Professional Documents
Culture Documents
Technical Training
Ryan Kelly
Chevron Energy Technology Company (ETC)
June 2008
© Chevron 2005
1
Welcome & Introductions
Ryan Kelly
Instrumentation & Controls Engineer
Chevron ETC – Process Automation Unit
ryan.kelly@chevron.com
Vincent Palughi
Snr Instrumentation & Controls Engineer
Chevron ETC – Process Automation Unit
vpalughi@chevron.com
2
Welcome & Introductions
Name
3
Safety Moment – Hazardous Areas
4
Safety Moment – Hazardous Areas
For full text of the standard, please see NEC Article 500.5
5
Safety Moment – Hazardous Areas
Area Classification (NEC Article 500.5 / API RP 500)
For full text of the standard, please see NEC Article 500.5
6
Safety Moment – Hazardous Areas
Area Classification (NEC Article 500.5 / API RP 500)
Class I, Division 2 is a location in which volatile
flammable gases, flammable liquid–produced vapors, or
combustible liquid–produced vapors are handled,
processed, or used, but in which the liquids, vapors, or
gases will
normally be confined within closed containers or closed
systems from which they can escape only in case of
accidental rupture or breakdown of such containers or
systems or in case of abnormal operation of equipment,
or
normally prevented by positive mechanical ventilation
and which might become hazardous through failure or
abnormal operation of the ventilating equipment, or
the area is adjacent to a Class I, Division 1 location
© Chevron 2005 ETC-PA: Foundation Fieldbus Training 7
For full text of the standard, please see NEC Article 500.5
7
Safety Moment – Hazardous Areas
8
Safety Moment – Hazardous Areas
9
Safety Moment – Hazardous Areas
10
Safety Moment – Hazardous Areas
The above techniques are more commonly used for electrical equipment than
instrumentation.
For full text of the standard, please see NEC Article 500.7
11
Agenda – Day 1
12
Agenda – Day 2
z Device troubleshooting
z Adding/removing/replacing devices
13
Introduction to Foundation Fieldbus
Image Source:
http://www.fieldbus.org/index.php?option=com_content&task=view&id=45&Ite
mid=195
14
What is Foundation Fieldbus?
From equipment up
More vendors, to user interface
interoperable
More functionality
More accurate
(no 4-20mA)
Definition from
http://www.fieldbus.org/index.php?option=com_content&task=view&id=23&Ite
mid=308
15
History of Foundation Fieldbus
Development of proprietary digital bus protocols during
the 1980s
Currently for use in process control systems only, not safety systems.
Shell Deer Park was the first major plant to use Foundation Fieldbus.
16
The Fieldbus Foundation
17
Industry Acceptance
Users:
z Major oil & gas companies
18
Industry Acceptance
19
Comparison with Analog Systems
Fieldbus uses a digital signal (1s and 0s) rather than
reading analog values (milliamps)
Digital signal
Actual waveform
Reading analog values requires correct setup of scaling at either end of the
control loop.
20
Comparison with Analog Systems
Fieldbus devices are also bus-powered (9-30 VDC)
Host Host
Marshalling Marshalling
Device Coupler
Field Devices
Field Devices
Bus-powered means that the device obtains power and communicates on the
same pair of wires (i.e. 2-wire device).
The above examples show field devices with Intrinsic Safety (IS) barriers –
these may or may not be required depending on equipment location and the
facility’s choice of hazardous area protection.
21
Comparison with Analog Systems
Smarter field devices
z Setup of inputs in the device (range, units, etc.)
H1
22
Comparison with HART
23
FF Topology
Host Interface
(DCS I/O card)
Spur Cables
Power
Conditioner
T
Trunk Cable
T
Surge Protector Device
Coupler
T = Terminator
Field Devices
© Chevron 2005 ETC-PA: Foundation Fieldbus Training 24
24
FF Design Limits
25
FF Protocol
User layer
z Function blocks
26
FF Benefits
Digital protocol
z No analog conversion, includes digital error correction,
less susceptible to noise
27
FF Benefits
Fully digital communications from the sensor to the
control system without D/A conversion
D/A conversion reduces accuracy and the electronics are more susceptible to
current drift over time than fully digital electronics. This is the main reason that
analog and HART instrumentation require more frequent field calibration than
FF devices. For example, the EJX pressure transmitter guarantees error < 0.1%
of URL for 10 years.
28
FF Benefits
Less field wiring/terminations and more physical layer
diagnostics available
Open standards
Interoperability required
The Fieldbus Foundation check mark shown indicates that a device has passed
the Foundation’s testing
29
Fieldbus System Components
30
FF Components – Host Interface Card
Yokogawa CS3000 DCS
ALF111 Card
31
FF Components – Power Conditioner
MTL-Relcom
F880 hub w/F801 modules
Special power hub for
Yokogawa connectors
8 segments per hub
Supplies power to field
devices (24 VDC)
Special power supplies
required for FF
Redundant power
conditioner modules
F809f Diagnostic module in
the center
Built-in terminator
© Chevron 2005 ETC-PA: Foundation Fieldbus Training 32
32
FF Components – Surge Protector
Pepperl+Fuchs
DB-LB w/ DP-LBF-1.34
Surge protection devices are also available that can be placed at the instrument
end (not part of the R00#1 spec)
33
FF Components – Div 2 Device Coupler
Moore Hawke
Trunksafe TG20W (12-spur)
Short-circuit protection
The bottom two connectors on the device coupler are for trunk connections only
(only one is used). The others are for the spurs to devices and contain energy
limiting circuitry. The device coupler must be connected in accordance with its
control drawing (TG200-FM)
34
FF Components – Div 1 Device Coupler
Turck
MBD49-T415/Ex (4-spur)
Switchable terminator
Short-circuit protection
Also known as a
“Multibarrier”
© Chevron 2005 ETC-PA: Foundation Fieldbus Training 35
35
FF Components – Field Devices
Pressure: Yokogawa EJX
Temp: Yokogawa YTA
Valve: Fisher DVC6000f
Vortex: Yokogawa DY
Radar: Vegaflex 62
Contains special FF
microprocessor
FF tick of compliance
All devices will have + and – terminals – some devices require correct polarity
while some are able to operate correctly if the polarity is reversed. The best
solution is to assume all devices are polarity sensitive and always connect the
devices according to the polarity indicated on the terminals. + to brown, - to
blue.
36
FF Components – Wiring
Trunks: 16AWG (1.5mm2)
Spurs: 18AWG (1mm2)
Similar to analog
instrument wiring
Two pair with shield
z Jacket : orange
z Positive : brown
z Negative : blue
Turck Minifast
connectors are used
for field devices
(hand tighten only!)
16AWG trunk wire was selected to eliminate the need for volt drop calculations.
Trunk wire is generally run in multipair (8 pair) cables.
For the Turck Minifast connectors, ensure you hand tighten only, don’t use a
wrench!
Field wiring has a drain wire which is used to connect the shield to instrument
ground at the control room end.
37
FF Components – Terminators
Resistor and capacitor in
series.
Two required on a
segment, one at each
end of the trunk
z Power Conditioner
z Device Coupler
Any number of
terminators other than 2
causes signal problems
38
FF System Grounding
Similar to analog instrument grounding:
Connect the shield to instrument ground at one point only
(where the trunk cable enters the marshalling cabinet)
Ensure that only the signal wires (+ and -) are connected to
the field device
Signal wires should NEVER be grounded or allowed to come
into contact with the shield.
More than one ground point on a segment creates ground loops which can
introduce noise onto the network.
39
FF Hazardous Areas
IMPORTANT
Fieldbus trunk cables are NOT rated
for live connection/disconnection and
must be de-engergized first
40
FF Hazardous Areas: Division 2
Field devices
z Non-Incendive (NI)
Generally most equipment will have equivalent ratings for both NEC and IEC
standards. Always view the actual approval certificate/drawing, since some
manufacturers may say the approval is “in progress” which can take a while.
41
FF Hazardous Areas: Division 2
Power
Conditioner
Spur Cables
T
Junction Box
T
Surge Protector
Device Coupler
(NI & ANI)
Remember, only the spurs can be disconnected under power. Fieldbus trunk
cables are NOT rated for live connection/disconnection and must be de-
engergized first.
Refer to the FF Hazardous Area Verification Drawings document for further
information
Higher rated equipment (e.g. intrinsically safe devices) can be used in this
configuration, but will still only be allowed for used in Division 2 areas.
42
FF Hazardous Areas: Division 1
Field devices
z Intrinsically Safe (IS)
Generally most equipment will have equivalent ratings for both NEC and IEC
standards. Always view the actual approval certificate/drawing, since some
manufacturers may say the approval is “in progress” which can take a while.
43
FF Hazardous Areas: Division 1
Power
Conditioner
Spur Cables
T
Device Coupler
(NI & AIS)
Surge T
Protector
Remember, only the spurs can be disconnected under power. Fieldbus trunk
cables are NOT rated for live connection/disconnection and must be de-
engergized first.
Refer to the FF Hazardous Area Verification Drawings document for further
information
44
Key Fieldbus Concepts
45
FF Concepts – Tags & Addresses
46
FF Concepts – Address Range
47
FF Concepts – LAS
Link Master capable devices can also become the LAS, but the R00#1 fieldbus
design specification dictates that the LAS shall be the primary ALF111 card and
the backup LAS shall be the redundant ALF111 card.
48
FF Concepts – Blocks
z DD Information
z Manufacturer
z Serial Number
The user application layer is based on blocks which perform different application
functions
49
FF Concepts – Blocks
z Measurement setup
z Calibration data
z Sensor type
50
FF Concepts – Blocks
Function Blocks
z Provide input, output and control functions
51
FF Concepts – Block Modes
If you set the “target” mode and the “actual” does not change to match, then
there may be a problem in the device preventing it from moving to the “target”
mode.
52
FF Concepts - Parameters
The data inside each
block is organized into
parameters.
z Integer: “243”
z Floating: “25.6234”
Similar to the way HART uses parameters inside the field device to store
information.
Each Parameter can have several Elements, which are individual pieces of data
that make up a parameters (e.g. range, units, decimal point)
The allowable format will depend on what the parameter is used for. Examples
of different types of parameters:
•String: TAG_NAME
•Bit: CHANNEL
•Integer: ADDRESS
•Floating: AI1_OUT
53
FF Concepts – Resource Block
54
FF Concepts – Transducer Block
55
FF Concepts – Analog Input Block
Important parameters – remember that the AI block is the same for every
fieldbus device, regardless of instrument type or manufacturer.
56
FF Concepts – Analog Output Block
Important parameters – remember that the AO block is the same for every
fieldbus device, regardless of instrument type or manufacturer.
57
FF Concepts – VCRs
Virtual Communication
Relationships (VCRs) are
the links between function
blocks which enable data to
be exchanged.
58
FF Concepts - Macrocycle
Scheduled communications are for control data – occur at the same time every
macrocycle (deterministic).
Unscheduled communications are non-critical and will occur when spare time is
available (like ethernet).
59
FF Concepts - Macrocycle
60
FF Concepts - DDs
z http://www.yokogawa.com/fbs/fbs-download2-en.htm
Similar to the way that a computer uses drivers so it knows how to interface
with hardware such as printers.
Recommend getting updated DD files from the host’s website (Yokogawa)
because they have undergone the HIST (Host Interoperability Systems Test)
61
FF Concepts - CFFs
Capabilities files (CFF - Common File Format) describe the
functionality of the devices to enable engineering and
configuration of the devices.
DD = Device revision number
RR = DD revision number
FF = Capabilities file revision number
DDs and CFFs will be located under a directory for the supplier and then device
type.
•Yokogawa = 594543
•Fisher = 005100
•Rosemount = 001151
62
FF Concepts - Interoperability
63
R00#1 FF Segment Design
The defining document for R00#1 is the FOUNDATION Fieldbus Segment
Design (YR-PAS-DSP-203) which is an addendum to the CVX standard
ICM-DU-5161
Key requirements:
Redundant ALF111 modules (which is also the backup LAS)
16AWG (1.5 mm2) segment trunk wiring with orange jacket
Maximum of 12 devices for Div 2 segments
z Last 2 spurs reserved for owner use (spare)
64
R00#1 FF Segment Design
Only one device shall be connected to a device coupler spur
Device spur wiring shall not exceed 120 meters (393 ft)
Segment trunk wiring plus all device spurs shall not exceed a
cumulative length of 1660 meters (5446 ft)
65
R00#1 Segment Topology
Device Coupler
Junction Box
Multipair JB
Power Marshalling
Conditioner Panel
Devices
66
R00#1 Device Coupler Junction Boxes
Device Coupler
Wiring Diagram
67
Fieldbus and Yokogawa Centum CS3000
68
FF and Yokogawa Centum CS3000
System Hardware:
69
FF and Yokogawa Centum CS3000
70
System View - Screenshot
71
FF and Yokogawa Centum CS3000
Download
Upload
72
Fieldbus Builder - Screenshot
Device
Blocks
Linked blocks (i.e. those that are in the control drawing builder and used for
process control) are indicated with a star (*)
73
Fieldbus Builder – Parameter Edit
74
FF and Yokogawa Centum CS3000
75
Device Panel - Screenshot
Address Tag
Devices in
engineering
database
“Live List”
Devices currently
attached to segment
76
FF and Yokogawa Centum CS3000
Faceplate for the device AI PVI AO
(e.g. TL-TIT-7935B)
output
77
FF and Yokogawa Centum CS3000
Alarms occur on the banner and alarm screen in a similar
way to analog devices
Device errors (e.g. IOP, OOP, CNF) will occur with the
device tag
78
Yokogawa Plant Resource Manager
79
Plant Resource Manager (PRM)
80
PRM – Network View
Segment
Device Status
Green = Device Ok
Red = Device Error
Yellow ! = Unacknowledged Alarm
Network view displays all the fieldbus devices and which segment they are
connected to.
Plant view can be configured to group the devices based on geographic area,
unit number, equipment number.
81
Plant Resource Manager (PRM)
Key functions used in PRM:
Device Status – indicates if a device is OK
Device Viewer – more detail on errors
Maintenance History – alarm/event history
DD Menu (Methods) – use to perform tasks such
as device setup and calibration
Parameter Manager – save/restore parameters
Plug-Ins – launches specialized applications
82
PRM – Device Viewer
Cause of Alarm
Alarm Code
Current
Parameters
Red = Alarm
Yellow = Warning
Green = Ok
The trend tab allows you to trend the values in the parameter list.
83
PRM – Maintenance Alarm
•Problem
•Cause
•Action
84
PRM – DD Menu
e.g. Configuring
temperature sensor type
The problem with using PRM for configuration is that these changes are not
reflected in the engineering database (Fieldbus Builder).
85
PRM – Parameter Manager
Current Saved
© Chevron 2005 ETC-PA: Foundation Fieldbus Training 86
86
Yokogawa Fieldmate
Device Viewer
DD Menu
Parameter save
87
Yokogawa Fieldmate
Device Status
Green = Device Ok
Yellow = Error (optional)
Red = Error (mandatory)
88
FDT/DTM Technology
FDT = Field Device Tool
z (the program that runs DTMs)
89
FDT/DTM Technology
90
Fisher ValveLink
91
Fisher ValveLink
Select the device in PRM and click on the “Plug-In” tab. Double click on “Fisher
ValveLink” to launch the application.
92
Fisher ValveLink - Status
Red tabs
indicate errors
Live data
from device
Click “Start Monitoring” to obtain valve information, then end and “Save
Dataset” to record the values.
93
Fisher ValveLink – Total Scan
94
Foundation Fieldbus Commissioning
95
FF Commissioning
96
FF Segment Check
Segment Check
Tag/Address
Assignment
(Device Panel)
Cable/Network
Test
(F809f module)
Segment Config./
Download
(inc. PRM save)
Sign-off Segment
Check Sheet
97
FF Loop Check
Loop Check
Check Inputs
(AI/DI blocks)
Check Outputs
(AO/DO blocks)
Sign-off Loop
Check Sheet
98
Maintenance of Fieldbus Systems
99
Maintenance of FF Systems
100
Physical Layer Maintenance
Examples of physical layer problems that can occur:
Faulty components
101
Physical Layer Maintenance
(*) Note that these measurements are taken from the control system end with
the trunk cable disconnected from the power conditioner (so that there is only
one terminator present on the segment). The capacitance between positive and
negative signal wires may be less that stated if active terminators are used in
the device coupler.
102
Physical Layer Maintenance
Tools for physical layer
troubleshooting:
F809f diagnostic
modules on power
conditioners (fixed)
FBT-6 handheld
diagnostic tool (portable)
Multimeter for
measuring resistance
and capacitance
103
Physical Layer Maintenance: FBT-6
Portable diagnostics unit:
The FBT-6 comes with a USB cable and software for exporting measured data to
a PC as an excel .csv file.
104
Physical Layer Maintenance: FBT-6
Connect the FBT-6 to a laptop and launch the FBT-6
Assistant software.
105
Physical Layer Maintenance: F809f
Fixed on the power hub, F809F
106
Physical Layer Maintenance: F809f
HIS PRM Client
H1 Fieldbus
Basic failure
alarms
Controller I/O (ALF111) On-line
Diagnostic Module
© Chevron 2005 ETC-PA: Foundation Fieldbus Training 107
The diagnostic measurements in the F809f are read by a fieldbus tool such as
PRM that can look at the individual parameters in the module’s transducer
blocks.
There is a dry contact on the power hub to indicate failure of either of the
redundant power conditioner modules. This should be connected to a discrete
input (DI) card.
107
Physical Layer Maintenance: F809f
Segment measurement
108
F809f: Fieldbus Block Structure
Resource Block
System Transducer Block
Segment
Transducer Blocks
Alarm DI Block
F809f on System Alarm DI Block
Fieldbus seg.
Segment Alarm
DI Blocks
RESRC: Resource block, defines the physical resources of the device including
type of measurement, memory, etc.
DITB_S: System transducer block (SysTB), allows the user to view system and
self-test alarms together with the system power feed voltages and temperature.
DITB_1 – DITB_8: Segment transducer blocks (SegTB), provide all the
measured parameters and associated alarms for each fieldbus segment and its
devices.
DIFB_1: Alarm DI block, set to 1 if any of the System Alarm, Segment / Device
Alarm or Self Test Fault Alarm bits is set.
DIFB_2: System alarm DI block, set to 1 if any System Alarm and Self Test
Fault Alarm bits are set.
DIFB_3 – DIFB_10: Segment alarm DI blocks, set to 1 if any of the Segment
/ Device Alarm bits is set for the respective segment.
109
F809f: Device Alarm
•Problem
•Cause
•Action
Maintenance alarms for the diagnostics module are logged the same way as
field devices. Note that in general, the recommended actions are not
particularly useful, so it is recommended to look at the segment transducer
block parameters to determine the cause of the alarm.
110
F809f: System Transducer Block
Current Saved
The above example shows the system transducer block parameters when the
secondary power feed to the power hub is disconnected. Note the
SYSTEM_ALARMS parameter shows the description “Power feed B voltage low
alert” – use this parameter to determine the cause of the alarm. Looking at the
parameters that have changed since last save (highlighted in yellow) we can
see that the secondary power feed voltage decreased from 27.8V to 0.1V,
indicating it has either been disconnected or the bulk power supply is faulty.
111
F809f: Segment Transducer Block
Current Saved
112
F809f: Segment Transducer Block
Current Saved
The screenshot above shows typical device parameters viewed in the segment
transducer block, including:
•Device address
•Device tag (This has to be entered manually and is stored in volatile memory,
so it will be lost if power fails. It is recommended to save all parameters to the
PRM database so the tags can be reloaded into the module in the event of a
power failure.)
•Device signal level
•Device retransmissions
•Device jitter
113
F809f: Know Issues
The hardwired contact on the power hub is the only indicator
of primary or secondary power module failure (contacts are
closed when normal, and open when there is a fault). This
contact should be wired to a DI card in the DCS to provide an
alarm if there is a problem.
114
F809f: Forthcoming DTM Interface
This screenshot is from a prototype DTM (Device Type Manager) which will
make it easier to view the diagnostic measurements and perform
troubleshooting. It will also have the ability to generate a commissioning report
115
Device Troubleshooting
Examples of device problems that can occur:
Incorrect setup of a device
Block left out of service
Alarms requesting maintenance
Out of range alarm
Problems with temperature sensor connection
Problems with instrument air supply
Advanced diagnostics (e.g. impulse line plugging)
116
Device Troubleshooting
117
375 Field Communicator
The 375 is a field
communicator for both FF
and HART devices
118
Replacing Fieldbus Devices
119
Adding Fieldbus Devices
120
Removing Fieldbus Devices
121
Fieldbus Device Calibration
Sensor or actuator
Digital/Analog conversion
With an analog device, such as a transmitter, the output is scaled so that the
expected operating range uses the entire 16 mA of a 4-20 mA signal. This
minimizes the effect of error in both the transmitter analog output and the host
analog input. However, it's common to see errors resulting from a mismatch
between the scaling of the field device and the host.
With digital fieldbus devices, output scaling isn't required — so there's no such
mismatch. Fieldbus does require that the unit of measure be the same in both
the device transducer block and the function blocks.
http://www.yokogawa.com/fld/3D/EJX/p03.html
122
Fieldbus Device Calibration
1. Add calibration record in PRM and enter settings
123
Calibration Data in PRM
124
Calibration Data in PRM
Set up calibration
The input/output values are set based on the individual device’s range settings.
125
Calibration with DD Menu - YTA
O/S
Follow the steps in the Yokogawa YTA manual to calibrate the transmitter –
start by setting CAL_STATE to “Calibration Exec”.
126
Calibration with DD Menu - EJX
Click on “Pressure
Calibration” and follow the
O/S
steps to calibrate
The Yokogawa EJX has a “Calibration Wizard” that helps automate the
calibration steps.
127
Calibration with DTM - EJX
The Yokogawa EJX has a “Calibration Wizard” that helps automate the
calibration steps.
128
Calibration Data in PRM
“Input” is the simulated value from the reference source (such as a pressure
pump, temperature element simulator or Fluke 744 calibrator).
“Output” is the value measured by the transmitter – suggest using Device
Viewer to read the current value.
129
Calibration Data in PRM – Fluke 744
The Fluke 744 is capable of HART communication only. The only calibrator
currently available that supports Fieldbus is the Beamex MC5 (a plug-in for the
MC5 does not exist yet, but is under consideration/development)
Create a new entry in the “Calibration Data” tab and select “Fluke 74X” as the
Calibrator. Add details as appropriate into the Fluke 74X tab at the bottom of
the screen.
130
Calibration Data in PRM – Fluke 744
131
Troubleshooting DD/CFF files
These files need to be in the following locations:
z On the engineering station in:
C:\CS3000\eng\BKProject\TOMBUA\Fieldbus\CFDDFILE\
z In the PRM server and Field Communication Server in:
C:\PRM\DD
Sometimes capabilities files (CFF) have several options for the same
device – e.g. linkmaster capability, PID blocks, advanced diagnostics.
Check that you have selected the right option for a particular device.
132
FF Tools Summary
Device Panel
Downloading to devices
Fieldbus Builder
FBT-6
Note that for calibrating devices, the Fluke 744 is required as a reference
source (for temperature and pressure) while PRM to write calibration data to the
device and record the results.
133
Key Resources
Check out the “References” folder on your flash drive:
FF Web Links
134
The end of the theory…
135
R00#1 Foundation Fieldbus Training Exercises
136
Exercise 1 – Using Device Panel & Fieldbus Builder
This step provides an introduction to Device Panel, a software package that is part of CS3000
and used to view and set up fieldbus devices. In this exercise, you will learn how to set the tag
and address of fieldbus devices.
1. From System View, open the Device Panel application by selecting the segment and clicking
in the menu: Tools > Fieldbus > Display Device Information
2. The Device Panel screen is split, with the devices in the project database shown on the left,
and the actual devices connected to the segment shown on the right (known as the live list).
3. Locate the following items on the Device Panel screen:
a. Tag Name
b. Address
c. Device ID
d. Device Revision information
4. If device tags and addresses have not been assigned, the system will assign temporary
addresses in the range 248-251 (0xF8-0xFB). Note that only 4 unconfigured devices can be
displayed at a time. If the desired device does not appear on the live list, then the devices will
need to be connected to the segment (and the addresses assigned) one at a time.
Device ID
5. Identify the instrument tag and matching Device ID as shown on the instrument’s
commissioning tag.
6. Locate the instrument on the live list with the desired Device ID, right click and select “Tag
Assignment”. De-select “Assign Automatically” and input the instrument tag and address that
matches the values in the database on the left.
137
Matching
This step provides an introduction to Fieldbus, a software package that is part of CS3000 and
used for engineering and downloading of configuration to fieldbus devices. In this exercise, you
will learn how to download configuration to as segment and check that it is working.
1. From System View, locate the segment and double-click on it to open Fieldbus Builder.
2. This screen shows the devices configured in the engineering database (same as the left part
of the screen in Device Panel). Locate the following items on the Fieldbus Builder screen:
a. Tag Name
b. Address
c. Device ID
d. Device Revision information
e. Polled address range for the segment (this setting dictates which addresses the
ALF111 looks for – if this range doesn’t include a device it will be invisible!)
3. Select the ALF111 card and select: File > Download (ensure all boxes are ticked)
138
4. Confirm that there are no errors and verify that all the devices were downloaded successfully
by checking that the “Device ID” column has been filled in for each tag. If there are any
errors, view the “Message” window at the bottom of the screen for details and rectify the
problem.
Device IDs
No Errors
5. From Fieldbus Builder, open the Device Panel application by selecting the segment and
clicking in the menu: Tools > Display Device Information
6. If any of the devices have a yellow lightning bolt icon next to them, then they have not been
equalized successfully. Sometimes parameters such as software revision are not
successfully imported to the database by Fieldbus Builder so this has to be corrected
manually.
7. Double-click on the device to launch the “Device Information Display” and perform the
following steps:
a. Click on “Update” to show the current parameters.
139
b. Select “Equalization Mode” and “Difference” to see the parameters that are not yet
equalized.
c. Tick “Equalization of block parameters is executed”
140
(normal) with no errors (note that since the instrument is not yet in service, the faceplate may
display a LL or HH alarm – this should be normal depending on the alarm settings). The
faceplate should NOT display an IOP (input open), OOP (output open), CNF (connection fail)
or O/S (block out of service) status. Faceplates for input blocks (AI/DI) should be in AUT and
output blocks (AO/DO) should be in CAS.
11. Experiment with the instrument by making the following changes and observing the effect it
has on the instrument faceplate (and associated indicator or PID faceplate):
a. Change the process value (e.g. test pump on a pressure transmitter)
b. Change the process value outside of alarm limits (PL/PH)
c. Change the process value outside of range limits (LL/HH)
d. Disconnect the device and then reconnect it
e. Disconnect the temperature element (temperature transmitters only)
141
Exercise 2 – Using Fieldmate
This exercise provides an introduction to Fieldmate, a portable software tool that is used to
configure fieldbus devices. In this exercise, you will learn how to connect Fieldmate to a segment
and set the tag and address of fieldbus devices, and troubleshoot using Device Viewer.
1. Open the NI-FBUS Interface Configuration utility from the start menu:
Start > National Instruments > NI-FBUS > Utilities > Interface Configuration Utility
2. Select each port and click edit to configure only the first port with the following settings:
When there is no other LAS on the segment (i.e. no ALF111 card connected) and you want
Fieldmate to become the LAS:
• Device Address: 0x10
• Device Type: Link Master Device
• Usage: NI-FBUS
3. Connect one port of the NI-FBUS card to the segment to a spare device coupler terminal.
4. Start up the Yokogawa Fieldmate application and select “FF-H1” as the default scan
segment. Click “Ok” to start up NI-FBUS Communications Manager which will pop up the
following window once it has started successfully.
5. Ensure the “Segment Viewer” tab and “Foundation Fieldbus” are selected on the left panel.
The actual devices connected to the segment are shown on the right (known as the live list).
Note that there is no panel on the left showing the devices in the engineering database – this
feature is only available in Device Panel on an engineering workstation.
142
Device ID
Live List
143
Matching
Fieldbus
Builder
print-out
Device
Status
12. Right-click on the device and select “Device Viewer” to see more detailed status of the
device.
13. Since the devices have not yet been configured by the DCS, Device Viewer may see some
errors such as “AI FB not scheduled”. This is expected and can be ignored as it will be
resolved once the instruments are connected to the DCS and downloaded.
144
14. Experiment with the instrument by making the following changes and observing the effect it
has on Device Viewer (Right-click on the instrument and select “DD Menu” or “Assigned
DTM” to launch the application used to make these changes)
a. Change the block mode of AI1 to out of service (O/S)
145
Exercise 3 – Using Plant Resource Manager (PRM)
This exercise provides an introduction to PRM, the application used for management of
Foundation Fieldbus and HART instrumentation. It shows how to set up PRM for a segment and
introduces its device troubleshooting tools.
3. Check the Device Status for all devices on the segment (the colored oval next to the device
icon). The Device Status should be good (green) for every device on the segment.
146
Device
Status
4. Experiment with the instrument by making the following changes and observing the effect it
has on Device Viewer (Right-click on the instrument and select “DD Menu” or “Assigned
DTM” to launch the application used to make these changes)
a. Change the block mode of AI1 to out of service (O/S)
5. Click on the “History” then “Maintenance” tab of the device to view the alarm generated –
read the message regarding problem, cause and action. Right-click on the alarm and select
“Acknowledge” – enter a reason and you should see the yellow exclamation point icon
disappear from the device.
147
6. Right-click on the device and select “Device Viewer” to launch. The following screenshot
shows an example of a device viewer warning that states “AI1 FB is in O/S mode”. This
means that the analog input block is out of service, so the process value is not being
transmitted to the control system.
7. Fix the problem using DD Menu or the DTM and observe the device return to normal.
8. Right click on the segment and select “Save All Parameters”. Type ‘Commissioning’ into the
“Reason” box, tick the “Read details from the field devices” box and select ok. This will save
the current set of parameters in the device.
148
9. In the following steps you will compare previously saved parameters to the current
parameters read from the device:
a. Select a device on the segment and click on the “Parameter” tab
b. Select the desired block tag (resource, transducer or function blocks)
c. The column on the left displays the current parameters in the device – click “Update”
to read in current parameters from the device
d. The arrow in the middle is used to change a device’s parameters back to a saved
configuration – click “Set” to execute
Current Saved
149
Exercise 4 – Physical Layer Diagnostics
The FBT-6 is a handheld fieldbus monitor that can detect physical layer problems on the
segment. It is bus-powered and rated for use in hazardous areas. This exercise will show you
how to use the FBT-6 to check a segment and identify common problems.
1. Connect the FBT-6 Fieldbus Monitor to the segment at the device coupler and wait for it to
check (approximately 20 seconds). The FBT-6 should display “ALL MEASUREMENTS OK” if
there are no problems. Press the “FUNC” button to scroll through the various measurements
for the segment.
2. With the FBT-6 still connected, introduce the following faults onto the segment and observe
the reading on the FBT-6 to see whether the changes are identified.
a. Disconnect a device and then reconnect it
b. Place a short between the shield wire and one of the signal wires
c. Switch off the terminator at the power supply end
3. Press “FUNC” to scroll through to the save function. Hold down the “SEL” button to save the
segment measurements into one of the empty slots (there are 8 slots available). Make sure
the number of the slot is noted on the check sheet as this will be needed for the next step.
150
4. Connect the FBT-6 to a laptop and launch the FBT-6 Assistant software. Click “Transfer
Reports from FBT-6” to transfer the reports to the laptop. By default they will be saved with
the report slot number - rename the files with the segment number for easy identification.
The MTL F809f is a physical layer diagnostics module that mounts on the segment power hub for
continuous monitoring. This exercise will show you how to use the module to check a segment
and identify common problems.
151
3. Click on the “Parameter” tab, then right-click on <Show actual parameter> and select
“Parameter Manager”. This will enable you to read the current parameters in the F809f.
152
4. The parameters in the F809f display the measured values from the segment, and any active
alarms that are present. Read through the parameters for the two types of transducer blocks
to see what the current status is (TB01 is the system transducer block, and TB02-TB09 are
the segment transducer blocks). Consult the F809f user manual on your flash drive if you are
not sure what a parameter means.
5. Generate a print-out of the current parameter values – this can be useful as a commissioning
report to document the measurements taken.
6. Right-click on the F809f module and select “Save all parameters” to save all the current
parameters in the device to the PRM database. In Parameter Manager you will then be able
to view the saved values alongside current measurements taken from the segment.
7. Introduce the following faults onto the segment and observe the measurements by updating
the current parameters in Parameter manager. Compare these to the saved parameters in
the previous step to see whether the changes are identified.
a. Unplug the secondary 24VDC power connector from the power hub
b. Place a short between the shield wire and one of the signal wires
c. Switch off the terminator at the power supply end
153
Current Saved
8. Click on the “History” then “Maintenance” tabs of the device to view the alarms generated,
and read the message regarding problem, cause and action. Right-click on the alarm and
select “Acknowledge” then enter a reason. You should see the yellow exclamation point icon
disappear from the device.
154