You are on page 1of 5

RATCH COGENERATION CO.

, LTD
Tender Document – RCO Expansion Project
Volume II – Scope of Work and Technical Requirements

APPENDIX 4
SITE LOCATIONS AND SITE CONDITIONS
RATCH COGENERATION CO., LTD
Tender Document – RCO Expansion Project
Volume II – Scope of Work and Technical Requirements

APPENDIX 4
SITE LOCATIONS AND SITE CONDITIONS

SITE LOCATION
The Project is in boundary of existing plant which is located in Chumnumsap industrial
park at Tambon Klong-nueng, Amphur Klongluang, Pathumthani, Thailand. The Project
is 46 kilometers (approximate 45 minutes) far from center of Bangkok.
Figure 1: RCO Location

Source: Google Map

The Project will be constructed on the area of existing raw water pond which is
demarked by yellow rectangular frame in Figure 2. The existing raw water pond
(approximately 2.3 meters depth) will be backfilled into the same level of the existing
plant by the Owner before handover construction area to Bidder. Final Levelling and
soil compacting shall be verified by Bidder before Piling works. The plot plan shall be
plotted from the east fence. The Bidder shall minimize the plotting area in order to
minimize backfilling of raw water pond and specify the minimum area (Square Meter)
into the proposal.
RATCH COGENERATION CO., LTD
Tender Document – RCO Expansion Project
Volume II – Scope of Work and Technical Requirements

Figure2: Project Construction Area

Noted: Expansion phase areas are highlighted with yellow


RATCH COGENERATION CO., LTD
Tender Document – RCO Expansion Project
Volume II – Scope of Work and Technical Requirements

SITE CONDITIONS

Remarks:
1. The following information on climatic and ambient condition shall not be construed to represent
all or complete data. The Bidder shall be responsible for making available any data that is deemed
necessary for the performance of his work. Where Bidder presents guarantee on performance such
guarantee figure shall be at the reference ambient condition as indicated in this Schedule 1.
2. For auxiliary equipment design the climatological conditions provided herein shall apply.

(A) Climatological Conditions

Reference Ambient
Unit of Condition for
Value
measure Performance
Guarantee
(a) Elevation: Meter MSL+5.05 -
(b)Atmospheric mbar 1,013 Used for Guarantee
Pressure:
(c) Temperature:
Extreme maximum °C 40.0
Mean °C 32.0 Used for Guarantee
Extreme minimum °C 20.9
(d) Relative Humidity:
Annual mean maximum % 86.6
Mean % 80.0 Used for Guarantee
Annual mean minimum % 56.3
Annual extreme % 43.7
minimum
(e) Rainfall:
Rainfall intensity mm/hr 172 -
(f) Maximum wind m/s 38 -
speed
RATCH COGENERATION CO., LTD
Tender Document – RCO Expansion Project
Volume II – Scope of Work and Technical Requirements

(B) Classification for Site Seismic Hazard

For the purpose of design consideration regarding equipment and structural safety
against seismic activity, the site is located at Bangkok area, zone 7 as per Figure A-1. The
spectral response acceleration for equivalent static design of the site at 0.2 second and 1
second shall be 0.246 and 0181 and dynamic design shall be 0.167 and 0.181,
respectively, according to the DPT1301_1302-61. The Bidder shall follow
DPT1301_1302-61 and the latest version of ASCE7 and comply with the latest local
regulatory requirements.

Figure A-1 Zone Arrangement in Bangkok Basin Area for Design Seismic in
Thailand

Source: DPT 1301-1302-61

(C) Reference Ground Elevation

The reference ground elevation, ± 0.000 m, of the Cogeneration Plant, which applies to
all design and level setting, the backfilling shall be fixed at +5.050m MSL. Soil
Investigation Report from the existing plant study is enclosed in Appendix 1 Geotech &
Soil Investigation Report. However, the construction area is the backfilling area in the
existing raw water pond. Bidder shall verify the soil investigation result.

This area is considering as the flood area, the flooding level consider 2.00 m from plant
elevation EL 0.00 m. (Refer to NNE drawing no. D-D154-193Fa). However, RCOX power
plant area has his own flood protection wall for the whole area.