (ULS) are associated with collapse or other structural failure, for example,
through flexural failure, shear failure, stability.
Serviceability Limit States (SLS) correspond to conditions beyond which specified service
requirements are no longer met, for example, excessive deformation, excessive cracking or stress.
From the output, the RC elements covered in this structural report are within allowable ULS & SLS limit
as per applicable standards. These structural elements have been verified and to have been designed with
safety factors in accordance with project specification, BD 31/01 and QCS 2010. The SLS & ULS
checking is addressed in the calculation in Appendix.
CLIENT: BL HATBERT INTERNATIONAL PROJECT: DESIGN AND BUILD OF
MODULAR BUILDING SITE
FACILITIES.
COMO
CONSTRUCTION Subject: SEWAGE HOLDING TANK CALCULATION
Prepared: AS Checked :SJ Approved : IG Date: Rev.: 00 Page:
30/04/2018
CLIENT: BL HATBERT INTERNATIONAL PROJECT: DESIGN AND BUILD OF
MODULAR BUILDING SITE
FACILITIES.
COMO
CONSTRUCTION Subject: SEWAGE HOLDING TANK CALCULATION
Prepared: AS Checked :SJ Approved : IG Date: Rev.: 00 Page:
30/04/2018