No. Signal Name Type I/O addressing IEC61850 Addressing Bit TN IEC104 Addr
Page 2 of 51
81 Phase voltage Ua Signal Name
No. MV
Type I/O addressing E02_BCU\System\MMXU1$PhV$phsA$cVal$mag
IEC61850 Addressing Bit TN IEC104 Addr
82 Phase voltage Ub MV E02_BCU\System\MMXU1$PhV$phsB$cVal$mag
83 Phase voltage Uc MV E02_BCU\System\MMXU1$PhV$phsC$cVal$mag
84 Line voltage Uab MV E02_BCU\System\MMXU1$PPV$phsAB$cVal$mag
85 Line voltage Ubc MV E02_BCU\System\MMXU1$PPV$phsBC$cVal$mag
86 Line voltage Uca MV E02_BCU\System\MMXU1$PPV$phsCA$cVal$mag
87 Phase current Ia MV E02_BCU\System\MMXU1$A$phsA$cVal$mag
88 Phase current Ib MV E02_BCU\System\MMXU1$A$phsB$cVal$mag
89 Phase current Ic MV E02_BCU\System\MMXU1$A$phsC$cVal$mag
90 Active Power P MV E02_BCU\System\MMXU1$W$res$cVal$mag
91 Reactive Power Q MV E02_BCU\System\MMXU1$VA$res$cVal$mag
92 Frequency F MV E02_BCU\System\MMXU1$Hz$mag
93 Cosϕ MV E02_BCU\System\MMXU1$PF$res$cVal$mag
II. Relay signals
II.1, F67 (GRD200-51-113-00-4L-30-110, softw.: GRD200-503E-4L2-1E)
1 Relay General Trip SPS E02_F67\System\GGIO3$Ind1.StVal
2 Relay General Alarm SPS E02_F67\System\GGIO3$Ind2.StVal
3 Operating Phase A SPS E02_F67\System\GGIO3$Ind3.StVal
4 Operating Phase B SPS E02_F67\System\GGIO3$Ind4.StVal
5 Operating Phase C SPS E02_F67\System\GGIO3$Ind5.StVal
6 Operating Phase N SPS E02_F67\System\GGIO3$Ind6.StVal
7 Port 1 Link Status SPS E02_F67\System\GGIO3$Ind7.StVal
8 Port 2 Link Status SPS E02_F67\System\GGIO3$Ind8.StVal
9 OC-1 Trip SPS
10 OC-2 Trip SPS
11 OC-3 Trip SPS
12 EF-1 Trip SPS
13 EF-2 Trip SPS
14 EF-3 Trip SPS
15 F27 Alarm SPS
16 F59 Alarm SPS
17 F59 Trip SPS
18 Start F79 SPS E02_F67\System\GGIO3$Ind9.StVal
19 Start 50BF Stg2 SPS
20 SOTF OC Trip SPS
21 Phase current Ia MV
22 Phase current Ib MV
23 Phase current Ic MV
24 Phase voltage Ua MV
25 Phase voltage Ub MV
26 Phase voltage Uc MV
27 Reset LED SPC
II.2, F87L (GRL200-11-224-12-4L-30-110, softw: GRL200-1033-4L2-2E)
1 Relay General Trip SPS E02_F87L\System\GGIO3$Ind1.StVal
2 Relay General Alarm SPS E02_F87L\System\GGIO3$Ind2.StVal
3 Operating Phase A SPS E02_F87L\System\GGIO3$Ind3.StVal
4 Operating Phase B SPS E02_F87L\System\GGIO3$Ind4.StVal
5 Operating Phase C SPS E02_F87L\System\GGIO3$Ind5.StVal
6 Operating Phase N SPS E02_F87L\System\GGIO3$Ind6.StVal
Page 3 of 51
7
No. Port 1 Link Status Signal Name SPS
Type I/O addressing E02_F87L\System\GGIO3$Ind7.StVal
IEC61850 Addressing Bit TN IEC104 Addr
8 Port 2 Link Status SPS E02_F87L\System\GGIO3$Ind8.StVal
9 Z1 (3 Phase OR) Trip SPS E02_F87L\System\GGIO3$Ind9.StVal BIT_10_0
10 Z2 (3 Phase OR) Trip SPS E02_F87L\System\GGIO3$Ind10.StVal BIT_10_1
11 Z3 (3 Phase OR) Trip SPS Logic in PLC E02_F87L\System\GGIO3$Ind11.StVal BIT_10_2
12 Z4 (3 Phase OR) Trip SPS E02_F87L\System\GGIO3$Ind12.StVal BIT_10_3
13 SOTF Trip SPS E02_F87L\System\GGIO3$Ind13.StVal BIT_10_4
14 F87L Trip (Diff Trip) SPS
15 OC-1 Trip SPS
16 OC-2 Trip SPS
17 OC-3 Trip SPS
18 OC-4 Trip SPS
19 EF-1 Trip SPS
20 EF-2 Trip SPS
21 EF-3 Trip SPS
22 EF-4 Trip SPS
23 50BF Retrip SPS
24 50BF Trip SPS
25 F79 Ready SPS
26 F79 In progress SPS
27 F79 Final Trip SPS
28 F79 Successful SPS
29 F79 Block SPS
30 DIFL Blocked SPS Logic in PLC E02_F87L\System\GGIO3$Ind14.StVal BIT_10_5
31 Differential current Phase A (Id-A) MV
32 Differential current Phase B (Id-B) MV
33 Differential current Phase C (Id-C) MV
34 Restraining current Phase A (Ir-A) MV
35 Restraining current Phase B (Ir-B) MV
36 Restraining current Phase C (Ir-C) MV
37 Fault Distance MV
38 Fault Zone MV
39 Phase current Ia MV
40 Phase current Ib MV
41 Phase current Ic MV
42 Phase voltage Ua MV
43 Phase voltage Ub MV
44 Phase voltage Uc MV
45 Reset LED SPC
Hà Nội, ngày 24 /10/2019
KSHT
(ký, ghi tên)
Nguyễn Bá Bun
Page 4 of 51
BM-KT-23
NBH: 10/10/2012
LBH: 01
R-061/CPC-ENTEC
BO For Interlock
DPSY01
DPOS01
DPOS02
DPOS03
DPOS04
DPOS05
DPSY01
DPOS01
DPOS02
DPOS05
SPOS01
SPOS02
SPOS03
SPOS04
SPOS05
SPOS06
Page 5 of 51
BO For Interlock
Ko cầ n đưa lên
Ko cầ n đưa lên
Page 6 of 51
BO For Interlock
GEN.TRIP
GEN.ALARM
OPT.PHASE-A
OPT.PHASE-B
OPT.PHASE-C
OPT.PHASE-N
Port 1 Link Status
Port 2 Link Status
OC1-OPT-TRIP
OC2-OPT-TRIP
OC3-OPT-TRIP
EF1-OPT-TRIP
EF2-OPT-TRIP
EF3-OPT-TRIP
UV1-OPT-ALARM
OV1-OPT-ALARM
OV1-OPT-TRIP
Slot1/BO5
CBF1_TRIP
SOTFOC-TRIP
E02_F67/System$LLN0$CO$LEDRs:0
GEN.TRIP
GEN.ALARM
OPT.PHASE-A
OPT.PHASE-B
OPT.PHASE-C
OPT.PHASE-N
Page 7 of 51
PortFor
BO 1 Link Status
Interlock
Port 2 Link Status
Z1S-OPT OR Z1G-OPT
Z2S-OPT OR Z2G-OPT
Z3S-OPT OR Z3G-OPT
Z4S-OPT OR Z4G-OPT
SOTF-OC TRIP or SOFT ZS Trip or SOFT ZG Trip
DIFL-OPT
OC1-OPT-TRIP
OC2-OPT-TRIP
OC3-OPT-TRIP
OC4-OPT-TRIP
EF1-OPT-TRIP
EF2-OPT-TRIP
EF3-OPT-TRIP
EF4-OPT-TRIP
CBF1_RETRIP
CBF1_TRIP
ARC1 READY
ARC1 IN-PROG
ARC1 FT
ARC1 CLOSE SUCCESS
ARC1_BLOCK
Prot/DIFL_PDIF1.DifAClc.phsA.phsA.cVal.mag.f
Prot/DIFL_PDIF1.DifAClc.phsB.phsA.cVal.mag.f
Prot/DIFL_PDIF1.DifAClc.phsC.phsA.cVal.mag.f
Prot/DIFL_PDIF1.RstA.phsA.phsA.cVal.mag.f
Prot/DIFL_PDIF1.RstA.phsA.phsB.cVal.mag.f
Prot/DIFL_PDIF1.RstA.phsA.phsC.cVal.mag.f
Prot/FLAZ_RFLO1.FltDiskm
Prot/FLAZ_RFLO1.FltZ
E02_F87LSystem$LLN0$CO$LEDRs:0
, ngày 24 /10/2019
KSHT
(ký, ghi tên)
guyễn Bá Bun
Page 8 of 51
CÔNG TY CỔ PHẦN ENTEC KỸ THUẬT NĂNG LƯỢNG
Số 21, Lô 13B, khu Đô thị mới Trung Yên
P.Trung Hòa, Q.Cầu Giấy, Hà Nội, Việt Nam
Tel: +84-4-37830640 Fax: +84-4-37830635
Website: http://www.entec.com.vn Email: entec@entec.com.vn
No. Signal Name Type I/O addressing IEC61850 Addressing A1 IEC101 Addr TN IEC104 Addr
Page 9 of 51
29
No. QF01 control at localSignal Name SPS
Type BCU.T3\BI6
I/O addressing IEC61850 Addressing
E03_BCU\Ctrl\S03_gbi_GGIO103$Ind6.StVal A1 IEC101 Addr TN IEC104 Addr
30 QF01 MCB trip SPS BCU.T3\BI7 E03_BCU\Ctrl\S03_gbi_GGIO103$Ind7.StVal
31 QL01 MCB trip SPS BCU.T3\BI11 E03_BCU\Ctrl\S03_gbi_GGIO103$Ind11.StVal
32 QL01 control remote SPS BCU.T3\BI12 E03_BCU\Ctrl\S03_gbi_GGIO103$Ind12.StVal
33 QL02 MCB trip SPS BCU.T3\BI15 E03_BCU\Ctrl\S03_gbi_GGIO103$Ind15.StVal
34 QL02 control remote SPS BCU.T3\BI16 E03_BCU\Ctrl\S03_gbi_GGIO103$Ind16.StVal
35 QE14 MCB trip SPS BCU.T3\BI19 E03_BCU\Ctrl\S03_gbi_GGIO103$Ind19.StVal
36 QE15 MCB trip SPS BCU.T3\BI22 E03_BCU\Ctrl\S03_gbi_GGIO103$Ind22.StVal
37 QE24 MCB trip SPS BCU.T3\BI25 E03_BCU\Ctrl\S03_gbi_GGIO103$Ind25.StVal
38 QE25 MCB trip SPS BCU.T3\BI28 E03_BCU\Ctrl\S03_gbi_GGIO103$Ind28.StVal
39 BVT C12 MCB CL0.5 OFF SPS BCU.T3\BI29 E03_BCU\Ctrl\S03_gbi_GGIO103$Ind29.StVal
40 SWITCH at E02+CRP2 Failure SPS BCU.T3\BI31 E03_BCU\Ctrl\S03_gbi_GGIO103$Ind31.StVal
41 MCB LVT CL0.5 OFF SPS BCU.T4\BI1 E03_BCU\Ctrl\S04_gbi_GGIO104$Ind1.StVal
42 M/B Key at MIMIC SPS BCU.T4\BI2 E03_BCU\Ctrl\S04_gbi_GGIO104$Ind2.StVal
43 S25 Key at SYN SPS BCU.T4\BI3 E03_BCU\Ctrl\S04_gbi_GGIO104$Ind3.StVal
44 Close CB check SYN SPS BCU.T4\BI4 E03_BCU\Ctrl\S04_gbi_GGIO104$Ind4.StVal
45 F861 Trip SPS BCU.T4\BI5 E03_BCU\Ctrl\S04_gbi_GGIO104$Ind5.StVal
46 F862 Trip SPS BCU.T4\BI6 E03_BCU\Ctrl\S04_gbi_GGIO104$Ind6.StVal
47 F741 Failure (Active low) SPS BCU.T4\BI7 E03_BCU\Ctrl\S04_gbi_GGIO104$Ind7.StVal
48 F742 Failure (Active low) SPS BCU.T4\BI8 E03_BCU\Ctrl\S04_gbi_GGIO104$Ind8.StVal
49 F67 Failure SPS BCU.T4\BI9 E03_BCU\Ctrl\S04_gbi_GGIO104$Ind9.StVal
50 E03+CRP3 MCB TRIP SPS BCU.T4\BI10 E03_BCU\Ctrl\S04_gbi_GGIO104$Ind10.StVal
51 E03+CRP3 MCB AC OFF SPS BCU.T4\BI11 E03_BCU\Ctrl\S04_gbi_GGIO104$Ind11.StVal
52 E03+CRP3 MCB DC OFF SPS BCU.T4\BI12 E03_BCU\Ctrl\S04_gbi_GGIO104$Ind12.StVal
53 CB QF01 Close Release SPS E03_BCU\System\GGIO2$Ind1.StVal BIT_10_0
54 CB QF01 Open Release SPS E03_BCU\System\GGIO2$Ind2.StVal BIT_10_1
55 DS QL01 Release SPS E03_BCU\System\GGIO2$Ind3.StVal BIT_10_2
56 DS QL02 Release SPS E03_BCU\System\GGIO2$Ind4.StVal BIT_10_3
Logic in PLC
57 ES QE14 Release SPS E03_BCU\System\GGIO2$Ind5.StVal BIT_10_4
58 ES QE15 Release SPS E03_BCU\System\GGIO2$Ind6.StVal BIT_10_5
59 ES QE24 Release SPS E03_BCU\System\GGIO2$Ind7.StVal BIT_10_6
60 ES QE25 Release SPS E03_BCU\System\GGIO2$Ind8.StVal BIT_10_7
61 Port 1 Link Status SPS E03_BCU\System\GGIO3$Ind1.StVal
62 Port 2 Link Status SPS E03_BCU\System\GGIO3$Ind2.StVal
63 BCU Failure SPS F67.T1\BI1 E03_F67\System\GGIO2$Ind1.StVal
64 F67 Start SOTF SPS F67.T1\BI2 E03_F67\System\GGIO2$Ind2.StVal
65 MCB BCU OFF SPS F67.T1\BI3 E03_F67\System\GGIO2$Ind3.StVal
66 MCB BCU Trip SPS F67.T1\BI4 E03_F67\System\GGIO2$Ind4.StVal
67 MCB BVT C11 CL 3P OFF SPS F67.T1\BI5 E03_F67\System\GGIO2$Ind5.StVal
68 Phase voltage Ua MV E03_BCU\System\MMXU1$PhV$phsA$cVal$mag
69 Phase voltage Ub MV E03_BCU\System\MMXU1$PhV$phsB$cVal$mag
70 Phase voltage Uc MV E03_BCU\System\MMXU1$PhV$phsC$cVal$mag
71 Line voltage Uab MV E03_BCU\System\MMXU1$PPV$phsAB$cVal$mag
72 Line voltage Ubc MV E03_BCU\System\MMXU1$PPV$phsBC$cVal$mag
73 Line voltage Uca MV E03_BCU\System\MMXU1$PPV$phsCA$cVal$mag
Page 10 of 51
74 Phase current Ia
No. Signal Name MV
Type I/O addressing IEC61850 Addressing
E03_BCU\System\MMXU1$A$phsA$cVal$mag A1 IEC101 Addr TN IEC104 Addr
75 Phase current Ib MV E03_BCU\System\MMXU1$A$phsB$cVal$mag
76 Phase current Ic MV E03_BCU\System\MMXU1$A$phsC$cVal$mag
77 Active Power P MV E03_BCU\System\MMXU1$W$res$cVal$mag
78 Reactive Power Q MV E03_BCU\System\MMXU1$VA$res$cVal$mag
79 Frequency F MV E03_BCU\System\MMXU1$Hz$mag
80 CosPhi MV E03_BCU\System\MMXU1$PF$res$cVal$mag
II. Relay signals
II.1, F67 - (GRD200-51-113-00-4L-30-110, softw.: GRD200-503E-4L2-1E)
1 Relay General Trip SPS E03_F67\System\GGIO3$Ind1.StVal
2 Relay General Alarm SPS E03_F67\System\GGIO3$Ind2.StVal
3 Operating Phase A SPS E03_F67\System\GGIO3$Ind3.StVal
4 Operating Phase B SPS E03_F67\System\GGIO3$Ind4.StVal
5 Operating Phase C SPS E03_F67\System\GGIO3$Ind5.StVal
6 Operating Phase N SPS E03_F67\System\GGIO3$Ind6.StVal
7 Port 1 Link Status SPS E03_F67\System\GGIO3$Ind7.StVal
8 Port 2 Link Status SPS E03_F67\System\GGIO3$Ind8.StVal
9 OC-1 Trip SPS
10 OC-2 Trip SPS
11 OC-3 Trip SPS
12 EF-1 Trip SPS
13 EF-2 Trip SPS
14 EF-3 Trip SPS
15 F27 Alarm SPS
16 F59 Alarm SPS
17 F59 Trip SPS
18 Start 50BF Stg2 SPS
19 SOTF OC Trip SPS
20 Phase current Ia MV
21 Phase current Ib MV
22 Phase current Ic MV
23 Phase voltage Ua MV
24 Phase voltage Ub MV
25 Phase voltage Uc MV
26 Reset LED SPC
Nguyễn Bá Bun
Page 11 of 51
BM-KT-23
NBH: 10/10/2012
LBH: 01
1/CPC-ENTEC
BO For Interlock
DPSY01
DPOS01
DPOS02
DPOS03
DPOS04
DPOS05
DPOS06
DPSY01
DPOS01
DPOS02
SPOS01
SPOS02
Page 12 of 51
BO For Interlock
Page 13 of 51
BO For Interlock
GEN.TRIP
GEN.ALARM
OPT.PHASE-A
OPT.PHASE-B
OPT.PHASE-C
OPT.PHASE-N
Port 1 Link Status
Port 2 Link Status
OC1-OPT-TRIP
OC2-OPT-TRIP
OC3-OPT-TRIP
EF1-OPT-TRIP
EF2-OPT-TRIP
EF3-OPT-TRIP
UV1-OPT-ALARM
OV1-OPT-ALARM
OV1-OPT-TRIP
CBF1_TRIP
SOTFOC-TRIP
E03_F67/System$LLN0$CO$LEDRs:0
gày 24 /10/2019
KSHT
(ký, ghi tên)
guyễn Bá Bun
Page 14 of 51
CÔNG TY CỔ PHẦN ENTEC KỸ THUẬT NĂNG LƯỢNG
Số 21, Lô 13B, khu Đô thị mới Trung Yên
P.Trung Hòa, Q.Cầu Giấy, Hà Nội, Việt Nam
Tel: +84-4-37830640 Fax: +84-4-37830635
Website: http://www.entec.com.vn Email: entec@entec.com.vn
No. Signal Name Type I/O addressing IEC61850 Addressing Bit TN IEC104 Addr
Page 16 of 51
81 Phase voltage Ua Signal Name
No. MV
Type I/O addressing E04_BCU\System\MMXU1$PhV$phsA$cVal$mag
IEC61850 Addressing Bit TN IEC104 Addr
82 Phase voltage Ub MV E04_BCU\System\MMXU1$PhV$phsB$cVal$mag
83 Phase voltage Uc MV E04_BCU\System\MMXU1$PhV$phsC$cVal$mag
84 Line voltage Uab MV E04_BCU\System\MMXU1$PPV$phsAB$cVal$mag
85 Line voltage Ubc MV E04_BCU\System\MMXU1$PPV$phsBC$cVal$mag
86 Line voltage Uca MV E04_BCU\System\MMXU1$PPV$phsCA$cVal$mag
87 Phase current Ia MV E04_BCU\System\MMXU1$A$phsA$cVal$mag
88 Phase current Ib MV E04_BCU\System\MMXU1$A$phsB$cVal$mag
89 Phase current Ic MV E04_BCU\System\MMXU1$A$phsC$cVal$mag
90 Active Power P MV E04_BCU\System\MMXU1$W$res$cVal$mag
91 Reactive Power Q MV E04_BCU\System\MMXU1$VA$res$cVal$mag
92 Frequency F MV E04_BCU\System\MMXU1$Hz$mag
93 Cosϕ MV E04_BCU\System\MMXU1$PF$res$cVal$mag
II. Relay signals
II.1, F67 (GRD200-51-113-00-4L-30-110, softw.: GRD200-503E-4L2-1E)
1 Relay General Trip SPS E04_F67\System\GGIO3$Ind1.StVal
2 Relay General Alarm SPS E04_F67\System\GGIO3$Ind2.StVal
3 Operating Phase A SPS E04_F67\System\GGIO3$Ind3.StVal
4 Operating Phase B SPS E04_F67\System\GGIO3$Ind4.StVal
5 Operating Phase C SPS E04_F67\System\GGIO3$Ind5.StVal
6 Operating Phase N SPS E04_F67\System\GGIO3$Ind6.StVal
7 Port 1 Link Status SPS E04_F67\System\GGIO3$Ind7.StVal
8 Port 2 Link Status SPS E04_F67\System\GGIO3$Ind8.StVal
9 OC-1 Trip SPS
10 OC-2 Trip SPS
11 OC-3 Trip SPS
12 EF-1 Trip SPS
13 EF-2 Trip SPS
14 EF-3 Trip SPS
15 F27 Alarm SPS
16 F59 Alarm SPS
17 F59 Trip SPS
18 Start F79 SPS E04_F67\System\GGIO3$Ind9.StVal
19 Start 50BF Stg2 SPS
20 SOTF OC Trip SPS
21 Phase current Ia MV
22 Phase current Ib MV
23 Phase current Ic MV
24 Phase voltage Ua MV
25 Phase voltage Ub MV
26 Phase voltage Uc MV
27 Reset LED SPC
II.2, F87L (GRL200-11-224-12-4L-30-110, softw: GRL200-1033-4L2-2E)
1 Relay General Trip SPS E04_F87L\System\GGIO3$Ind1.StVal
2 Relay General Alarm SPS E04_F87L\System\GGIO3$Ind2.StVal
3 Operating Phase A SPS E04_F87L\System\GGIO3$Ind3.StVal
4 Operating Phase B SPS E04_F87L\System\GGIO3$Ind4.StVal
5 Operating Phase C SPS E04_F87L\System\GGIO3$Ind5.StVal
6 Operating Phase N SPS E04_F87L\System\GGIO3$Ind6.StVal
Page 17 of 51
7
No. Port 1 Link Status Signal Name SPS
Type I/O addressing E04_F87L\System\GGIO3$Ind7.StVal
IEC61850 Addressing Bit TN IEC104 Addr
8 Port 2 Link Status SPS E04_F87L\System\GGIO3$Ind8.StVal
9 Z1 (3 Phase OR) Trip SPS E04_F87L\System\GGIO3$Ind9.StVal BIT_10_0
10 Z2 (3 Phase OR) Trip SPS E04_F87L\System\GGIO3$Ind10.StVal BIT_10_1
11 Z3 (3 Phase OR) Trip SPS Logic in PLC E04_F87L\System\GGIO3$Ind11.StVal BIT_10_2
12 Z4 (3 Phase OR) Trip SPS E04_F87L\System\GGIO3$Ind12.StVal BIT_10_3
13 SOTF Trip SPS E04_F87L\System\GGIO3$Ind13.StVal BIT_10_4
14 F87L Trip (Diff Trip) SPS
15 OC-1 Trip SPS
16 OC-2 Trip SPS
17 OC-3 Trip SPS
18 OC-4 Trip SPS
19 EF-1 Trip SPS
20 EF-2 Trip SPS
21 EF-3 Trip SPS
22 EF-4 Trip SPS
23 50BF Retrip SPS
24 50BF Trip SPS
25 F79 Ready SPS
26 F79 In progress SPS
27 F79 Final Trip SPS
28 F79 Successful SPS
29 F79 Block SPS
30 DIFL Blocked SPS Logic in PLC E04_F87L\System\GGIO3$Ind14.StVal BIT_10_5
31 Differential current Phase A (Id-A) MV
32 Differential current Phase B (Id-B) MV
33 Differential current Phase C (Id-C) MV
34 Restraining current Phase A (Ir-A) MV
35 Restraining current Phase B (Ir-B) MV
36 Restraining current Phase C (Ir-C) MV
37 Fault Distance MV
38 Fault Zone MV
39 Phase current Ia MV
40 Phase current Ib MV
41 Phase current Ic MV
42 Phase voltage Ua MV
43 Phase voltage Ub MV
44 Phase voltage Uc MV
45 Reset LED SPC
Nguyễn Bá Bun
Page 18 of 51
BM-KT-23
NBH: 10/10/2012
LBH: 01
R-061/CPC-ENTEC
BO For Interlock
DPSY01
DPOS01
DPOS02
DPOS03
DPOS04
DPOS05
DPSY01
DPOS01
DPOS02
DPOS05
SPOS01
SPOS02
SPOS03
SPOS04
SPOS05
SPOS06
Page 19 of 51
BO For Interlock
Ko cầ n đưa lên
Ko cầ n đưa lên
Page 20 of 51
BO For Interlock
GEN.TRIP
GEN.ALARM
OPT.PHASE-A
OPT.PHASE-B
OPT.PHASE-C
OPT.PHASE-N
Port 1 Link Status
Port 2 Link Status
OC1-OPT-TRIP
OC2-OPT-TRIP
OC3-OPT-TRIP
EF1-OPT-TRIP
EF2-OPT-TRIP
EF3-OPT-TRIP
UV1-OPT-ALARM
OV1-OPT-ALARM
OV1-OPT-TRIP
Slot1/BO5
CBF1_TRIP
SOTFOC-TRIP
E04_F67/System$LLN0$CO$LEDRs:0
GEN.TRIP
GEN.ALARM
OPT.PHASE-A
OPT.PHASE-B
OPT.PHASE-C
OPT.PHASE-N
Page 21 of 51
PortFor
BO 1 Link Status
Interlock
Port 2 Link Status
Z1S-OPT OR Z1G-OPT
Z2S-OPT OR Z2G-OPT
Z3S-OPT OR Z3G-OPT
Z4S-OPT OR Z4G-OPT
SOTF-OC TRIP or SOFT ZS Trip or SOFT ZG Trip
DIFL-OPT
OC1-OPT-TRIP
OC2-OPT-TRIP
OC3-OPT-TRIP
OC4-OPT-TRIP
EF1-OPT-TRIP
EF2-OPT-TRIP
EF3-OPT-TRIP
EF4-OPT-TRIP
CBF1_RETRIP
CBF1_TRIP
ARC1 READY
ARC1 IN-PROG
ARC1 FT
ARC1 CLOSE SUCCESS
ARC1_BLOCK
Prot/DIFL_PDIF1.DifAClc.phsA.phsA.cVal.mag.f
Prot/DIFL_PDIF1.DifAClc.phsB.phsA.cVal.mag.f
Prot/DIFL_PDIF1.DifAClc.phsC.phsA.cVal.mag.f
Prot/DIFL_PDIF1.RstA.phsA.phsA.cVal.mag.f
Prot/DIFL_PDIF1.RstA.phsA.phsB.cVal.mag.f
Prot/DIFL_PDIF1.RstA.phsA.phsC.cVal.mag.f
Prot/FLAZ_RFLO1.FltDiskm
Prot/FLAZ_RFLO1.FltZ
E04_F87LSystem$LLN0$CO$LEDRs:0
, ngày 24 /10/2019
KSHT
(ký, ghi tên)
guyễn Bá Bun
Page 22 of 51
CÔNG TY CỔ PHẦN ENTEC KỸ THUẬT NĂNG LƯỢNG
Số 21, Lô 13B, khu Đô thị mới Trung Yên
P.Trung Hòa, Q.Cầu Giấy, Hà Nội, Việt Nam
Tel: +84-4-37830640 Fax: +84-4-37830635
Website: http://www.entec.com.vn Email: entec@entec.com.vn
No. Signal Name Type I/O addressing IEC61850 Addressing Bit TN IEC104 Addr
Page 24 of 51
81 OLTC Pressure relay
No. trip Name
Signal SPS
Type F87T.T2\BI6
I/O addressing E05_F87T\System\GGIO2$Ind6.StVal
IEC61850 Addressing Bit TN IEC104 Addr
82 Transf Oil temp. trip SPS F87T.T2\BI7 E05_F87T\System\GGIO2$Ind7.StVal
83 Transf Winding temp trip SPS F87T.T2\BI8 E05_F87T\System\GGIO2$Ind8.StVal
84 F67 Start SOTF SPS F67.T1\BI1 E05_F67\System\GGIO2$Ind1
85 BCU Failure SPS F67.T1\BI2 E05_F67\System\GGIO2$Ind2
86 F87T trip start 50BF SPS F67.T1\BI3 E05_F67\System\GGIO2$Ind3
87 MCB BCU OFF SPS F67.T1\BI4 E05_F67\System\GGIO2$Ind4
88 MCB BCU Trip SPS F67.T1\BI5 E05_F67\System\GGIO2$Ind5
89 OLTC inprogress SPS F90\E1
90 Tap control mode independent SPS F90\E2
91 OLTC control mode master SPS F90\E3
92 OLTC control mode slave SPS F90\E4
93 OLTC operate Auto SPS F90\E5
94 OLTC operate Man SPS F90\E6
95 CB QF01 Close Release SPS E05_BCU\System\GGIO2$Ind1.StVal BIT_10_0
96 CB QF01 Open Release SPS E05_BCU\System\GGIO2$Ind2.StVal BIT_10_1
Logic in PLC
97 DS QL02 Release SPS E05_BCU\System\GGIO2$Ind3.StVal BIT_10_2
98 ES QE25 Release SPS E05_BCU\System\GGIO2$Ind4.StVal BIT_10_3
99 Port 1 Link Status SPS E05_BCU\System\GGIO2$Ind5.StVal
100 Port 2 Link Status SPS E05_BCU\System\GGIO2$Ind6.StVal
101 T2 Tap Changer MV F90\AI1
102 Oil Temp Transformer MV PTO
103 115kV Side Winding Temp MV PTW1
104 22kV Side Winding Temp MV PTW2
105 Phase voltage Ua MV E05_BCU\System\MMXU1$PhV$phsA$cVal$mag
106 Phase voltage Ub MV E05_BCU\System\MMXU1$PhV$phsB$cVal$mag
107 Phase voltage Uc MV E05_BCU\System\MMXU1$PhV$phsC$cVal$mag
108 Line voltage Uab MV E05_BCU\System\MMXU1$PPV$phsAB$cVal$mag
109 Line voltage Ubc MV E05_BCU\System\MMXU1$PPV$phsBC$cVal$mag
110 Line voltage Uca MV E05_BCU\System\MMXU1$PPV$phsCA$cVal$mag
111 Phase current Ia MV E05_BCU\System\MMXU1$A$phsA$cVal$mag
112 Phase current Ib MV E05_BCU\System\MMXU1$A$phsB$cVal$mag
113 Phase current Ic MV E05_BCU\System\MMXU1$A$phsC$cVal$mag
114 Active Power P MV E05_BCU\System\MMXU1$W$res$cVal$mag
115 Reactive Power Q MV E05_BCU\System\MMXU1$VA$res$cVal$mag
116 Frequency F MV E05_BCU\System\MMXU1$Hz$mag
117 Cosϕ MV E05_BCU\System\MMXU1$PF$res$cVal$mag
II. Relay signals
II.1, F67 (GRD200-51-113-00-4L-30-110, softw.: GRD200-503E-4L2-1E)
1 Relay General Trip SPS E05_F67\System\GGIO3$Ind1.StVal
2 Relay General Alarm SPS E05_F67\System\GGIO3$Ind2.StVal
3 Operating Phase A SPS E05_F67\System\GGIO3$Ind3.StVal
4 Operating Phase B SPS E05_F67\System\GGIO3$Ind4.StVal
5 Operating Phase C SPS E05_F67\System\GGIO3$Ind5.StVal
6 Operating Phase N SPS E05_F67\System\GGIO3$Ind6.StVal
7 Port 1 Link Status SPS E05_F67\System\GGIO3$Ind7.StVal
8 Port 2 Link Status SPS E05_F67\System\GGIO3$Ind8.StVal
9 OC-1 Trip SPS
10 OC-2 Trip SPS
Page 25 of 51
11 OC-3 Trip
No. Signal Name SPS
Type I/O addressing IEC61850 Addressing Bit TN IEC104 Addr
12 EF-1 Trip SPS
13 EF-2 Trip SPS
14 EF-3 Trip SPS
15 F27 Alarm SPS
16 F59 Alarm SPS
17 F59 Trip SPS
18 Start 50BF Stg1 SPS
19 Start 50BF Stg2 SPS
20 SOTF OC Trip SPS
21 Phase current Ia MV
22 Phase current Ib MV
23 Phase current Ic MV
24 Phase voltage Ua MV
25 Phase voltage Ub MV
26 Phase voltage Uc MV
27 Reset LED SPC
II.2, F87T (GRT200-31-224-00-4L-30-111, SW: GRT200-303D-4L2-2E)
1 Relay General Trip SPS E05_F87T\System\GGIO3$Ind1.StVal
2 Relay General Alarm SPS E05_F87T\System\GGIO3$Ind2.StVal
3 Operating Phase A SPS E05_F87T\System\GGIO3$Ind3.StVal
4 Operating Phase B SPS E05_F87T\System\GGIO3$Ind4.StVal
5 Operating Phase C SPS E05_F87T\System\GGIO3$Ind5.StVal
6 Operating Phase N SPS E05_F87T\System\GGIO3$Ind6.StVal
7 Port 1 Link Status SPS E05_F87T\System\GGIO3$Ind7.StVal
8 Port 2 Link Status SPS E05_F87T\System\GGIO3$Ind8.StVal
9 DIF-OPT SPS
10 DIF-OPT-A SPS
11 DIF-OPT-B SPS
12 DIF-OPT-C SPS
13 REF1-OPT SPS
14 REF2-OPT SPS
15 OC-1 Trip SPS
16 OC-2 Trip SPS
17 OC-3 Trip SPS
18 EF-1 Trip SPS
19 EF-2 Trip SPS
20 EF-3 Trip SPS
21 DIFT-Id-A MV
22 DIFT-Id-B MV
23 DIFT-Id-C MV
24 DIFT Ir-A MV
25 DIFT Ir-B MV
26 DIFT Ir-C MV
27 REF1 Id-N MV
28 REF2 Id-N MV
29 REF1 Ir-N MV
30 REF2 Ir-N MV
31 Reset LED SPC
Page 26 of 51
No. Signal Name Type I/O addressing IEC61850 Addressing Bit TN IEC104 Addr
Nguyễn Bá Bun
Page 27 of 51
BM-KT-23
NBH: 10/10/2012
LBH: 01
R-061/CPC-ENTEC
BO For Interlock
DPSY01
DPOS01
DPOS02
DPSY01
DPOS01
SPOS01
SPOS02
SPOS03
SPOS04
SPOS05
SPOS06
SPOS07
SPOS08
SPOS09
SPOS10
SPOS11
SPOS12
Page 28 of 51
BO For Interlock
Page 29 of 51
BO For Interlock
Modbus RTU
GEN.TRIP
GEN.ALARM
OPT.PHASE-A
OPT.PHASE-B
OPT.PHASE-C
OPT.PHASE-N
Port 1 Link Status
Port 2 Link Status
OC1-OPT-TRIP
OC2-OPT-TRIP
Page 30 of 51
OC3-OPT-TRIP
BO For Interlock
EF1-OPT-TRIP
EF2-OPT-TRIP
EF3-OPT-TRIP
UV1-OPT-ALARM
OV1-OPT-ALARM
OV1-OPT-TRIP
CBF1_RETRIP
CBF1_TRIP
SOTFOC-TRIP
E05_F67/System$LLN0$CO$LEDRs:0
GEN.TRIP
GEN.ALARM
OPT.PHASE-A
OPT.PHASE-B
OPT.PHASE-C
OPT.PHASE-N
Port 1 Link Status
Port 2 Link Status
DIF-OPT
DIF-OPT-A
DIF-OPT-B
DIF-OPT-C
REF1-OPT
REF2-OPT
OC1-OPT
OC2-OPT
OC3-OPT
EF1-OPT
EF2-OPT
EF3-OPT
Prot/DIFT_PDIF1.DifAClc.phsA.phsA.cVal.mag.f
Prot/DIFT_PDIF1.DifAClc.phsB.phsB.cVal.mag.f
Prot/DIFT_PDIF1.DifAClc.phsC.phsC.cVal.mag.f
Prot/DIFT_PDIF1.RstA.phsA.phsA.cVal.mag.f
Prot/DIFT_PDIF1.RstA.phsB.phsB.cVal.mag.f
Prot/DIFT_PDIF1.RstA.phsC.phsC.cVal.mag.f
Prot/REF_PDIF1.DifAClc1.neut.neut.cVal.mag.f
Prot/REF_PDIF1.DifAClc2.neut.neut.cVal.mag.f
Prot/REF_PDIF1.RstA1.neut.neut.cVal.mag.f
Prot/REF_PDIF1.RstA2.neut.neut.cVal.mag.f
E05_F87TSystem$LLN0$CO$LEDRs:0
Page 31 of 51
BO For Interlock
, ngày 24 /10/2019
KSHT
(ký, ghi tên)
guyễn Bá Bun
Page 32 of 51
CÔNG TY CỔ PHẦN ENTEC KỸ THUẬT NĂNG LƯỢNG
Số 21, Lô 13B, khu Đô thị mới Trung Yên
P.Trung Hòa, Q.Cầu Giấy, Hà Nội, Việt Nam
Tel: +84-4-37830640 Fax: +84-4-37830635
Website: http://www.entec.com.vn Email: entec@entec.com.vn
No. Signal Name Type I/O addressing IEC61850 Addressing TN IEC104 Addr Note 1
Page 34 of 51
81 Switch at Server Failure
No. Signal Name SPS BCU.T4\BI19
Type I/O addressing SC_IO\Ctrl\S04_gbi_GGIO104$Ind19.stVal
IEC61850 Addressing TN IEC104 Addr Note 1
Nguyễn Bá Bun
Page 35 of 51
BM-KT-23
NBH: 10/10/2012
LBH: 01
-ENTEC
Note 2
SPOS01
SPOS02
SPOS03
SPOS04
SPOS05
SPOS06
SPOS07
SPOS08
SPOS09
SPOS10
SPOS11
SPOS12
SPOS13
SPOS14
SPOS15
SPOS16
SPOS17
SPOS18
SPOS19
SPOS20
Page 36 of 51
Note 2
Page 37 of 51
Note 2
24 /10/2019
HT
hi tên)
Bá Bun
Page 38 of 51
CÔNG TY CỔ PHẦN ENTEC KỸ THUẬT NĂNG LƯỢNG
Số 21, Lô 13B, khu Đô thị mới Trung Yên
P.Trung Hòa, Q.Cầu Giấy, Hà Nội, Việt Nam
Tel: +84-4-37830640 Fax: +84-4-37830635
Website: http://www.entec.com.vn Email: entec@entec.com.vn
BM-KT-23
BẢNG DANH SÁCH TÍN HIỆU HỆ THỐNG NBH: 10/10/2012
- Tủ nguồn AC_DC- LBH: 01
Dự án: Trạm biến áp 110kV Sân bay Cam Ranh và đấu nối Số HĐ: 1906X02-SBCR-061/CPC-ENTEC
Khách hàng: Tổng Công ty Điện lực Miền Trung
Sản phẩm: Hệ thống Điều Khiển Máy Tính
No. Signal Name Type I/O addressing IEC61850 Addressing TN IEC104 Addr Note
Nguyễn Bá Bun
Page 40 of 51
BẢNG DANH SÁCH TÍN HIỆU HỆ THỐNG
- Ngăn 22kV Incoming C41-
Dự án: Trạm biến áp 110kV Phước Hữu
Khách hàng:
Sản phẩm: Hệ thống Điều Khiển Máy Tính
No. Signal Name Type I/O addressing IEC61850 Addressing TN IEC104 Addr Note
Page 42 of 51
CÔNG TY CỔ PHẦN ENTEC KỸ THUẬT NĂNG LƯỢNG
Số 21, Lô 13B, khu Đô thị mới Trung Yên
P.Trung Hòa, Q.Cầu Giấy, Hà Nội, Việt Nam
Tel: +84-4-37830640 Fax: +84-4-37830635
Website: http://www.entec.com.vn Email: entec@entec.com.vn
BM-KT-23
BẢNG DANH SÁCH TÍN HIỆU HỆ THỐNG NBH: 10/10/2012
- Ngăn 22kV TUC41- LBH: 01
Dự án: Trạm biến áp 110kV Sân bay Cam Ranh và đấu nối Số HĐ: 1906X02-SBCR-061/CPC-ENTEC
Khách hàng: Tổng Công ty Điện lực Miền Trung
Sản phẩm: Hệ thống Điều Khiển Máy Tính
No. Signal Name Type I/O addressing IEC61850 Addressing TN IEC104 Addr Note
Page 43 of 51
CÔNG TY CỔ PHẦN ENTEC KỸ THUẬT NĂNG LƯỢNG
Số 21, Lô 13B, khu Đô thị mới Trung Yên
P.Trung Hòa, Q.Cầu Giấy, Hà Nội, Việt Nam
Tel: +84-4-37830640 Fax: +84-4-37830635
Website: http://www.entec.com.vn Email: entec@entec.com.vn
BM-KT-23
BẢNG DANH SÁCH TÍN HIỆU HỆ THỐNG NBH: 10/10/2012
- Ngăn 22kV Aux tranformer TD41- LBH: 01
Dự án: Trạm biến áp 110kV Sân bay Cam Ranh và đấu nối Số HĐ: 1906X02-SBCR-061/CPC-ENTEC
Khách hàng: Tổng Công ty Điện lực Miền Trung
Sản phẩm: Hệ thống Điều Khiển Máy Tính
No. Signal Name Type I/O addressing IEC61850 Addressing TN IEC104 Addr Note
Page 45 of 51
CÔNG TY CỔ PHẦN ENTEC KỸ THUẬT NĂNG LƯỢNG
Số 21, Lô 13B, khu Đô thị mới Trung Yên
P.Trung Hòa, Q.Cầu Giấy, Hà Nội, Việt Nam
Tel: +84-4-37830640 Fax: +84-4-37830635
Website: http://www.entec.com.vn Email: entec@entec.com.vn
Dự án: Trạm biến áp 110kV Sân bay Cam Ranh và đấu nối Số HĐ: 1906X02-SBCR-061/CPC-ENTEC
Khách hàng: Tổng Công ty Điện lực Miền Trung
Sản phẩm: Hệ thống Điều Khiển Máy Tính
No. Signal Name Type I/O addressing IEC61850 Addressing TN IEC104 Addr Note
Page 47 of 51
CÔNG TY CỔ PHẦN ENTEC KỸ THUẬT NĂNG LƯỢNG
Số 21, Lô 13B, khu Đô thị mới Trung Yên
P.Trung Hòa, Q.Cầu Giấy, Hà Nội, Việt Nam
Tel: +84-4-37830640 Fax: +84-4-37830635
Website: http://www.entec.com.vn Email: entec@entec.com.vn
BM-KT-23
BẢNG DANH SÁCH TÍN HIỆU HỆ THỐNG NBH: 10/10/2012
- Ngăn 22kV C41 Outgoing 02- LBH: 01
Dự án: Trạm biến áp 110kV Sân bay Cam Ranh và đấu nối Số HĐ: 1906X02-SBCR-061/CPC-ENTEC
Khách hàng: Tổng Công ty Điện lực Miền Trung
Sản phẩm: Hệ thống Điều Khiển Máy Tính
No. Signal Name Type I/O addressing IEC61850 Addressing TN IEC104 Addr Note
Page 49 of 51
CÔNG TY CỔ PHẦN ENTEC KỸ THUẬT NĂNG LƯỢNG
Số 21, Lô 13B, khu Đô thị mới Trung Yên
P.Trung Hòa, Q.Cầu Giấy, Hà Nội, Việt Nam
Tel: +84-4-37830640 Fax: +84-4-37830635
Website: http://www.entec.com.vn Email: entec@entec.com.vn
BM-KT-23
BẢNG DANH SÁCH TÍN HIỆU HỆ THỐNG NBH: 10/10/2012
- Ngăn 22kV C41 Outgoing 03- LBH: 01
Dự án: Trạm biến áp 110kV Sân bay Cam Ranh và đấu nối Số HĐ: 1906X02-SBCR-061/CPC-ENTEC
Khách hàng: Tổng Công ty Điện lực Miền Trung
Sản phẩm: Hệ thống Điều Khiển Máy Tính
No. Signal Name Type I/O addressing IEC61850 Addressing TN IEC104 Addr Note
Page 51 of 51