You are on page 1of 5

2019 International Conference on Robotics,Electrical and Signal Processing Techniques (ICREST)

Supercapacitor E-STATCOM for Power System


Performance Enhancement
M.R.A.Wara A.H.M.A.Rahim
Department of Electrical and Electronic Engineering Department of Electrical and Electronic Engineering
Ahsanullah University of Science and Technology Ahsanullah University of Science and Technology
Dhaka, Bangladesh Dhaka, Bangladesh
ruhulwara@gmail.com ahrahim.eee@aust.edu

Abstract—E-STATCOMs are static compensator devices stability of the system. In [18], coordination between
incorporated with energy storage devices. In this paper, a STATCOM and the excitation system has been proposed for
supercapacitor energy storage system (SCESS) has been stability purpose. In [23], a nonlinear control mechanism has
interfaced with a static compensator (STATCOM) for been implemented in STATCOM to improve the voltage
transient control of a power system. While STATCOM is regulation of the power system. In [21] and [22], adaptive PI
known to improve the reactive power unbalance following a controllers have been applied for voltage regulation.
contingency, a STATCOM SCESS system can affect both real
and reactive power needs. Performance of a single machine Only the capability to compensate the reactive power has
infinite bus system has been considered as a test case. It has restricted the application of STATCOM during severe
been observed that a simple STATCOM SCESS can stabilize disturbances in a power system [4]. With the inclusion of an
an unstable system. Additionally, supplementary PI controllers energy storage system into STATCOM, a more powerful
in both voltage magnitude and phase angle loops can provide device E-STATCOM can be obtained. E-STATCOM can
extra damping to the system. The controllers have been shown provide the support of both real and reactive power. Having a
to provide very good responses even when the system is wide spectrum of troubleshooting ability, it can deal with
subjected to severe three-phase fault conditions. severe perturbations in the power systems [4], [8], [9]. It can
also improve the transient stability margin by exchanging
Keywords— SMIB, STATCOM, SCESS, PI control
real power along with reactive power [8].

I. INTRODUCTION The capability of E-STATCOM to handle forced


oscillations is proposed in [4]. In [9], E-STATCOM based
With the fast growth of power systems, efficient adaptive damping controller has been designed. In [10],
operation of the system has become a challenging job [1], stochastic time domain analysis has been carried out to
[2]. Load variations, faults in the system can introduce assess the dynamic performance of E-STATCOM in the
oscillations affecting the voltage, frequency and the power power system. In [8], [11], STATCOM BESS has been used
transfer capability of the system [1]–[4]. Oscillations may to improve the dynamic performance of a multimachine
sometimes lead to blackout of the whole power system [5]. system covering both synchronous and asynchronous
Energy storage devices can provide extra damping to generators. In [16], STATCOM SCESS has been connected
mitigate power system oscillations [3]. Energy storage with the wind generators to ensure both active and reactive
devices such as, batteries, supercapacitors, superconducting power support. In [15], STATCOM SMES has been
magnetic energy storages (SMES) are the most suitable implemented to enhance the power transfer capability of the
candidates for this purpose [6]. Research indicates the use of grid.
energy storage systems in the conventional power systems,
the renewable energy sources, and the microgrids can ensure In this article, a supercapacitor energy storage system is
the quality, stability and reliability of the systems [3], [4], interfaced with a STATCOM device in a single machine
[6]–[17]. The damping capability of battery energy storage infinite bus test model. Supplementary PI controllers in the
system (BESS) has been analyzed in [3]. In [13], STATCOM circuit are designed for control of reactive as
supercapacitor energy storage system has been implemented well as real power. Transient simulation is carried out to
to increase the transient behavior of a system connected with evaluate the dynamic performance of STATCOM SCESS
wind farms. In [14], SCESS has been deployed at the with and without the additional controllers.
common terminal of a grid connected with wind-solar hybrid The remaining part of the paper is organized as follows.
farm. Section II describes the system model including synchronous
The flexible ac transmission system (FACTS) devices are generator, STATCOM and supercapacitor. Section III
being used in power grids to improve the voltage regulation, presents the supplementary controller design. The simulation
power transfer capability and also the stability [2], [18]. The results are shown in section IV and the conclusions are
static synchronous compensator, a member of the FACTS presented in section V.
family, is used to enhance the steady state as well as transient
performance of the power system by providing sufficient II. SYSTEM MODEL
reactive power support [2], [19]–[22]. Various control
Fig.1 shows the configuration of a single machine
mechanisms have been researched and analyzed for
infinite bus system considered in this study. The system
STATCOM for different uses [2], [4], [8], [9], [11], [15], consists of a synchronous generator, local load, transmission
[16], [18], [19], [21]–[23]. In [2], a nonlinear attenuation line and supercapacitor energy storage system with
controller has been designed for STATCOM to enhance the

978-1-5386-8014-8/19/$31.00 ©2019 IEEE


69
2019 International Conference on Robotics,Electrical and Signal Processing Techniques (ICREST)

STATCOM. The storage devices are connected at the STATCOM output current. The model is written as follows
midpoint of the transmission line. The model for the [16] [17] [23],
component systems are given in the following.

dVDC
CDC
dt
( )
= −m isd cos (ϕ + ψ ) + isq sin (ϕ + ψ ) − I SC (5)

disd  ω 
Ls = ω0  − Rs isd + Ls isq + mVDC cos (ϕ + ψ ) − Vd  (6)
dt  ω0 
disq  ω 
Ls = ω0  − Rs isq − Ls isd + mVDC sin (ϕ + ψ ) − Vq  (7)
dt  ω0 

Here, Rs and Ls indicate the resistance and inductance


of the transformer connected between the STATCOM and
Fig. 1. Single machine infinite bus system with E-STATCOM. the line, Vd and Vq are the d-q axis components of the
voltage at the connecting point; VDC and CDC are the
A. Synchronous Generator Model voltage and capacitance of the dc link capacitor. ISC is the
A synchronous generator is modeled in terms of four current contributed by the supercapacitor.
ordinary differential equations. The electro-mechanical
dynamics is expressed by the second order swing equation. C. SCESS Model
The other equations come from the internal voltage dynamics
The SCESS model is expressed in terms of
of the generator and a first order exciter model. The 4 state
equations are expressed as [16], supercapacitor current and voltage ( VSC ) and is written as
[16],

dδ dESC
= ω0 (ω − ω0 ) (1) I SC = CSC (8)
dt dt
VSC = ESC + RSC I SC (9)

2H = ( Pmech − Pelec ) (2)
dt where, RSC and CSC are the resistance and capacitance of
dEq' the supercapacitor, respectively.
Td' 0
dt
( )
= EFD − Eq' − xd − xd' id (3)
III. SUPPLEMENTARY CONTROLLER DESIGN
dEFD A supplementary PI controller has been designed to
TE = k E (Vt 0 − Vt ) − ( EFD − EFD 0 ) (4)
dt control the modulation index m and phase angle ψ . Speed
error has been considered as the input for the controller. The
Quantities δ , ω , Eq' , EFD are the rotor angle, angular output of the PI controller is summed with the initial value to
get the desired modulation index. The gain parameters of the
frequency, quadrature axis component of generator internal
controllers are selected by adopting trial and error technique.
voltage and generator field voltage, respectively; ω0 is the The block diagram for the m and ψ controllers are given in
base speed; Pelec and Pmech are the electrical power and the
Figs. 2 and 3, respectively. The quantities Δm and Δψ are
mechanical power of the generator, respectively. The terms
generated by solving the differential equations,
xd and xd' are the direct axis synchronous and transient
y1 = K im Δω
reactances of the generator, respectively; id is the direct (10)
axis component of stator current; H represents the inertia y 2 = K iψ Δω
constant; Td' 0 is the open circuit field time constant; k E and Then,
TE represent the exciter gain and time constant; Vt and Vt 0 Δm = K pm Δω + y1
(11)
are the instantaneous and steady values of the terminal Δψ = K pψ Δω + y2
voltage, respectively.
k
B. STATCOM Model ω0 k pm + im Δm
s
The terminal voltage of STATCOM can be stated as, −
Vs = mVDC ∠ϕ + ψ , where m is the modulation index and +
ψ is the phase angle of the voltage, ϕ is the angle of the
voltage at the connecting point of the STATCOM. The ω
STATCOM model consists of three differential equations
containing the voltage across the dc-link capacitor and the
direct and quadrature axis (d-q axis) components of Fig. 2. Modulation index controller block diagram.

70
2019 International Conference on Robotics,Electrical and Signal Processing Techniques (ICREST)

kiψ 1.8
ω0 k pψ + Δψ No control

− s 1.6 SCESS without supplementary control

Generator Terminal Voltage (p.u.)


SCESS with supplementary control
+ 1.4

1.2

ω 1

0.8
Fig. 3. Phase angle controller block diagram..
0.6

0.4
IV. SIMULATION RESULTS
0.2
The single machine infinite bus system with the E-
STATCOM given in Fig. 1 was simulated for two different 0
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5
disturbance scenarios. These are: a single three-phase fault at Time (sec)
the grid bus, and sequential faults. The system parameters are
given in the appendix. Fig. 4. Generator terminal voltage following 3-phase fault at the grid bus for
250ms duration
The synchronous generator terminal voltage, speed, and
the terminal voltage, etc. following the various disturbances 1.025
are shown in Figs. 4 through Fig. 9. A 3-phase, 250ms short No control

circuit fault is applied at the grid bus first. In the absence of 1.02 SCESS without supplementary control
SCESS with supplementary control
SCESS, the generator voltage drops to very small values 1.015
(Fig. 4) causing the generator to speed up (Fig. 5). The

Speed Deviation (p.u.)


1.01
generator speeds up and voltages are heavily depressed. The
output power of the generator decreases significantly during 1.005

fault shown in Fig. 6. Because of the fast transients in the 1


output voltage, the power output also swings with large
amplitude. The large variations in electrical power leads the 0.995

generator to accelerate more. The terminal voltage of the 0.99

generator and the line mid-point voltage are very low (Fig. 4 0.985
and Fig. 7). The generator continues to accelerate even after
the fault is removed, eventually rendering the system to 0.98
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5
instability. Time (sec)

The SCESS along with STATCOM is able to absorb or Fig. 5. Speed deviation following 3-phase fault at the grid bus for 250ms
deliver real and reactive power. The supercapacitor absorbs duration.
active power through STATCOM during fault. The
absorption of real power impedes the generator to accelerate.
The supercapacitor continuously exchanges power until the
system is stable. The speed, the voltages and the generator 2.5

power output continues to oscillate with a very low 2


No control
SCESS without supplementary control
frequency and large amplitude. The power variation of the SCESS with supplementary control
SCESS system for the no control and controlled cases are 1.5
Generator Power (p.u.)

shown in Fig. 8. The SCESS along with the supplementary 1


PI controller can provide sufficient damping to the
oscillations. As can be observed, the system transients are 0.5

stabilized in less than 2s. 0

In the second disturbance scenario, two severe three -0.5


phase faults have been applied consecutively. The first one is
-1
applied at t=0 and the second one is initiated at t=3s. As can
be seen in Fig. 9, without SCESS supplementary control, the -1.5

speed is oscillatory following the first disturbance and 0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5
worsens to unstable condition when the second disturbance Time (sec)
comes in. The SCESS with supplementary control can damp
the oscillations quickly and keep the system stable. Fig. 6. Generator power output following 3-phase fault at the grid bus for
250ms duration.

71
2019 International Conference on Robotics,Electrical and Signal Processing Techniques (ICREST)

STATCOM control improves both the real and reactive


2
No control power imbalances resulting in improvement of both
Mid-point Voltage of the Line (p.u.) 1.8 SCESS without supplementary control
SCESS with supplementary control
damping and transient voltage profiles. Additional controls
1.6 in the voltage magnitude and phase loop provide extremely
1.4 good transient response even under severe multiple
1.2
disturbance contingencies. The control design was carried
out considering detailed modeling of the synchronous
1
generator, STATCOM system and the supercapacitor energy
0.8 storage device. It was observed that the energy requirement
0.6 of the supercapcacitor is not excessive in comparison to
0.4
system ratings.
0.2
ACKNOWLEDGEMENT
0
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5
Time (sec) The authors wish to acknowledge the facilities provided
towards this research by the Ahsanullah University of
Science & Technology, Dhaka.
Fig. 7. The voltage at the mid-point of the line following 3-phase fault at
the grid bus for 250ms duration.
APPENDIX
STATCOM and supercapacitor parameters:
3
No control Rs = 0.02 p.u. Ls = 0.15 p.u. CDC = 0.01 p.u.
2.5 SCESS without supplementary control

2
SCESS with supplementary control Rsc = 0.1 p.u. Csc = 3500 p.u.
Supercapcitor Power (p.u.)

1.5
Power system parameters:
1
H=3sec Td' 0 = 6.3 sec kE = 1 TE = 0.01 sec
0.5

0
Load admittance = 0.12 − j *0.16 p.u.
-0.5

-1
Operating conditions:
Pmech = 0.9 p.u. Vt 0 = 1.02 p.u. Pf = 0.9 lag m0 = 0.5
-1.5

-2
ψ0 = 0
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5
Time (sec)

Fig. 8. Supercapacitor power output following 3-phase fault at the grid bus REFERENCES
for 250ms duration.
[1] T. K. Roy, M. A. Mahmud, W. Shen, and A. M. T. Oo, “Nonlinear
Adaptive Excitation Controller Design for Multimachine Power
Systems with Unknown Stability Sensitive Parameters,” IEEE
1.025
Transactions on Control Systems Technology, vol. 25, pp. 2060–2072,
1.02 Nov. 2017.
[2] N. Jiang, S. Li, T. Liu, and X. Dong, “Nonlinear large disturbance
1.015
attenuation controller design for the power systems with
Speed Deviation (p.u.)

1.01 STATCOM,” Applied Mathematics and Computation, vol. 219, pp.


10378–10386, 2013.
1.005 [3] Y. Zhu, C. liu, B. Wang, and K. Sun, “Damping control for a target
oscillation mode using battery energy storage”, Journal of Modern
1
Power Systems and Clean Energy, pp.1–13, 2018.
0.995 [4] S. Feng, X. Wu, P. Jiang, L. Xie, and J. Lei, “Mitigation of Power
System Forced Oscillations: An E-STATCOM Approach,” IEEE
0.99 Access, vol. 6, pp. 31599–31608, 2018.
0.985
[5] C. Canizares et al., “Benchmark Models for the Analysis and
SCESS without supplementary control
SCESS with supplementary control
Control of Small-Signal Oscillatory Dynamics in Power Systems,”
0.98 IEEE Transactions on Power Systems, vol. 32, pp. 715–722, Jan.
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5
Time (sec)
2017.
[6] M. Farhadi and O. Mohammed, “Energy Storage Technologies for
High-Power Applications,” IEEE Transactions on Industry
Fig. 9. Speed deviation following consecutive 3-phase fault at the grid bus Applications, vol. 52, pp. 1953–1961, May–June 2016.
for 250ms duration. [7] Á. Ortega and F. Milano, “Generalized Model of VSC-Based Energy
Storage Systems for Transient Stability Analysis,” IEEE
Transactions on Power Systems, vol. 31, pp. 3369–3380, Sept. 2016.
V. CONCLUSIONS [8] A. Kanchanaharuthai, V. Chankong, and K. A. Loparo, “Transient
Stability and Voltage Regulation in Multimachine Power Systems
Transient performance of a single machine infinite bus Vis–à–Vis STATCOM and Battery Energy Storage,” IEEE
system has been investigated with and without Transactions on Power Systems, vol. 30, pp. 2404–2416, Sept. 2015.
supercapacitor energy storage system supported STATCOM [9] M. Beza and M. Bongiorno, “An Adaptive Power Oscillation
Damping Controller by STATCOM with Energy Storage,” IEEE
devices. While the system without E-STATCOM support Transactions on Power Systems, vol. 30, pp. 484–493, Jan. 2015.
leads the power system to instability, inclusion of the E-

72
2019 International Conference on Robotics,Electrical and Signal Processing Techniques (ICREST)

[10] Á. Ortega and F. Milano, “Stochastic Transient Stability Analysis of [17] O. D. Montoya, A. Garcés, and G. Espinosa-Pérez, “A generalized
Transmission Systems with Inclusion of Energy Storage Devices,” passivity-based control approach for power compensation in
IEEE Transactions on Power Systems, vol. 33, pp. 1077–1079, Jan. distribution systems using electrical energy storage systems,”
2018. Journal of Energy Storage, vol. 16, pp.259–268, 2018.
[11] J. Liu, C. Su, X. Wang, W. Fang, S. Niu and L. Cheng, [18] A. Khodabakhshian, M. J. Morshed, and M. Parastegari,
“Abnormality in power system transient stability control of “Coordinated design of STATCOM and excitation system
BESS/STATCOM,” The Journal of Engineering, vol. 2017, no. 13, controllers for multimachine power systems using zero dynamics
pp. 1040–1044, 2017. method,” Int. Journal of Electrical Power and Energy Systems, vol.
[12] F. A. Inthamoussou, J. Pegueroles-Queralt, and F. D. Bianchi, 49, pp. 269–279, 2013.
“Control of a Supercapacitor Energy Storage System for Microgrid [19] B. K. Bose, “Global Energy Scenario and Impact of Power
Applications,” IEEE Transactions on Energy Conversion, vol. 28, pp. Electronics in 21st Century,” IEEE Transactions on Industrial
690–697, Sept. 2013. Electronics, vol. 60, pp. 2638–2651, July 2013.
[13] M. K. Dösoglu and A. B. Arsoy, “Transient modeling and analysis [20] Y. Gui, W. Kim, and C. C. Chung, “Passivity–Based Control With
of a DFIG based wind farm with supercapacitor energy storage,” Nonlinear Damping for Type 2 STATCOM Systems,” IEEE
International Journal of Electrical Power & Energy Systems, vol. 78, Transactions on Power Systems, vol. 31, pp. 2824–2833, July 2016.
pp. 414–421, 2016. [21] M. R. Tavana, M. H. Khooban, and T. Niknam, “Adaptive PI
[14] L. Wang, Q. S. Vo, and A. V. Prokhorov, “Stability Improvement of controller to voltage regulation in power systems: STATCOM as a
a Multimachine Power System Connected With a Large-Scale case study,” ISA Transactions, vol. 66, pp. 325–334, Jan. 2017.
Hybrid Wind-Photovoltaic Farm Using a Supercapacitor,” IEEE [22] Y. Xu and F. Li, “Adaptive PI Control of STATCOM for Voltage
Transactions on Industry Applications, vol. 54, pp. 50–60, Jan.–Feb. Regulation,” IEEE Transactions on Power Delivery, vol. 29, pp.
2018. 1002–1011, June 2014.
[15] S. Ananthavel, S. Padmanaban, S. Shanmugham, F. Blaabjerg, A. H. [23] K. Wang and M. L. Crow, “Power System Voltage Regulation via
Ertas, and V. Fedak, “Analysis of enhancement in available power STATCOM Internal Nonlinear Control,” IEEE Transactions on
transfer capacity by STATCOM integrated SMES by numerical Power Systems, vol. 26, pp. 1252–1262, Aug. 2011.
simulation studies,” Engineering Science and Technology, an
International Journal, vol. 19, pp.671–675, 2016.
[16] A. H. M. A. Rahim and M. A. Alam, “STATCOM-Supercapacitor
Control for Low Voltage Performance Improvement of Wind
Generation Systems,” Arab. J. Sci. Eng., vol. 38, pp. 3133–3143,
Nov. 2013.

73

You might also like