Sr.No Ref Clause Page no Tender conditions Queries/ Request Client Reply
ion
GENERAL
Extensio
Considering the quantum of the work and
n for
198 specialised items in the scope, request you to No Change
submissi
extend the date of submission by at least 45 days.
on

The recovery of the pipe already laid will be made on measurement rate
basis or
point rate basis or on actual expenditure basis which ever is on high side. In
case of Departmental work, 10% supervision charges shall also be added.
Conduit pipe where already laid for wiring purpose will be delivered to the
TECHANICAL contractor in absolutely clean condition with round inspection boxes duly
Pg 70, Point Please clarify whether project is already existing
199 CONDITION painted, covered and whole system tested. After the conduit system is It is a new project.
No. 1, 2 & 3 or in new building.
FOR EI WORK handed over to the contractor to whom the work is allotted, he will be
responsible for its upkeep.
During execution of work, if the contractor does not lay pipe and its
accessories in the slab within time prescribed by the Engineer-in-Charge of
the work, the Deptt. can then lay the said pipe-departmentally at contractors
risk and cost without operating the clause 2 and 3 of the contract agreement.

Pg 70, Point
Please Clarify "No Extra payment will be
200 No.8, 10, 11 No Change
made".
& 12

The contractor shall install the material from the list of approved electrical
Pg 70, Point Item Rate shall be as per actual, however rate
201 material appended in the NIT. Material not covered in the list will be used as No Change
No.13 analysis to be done as per DSR 2018 Format.
per DSR 2018, and CPWD.

Please proivde the list of drawings required from Drawings are


Pg 70, Point
202 us. Also share the autocadd drawing for the tender available online in
No.14
works. pdf format.
Descript
Sr.No Ref Clause Page no Tender conditions Queries/ Request Client Reply
ion
GENERAL For makes &
Brands, List of
List of There are two list of approved makes given in
Pg 74. & Pg. brands in Anxure A
203 approved tender document. Please clarify which one to
178 of this
makes follow.
Corrigendum shall
be followed.

The quantity given


There is discripency in Excel BOQ and PDF
204 General in excel sheet shall
Document. Please clarify which on to follow.
be followed.

For makes &


Brands, List of
In BOQ items, Some of the makes mentioned in
brands in Anxure A
205 General the boq but not in approved makes. Kindly
of this
Clarify.
Corrigendum shall
be followed.
206 BOQ Please proivde editable boq. Not Acepeted
MEP Drawings are
Please proivde the All MEP Drawings in
207 Drawing available online in
autocadd format for our working.
s pdf format.
ELECTR Drawings are
Please Provide the Electrical Schematic diagram
208 ICAL available online in
for the same.
SLD pdf format.
For makes &
Brands, List of
BOQ As per BOQ Prolite is mentioned where in list of
brands in Anxure A
209 item No. 1 x 6W exist Sign approved makes Porlite is not mentioned. Kindly
of this
37 clarify.
Corrigendum shall
be followed.
For makes &
Brands, List of
BOQ
Please proive the the detailed item description for brands in Anxure A
210 item No. 6.5W LED Wall Light Fitting
the same. of this
43
Corrigendum shall
be followed.
Descript
Sr.No Ref Clause Page no Tender conditions Queries/ Request Client Reply
ion
GENERAL
BOQ as per BOQ wattage range is given which may
211 item No. Bollard Light (8 to 16 W) effect price quoting for the same. Also proivde No Change
253 the detailed item description for the same.

BOQ Drawings are


Please proivde the Size of OT area i.e. Length x
212 item No. available online in
Width X Height
365 pdf format.
BOQ Please proivde the technical specification for the Technical
213 item No. Hospital Management System same. Also proivde the details of location to be Specifications are
370 considered. available online.
Technical
BOQ Specifications are
No specs is proivded in specification. Please
214 item No. PNEUMATIC TUBE SYSTEM given in Annexure
proivde the techincal specification for the same.
424 B of this
corrigendum.
Technical
BOQ
Please proivde the technical specification for the Specifications are
item No.
215 CCTV System same. Also proivde the details of location to be given in Annexure
436 t0
considered. B of this
451
corrigendum.
BOQ
Plz provide quantity break up as per thickness
216 Item No Duct SITC of site fabricated GI Ducts as per IS Std complete with accessories As per IS standard.
thickness of GI Sheet
586

BOQ
In this item
Item No
As per BOQ Excel 10HP / 12 HP is mentioned. wording Units 10
217 553 & VRV
Please calrify which Capacity to conern. HP 12 HP shall be
Spec. Pg
read as 12 HP.
NO 333

BOQ
Items from 645 to
Item No
In BOQ Specs are missing, wheather in PDF 650 are sub
218 645 & VRV
specs are their. Kindly clarfy which to follow. divisions of item
Spec. Pg
644 in BOQ.
NO 342
Descript
Sr.No Ref Clause Page no Tender conditions Queries/ Request Client Reply
ion
GENERAL
219 BMS Please provide the IO summary for the same. No Change

Per Job as per site


requirement
BOQ Unit mentioned in "RMT", please change in
220 RCC Foundation approved shop
596 "Cum".
drawings for 112
no. out door units.
SOLAR POWER GENERATION SYSTEM Poly Crystalline 330Wp The unit of the item
Modules,With inbilt bypass diode, Frame should be Al anodize,power
BOQ sr. The unit is given 500KW & qty. is given 1516, shall be read as
tolerance of +/-3%,Vmp and Imp shall not vary more than 2%, With junction
221 No. 269 we request you to conferm the capacity of solar Number, The
box arrangement having inbuild bypass diode,weather proof,IP-65,with
PDF RFID tag. Material warranty upto 5 year and performance warranty 25 year.
PV system capacity of Plant is
MAKE- SOVA, SAATVIK, ADANI 500KW.