[ ProDiag Corona ]
CONTENT
Content .......................................................................................................................................................... 2
2 of 19
[ ProDiag Corona ]
1. SERVICE SYNTHESIS
Recommendations
Plan a regular maintenance of filters
Some Partial discharged phenomenon were detected mainly on both IM Panel and two QM Panel
- IM1L : Phase 2&3 are impacted by low internal partial discharge
- QMTR1 : Phase 1&2 are impacted by low internal partial discharge
Phase 2&3 are impacted by low internal partial discharge
- QMTR2 : Phase 1&2 are impacted by low internal partial discharge
- IM2L : Phase 1&2 are impacted by low internal partial discharge
Phase 2&3 are impacted by low internal partial discharge
Phase 3&1 are impacted by major internal partial discharge
1. To do visual inspection on each cubicles are impacted partial discharge (IM1L, QMTR1, QMTR2, IM2L) with
shutdown
2. To do preventive maintenance on each cubicles are impacted partial discharge (IM1L, QMTR1, QMTR2, IM2L)
with shutdown. as for, scope of work for preventive maintenance are:
a. Cleaning each cubicles by using alcohol > 96 %
b. Greasing mechanical part and electrical part
c. To ensure the tighteness of main busbar connection by using torque wrench as standart determined
d. To ensure the tighteness of cable connection by using torque wrench as standart determined
e. To do insulation testing each cubicles to know critical level of insulation failure inside cubicles
f. To ensure anti condensation heater each cubicles work properly
3. Equipment to be checked by using procorona measurement again after doing assesment on offline cubicle
3 of 19
[ ProDiag Corona ]
1.4. Documentation
Fig 1. Temperature & Humidity Fig 2. Overall Cubicle Fig 3. Forced Ventilation
Fig 4. Inside view of IM1L Fig 5. Inside view of QM1TR Fig 6. Inside view of QM2TR
Fig 7. Inside view of QM3TR Fig 8. Inside view of QM4TR Fig 9. Inside view of IM2L
4 of 19
[ ProDiag Corona ]
Visual inspection
Marks of condensation No Localisation
Dust No
Smell of ozone No Localisation
Water in the trench No
Background
Comments
Background noise: 10dB
5 of 19
[ ProDiag Corona ]
Design type
Nominal voltage (Un) 36kV Short-circuit current (Icc) 16kA
Service voltage (Us) 33kV Busbar rating 630A
IP IP2XC
Magnitude
Qm (mV)
Cubicle Criticity
Phase
NQN
N
1 19dB 105 1 3
MV Switch cubicle 1L 2 36dB 128 17 22 To follow
3 22dB 22 2 5
1 33dB 30 7 17
MV Fuses-switch cubicle TR1 2 33dB 229 13 17 To follow
3 14dB 139 1 2
1 33dB 116 12 18
MV Fuses-switch cubicle TR2 2 27dB 8 0 0 To follow
3 30dB 15 2 0
1 28dB 472 10 10
MV Fuses-switch cubicle TR3 2 15dB 360 1 2 Normal
3 12dB 34 1 1
1 23dB 26 2 3
MV Fuses-switch cubicle TR4 2 10dB 4 0 0 Normal
3 14dB 82 1 2
1 38dB 409 32 33
MV Switch cubicle 2L 2 38dB 79 22 31 Major defect
3 42dB 116 41 49
6 of 19
[ ProDiag Corona ]
Corrosion marks No
Carbonized insulation No
White powder on isolator No
White powder on cables No
Acquisitions
Time signal Wave front Peak/angle
7 of 19
[ ProDiag Corona ]
Diagnosis
Partial discharges detected, low defect
Recommendations
Assessment to be done on off line cubicle
Equipment to be checked by using Procorona Measurement after doing assessment on off line cubicle/
preventive maintenance
8 of 19
[ ProDiag Corona ]
Corrosion marks No
Carbonized insulation No
White powder on isolator No
White powder on cables No
Acquisitions
Time signal Wave front Peak/angle
9 of 19
[ ProDiag Corona ]
Diagnosis
Partial discharges detected, low defect
Recommendations
Assessment to be done on off line cubicle
Equipment to be checked by using Procorona Measurement after doing assessment on off line cubicle/
preventive maintenance
10 of 19
[ ProDiag Corona ]
Corrosion marks No
Carbonized insulation No
White powder on isolator No
White powder on cables No
Acquisitions
Time signal Wave front Peak/angle
11 of 19
[ ProDiag Corona ]
Diagnosis
Partial discharges detected, low defect
Recommendations
Assessment to be done on off line cubicle
Equipment to be checked by using Procorona Measurement after doing assessment on off line cubicle/
preventive maintenance
12 of 19
[ ProDiag Corona ]
Corrosion marks No
Carbonized insulation No
White powder on isolator No
White powder on cables No
Acquisitions
Time signal Wave front Peak/angle
13 of 19
[ ProDiag Corona ]
Diagnosis
No partial discharges detected
Recommendations
Expertise to be done every year
14 of 19
[ ProDiag Corona ]
Corrosion marks No
Carbonized insulation No
White powder on isolator No
White powder on cables No
Acquisitions
Time signal Wave front Peak/angle
15 of 19
[ ProDiag Corona ]
Diagnosis
No partial discharges detected
Recommendations
Expertise to be done every year
16 of 19
[ ProDiag Corona ]
Corrosion marks No
Carbonized insulation No
White powder on isolator No
White powder on cables No
Acquisitions
Time signal Wave front Peak/angle
17 of 19
[ ProDiag Corona ]
Diagnosis
Incomplete partial discharges measurement due to open circuit
Partial discharges detected, major defect
Recommendations
Analysis of preventive and curative solutions
Assessment to be done on off line cubicle
Equipment to be checked by using Procorona Measurement after doing assessment on off line cubicle/
preventive and corrective maintenance
18 of 19
[ ProDiag Corona ]
19 of 19