CLIENT KEPCO
SITE
ASTA SHINNAGATA
SANBANKA
10/5/2017

AUTHOR Aditya Agasi

1 of 19
[ ProDiag Corona ]

CONTENT

Content .......................................................................................................................................................... 2

1. Service synthesis ..................................................................................................................................... 3


1.1. Electrical room Electrical room ........................................................................................................... 3
1.2. Switchboard MV SM6 ......................................................................................................................... 3
1.3. Conclusions & recommendations ....................................................................................................... 3
1.4. Documentation ................................................................................................................................... 4

2. Electrical Room details Electrical room ................................................................................................. 5

3. Switchboard details MV SM6 ................................................................................................................... 6


3.1. Partial discharge measurements synthesis ........................................................................................ 6
3.2. Cubicle details MV Switch cubicle 1L ................................................................................................. 7
3.3. Cubicle details MV Fuses-switch cubicle TR1.................................................................................... 9
3.4. Cubicle details MV Fuses-switch cubicle TR2.................................................................................. 11
3.5. Cubicle details MV Fuses-switch cubicle TR3.................................................................................. 13
3.6. Cubicle details MV Fuses-switch cubicle TR4.................................................................................. 15
3.7. Cubicle details MV Switch cubicle 2L ............................................................................................... 17

4. PARTIAL DISCHARGE RANGE ............................................................................................................. 19

2 of 19
[ ProDiag Corona ]

1. SERVICE SYNTHESIS

1.1. Electrical room Electrical room


Diagnosis
Defective maintenance of dust filters

Recommendations
Plan a regular maintenance of filters

1.2. Switchboard MV SM6

Equipment name Status

MV Switch cubicle 1L To follow


MV Fuses-switch cubicle TR1 To follow
MV Fuses-switch cubicle TR2 To follow
MV Fuses-switch cubicle TR3 Normal
MV Fuses-switch cubicle TR4 Normal
MV Switch cubicle 2L Major defect

1.3. Conclusions & recommendations


Defective maintenance of dust filter
Plan a regular maintenance of filters

Some Partial discharged phenomenon were detected mainly on both IM Panel and two QM Panel
- IM1L : Phase 2&3 are impacted by low internal partial discharge
- QMTR1 : Phase 1&2 are impacted by low internal partial discharge
Phase 2&3 are impacted by low internal partial discharge
- QMTR2 : Phase 1&2 are impacted by low internal partial discharge
- IM2L : Phase 1&2 are impacted by low internal partial discharge
Phase 2&3 are impacted by low internal partial discharge
Phase 3&1 are impacted by major internal partial discharge

1. To do visual inspection on each cubicles are impacted partial discharge (IM1L, QMTR1, QMTR2, IM2L) with
shutdown
2. To do preventive maintenance on each cubicles are impacted partial discharge (IM1L, QMTR1, QMTR2, IM2L)
with shutdown. as for, scope of work for preventive maintenance are:
a. Cleaning each cubicles by using alcohol > 96 %
b. Greasing mechanical part and electrical part
c. To ensure the tighteness of main busbar connection by using torque wrench as standart determined
d. To ensure the tighteness of cable connection by using torque wrench as standart determined
e. To do insulation testing each cubicles to know critical level of insulation failure inside cubicles
f. To ensure anti condensation heater each cubicles work properly
3. Equipment to be checked by using procorona measurement again after doing assesment on offline cubicle

3 of 19
[ ProDiag Corona ]

1.4. Documentation

Fig 1. Temperature & Humidity Fig 2. Overall Cubicle Fig 3. Forced Ventilation

Fig 4. Inside view of IM1L Fig 5. Inside view of QM1TR Fig 6. Inside view of QM2TR

Fig 7. Inside view of QM3TR Fig 8. Inside view of QM4TR Fig 9. Inside view of IM2L

4 of 19
[ ProDiag Corona ]

2. ELECTRICAL ROOM DETAILS ELECTRICAL ROOM

Electrical room type: Indoor


Ventilation: Forced ventilation
Heating: Central heating system
Air conditionning: No air cond
Environment
Temperature 25°C Due point 16°C
Humidity 58% Margin before condensation 9°C

Weather during service Dry


Estimated daily temperature amplitude > 16°C

Electrical room ventilation analysis


Ventilation directed towards the transformer No
Ventilation directed towards the cubicles No
Presence of dust prevention filters Dirty filter

Visual inspection
Marks of condensation No Localisation
Dust No
Smell of ozone No Localisation
Water in the trench No

Background

Acquisition 1 Acquisition 2 Acquisition 3

Comments
Background noise: 10dB

5 of 19
[ ProDiag Corona ]

3. SWITCHBOARD DETAILS MV SM6

Brand / Range / Type Merlin Gerin / SM6-36 / -


Manufacturing year 2003

Design type
Nominal voltage (Un) 36kV Short-circuit current (Icc) 16kA
Service voltage (Us) 33kV Busbar rating 630A
IP IP2XC

3.1. Partial discharge measurements synthesis

Magnitude

Qm (mV)
Cubicle Criticity
Phase

NQN
N
1 19dB 105 1 3
MV Switch cubicle 1L 2 36dB 128 17 22 To follow
3 22dB 22 2 5
1 33dB 30 7 17
MV Fuses-switch cubicle TR1 2 33dB 229 13 17 To follow
3 14dB 139 1 2
1 33dB 116 12 18
MV Fuses-switch cubicle TR2 2 27dB 8 0 0 To follow
3 30dB 15 2 0
1 28dB 472 10 10
MV Fuses-switch cubicle TR3 2 15dB 360 1 2 Normal
3 12dB 34 1 1
1 23dB 26 2 3
MV Fuses-switch cubicle TR4 2 10dB 4 0 0 Normal
3 14dB 82 1 2
1 38dB 409 32 33
MV Switch cubicle 2L 2 38dB 79 22 31 Major defect
3 42dB 116 41 49

6 of 19
[ ProDiag Corona ]

3.2. Cubicle details MV Switch cubicle 1L


Identification
Brand / Range / Type Merlin Gerin / SM6-36 / IM
Manufacturing year 2003

Serial number 0321049Z.M Function Incomer


Nominal voltage (Un) 36 kV Nominal current(In) 630 A
Service voltage (Us) 33 kV Short circuit current (Icc) 16 kA
Characteristics
Internal arc withstand
Auxiliaries
Heaters in cubicle Not specified
Observations
Audible cracklings No
Blue lights visible No

Corrosion marks No
Carbonized insulation No
White powder on isolator No
White powder on cables No

Dust in the cubicle Not specified


Poor cable endings No
Comments

Acquisitions
Time signal Wave front Peak/angle

7 of 19
[ ProDiag Corona ]

Diagnosis
Partial discharges detected, low defect
Recommendations
Assessment to be done on off line cubicle
Equipment to be checked by using Procorona Measurement after doing assessment on off line cubicle/
preventive maintenance

8 of 19
[ ProDiag Corona ]

3.3. Cubicle details MV Fuses-switch cubicle TR1


Identification
Brand / Range / Type Merlin Gerin / SM6-36 / QM
Manufacturing year 2003

Serial number 0321016Z.M Function Feeder


Nominal voltage (Un) 36 kV Nominal current(In) 63 A
Service voltage (Us) 33 kV Short circuit current (Icc) 16 kA
Characteristics
Internal arc withstand
Auxiliaries
Heaters in cubicle Not specified
Observations
Audible cracklings No
Blue lights visible No

Corrosion marks No
Carbonized insulation No
White powder on isolator No
White powder on cables No

Dust in the cubicle Not specified


Poor cable endings No
Comments

Acquisitions
Time signal Wave front Peak/angle

9 of 19
[ ProDiag Corona ]

Diagnosis
Partial discharges detected, low defect
Recommendations
Assessment to be done on off line cubicle
Equipment to be checked by using Procorona Measurement after doing assessment on off line cubicle/
preventive maintenance

10 of 19
[ ProDiag Corona ]

3.4. Cubicle details MV Fuses-switch cubicle TR2


Identification
Brand / Range / Type Merlin Gerin / SM6-36 / QM
Manufacturing year 2003

Serial number 0323040Z.M Function Feeder


Nominal voltage (Un) 36 kV Nominal current(In) 63 A
Service voltage (Us) 33 kV Short circuit current (Icc) 16 kA
Characteristics
Internal arc withstand
Auxiliaries
Heaters in cubicle Not specified
Observations
Audible cracklings No
Blue lights visible No

Corrosion marks No
Carbonized insulation No
White powder on isolator No
White powder on cables No

Dust in the cubicle Not specified


Poor cable endings No
Comments

Acquisitions
Time signal Wave front Peak/angle

11 of 19
[ ProDiag Corona ]

Diagnosis
Partial discharges detected, low defect
Recommendations
Assessment to be done on off line cubicle
Equipment to be checked by using Procorona Measurement after doing assessment on off line cubicle/
preventive maintenance

12 of 19
[ ProDiag Corona ]

3.5. Cubicle details MV Fuses-switch cubicle TR3


Identification
Brand / Range / Type Merlin Gerin / SM6-36 / QM
Manufacturing year 2003

Serial number 0323041Z.M Function Feeder


Nominal voltage (Un) 36 kV Nominal current(In) 63 A
Service voltage (Us) 33 kV Short circuit current (Icc) 16 kA
Characteristics
Internal arc withstand
Auxiliaries
Heaters in cubicle Not specified
Observations
Audible cracklings No
Blue lights visible No

Corrosion marks No
Carbonized insulation No
White powder on isolator No
White powder on cables No

Dust in the cubicle Not specified


Poor cable endings No
Comments

Acquisitions
Time signal Wave front Peak/angle

13 of 19
[ ProDiag Corona ]

Diagnosis
No partial discharges detected
Recommendations
Expertise to be done every year

14 of 19
[ ProDiag Corona ]

3.6. Cubicle details MV Fuses-switch cubicle TR4


Identification
Brand / Range / Type Merlin Gerin / SM6-36 / QM
Manufacturing year 2003

Serial number 0317018Z.M Function Feeder


Nominal voltage (Un) 36 kV Nominal current(In) 63 A
Service voltage (Us) 33 kV Short circuit current (Icc) 16 kA
Characteristics
Internal arc withstand
Auxiliaries
Heaters in cubicle Not specified
Observations
Audible cracklings No
Blue lights visible No

Corrosion marks No
Carbonized insulation No
White powder on isolator No
White powder on cables No

Dust in the cubicle Not specified


Poor cable endings No
Comments

Acquisitions
Time signal Wave front Peak/angle

15 of 19
[ ProDiag Corona ]

Diagnosis
No partial discharges detected
Recommendations
Expertise to be done every year

16 of 19
[ ProDiag Corona ]

3.7. Cubicle details MV Switch cubicle 2L


Identification
Brand / Range / Type Merlin Gerin / SM6-36 / IM
Manufacturing year 2003

Serial number 0321048Z.M Function Incomer


Nominal voltage (Un) 36 kV Nominal current(In) 630 A
Service voltage (Us) 33 kV Short circuit current (Icc) 16 kA
Characteristics
Internal arc withstand
Auxiliaries
Heaters in cubicle Not specified
Observations
Audible cracklings No
Blue lights visible No

Corrosion marks No
Carbonized insulation No
White powder on isolator No
White powder on cables No

Dust in the cubicle Not specified


Poor cable endings No
Comments

Acquisitions
Time signal Wave front Peak/angle

17 of 19
[ ProDiag Corona ]

Diagnosis
Incomplete partial discharges measurement due to open circuit
Partial discharges detected, major defect
Recommendations
Analysis of preventive and curative solutions
Assessment to be done on off line cubicle
Equipment to be checked by using Procorona Measurement after doing assessment on off line cubicle/
preventive and corrective maintenance

18 of 19
[ ProDiag Corona ]

4. PARTIAL DISCHARGE RANGE

No Magnitude (db) Magnitude Qm (mV) NQN (mV) Remarks

1 0-29 0-12.5 0-12.5 Normal

2 30-39 12.6-39.5 12.5-19.9 To Follow

3 40-49 39.6-125 20-99.9 Major

4 50-59 ≥ 125.1 ≥100 Critical

19 of 19