Date

TECHNICAL SERVICES GROUP 9/3/2019


Location
NTDCL, Lahore 500/220/132KV G/S NTDC Rawat

TEST PROTOCOL OF THERMAL OVERLOAD Relay


Intalled On R13A Protection Relay Panel
Make : 7SJ602 Siemens LV CT Ratio: 2400/1
Sr. No. BF11040783758
Measurement Test
Phase Applied Current Calculated Value Relay Measurement

Red 1A 2.4kA 100%


Yellow 1A 2.4kA 100%
Blue 1A 2.4kA 100%
Trip Time Test
Phase Applied Current (A) Calculated Time(Sec) Observed Time(Sec)

1.5 234.316 233.5


Red 2 121.498 121.49
2.5 75.12 75.356
1.5 234.316 233.2
Yellow 2 121.498 121.27
2.5 75.12 75.25
1.5 234.316 232.839
Blue 2 121.498 121.25
2.5 75.12 75.115

Remarks:

Tested By Supervised By Witness By Witness By Witness By Contactor


TSG, NTDCL TSG, NTDC NESPAK GSO, NTDCL EHV, NTDCL M/S Transmark

Page 1 of 1