SAIC-K-4039 Rev 08 - Air-Cooled Condenser Installation
SAIC-K-4039 Rev 08 - Air-Cooled Condenser Installation
EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Air handlers, refrigeration condenser units, pumps, or any equipment
shall be mounted on a concrete housekeeping pad, at a minimum of 100 SAES-K-001
A1
mm (4") above the floor or a minimum of 150 mm (6") above unpaved Para 5.1.1
ground.
Condenser fan motors, 25 tons and larger units, shall have a separate
overload relay protection, as described in Article 440 of the National SAES-K-001
A5
Electric Code (NEC). This protection shall be in addition to other built-in Para 4.8.10.4
condenser motor protection devices.
REMARKS:
REFERENCE DOCUMENTS:
1-SAES-K-100 -- Saudi Aramco Mechanical (HVAC) Code, 20 Oct 2012
2-SAES-K-001 -- Heating, Ventilating and Air Conditioning (HVAC), 5 Dec 2012
3-Uniform Mechanical Code (UMC), 2009