You are on page 1of 1

CÁLCULO TÉRMICO Condiciones de diseño :

TBS = 75 ºF
Sala :
PROYECTO HVAC MULTIMEDIA HR = 60 %
TBS = 85 ºF
Exterior :
ZONA TIENDA TBH = 75 ºF
SIN TECHO AL SOL
Conductividad termica :
MES/HORA MARZO 10 AM
Factor Rad.-vidrio (vent) 0.7
Nº PERSONAS 30 Vidrio (ventana) 1.0 Btu/h-ft²-ºF
Pared exterior 0.35 Btu/h-ft²-ºF
AREA 30.0 m² 324.0 ft² Pared interior 0.35 Btu/h-ft²-ºF
Piso 0.35 Btu/h-ft²-ºF
VOLUMEN 120.0 m³ 4248.0 ft³ Techo 0.35 Btu/h-ft²-ºF

VENTANA
0.0 ft2 x 0.7 x 14 Btu/h-ft² = 0.0 Btu/h
VE-S 0.0 m2
0.0 ft2 x 1 Btu/h-ft2-ºF x 10 ºF = 0.0 Btu/h
0.0 ft2 x 0.7 x 45 Btu/h-ft² = 0.0 Btu/h
VE-SE 0.0 m2
0.0 ft2 x 1 Btu/h-ft2-ºF x 10 ºF = 0.0 Btu/h
2 0.0 ft2 x 0.7 x 106 Btu/h-ft² = 0.0 Btu/h
VE-E 0.0 m
0.0 ft2 x 1 Btu/h-ft2-ºF x 10 ºF = 0.0 Btu/h
58.3 ft2 x 0.7 x 94 Btu/h-ft² = 3837.5 Btu/h
VE-NE 5.4 m2
58.3 ft2 x 1 Btu/h-ft2-ºF x 10 ºF = 583.2 Btu/h
0.0 ft2 x 0.7 x 24 Btu/h-ft² = 0.0 Btu/h
VE-N 0.0 m2
0.0 ft2 x 1 Btu/h-ft2-ºF x 10 ºF = 0.0 Btu/h
2 31.3 ft2 x 0.7 x 14 Btu/h-ft² = 306.9 Btu/h
VE-NO 2.9 m
31.3 ft2 x 1 Btu/h-ft2-ºF x 10 ºF = 313.2 Btu/h
2 0.0 ft2 x 0.7 x 14 Btu/h-ft² = 0.0 Btu/h
VE-O 0.0 m
0.0 ft2 x 1 Btu/h-ft2-ºF x 10 ºF = 0.0 Btu/h
0.0 ft2 x 0.7 x 14 Btu/h-ft² = 0.0 Btu/h
VE-SO 0.0 m2
0.0 ft2 x 1 Btu/h-ft2-ºF x 10 ºF = 0.0 Btu/h
VE-INTERIOR 0.0 m2 0.0 ft2 x 1 Btu/h-ft2-ºF x 10 ºF = 0.0 Btu/h
PARED
PA-S 0.0 m2 0.0 ft2 x 0.35 Btu/h-ft2-ºF x 10 ºF = 0.0 Btu/h
PA-SE 0.0 m2 0.0 ft2 x 0.35 Btu/h-ft2-ºF x 4 ºF = 0.0 Btu/h
PA-E 0.0 m2 0.0 ft2 x 0.35 Btu/h-ft2-ºF x 30 ºF = 0.0 Btu/h
PA-NE 0.0 m2 0.0 ft2 x 0.35 Btu/h-ft2-ºF x 20 ºF = 0.0 Btu/h
PA-N 0.0 m2 0.0 ft2 x 0.35 Btu/h-ft2-ºF x 10 ºF = 0.0 Btu/h
PA-NO 0.0 m2 0.0 ft2 x 0.35 Btu/h-ft2-ºF x 10 ºF = 0.0 Btu/h
PA-O 0.0 m2 0.0 ft2 x 0.35 Btu/h-ft2-ºF x 10 ºF = 0.0 Btu/h
PA-SO 0.0 m2 0.0 ft2 x 0.35 Btu/h-ft2-ºF x 10 ºF = 0.0 Btu/h
P- INTERIOR 0.0 m2 0.0 ft2 x 0.35 Btu/h-ft2-ºF x 10 ºF = 0.0 Btu/h
PISO 0.0 m2 0.0 ft2 x 0.35 Btu/h-ft2-ºF x 10 ºF = 0.0 Btu/h
TECHO 0.0 m2 0.0 ft2 x 0.35 Btu/h-ft2-ºF x 10 ºF = 0.0 Btu/h
ILUMIN. 90 watts/m 2 x 1.25 x 30.0 m² x 3.41 Btu/h-watts = 11508.8 Btu/h
EQUIPOS 1000 watts x 3.41 Btu/h-watts = 3410.0 Btu/h
PERS - Cs 250 Btu/h-persona x 30 personas = 7500.0 Btu/h
QS = 27460 Btu/h

PERS - CL 200 Btu/h-persona x 30 personas = 6000.00 Btu/h


QT = 33460 Btu/h
R = 0.82

TBSINSUF TBHINSUF Delta TINSUF HINSUF


59.90 ºF 58.90 ºF 15.10 ºF 25.70 Btu/Lb

Caudal Aire x persona Aire Exterior (AE) % AE # Cambios / h


1684 cfm 20 cfm 600 cfm 35.63 % 8.5

Asumiendo nuevo % AE : 36 %

Aire Exterior (AE) % AE # Cambios/h


600 cfm 36 % 8.5

TBSMEZCLA TBHMEZCLA HMEZCLA


78.60 ºF 68.99 ºF 33.18 Btu/Lb

HS HT TON Btu/h-m2 CFM/TON


34321 Btu/h 56082 Btu/h 4.7 ton. 1869 360

You might also like