DESIGN BASIS
MODULE MOUNTING STRUCTURE AND
FOUNDATION DESIGNER
PROJECT: DELHI GPO
PART Material
DESCRIPTION Coating
No. Grade Section
Column – hot rolled ISA 50X50X4
1 E250 HDG
section
Rafter – hot rolled ISA 30X30X3
2 E250 HDG
section
3 Purlin – hot rolled section E250 HDG 65Z40X10 (Zee)
4 Brace E250 HDG 30LU30X2
WIND LOADS:
The following describes the wind calculation in detail as IS 875:3:2015
SERVICE:
DEAD + WIND
DURABILITY: Expected life of structure would be minimum 25 years. Hot-dip-galvanizing or Pre-galvanization as per ASTM123 to be adopted.
= 𝐹𝑦 /2 + M.y/I
= 2.51 KN
12 | P a g e Doc No:
Design Basis Report for MMS and Foundation
Checks:
1) Tensile capacity of 1 bolt=
2.51 KN < 29 KN
The attached table from ISO ISO 898-1:2009(E) shows that the provided bolt size is sufficient in taking Maximum Tension
13 | P a g e Doc No:
Design Basis Report for MMS and Foundation
2) BALLAST CALCULATION
Hence the strength will be governed by tensile strength of concrete (fct = 0.7 sqrt (fck) = 3.13 mpa)
Applying a further FoS of 2.0,
Ballast Capacity = fct*Ab/FoS + weight of ballast --- where Ab is area of base of ballast
= 3.13 N/mm2*400*400/2/1000 + 24 kN/m3*0.4*0.4*0.3
= 500 kN ( mainly governed by tensile bond)
Hence, the ballast will be sufficient for the expected wind load uplift.