13: Finishing
Vol-2 , 2013
CONTENTS
Clause No. Brief Description Page No.
List of Bureau of Indian Standards Codes 005
13.13 Pointing on Brick Work, Tile Work and Stone Work 015
Vol-2 , 2013
13.24 Painting Priming Coat on Wood, Iron or Plastered Surfaces 030
13.26 Painting Cast Iron Rain Water, Soil, Waste and Vent Pipes and 032
Fittings
13.29 Spray Painting with Flat Wall Paint on New Surface 034
13.30 Spray Painting with Flat Wall Paint on Old Surface 034
Vol-2 , 2013
LIST OF BUREAU OF INDIAN STANDARD CODES
Vol-2 , 2013
13.0 FINISHING
13.1.1 Scaffolding
For a ll ex posed br ick w ork or tile w ork double s caffolding independent o f t he w ork having t wo s ets o f
vertical supports shall be pr ovided. The s upports shall be sound and s trong, tied t ogether w ith hor izontal
pieces over which scaffolding planks shall be fixed.
For al l other w ork in bu ildings, s ingle s caffolding s hall be per mitted. In s uch c ases the i nner end of
the horizontal scaffolding pole shall rest in a hole provided only in the head er course for the pu rpose.
Only one header for each pole shall be left out. S uch holes for scaffolding s hall, ho wever, not be allowed
in pi llars/columns l ess t han one metre i n width o r i mmediately near the skew backs o f a rches. The hol es
left in masonry works for scaffolding purposes shall be filled and made good before plastering.
Note : In c ase o f special t ype o f brick w ork, scaffolding s hall be got appr oved f rom E ngineer-in-charge i n
advance.
In c ase of c oncrete s urface i f a c hemical retarder has b een ap plied t o t he f orm w ork, t he s urface
shall be ro ughened by wire brus hing and al l t he res ulting du st and l oose p articles c leaned of f and care
shall be taken that none of the retarders is left on the surface.
13.1.3 Mortar
The mortar of the specified mix using the t ype of s and described in the item shall be used. It s hall be
as specified in S ubhead 3 .0. F or ex ternal w ork and under coat work, the fine aggr egate s hall c onform t o
grading IV. For finishing coat work the fine aggregate conforming to grading zone V shall be used.
13.1.4.2 Plastering s hall be started from the top and w orked down t owards the floor. All p utlog h oles
shall be pr operly f illed i n advance of t he pl astering as t he s caffolding i s being t aken dow n. T o ens ure
even t hickness and a tr ue s urface, plaster a bout 15 × 15 c m shall be fir st ap plied, h orizontally and
vertically, at not m ore t han 2 m etres i ntervals ov er the ent ire s urface t o s erve as gauges . T he s urfaces
of these gauged ar eas shall be truly in the plane of the finished plaster surface. The mortar shall t hen be
laid on the wall, bet ween the gauges with trowel. The mortar shall be applied in a uniform surface slightly
more than the specified thickness. This shall be brought to a true surface, by working a wooden straight
edge rea ching across t he ga uges, with small upw ard and s ide ways movements at a t ime. F inally the
surface s hall be finished off t rue w ith trowel or wooden f loat according as a smooth or a sandy granular
texture is required. Excessive troweling or over working the float shall be avoided.
13.1.4.3 All corners, a rrises, angl es and junctions shall be t ruly vertical or hor izontal as the c ase may b e
and shall be carefully finished. Rounding or chamfering corners, arrises, provision of grooves at
junctions etc. where required shall be done without any extra payment. Such rounding, chamfering or
grooving shall be carried out with proper templates or battens to the sizes required.
Vol-2 , 2013
13.1.4.4 When suspending w ork at the e nd of the day, the plaster shall be left, cut clean to line bot h
horizontally and vertically. When recommencing the plastering, the edge of the old work shall be
scrapped cl eaned an d w etted w ith cement sl urry before plaster is applied to th e ad jacent ar eas, t o
enable the two t o p roperly join t ogether. Plastering work s hall be closed at the e nd of the d ay on the
body of wall and not nearer than 15 cm to any corners or arrises. It shall not be closed on the body of
the features s uch as p lasters, b ands an d c ornices, nor a t the c orners o f ar rises. H orizontal joints i n
plaster work shall not al so oc cur on parapet tops and c opings as these invariably l ead to l eakages. The
plastering and finishing shall be completed within half an hour of adding water to the dry mortar.
No portion of the surface shall be left out initially to be patched up later on. The plastering and
finishing shall be completed within half an hour of adding water to the dry mortar.
13.1.5 Thickness
Where the thickness required as per description of the item is 20 mm the average thickness of the
plaster shall not be l ess than 20 m m whether the wall treated is of brick or stone. In the case of brick
work, the minimum thickness over any portion of the surface shall be not less than 15 mm while in case of
stone work the minimum thickness over the bushings shall be not less than 12 mm.
13.1.6 Curing
Curing s hall be s tarted as s oon as t he pl aster ha s har dened s ufficiently n ot t o be dam aged w hen
watered.
The plaster shall be k ept wet for a per iod of at least 7 day s. During this period, it shall be s uitably
protected f rom al l dam ages at t he c ontractor’s ex pense by s uch m eans as t he E ngineer-in-Charge m ay
approve. T he da tes on which the p lastering is d one s hall be legibly marked on the various s ections
plastered so that curing for the specified period thereafter can be watched.
13.1.7 Finish
The plaster shall be finished to a t rue and pl umb s urface and t o the pr oper de gree o f smoothness a s
required. T he w ork s hall be t ested f requently as t he w ork pr oceeds w ith a true s traight edge not l ess
than 2. 5 m long and with plumb bobs . All horizontal lines and surfaces shall be tested with a level and al l
jambs and corners with a plumb bob as the work proceeds.
13.1.8 Precaution
Any c racks w hich appear i n the s urface and al l po rtions w hich s ound hol low w hen tapped, or ar e
found to be soft or otherwise de fective, shall be cut out in rectangular shape and redon e as directed by
the Engineer-in-Charge.
(i) W hen ceiling plaster is done, it shall be finished to chamfered edge at an angl e at its junction
with a suitable tool w hen plaster is being done. S imilarly w hen the w all plaster is being done, it
shall be k ept s eparate f rom t he c eiling pl aster by a t hin s traight groove not deeper t han 6 m m
drawn with any suitable method with the wall while the plaster is green.
(ii) To p revent s urface cracks appear ing bet ween junctions o f c olumn/beam a nd w alls, 150 mm w ide
chicken w ire m esh s hould be f ixed w ith U nai ls 150 m m c entre to c entre before pl astering t he
junction. T he pl astering of w alls an d bea m/column in one vertical pl ane should be c arried o ut i n
one go. For providing and fixing chicken wire mesh with U nails payment shall be m ade
separately.
13.1.9 Measurements
13.1.9.1 Length and br eadth sh all be m easured corr ect to a c m a nd it s a rea s hall b e cal culated i n
square metres correct to two places of decimal.
Vol-2 , 2013
13.1.9.3 The measurement of wall pl aster s hall be taken bet ween the walls or partitions (the dimensions
before the plaster shall be taken) for the length and from the top of the floor or skirting to the ceiling for the
height. Depth of coves or cornices if any shall be deducted.
13.1.9.5 Plaster over masonry pilasters will be measured and paid for as plaster only.
13.1.9.8 Exterior pl astering at a hei ght greater t han 10 m f rom av erage ground l evel s hall be m easured
separately i n eac h s torey height. P atch pl astering (in repairs) shall be measured as pl astering ne w w ork,
where the patch exceed 2.5 sqm. extra payment being made for preparing old wall, such as dismantling
old pl aster, raking out the j oints and c leaning t he surface. W here t he patch does not ex ceed 2.5 s qm i n
area it shall be measured under the appropriate item under sub head ‘Repairs to Buildings.’
(b) Deduction f or opening e xceeding 0.5 sqm but n ot exceeding 3 s qm e ach s hall be m ade for
reveals, jambs, soffits sills, sills, etc. of these openings.
(i) When both faces of walls are plastered with same plaster, deductions shall be made for one
face only.
(ii) When t wo faces o f w alls ar e pl astered with di fferent t ypes of pl aster or i f one face i s pl astered
and o ther is po inted or one face is p lastered and o ther is u nplastered, ded uction s hall be
made from the plaster or pointing on the side of the frame for the d oors, windows etc. o n
which width of reveals is less than that on the other side but no deduction shall be made on
the other side.
Where width of reveals on both faces of wall are equal, deduction of 50% of area of opening on
each face shall be made from area of plaster and/or pointing as the case may be.
(iii) For opening having door frame equal t o or projecting beyond t hickness of w all, f ull deduction
for opening shall be made from each plastered face of wall.
(c) For op ening exceeding 3 s qm in area, deduction will be made in the measurements for the full
opening of the wall treatment on bot h faces, while at the same time, jambs, sills an d soffits will
be measured for payment.
8| Page HO Civil Specifications Volume -2....
Vol-2 , 2013
In m easuring j ambs, sills an d soffits, deduction shall n ot b e made for the area i n c ontact with t he
frame of doors, windows etc.
13.1.10 Rate
The rate shall include the cost of all labour and materials involved in all the operations described above.
13.2.0 The cement plaster shall be 12, 15, or 20 mm thick, finished with a floating coat of neat cement, as
described in the item.
13.2.1 Specifications for t his i tem of w ork s hall b e s ame a s de scribed in 1 3.1 ex cept for t he a dditional
floating coat which shall be carried out as below.
When the pl aster ha s bee n br ought to a t rue s urface w ith the wooden straight edge (clause 13. 1.4.2)
it shall be uniformly treated over its entire area with a paste of neat cement and rubbed smooth, so that
the whole surface is covered with neat cement coating. The quantity of cement applied for floating coat
shall be 1 kg per sqm. Smooth finishing shall be completed with trowel immediately and in no case later
than half an hour of adding water to the plaster mix. The rest of the specifications described in 13.1.4
shall apply.
13.3.1 The specification for scaffolding and preparation of surface shall be as described in 13.1
13.3.2 Mortar
The mix and type of fine aggregate specified in the description of the item shall be used for the
respective c oats. G enerally t he m ix of the f inishing coat s hall no t be richer t han the un der c oat unless
otherwise described in item.
Generally coarse sand shall be used for the under coat and fine sand for the finishing coat, unless
otherwise specified f or e xternal work and under c oat w ork, t he f ine a ggregate s hall conform t o grading
zone IV. For finishing coat work the fine aggregate conforming to grading zone V shall be used.
13.3.3 Application
13.3.3.1 The plaster shall be applied in two coats i.e. 12 mm under coat and then 6 mm finishing coat
and shall have an average total thickness of not less than 18 mm.
13.3.3.2 12 mm Under Coat : This shall be applied as specified in 13.1.4 except that when the plaster
has been br ought to a tr ue s urface a wooden s traight e dge an d th e sur face sh all b e le ft ro ugh an d
furrowed 2 mm deep with a s cratching tool d iagonally b oth ways, to form key for the finishing co at. The
surface shall be kept wet till the finishing coat is applied.
13.3.3.3 6 mm Finishing Coat : The finishing coat shall be applied after the under coat has sufficiently set
but not dried and in any case within 48 hours and finished in the manner specified in 13.1.4.
13.3.4 Specifications for Curing, Finishing, Precautions, Measurements and Rate shall be as described
under 13.1.
13.4.1 Scaffolding
Stage scaffolding shall be provided for the work. This shall be independent of the walls.
Vol-2 , 2013
13.4.2 Preparation of Surface
Projecting b urrs of mortar for med d ue t o th e g aps at j oints in shuttering s hall be r emoved. T he
surface shall be scrubbed clean w ith w ire b rushes. I n addi tion c oncrete s urfaces t o be pl astered s hall be
pock marked with a pointed tool, at spacing of not more than 5 cm. Centres, the pock being made not less
than 3 mm deep. This is to ensure a proper key for the plaster. The mortar shall be washed off and surface,
cleaned off all oil, grease etc. and well wetted before the plaster is applied.
13.4.3 Mortars
Mortar of the specified mix using the types of sand described in the item shall be us ed. It shall be a s
specified in 3.2.
13.4.4 Application
To ensure even thickness and a true surface, gauges of plaster 1 5 x 15 cm. shall be first applied a t
not m ore than 1.5 m intervals in both directions to serve as guides for the plastering. S urface of these
gauged areas shall be truly in the plane of the finished plaster surface. The plaster shall be then applied in
a uniform surface to a thickness slightly more than the specified thickness and shall then be brought to
true and ev en s urface b y w orking a w ooden s traight edge r eaching ac ross t he gauges . F inally t he
surface shall be f inished t rue w ith a t rowel or with wooden f loat t o give a s mooth or sandy granular
texture as requi red. E xcess t roweling or ov er w orking of t he f loats s hall be a voided. T he pl astering and
finishing shall be completed within half an hour of adding water to the dry mortar.
Plastering o f ceiling shall not be c ommenced unt il t he slab abo ve has been finished and c entring has
been removed. I n t he case o f ceiling o f roof s labs, pl aster s hall not be c ommenced until t he terrace w ork
has been completed. These precautions are necessary in order that the ceiling plaster is not disturbed by
the vibrations set up in the above operations.
13.4.5 Finish
The plaster shall be finished to a t rue and pl umb surface and t o t he pr oper de gree o f smoothness a s
required. T he w ork s hall be t ested f requently as t he w ork pr oceeds w ith a true s traight edge not l ess
than 2. 5 m long and with plumb bobs . All horizontal lines and surfaces shall be tested with a level and all
jambs and corners with a plumb bob as the work proceeds.
13.4.6 Thickness
The av erage thickness of plaster s hall no t be less than 6 m m. T he m inimum thickness ov er a ny
portion of the surface shall not be less than 5 mm.
13.4.7 Curing
The specifications shall be as detailed in 13.1.6.
13.4.8 Precautions
The specifications shall be as detailed in 13.1.8.
13.4.9 Measurements
13.4.9.1 Length a nd br eadth shall be m easured c orrect a cm. a nd i ts area s hall b e calculated i n sqm.
correct to two places of decimal. Dimensions before plastering shall be taken.
13.4.9.2 Thickness of plaster shall be exclusive of the thickness of the key i.e. depth or rock marks and
hacking.
13.4.9.3 Plastering on ceiling at height greater than 5 m above the corresponding floor level shall be so
described and shall be measured separately stating the height in stages of 1 m or part thereof.
10 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
13.4.9.4 Plastering on t he sides and s offits o f the projected bea ms o f ceiling at a height gr eater than 5 m
above the corresponding floor level shall be measured and added to the quantity measured under 13.4.9.3.
13.4.9.5 Plastering on spherical and groined ceiling and circular work not exceeding 6 m in radius, shall be
measured and paid for separately.
13.4.9.6 Flowing soffits (viz. portion under spiral stair case etc.) shall be measured and paid for separately.
13.4.9.7 Ribs and m ouldings on c eiling s hall be measured as for cornices, deductions being m ade from
the plastering on ceiling in case the width of the moulding exceed 15 cm.
13.4.9.8 The mode of measurement of exterior plastering and patch plastering (in repairs) s hall be as
laid down in 13.1.9.8
13.4.9.9 Deduction shall not be m ade for o penings or f or ends of columns, or columns caps of 0.5 sqm
each in area and under. No additions will be made either for the plastering of the sides of such openings.
For openings etc. of areas exceeding 0.5 sqm deduction will be made for the full opening but the sides of
such openings shall be measured for payment.
13.4.10 Rate
The rate shall include the cost of all labour and materials involved in all the operations described above.
13.5.0 Cement plaster shall be 6 mm thick finished with a floating coat of neat cement and thick coat of
lime wash on top of walls for bearing of slabs.
13.5.1 Application
The pl aster shall be appl ied ov er t he c leaned and wetted s urface o f t he w all. W hen t he p laster has
been brought to a true s urface w ith the wooden straight edge ( Clause 13.1.4) it s hall be uniformly
treated over its entire area with a p aste of neat cement and rubbed smooth, so that the whole surface is
covered w ith neat c ement c oating. T he q uantity of c ement a pplied f or f loating c oat s hall be 1 kg per
sqm. S mooth finishing shall be c ompleted w ith trowel i mmediately a nd i n no c ase l ater t han hal f an ho ur
of adding water to the plaster mix. The rest of the specifications described in 13.1.4 shall apply.
13.5.3 Measurements
Length and br eadth shall be m easured correct to a cm and ar ea worked out in sqm correct to two
places of decimal.
13.5.4 Rate
The rate shall include the cost of all labour and materials involved in all the operations described above.
13.6.1 The specifications given for floating coat described in 13.2.1 shall apply.
13.6.2 Specification f or s caffolding a nd c uring shall be a s d escribed i n 13. 1.1 and 13.1.6. res pectively.
Specifications for Finish and Precautions shall be as described in 13.1.7. and 13.1.8.
11 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
13.6.3 Measurements
13.6.3.1 The m easurements f or c ement punni ng s hall be t aken ov er t he f inished w ork. T he l ength an d
breadth shall be measured correct to a cm. The area shall be calculated in sqm correct to two places of
decimal.
13.6.3.2 Punning over Plaster on bands, skirting, coping, cornices, drip courses, string courses etc. shall not
be measured separately but only as wall surfaces. In these cases the measurements shall be taken girthed
over the above features.
13.6.3.3 Punning o ver pl aster on c ircular w ork a lso, of any rad ius s hall be m easured on ly as w all
surfaces, and not separately.
13.6.3.4 Cement punning in patch repairs irrespective of the size of the patch shall be measured as new
work, and in this case the rate s hall include for cutting the patch to rectangular s hape before lim e
punning.
13.6.3.5 Deductions in measurements for openings shall be regulated generally as described in 13.1.9.9.
13.6.4 Rate
The r ate shall i nclude t he c ost of all l abour a nd materials i nvolved i n al l t he operations described
above.
13.7.0 Rough cast finish comprises of a mixture of sand and gravel in specified proportions dashed over a
freshly plastered surface.
13.7.1 Scaffolding
Scaffolding shall be done as specified in 13.1.1.
13.7.3 Mortar
Mortar of specified m ix using the type of sand described in t he item shall be used, w here c oarse
sand is to be used, the fineness modulus of the sand shall not be less than 2.5 mm.
13.7.4 Application
13.7.4.1 The plaster base over which rough cast finish is to be applied shall consist of two coats, under
layer 12 mm thick and top layer 10 mm.
13.7.4.2 12 mm Under Layer : This shall be applied in the same manner as specified in para 13.1.3
under 18 mm cement plaster except that the finishing, after the mortar has been brought to a level with
the wooden straight edge, shall be done with wooden float only.
13.7.4.3 Top Layer : The top layer shall be a pplied a d ay or t wo after the un der layer has taken initial
set. The latter shall not be al lowed to dry out, before the top layer is laid on. The mortar used for
applying top layer shall be s ufficiently plastic an d of rich mix 1 : 3 ( 1 cement : 3 f ine sand) or a s
otherwise specified so that the mix of sand and gravel gets well pitched with the plaster surface. In order to
make th e ba se p lastic, ab out 1 0% of fin ely grouted hy drated lim e by v olume o f ce ment, s hall b e
added when preparing mortar for the top layer.
12 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
13.7.5 Finish
It s hall b e ens ured t hat t he bas e s urface w hich i s t o r eceive r ough c ast m ixture i s i n pl astic s tate. T he
rough cast mixture shall consist of sand or gravel or crushed stone of uniform colour from 2.36 mm to
12.5 mm or as specified and in the proportions as specified ac curately t o the effect required. The mixture
shall be wetted and shall be dashed on the plaster base in plastic state by hand scoop so that the mix
get well pitched into the plaster base. The mix shall again be dashed over the vacant spaces if any so
that the surface represents a homogeneous surfaces of sand mixed with gravel. A sample of rough cast
plaster shall be got approved by the Engineer-in-Charge.
13.7.6 Specification for o ther de tails like pr ecautions, m easurement a nd r ate s hall be as des cribed
under 13.1.
13.8.1 The s pecification s hall be the s ame a s f or r ough c ast pl aster, e xcept t hat t he washed pe bble or
crushed stone g raded from 12.5 m m to 6.3 mm or as specified shall be das hed over the plaster bas e
and t he vacant spaces if any shall be filled i n by pressing pebbles or crushed stone as s pecified b y
hand, so that the finished surface represents a homogeneous surface.
13.8.2 Specification for s caffolding, p reparation of surface, M ortar, Measurements and R ate s hall be as
described under 13.7.
13.9.0 ‘Plain b and’ i s a plaster s trip of uni form w idth n ot ex ceeding 30 c m an d of uni form t hickness,
provided f or decorative or ot her purpose f lush w ith, s unk bel ow or projecting beyond, t he w all pl aster. A
flush b and is o ne where due to the difference in mix o r shade of the mortar, the b and is e xecuted a s a
separate and distinct operation from the wall plaster.
13.9.1 Thickness
The thickness of a raised band is the thickness of the projection beyond the plane of the wall plaster.
In the c ase of a f lush o r a s unk b and, the thickness will b e the t hickness o f the plaster m easured
from the untreated wall surface.
13.9.2.1 In the case of flush or s unk bands the joints shall be raked out properly. Dust and loose mortar
shall be brus hed out . E fflorescence i f any s hall be removed by brushing t he s craping. T he s urface s hall
then be thoroughly washed with water, cleaned and kept wet before plastering is commenced.
In c ase of c oncrete s urface i f a c hemical retarder has b een ap plied t o t he f orm w ork, t he s urface
shall be ro ughened by wire brus hing and al l t he res ulting du st and l oose p articles c leaned of f and care
shall be taken that none of the retarders is left on the surface.
13.9.2.2 In case of raised band, the surface shall be prepared as specified in 13.1.4. The surface of the
wall pl aster behi nd t he band s hall be left rough and furrowed 2 m m deep with a scratching tool,
diagonally bot h ways t o form key for the band. No reduction in the rate for the above bac king wall pl aster
shall, however, be made for not finishing the same smooth.
13.9.3 Mortar
Mortar of the mix and type of sand specified in the description of the item shall be used.
13 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
13.9.4 Finish
The band s s hall be finished ex actly t o t he size as shown i n t he draw ings. T he hori zontal or vertical
lines of bands s hall b e t ruly p arallel a nd straight an d t he su rfaces s hall be finished tr uly plane a nd
smooth. The lines and surfaces shall be checked with fine threads for straightness, level and accuracy.
13.9.6 Measurements
Length w ill be m easured in r unning m etres c orrect to a c m. T he length s hall be taken a long the
finished face. T he width shall not b e m easured b y girth. For width of b and 30 c m or below, the width
shall be measured in cm correct to 5 mm. The quantity shall be calculated in metre-cm units.
13.9.7 Rate
The r ate shall i nclude t he c ost of all l abour a nd materials i nvolved i n al l t he operations described
above. Nothing extra shall be paid f or mitres, s tops nor for bands on c urved surfaces of whatever radius,
they may b e. The r ate is als o i nclusive of al l r ounding or chamfering a t c orners, a rrisers, providing
grooves at junctions etc.
13.10.0 Moulded band i s a pl aster s trip of uni form w idth but w ith v arying t hickness ac ross i ts s ection
formed over w all pl aster for d ecorative p urposes. The s ectional p eriphery of t he b and i s f ormed b y a
combination of straight lines or of curves or of straight lines and curves.
13.10.1 Thickness
The hi gher t hickness stipulated in the de scription of the i tem shall refer t o the upper l imiting
thickness of the moulding at its most projected portion, measured from the wall plaster.
13.10.2 Preparation of Surface, Mortar, Scaffolding, Curing and Precautions shall be as specified under
13.9.
13.10.4 Measurements
The width of the band 3 0 cm or below shall be m easured in cm correct to 5 m m and s hall be
measured along the sectional periphery of the moulded band, from wall plaster face to wall plaster face.
The length shall be measured, in running metres correct to a cm. It shall be taken along the finished face of
the band at the centre of its girth. The quantity should be calculated in metre-cm units.
13.10.5 Rate
The r ate shall i nclude t he c ost of all l abour a nd materials i nvolved i n al l t he operations described
above. Nothing extra shall be paid f or mitres, s tops nor for bands on c urved surfaces of whatever radius,
they may be. The rate is also inclusive of all rounding or chamfering at corners, arrisers etc.
13.11.0 Moulded band i s a pl aster s trip of uni form w idth but w ith v arying t hickness ac ross i ts s ection
formed over w all pl aster for d ecorative p urposes. The s ectional p eriphery of t he b and i s f ormed b y a
combination of straight lines or of curves or of straight lines and curves.
14 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
13.11.1 Thickness
The hi gher t hickness s tipulated f or t he un der c oat i n the d escription of t he i tem s hall r efer t o t he up per
limiting thickness of the under coat of the moulding at its most projected portion from the wall plaster.
The thickness stipulated for the finishing coat is the uniform thickness of the finished peripheral
surface of the moulded band from the under coat.
13.11.2 Mortar
The under coat shall consist of cement mortar 1 : 5 (1 cement : 5 coarse sand) and the top coat shall
be of cement mortar 1 : 4 (1 cement : 4 fine sand) unless otherwise specified in the description of item.
13.12.0 It shall be used for cement mortar for plastering or concrete work.
13.12.2 The contractor shall bring the materials to the site in their original packing. The containers will be
opened and the material mixed with dry cement in the proportion by weight, recommended by the
manufacturers o r as specifically des cribed in t he des cription o f the i tem. C are shall be t aken in mixing, t o
see that the water proofing material gets well and i ntegrally mixed with the cement and does not run out
separately when water is added.
13.12.4 The rate s hall include the c ost of all labour and materials involved in all the operations des cribed
above.
Raked
A. FLUSH
V. Joint
Thumb
B. RAISED & CUT
Struck Stripped
Weathered Beaded
15 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
13.13.1 Scaffolding
For al l e xposed br ick w ork, tile work o r s tone work i ndependent doubl e scaffolding hav ing two sets o f
vertical supports shall be provided. The supports shall be s ound and strong t ied t ogether w ith horizontal
pieces over which scaffolding planks shall be fixed.
For a ll ot her w ork in bu ilding, s ingle s caffolding shall be p ermitted. I n such c ases, the inner end of
the horizontal scaffolding pole shall rest in a hol e provided only in the head er course for the pu rpose.
Only one header for each pole shall be left out . Such hol es for scaffolding shall, however, not be al lowed
in pillars/columns l ess than one metre in width, or immediately near the skew backs of arches. The holes
left in masonry works for scaffolding purposes shall be filled and made good before plastering.
Note : In case of s pecial type of work, s caffolding shall be got ap proved from E ngineer-in-Charge i n
advance.
In c ase of c oncrete s urface i f a c hemical retarder has b een ap plied t o t he f orm w ork, t he s urface
shall be ro ughened by wire brus hing and al l t he res ulting du st and l oose p articles c leaned of f and care
shall be taken that none of the retarders is left on the surface.
The joints shall be ra ked to such a d epth that the m inimum depth of the ne w mortar measured from
either the sunk surface of the finished pointing or from the edge of the brick shall not be less than 12 mm.
13.13.3 Mortar
Mortar of specified mix shall be used. It shall be as specified under Chapter 3.0.
13.13.4.1 The mortar shall be pressed into the raked out joints, with a pointing trowel, either flush, sunk
or raised, according to the type of pointing required. The mortar shall not spread over the corner, edges
or surface of the masonry. The pointing shall then be finished with the proper tool, in the manner
described below:
13.13.4.2 Flush Pointing : The mortar shall be p ressed i nto the joints and shall be finished of f flush an d
level with the edges of the bricks, tiles or stones so as to gi ve a smooth appearance. The edges shall be
neatly trimmed with a trowel and straight edge.
13.13.4.3 Ruled Pointing : The j oints s hall be i nitially f ormed as for f lush pointing and t hen while the
mortar is still gree n, a gro ove of shape an d size as shown in dra wings or as instructed, shall be f ormed
by running a forming tool, straight al ong t he c entre l ine o f the joints. This oper ation s hall be c ontinued t ill
a s mooth and har d s urface i s obt ained. T he v ertical j oints s hall al so be finished i n a s imilar w ay. T he
vertical l ines shall m ake t rue ri ght angles at t heir j unctions w ith t he horizontal l ines and s hall not project
beyond the same.
13.13.4.4 Cut or Weather Struck Pointing : The mortar shall first be pr essed into the joints. The top of
the horizontal joints shall then be neatly pressed back about 3 mm or as directed, with the pointing tool so
that the joints are sloping from top to bottom.
The vertical joints shall be ruled pointed. The junctions of vertical joints with the horizontal joints shall be
at true right angles.
16 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
13.13.4.5 Raised and Cut Pointing : Raised an d cut po inting s hall project f rom t he wall f acing w ith i ts
edges cut parallel so as to have a uniformly raised band about 6 mm raised and width 10 mm more as
directed.
13.13.4.6 The superfluous mortar shall then be cut off from the edges of the lines and t he surface of the
masonry shall also be cleaned off all mortar. The finish shall be such that the pointing is to the exact size
and shape required and the edges are straight, neat and clean.
13.13.5 Curing
The pointing shall be kept wet for seven days. During t his period it shall be suitably pr otected from all
damages.
The po inting lines s hall be truly ho rizontal and v ertical ex cept w here the j oints ar e s lanting a s in
rubble random m asonry. L ines o f j oints from d ifferent directions s hould m eet neatly at t he j unctions
instead of crossing beyond.
13.13.6 Measurements
13.13.6.1 Length and breadth shall be measured c orrect to a c m and its area shall be calculated i n
square metres upto two places of decimal.
13.13.6.2 The v arious types o f po inting for ex ample, s truck, k eyed, f lush, tuc k, e tc. s hall eac h be
measured separately.
13.13.6.3 Pointing on different types of walls, floors, roofs etc. shall each be measured separately. The
type and material of the surface to be pointed shall be described.
13.13.6.4 Pointing in a single detached joint as for flashing shall be given in running metres.
13.13.6.5 For jambs, soffits, s ills etc. for opening not exceeding 0.5 sqm eac h in area, ends of joists, b eams,
posts, girders, steps et c. not e xceeding 0 .5 sqm each in ar ea and opening not e xceeding 3 sqm each
deductions and additions shall be made in the following way, in case of pointing on external face only.
(a) N o deduc tion s hall be m ade for ends o f joists, bea ms, pos ts et c. and ope nings not e xceeding 0. 5
sqm each, and no addition shall be made for reveals, jambs, soffits, sills, etc. of these openings.
(b) D eductions for op enings ex ceeding 0.5 s qm but not exceeding 3 s qm each s hall be made as
follows and no additions shall be made for reveals, jambs, soffits, sills, etc. for these openings.
(c) W hen bot h t he f aces of t he w all are poi nted w ith t he s ame pointing dedu ction s hall be m ade f or
one face only.
(d) When two faces of wall are pointed with different pointings or if one face is plastered and other is
pointed or plastered, deduction shall be made from the plaster or pointing on the side of frames
for doors, windows, etc. on which the width of the reveal is less than that on the other side, but
no deduction shall be made from the other side.
(e) Where width of reveals on both faces of wall are equal, deduction of 50% of area of opening on
each face shall be made from area of pointing or plaster as the case may be.
(f) F or opening hav ing door f rame equal t o or projecting beyond t hickness of w all, f ull deduc tion f or
opening shall be made from each pointed face of wall.
13.13.6.6 In case of openings of area ab ove 3 s qm each, deduction shall be made for the openings, but
jambs, soffits and sills shall be measured.
17 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
(c) Raking out joints of different types of old walls, floors etc. shall each be measured separately.
(d) Raking single detached joints as for flashing old work shall be given in running metres.
13.13.7 Rate
The rate shall include the cost of all materials and labour involved in all the operations described above.
13.14.1 Scaffolding
13.14.1.1 Wherever s caffolding i s n ecessary, i t shall be e rected on double supports t ied t ogether by
horizontal pieces, over which scaffolding planks shall be fixed. No ballies, bamboos or planks shall rest on
or touch the surface which is being white washed.
13.14.1.2 For all exposed brick work or tile work, double scaffolding having two sets of vertical supports
shall be provided. T he supports shall b e s ound and strong, t ied t ogether with h orizontal pi eces over
which scaffolding planks shall be fixed.
Note : In case of special type of brick work, scaffolding shall be got approved from Engineer-in-Charge
in advance.
13.14.1.3 Where ladders are used, pieces of old gunny bags shall be tied on their tops to avoid damage or
scratches to walls.
13.14.1.4 For white washing the ceiling, proper stage scaffolding shall be erected.
In case of old work, all loose particles and scales shall be scrapped off and holes in plaster as well
as patches of less than 50 cm area shall be filled up with mortar of the same mix. Where so specifically
ordered b y t he E ngineer-in-Charge, t he ent ire s urface o f ol d white wash s hall be t horoughly r emoved by
scrapping and this shall b e paid f or s eparately. W here e fflorescence i s observed the deposits m ay be
brushed clean and washed. T he s urface shall t hen b e allowed t o dr y f or a tleast 48 h ours before white
washing is done.
13.14.3.1 The l ime wash s hall b e p repared from fresh stone white l ime The lime s hall be t horoughly
slaked on the spot, mixed and stirred with sufficient water to make a thin cream. This shall be allowed to
stand for a period of 24 hours and then shall be screened through a clean coarse cloth. 40 gm of gum
dissolved in hot water, shall be added to each 10 cubic dicimetre of the cream. The approximate quantity
of water to be added in making the cream will be 5 litres of water to one kg of lime.
13.14.3.2 Indigo (Neel) up to 3 gm per kg of l ime dissolved in water, shall then be added and s tirred well.
Water shall then be added at the rate of about 5 litres per kg. of lime to produce a milky solution.
13.14.4 Application
13.14.4.1 The w hite w ash s hall be appl ied w ith m oonj brushes t o t he s pecified num ber of c oats. T he
operation for each coat shall consist of a stroke of the brush given from the top downwards, another
18 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
from t he bo ttom upw ards ov er t he f irst s troke, and s imilarly one s troke hor izontally f rom t he r ight an d
another from the left before it dries.
13.14.4.2 Each c oat s hall be al lowed to dr y b efore the n ext on e i s ap plied. F urther e ach c oat s hall be
inspected and approved by the Engineer-in-Charge before the subsequent coat is applied. No portion of the
surface shall be left out initially to be patched up later on.
13.14.4.3 For new w ork, t hree or m ore c oats s hall be a pplied t ill t he s urface presents a s mooth and
uniform f inish t hrough which t he plaster d oes not s how. The f inished d ry surface s hall not show a ny
signs of cracking and peeling nor shall it come off readily on the hand when rubbed.
13.14.4.4 For old work, after the surface has been prepared as described in Para 13.14.2 a coat of white
wash shall be appl ied over the patches and repairs. Then a s ingle coat or two or m ore coats of white
wash as s tipulated in the description o f the item s hall be app lied ov er the e ntire s urface. T he w hite
washed s urface s hould present a uniform finish t hrough w hich the p laster pa tches d o n ot a ppear. The
washing on ceiling should be done prior to that on walls.
Note : In case of Hessian ceiling, on no account, lime shall be used as it rots cloth and hessian.
13.14.6 Measurements
13.14.6.1 Length a nd br eadth shall be m easured correct to a c m. an d ar ea s hall b e c alculated in s qm
correct to two places of decimals.
13.14.6.2 Measurements for Jambs, Soffits and Fills etc. for openings shall be as described in 13.1.9.
13.14.6.3 Corrugated s urfaces s hall be measured flat as fi xed an d th e a rea s o m easured s hall b e
increased by the following percentages to allow for the girthed area.
13.14.6.4 Cornices and o ther s uch w all or ceiling features, shall be m easured a long the g irth and
included in the measurements.
13.14.6.5 The number of coats of each treatment shall be stated. The item shall include removing nails,
making good holes, cracks, patches e tc. no t exceeding 50 sq. cm. each w ith material similar in
composition to the surface to be prepared.
13.14.6.6 Work on old treated surfaces shall be measured separately and so described.
13.14.7 Rate
The rate shall include all material and labour involved in all the operations described above.
13.15.0 Satna lime wash shall be us ed as a bas e coat where so specified. The specifications for ‘white
washing with lime’ shall apply except that Satna or Katni quality lime shall be used in place of Narnaul or
19 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
Dehradun or other q uality l ime and t he w ash w ill b e m ixed t o a thicker c onsistency. T he ot her
details and specifications described in 13.14 will apply in toto.
13.16.2 Other specifications described in 13.14 shall apply in this case also.
13.17.1 The m ineral colours, no t affected by lime, s hall be add ed to white w ash. Indigo ( Neel) s hall
however, not be added. No colour wash shall be done until a sample of the colour wash of the required
tint or s hade has been g ot approved f rom t he E ngineer-in-Charge. T he c olour s hall be of ev en t int or
shade over the whole surface. If it is blotchy or otherwise badly applied, it shall be redone by the
contractor.
For new work, the priming coat shall be of white wash with lime or with whiting as specified in the
description of the item. Two or more coats, shall then be applied on the entire surface till it represents a
smooth and uniform finish.
For old work, after the surface has been prepared as described in 13.14.2 a coat of colour wash shall be
applied ov er t he pat ches and r epairs. T hen a s ingle c oat, or two or more c oats of c olour w ash, a s
stipulated in the des cription o f the item s hall b e a pplied ov er the en tire s urface. T he c olour w ashed
surface shall present a uniform finish.
The finished dry surface shall not be powdery and shall not readily come off on the hand when rubbed.
13.18.1 Materials
Dry di stemper of r equired c olour ( IS 427) and of approved br and and m anufacture s hall be us ed.
The shade shall be got approved from the Engineer-in-Charge before application of the distemper. The dry
distemper colour as required shall be stirred slowly in clean water using 6 decilitres (0.6 litre) of water
per kg of distemper or as specified by the makers. Warm water shall preferably be used. It shall be allowed
to stand for at least 30 minutes (or if practicable over night) before use. The mixture shall be well stirred
before and during use to maintain an even consistency.
Distemper shall not be mixed in larger quantity than is actually required for one day’s work.
13.18.2.1 Before new w ork i s di stempered, t he s urface s hall be t horoughly br ushed f ree f rom m ortar
droppings and other foreign matter and sand papered smooth.
13.18.2.2 New plastered surfaces shall be allowed to dry completely, before applying, distemper.
20 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
13.18.2.3 In the case of old work, all loose pieces and scales shall be removed by sand papering. The
surface shall be cleaned of all grease, dirt, etc.
13.18.2.4 Pitting in plaster shall be made good with plaster of Paris mixed with the colour to be used.
The surface shall then be rubbed down again with a fine grade sand paper and made smooth. A coat of
the distemper shall be applied over the patches. The patched surface shall be allowed to dry thoroughly
before the regular coat of distemper is applied.
13.18.4 Application
13.18.4.1 In the case of ne w work, the treatment shall consist of a pr iming coat of whiting (As per 13.16)
followed by the application of two or more coats of distemper till the surface shows an even colour.
13.18.4.2 For old w ork, the surface prepared a s d escribed in p ara 13.14 s hall be a pplied on e or m ore
coats of distemper till the surface attains an even colour.
The entire surface shall be coated with the mixture uniformly, with proper distemper brushes
(ordinary w hite w ash br ushed s hall not be al lowed) i n hor izontal strokes followed immediately b y v ertical
ones which together shall constitute one coat.
13.18.4.4 The subsequent coats shall be applied only after the previous coat has dried.
13.18.4.5 The finished surface shall be even and uniform and shall show no brush marks.
13.18.4.6 Enough distemper shall be mixed to finish on e room at a time. T he ap plication of a c oat in
each room shall be f inished in one op eration and no work shall be s tarted in any room, which cannot be
completed the same day.
13.18.4.7 After each day’s work, the brushes s hall be w ashed in h ot w ater and hung d own t o dr y. O ld
brushes which are dirty or caked with distemper shall not be used.
13.18.5 The specifications in respect of scaffolding, protective measures, measurements and rate shall be
as described under 13.14.
13.19.1 Materials
Oil e mulsion ( Oil Bound) washable distemper (I S 4 28) of a pproved brand an d m anufacture shall b e
used. The primer where used as on new work shall be cement primer or distemper primer as described in
the item. These shall be of the same manufacture as distemper. The distemper shall be diluted with water
or an y other pre scribed thinner in a m anner recommended b y the manufacturer. O nly sufficient quantity
of distemper required for day’s work shall be prepared.
The di stemper and pr imer shall be brought b y t he contractor i n s ealed tins i n s ufficient quantities at a
time to suffice for a fortnight’s work, and the same shall be kept in the joint custody of the contractor and
21 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
the Engineer-in-Charge. T he empty tins shall not be removed from the site of work, till this item o f work
has been completed and passed by the Engineer-in-Charge.
13.19.2.1 For new w ork the s urface shall b e thoroughly cleaned of dust, o ld white or c olour wash by
washing a nd s crubbing. T he surface s hall t hen b e allowed t o dry f or a t l east 48 h ours. I t s hall t hen b e
sand papered t o gi ve a s mooth a nd e ven s urface. A ny unevenness s hall b e m ade g ood b y a pplying
putty, made of pl aster of paris mixed w ith water on t he ent ire s urface i ncluding f illing up t he undulations
and then sand papering the same after it is dry.
13.19.2.2 In the case of old work, all loose pieces and scales shall be removed by sand papering. The
surface shall be cleaned of all grease, dirt etc.
Pitting in p laster s hall be made good w ith p laster o f p aris mixed w ith the c olour to be us ed. T he
surface shall then be rub bed down again with a f ine grade s and paper and made smooth. A coat o f the
distemper s hall be a pplied ov er t he p atches. T he pat ched s urface s hall b e al lowed t o dr y t horoughly
before the regular coat of distemper is applied.
13.19.3 Application
13.19.3.1 Priming Coat : The pr iming c oat shall be w ith di stemper pr imer or c ement p rimer, as required
in the description of the item. The application of the distemper primer shall be as described in 13.18.4.
Note : If the wall surface plaster has not dried completely, cement primer shall be applied before
distempering the walls. But if distempering is done after the wall surface is dried completely,
distemper primer shall be applied.
Oil bound d istemper i s no t rec ommended t o be ap plied, w ithin s ix m onths o f t he c ompletion of w all
plaster. H owever, ne wly p lastered s urfaces i f requi red t o be distempered bef ore a period of six m onths
shall be given a coat of alkali resistant priming Paint conforming to IS 109 and allowed to dry for atleast
48 hours before distempering is commenced.
13.19.3.2 Distemper Coat : For new work, after the primer coat has dried for at least 48 hours, the surface
shall be lightly sand papered to make it smooth for receiving the distemper, taking care not to rub out the
priming c oat. A ll l oose particles s hall be dus ted of f after rubbing. O ne c oat of di stemper properly di luted
with t hinner (water o r other l iquid as s tipulated by the m anufacturer) s hall be a pplied w ith b rushes i n
horizontal strokes followed immediately by vertical ones which together constitutes one coat.
The s ubsequent coats shall be applied i n t he same w ay. T wo o r m ore c oats of di stemper a s a re
found necessary shall be applied over the primer coat to obtain an even shade.
A ti me in terval of at le ast 2 4 h ours shall be all owed between s uccessive coats to permit p roper
drying of the preceding coat.
For ol d work t he distemper s hall be applied over the prepared surface in the s ame manner as in new
work. O ne or m ore coats of distemper as are found necessary shall be app lied to obtain an ev en and
uniform shade.
15 c m doubl e bri stled di stemper br ushes s hall be us ed. A fter eac h day s work, br ushes s hall be
thoroughly washed in hot water with soap solution and hung down to dry. Old brushes which are dirty and
caked with distemper shall not be used on the work.
22 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
13.19.4 The specifications in r espect o f s caffolding, pr otective measures and m easurements s hall be as
described under 13.14.
13.19.5 Rate
The rate shall include the cost of all labour and materials involved in all the above operations
(including priming coat) described above.
13.20.0 Cement primer coat is used as a base coat on wall finish of cement, lime or lime cement plaster or
on n on-asbestos c ement s urfaces bef ore oi l em ulsion di stemper P aints are a pplied o n t hem. T he
cement pri mer i s c omposed of a m edium and pi gment w hich are res istant t o t he al kalies pres ent i n t he
cement, lime or lime cement in wall finish and provides a barrier for the protection of subsequent coats of
oil emulsion distemper Paints.
Primer c oat s hall be pr eferably appl ied by br ushing and not by s praying. H urried pr iming s hall be
avoided particularly on ab sorbent s urfaces. N ew pl aster pat ches i n ol d w ork should al so be t reated w ith
cement primer before applying oil emulsion Paints etc.
13.20.2 Application
The c ement primer s hall be appl ied w ith a br ush on t he c lean d ry and s mooth s urface. H orizontal
strokes s hall be g iven first a nd v ertical s trokes s hall b e ap plied immediately af terwards. T his e ntire
operation w ill c onstitute one c oat. T he s urface s hall be finished a s un iformly as p ossible leaving no
brush marks. It shall be allowed to dry for at least 48 hours, before oil emulsion Paint is applied.
13.20.3 The Specifications in respect of scaffolding, protective measures, measurements and rate shall be
as described under 13.1.4.
13.21.1 Material
The cement Paint shall be (conforming to IS 5410) of approved brand and manufacture.
The cement Paint shall be br ought to the site of work by the contractor in its original containers is
sealed c ondition. The material s hall be br ought in at a time in adequate quantities t o suffice for the whole
work or at least a f ortnight’s work. The materials shall be k ept in the joint custody of the Contractor an d
the E ngineer-in-Charge. The e mpty c ontainers s hall not be r emoved from the s ite o f w ork till t he relevant
item of the work has been completed and permission obtained from the Engineer-in-Charge.
23 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
water in two s tages. T he first stage s hall c omprise o f 2 pa rts o f cement P aint an d one part o f w ater
stirred t horoughly and all owed to stand for 5 m inutes. C are shall be taken to ad d the ce ment P aint
gradually to the water and not vice versa. The second stage shall comprise of adding further one part of
water t o t he mix a nd s tirring t horoughly t o o btain a l iquid of workable and uniform c onsistency. I n all
cases the manufacturer’s instructions shall be followed meticulously.
The l ids of c ement P aint dru ms s hall be kept ti ghtly closed w hen no t in use, as by e xposure t o
atmosphere the cement Paint rapidly becomes air set due to its hygroscopic qualities.
In c ase of cement P aint brought i n g unny b ags, once t he b ag i s opened, t he contents should be
consumed in full on the day of its opening. If the same is not likely to be consumed in full, the balance
quantity should be transferred and preserved in an airtight container to avoid its exposure to
atmosphere.
13.21.4 Application
13.21.4.1 The s olution s hall be app lied on the c lean and w etted s urface w ith brus hes o r s praying
machine. The solution s hall be kept w ell stirred dur ing the per iod o f application. It shall be appl ied on the
surface w hich is o n the s hady side of the building so that the direct h eat of the s un on the s urface is
avoided. T he m ethod of application of c ement P aint s hall be as per m anufacturer’s s pecification. T he
completed surface shall be watered after the day’s work.
13.21.4.2 The second coat shall be appl ied after the first coat has been set for at least 24 h ours. Before
application of the second or subsequent coats, the surface of the previous coat shall not be wetted.
13.21.4.3 For new work, the s urface shall be t reated with t hree or m ore c oats of w ater proof cement
Paint as found necessary to get a uniform shade.
13.21.4.4 For ol d work, the tr eatment s hall be with on e or m ore co ats a s fou nd n ecessary to g et a
uniform shade.
13.21.5 Precaution
Water proof cement Paint s hall n ot b e a pplied o n surfaces al ready t reated with w hite w ash, c olour
wash, di stemper dry or o il bo und, v arnishes, Paints et c. I t shall n ot b e a pplied on g ypsums, wood a nd
metal surfaces.
If w ater proof ing c ement i s requi red t o be appl ied on ex isting surface, prev iously treated w ith white
wash, c olour w ash et c., the s urface s hall be thoroughly c leaned by s crapping of f all the w hite wash,
colour w ash et c. c ompletely. T hereafter, a c oat o f c ement primer s hall be applied f ollowed by t wo or
more coat of water proof cement.
13.21.6 The specifications in respect of scaffolding, protective measures, measurements and rate shall be
as described under 13.14. The coefficient for cement Paint on RCC Jalli shall be the same as
provided in Sl. No. 7 of Table 1 under para 13.23.6.4 for painting trellis for Jaffri work.
13.22.1 Material
The pa int s hall be ( Textured ex terior p aint/Acrylic s mooth ex terior pa int/premium ac rylic s mooth
exterior paint) of approved brand and manufacture.
This pai nt s hall be br ought t o t he s ite of w ork by t he c ontractor i n i ts original c ontainers i n s ealed
condition. T he material shall be bro ught in at a t ime in adequate quantities to suffice for the whole work
or at least a fortnight’s work. The materials shall be kept in the joint custody of the contractor and the
24 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
Engineer-in-Charge. T he empty c ontainers s hall n ot be r emoved f rom t he site of w ork t ill t he relevant
item of work has been completed and permission obtained from the Engineer-in-Charge.
13.22.3 Application
Base coat of water proofing cement paint
13.22.3.1 All specifications in respect of base coat of water proofing cement paint shall be as described
under 13.21.
13.22.3.2 Before pour ing into s maller c ontainers for us e, the pa int s hall be s tirred thoroughly in its
container, w hen appl ying also t he paint s hall be c ontinuously stirred i n t he smaller c ontainers s o that its
consistency is kept uniform. Dilution ratio of paint with potable water can be altered taking into
consideration the nature of surface c limate and as per recommended dilution gi ven by m anufacturer. In
all cases, the manufacturer’s instructions & directions of the Engineer-in-charge shall be followed
meticulously.
The lids of paint drums shall be kept tightly closed when not in use as by exposure to atmosphere the
paint may thicken and also be kept safe from dust.
13.22.3.3 Paint s hall b e ap plied with a br ush o n t he cleaned and s mooth surface. Horizontal strokes
shall be given, F irst an d vertical s trokes s hall b e a pplied i mmediately afterwards. T his ent ire operat ion
will constitute one coat. The surface shall be finished as uniformly as possible leaving no brush marks.
13.22.4 The specifications in respect of scaffolding, protective measures, measurements and rate shall be
as described under 13.14.
13.23 PAINTING
13.23.1 Materials
Paints, oils, varnishes etc. of approved brand and manufacture shall be used. Only ready mixed
Paint (Exterior grade) as received from the manufacturer without any admixture shall be used.
If for a ny reason, t hinning is necessary in c ase o f ready m ixed P aint, the brand of thinner
recommended by the manufacturer or as instructed by the Engineer-in-Charge shall be used.
Approved Paints, o il or varnishes s hall b e br ought t o t he s ite of w ork b y t he c ontractor i n t heir original
containers i n sealed c ondition. The material s hall be brought i n at a time in ad equate quant ities t o suffice
for the whole work or at least a fortnight’s work. The materials shall be kept in the joint custody of the
contractor and t he Engineer-in-Charge. T he em pties s hall not be rem oved f rom t he s ite of w ork, t ill t he
relevant item of work has been completed and permission obtained from the Engineer-in-Charge.
Painting, ex cept t he p riming c oat, s hall generally b e t aken i n ha nd af ter practically f inishing al l ot her
building work.
25 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
The rooms should be thoroughly swept out and the entire building cleaned up, at least one day in
advance of the Paint work being started.
13.23.4 Application
13.23.4.1 Before p ouring i nto s maller c ontainers for u se, t he P aint s hall be stirred t horoughly in i ts
containers, when applying also, the Paint shall be continuously stirred in the smaller containers so that its
consistency is kept uniform.
13.23.4.2 The pai nting s hall be l aid on ev enly and s moothly by m eans of crossing and l aying of f, the
latter i n the direction of t he grains of wood. T he crossing and l aying off c onsists of c overing t he area
over with P aint, br ushing t he s urface har d for t he first time ov er and t hen br ushing al ternately i n oppos ite
direction, two or t hree times and t hen finally brushing lightly in a di rection at right angles to the same. In
this process, no brush marks shall be left after the laying off is finished. The full process of crossing and
laying off will constitute one coat.
13.23.4.3 Where so stipulated, the painting shall be done b y spraying. Spray machine used may be (a)
high pr essure ( small a ir aperture) type, or ( b) a low pr essure (large a ir gap ) type, d epending on the
nature a nd l ocation of w ork to be c arried ou t. S killed a nd experienced w orkmen s hall b e em ployed f or
this class of work. Paints used shall be brought to the requisite consistency by adding a suitable thinner.
13.23.4.4 Spraying should be done only when dry condition prevails. Each coat shall be allowed to dry
out thoroughly and r ubbed smooth be fore t he nex t coat i s appl ied. This should be facilitated b y t horough
ventilation. Each c oat ex cept t he l ast c oat, s hall be l ightly rubbe d dow n w ith sand paper or f ine pum ice
stone and cleaned off dust before the next coat is laid.
13.23.4.5 No left over Paint shall be put back into the stock tins. When not in use, the containers shall be
kept properly closed.
13.23.4.6 No ha ir marks from the brush or c logging of Paint pu ddles in the corners of panels, angles of
mouldings etc. shall be left on the work.
13.23.4.7 In painting doors and windows, the putty round the glass panes must also be painted but care
must be t aken t o see t hat no P aint s tains etc. a re l eft on t he glass. T ops of s hutters a nd surfaces i n
similar hidden locations shall not be l eft out in painting. However, bottom edge of the shutters where the
painting is not practically possible, need not be done nor any deduction on this account will be done but
two coats of primer of approved make shall be done on the bottom edge before fixing the shutters.
13.23.4.8 On painting st eel w ork, s pecial c are s hall b e t aken w hile p ainting ov er b olts, nuts, rivets
overlaps etc.
13.23.4.9 The additional specifications for primer a nd other coats of Paints shall be as according to the
detailed specifications under the respective headings.
26 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
safe from dust. When the Paint has been used, the containers shall be washed with turpentine and wiped dry
with soft clean cloth, so that they are clean, and can be used again.
13.23.6 Measurements
13.23.6.1 The l ength and br eadth s hall be measured c orrect t o a c m. T he area s hall be c alculated in
sqm (correct to two places of decimal), except otherwise stated.
13.23.6.2 Small articles no t e xceeding 1 0 sq. dec imetre ( 0.1 sqm) o f painted s urfaces where no t i n
conjunction with similar painted work shall be enumerated.
13.23.6.3 Painting u pto 1 0 cm in width or in girth and not in conjunction with similar p ainted work shall
be given in running metres and shall include cutting to line where so required.
Note : Components of trusses, compound girders, stanchions, lattices and similar work shall, however,
be given in sq. metres irrespective of the size or girth of members. Priming coat of painting shall
be included in the work of fabrication.
13.23.6.4 In m easuring painting, v arnishing, oi ling etc. of j oinery and s teel work et c. T he c oefficients as
indicated in following tables shall be used to obtain the area payable. The coefficients shall be applied to the
areas measured flat and not girthed.
TABLE 13.1
Equivalent Plain Areas of Uneven Surface
S. Description of work How measured Multiplying
No. coefficients
1 2 3 4
I. Wood work doors, windows Etc.
1. Panelled or framed and braced Measured flat (not girthed including) 1.30 (for each side)
doors, windows etc.
2. Ledged and battened or ledged, Chowkhat or frame, Edges, chocks, - do -
battened and braced doors, cleats, et c. shall be dee med to be
windows etc. included in the item.
3. Flush doors etc. -do- 1.20 (for each side)
4. Part panelled and part glazed or -do- 1.00 (for each side)
gauzed doors, window etc.
(Excluding painting of
wire gauze portion)
5. Fully glazed or gauzed doors, -do- 0.80 (for each side)
windows et c. ( Excluding painting
of wire gauze portion)
6. Fully venetioned or louvered -do- 1.80 (for each side)
doors, windows etc.
7. Trellis (or Jaffri) work one way or Measured flat overall, no deduction 2 (for painting all over)
two way shall be m ade f or ope n s paces, s up-
porting members shall not be mea-
sured separately
8. Carved or enriched work Measured flat 2 (for each side)
9. Weather boarding Measured flat (not girthed supporting 1.20 (for each side)
frame work shall not be measured
separately
10. Wood shingle roofing Measured flat (not girthed) 1.10 (for each side)
27 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
1 2 3 4
11. Boarding with cover fillets Measured flat (not girthed) 1.05 (for each side)
and match boarding
12. Tile and slate battening Measured flat overall no deductions 0.80 (for painting
shall be made for open spaces all over)
III. General
19. Expanded metal, hard drawn Measured flat overall; no deduction 1 ( for P aint al l o ver)
steel wire fabric of approved shall be made for open spaces;
quality, grill works and gratings supporting members shall not be
in guard bars, balustrades, railing measured separately
partitions and MS Bars in
windows frames.
20. O pen pal isade f encing and -do- 1 ( for P aint all o ver)
gates including standards, (see note No. 12)
braces, rails stays etc. in timber or
steel
21. C orrugated i ron s heeting i n -do- Measured flat (not girthed) 1.14 (for each side)
roofs, side cladding etc.
22. AC c orrugated s heeting in roofs, -do- 1.20 (for each side)
side cladding etc.
23. AC s emi c orrugated s heeting in
roofs, side cladding etc. or -do- 1.10 (for each side)
Nainital pattern using plain sheets
24. Wire gauze shutters including -do- 1.00 (for each side)
painting of wire gauze
28 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
(3) T he coefficients f or d oor and windows s hall apply i rrespective o f t he size of f rames a nd shutter
members.
(4) In c ase s teel f rames ar e used the area of doors, windows s hutters shall b e measured flat
excluding frames.
(5) When the two faces of a door, window etc. are to be treated with different specified finishes,
measurable under separate items, the edges of frames and shutters shall be treated with the one
or the other type of finish as ordered by the Engineer-in-Charge and measurement of this will be
deemed to be included in the measurement of the face treated with that finish.
(6) In the case where shutters are fixed on both faces of the frames, the measurement for the door
frame and shutter on one face shall be taken in the manner already described, while the
additional shutter on the other face will be measured for the shutter only excluding the frame.
(7) Where shutters are provided with clearance at top or/and bottom each exceeding 15 cm height,
such openings shall be deducted from the overall measurements and relevant coefficient shall be
applied to obtain the area payable.
(8) Collapsible gates shall be measured for width from outside to outside of gate in its expanded
position and for height from bottom to top of channel verticals. No separate measurements shall
be taken for the top and bottom guide rails rollers, fittings etc.
(9) Coefficients for sliding doors shall be the same as for normal types of doors in the table.
Measurements shall be taken outside to outside of shutters, and no separate measurements
shall be taken for the painting guide rails, rollers, fittings etc.
(10) M easurements of p ainting as a bove s hall b e d eemed t o include pa inting all i ron fittings in the
same or different shade for which no extra will be paid.
(11)The measurements of guard bars, expanded metal, hard drawn steel wire fabric of approved
quality, grill work and gratings, when fixed in frame work, painting of which is once measured
else where shall be taken exclusive of the frames. In other cases the measurements shall be
taken inclusive of the frames.
(12) For painting open palisade fencing and gates etc., the height shall be measured from the bottom
of the lowest rail, if the palisades do not go below it, (or from the lower end of the palisades, if
they project below the lowest rail), upto the top of rails or palisades whichever are higher, but not
up to the top of standards when the latter are higher than the top rails or the palisades.
13.23.6.5 Width of m oulded w ork of al l ot her k inds, as i n hand rai ls, c ornices, arc hitraves s hall b e
measured by girth.
13.23.6.6 For trusses, compound girders, stanchions, lattice girders, and similar work, actual areas will be
measured in sq. metre and no extra shall be paid for painting on bolt heads, nuts, washers etc. even when
they are picked out in a different tint to the adjacent work.
13.23.6.7 Painting of r ain w ater, s oil, w aste, vent an d water pipes et c. s hall b e m easured i n running
metres of the particular diameter of the pipe concerned. Painting of specials such as bends, heads,
branches, j unctions, s hoes, et c. shall b e i ncluded i n t he l ength and n o s eparate m easurements s hall be
taken for these or for painting brackets, clamps etc.
13.23.6.8 Measurements of w all s urfaces and w ood a nd o ther w ork n ot r eferred to al ready s hall be
recorded as per actual.
13.23.6.9 Flag st affs, st eel c himneys, a erial m asts, spires and ot her su ch ob jects r equiring special
scaffolding shall be measured separately.
13.23.7 Precautions
All furniture, fixtures, glazing, floors etc. shall be protected by covering and stains, smears, splashing, if any
shall be removed and any damages done shall be made good by the contractor at his cost.
29 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
13.23.8 Rate
Rates s hall i nclude c ost of al l l abour and m aterials i nvolved i n al l t he oper ations des cribed abov e
and in the particular specifications given under the several items.
13.24.1 Primer
13.24.1.1 The p rimer for w ood w ork, iron work or pl astered surface shall be as specified in t he
description of item.
13.24.1.2 Primer for plaster/wood work/Iron & Steel/Aluminium surfaces shall be as specified below:
TABLE 13.2
13.24.1.3 The primer shall be ready mixed primer of approved brand and manufacture.
13.24.1.4 Where primer for wood work is specified to be mixed at site, it shall be prepared from a
mixture of red lead, white lead and double boiled linseed oil in the ratio of 0.7 kg : 0.7 kg : 1 litre.
13.24.1.5 Where primer for steel work is specified to be mixed at site, it shall be prepared from a mixture of
red lead, raw linseed oil and turpentine in the ratio of 2.8 kg : 1 litre : 1 litre.
13.24.1.6 The specifications for the base vehicle and thinner for mixed on site primer shall be as follows:
(a) White Lead : The White lead shall be pur e an d free from adulterants like barium sulphate and
whiting. It shall conform to IS 103.
(b) Red Lead : This shall be i n powder form and s hall be pur e and f ree from adulterants like brick
dust etc. It shall conform to IS 102.
(c) Raw Linseed Oil : Raw linseed oil shall be lightly viscous but clear and of yellowish colour with light
brown tinge. Its specific gravity at a temperature of 30 degree C shall be between 0.923 and 0.928.
Note : The oil shall be mellow and sweet to the taste with very little smell. The oil shall be of
sufficiently matured quality. Oil turbid or thick, with acid and bitter taste and rancid odour
and which remains sticky for a considerable time shall be rejected. The oil shall conform
in all respects to IS 75. The oil shall be of approved brand and manufacture.
(d) Double Boiled Linseed Oil : This shall be more viscous than the raw oil, have a deeper colour
and specific gravity between 0.931 and 0.945 at a temperature of 30 degree C. It shall dry with a
glossy surface. It shall conform in all respects to IS 77. The oil shall be of approved brand and
manufacture.
30 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
Turpentine : Mineral turpentine i.e. pe troleum d istillate w hich h as the s ame r ate o f evaporation as
vegetable t urpentine (di stillate product of ol eeresin of c onifers) s hall be us ed. I t s hall hav e no greas e or
other residue when allowed to evaporate. It shall conform to IS 533.
13.24.1.7 All t he abo ve materials s hall be o f appr oved m anufacture and br ought t o site i n t heir or iginal
packing in sealed condition.
13.24.2.1 Wooden Surface : The wood work to be painted shall be dry and free from moisture.
The s urface s hall be t horoughly c leaned. A ll unev enness s hall be r ubbed down s mooth w ith s and
paper and s hall be w ell d usted. K nots, if any s hall be c overed with preparation of red lead m ade by
grinding r ed l ead i n w ater an d m ixing w ith strong gl ue s ized a nd us ed hot. A ppropriate f iller m aterial
conforming t o I S 34 5 w ith s ame s hade a s P aint s hall be us ed where s pecified. T he s urface t reated f or
knotting s hall be dr y bef ore P aint i s appl ied. A fter obtaining appr oval of E ngineer-in-Charge f or w ood
work, the priming coat shall be applied before the wood work is fixed in position. After the priming coat is
applied, t he ho les and i ndentation on t he s urface shall be s topped w ith gl azier’s put ty or w ood putty.
Stopping shall not be done before the priming coat is applied as the wood will absorb the oil in stopping
and the latter is therefore liable to crack.
13.24.2.2 Iron & Steel Surface : All rus t and scales s hall be removed by s crapping or by brushing w ith
steel wire brushes. Hard skin of oxide formed on t he surface of wrought iron during rolling which
becomes loose by rusting, shall be removed.
All dust and dirt shall be thoroughly wiped away from the surface.
13.24.2.3 Plastered Surface : The s urface s hall o rdinarily not be pai nted u ntil i t has dri ed c ompletely.
Trial p atches of primer shall be laid at i ntervals an d w here dr ying i s satisfactory, p ainting shall then b e
taken i n hand. B efore p rimer is appl ied, hol es and undulations, shall be filled up w ith pl aster o f par is and
rubbed smooth.
13.24.3 Application
The pr imer s hall be appl ied with br ushes, worked w ell i nto t he surface and s pread ev en and s mooth.
The painting shall be done by crossing and laying off as described in 13.22.3.3.
13.24.4.1 A s econd coat o f ready m ixed red o xide zinc c hromate primer may be ap plied w here c onsi-
dered nec essary i n aggr essive env ironment s uch a s near I ndustrial E stablishment a nd C oastal r egions
where the s teel m embers are prone to corrosion. T he s econd c oat ( which shall be paid f or s eparately) is
to be appl ied af ter pl acing t he m ember i n pos ition and j ust bef ore appl ying P aint. T he s econd c oat of
primer i s not nec essary i n c ase of pai nting w ith synthetic enam el P aint as it is appl ied ov er an und er
coat of ordinary Paint.
13.24.4.2 The specifications described under 13.33 shall hold good so far as they are applicable.
31 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
13.25.1 Preparation of Surface
13.25.1.1 Painting New Surface : The p ainting of ne w G .S. s heets s hall not u sually be d one t ill t he
sheets have weathered for a bout a year. When ne w sheets ar e to be pai nted before they ha ve
weathered they s hall be treated with a mordant solution prepared by mixing 38 gm of copper acetate in a
litre of s oft w ater o r 1 3 g m h ydrochloric a cid in a s olution of 1 3 gm eac h of copper c hloride, c opper
nitrate and am monium c hloride di ssolved i n a l itre of s oft w ater. T his quant ity of s olution i s s ufficient f or
about 235 sqm. to 280 sqm of area and is applied for ensuring proper adhesion of P aint. T he painting
with the mordant solution will be paid for separately.
Before pai nting on ne w or weathered G .S. s heets, rust patches s hall be c ompletely c leaned with
coarse em ery pa per and brush. A ll grease m arks shall al so be r emoved and t he s urface w ashed an d
dried and rus ted s urface shall be t ouched w ith s ynthetic ena mel p aint of a pproved brand, m anufacturer
and shade.
13.25.1.2 Painting Old Surface: If the old Paint is firm and sound, it shall be cleaned of grease, smoke
etc. The surface shall then be rubbed down with sand paper and dusted. Rusty patches shall be cleaned up
and touched with synthetic enamel paint.
If t he ol d Paint i s blistered an d f laked, i t shall be c ompletely r emoved as des cribed i n 13 .41. Such
removal shall be paid for separately and painting shall be treated as on new work.
13.25.2 Application
The num ber of c oats t o be appl ied s hall b e as i n t he des cription of i tem. I n t he c ase of C .G.S. s heets,
the crowns of the corrugations shall be painted first and when these get dried the general coat shall be
given to ensure uniform finish over the entire surface without the crowns showing signs of thinning.
The second or additional coats shall be applied when the previous coat has dried.
13.25.3 The specifications described in 13.23 shall hold good so far as they are applicable.
13.26 PAINTING CAST IRON RAIN WATER, SOIL, WASTE AND VENT PIPES AND FITTINGS
13.26.1 The primer shall be pr epared on s ite or shall be of approved brand and m anufacture a s
specified in the item.
Paint shall be anti-corrosive bitumastic Paint, aluminium Paint or other type of Paint as specified in the
description of the item.
13.26.2.1 Preparation of Surface : The surface shall be prepared for priming coat as described in
13.24.2.2.
13.26.2.2 Application : The n umber o f c oat of p ainting o ver t he p riming c oat s hall be as stipulated i n
the description of the item. The application of Paint over priming coat shall be carried out as specified in
13.25.
13.26.2.3 Measurements : Measurements w ill be t aken o ver t he f inished l ine of pipe i ncluding s pecials
etc. in running metres, correct to a cm.
Pipes of different diameters of bore shall be measured and paid for separately.
Specials and fittings such as holder bat clamps, plugs etc. will not be measured separately.
32 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
13.26.2.4 Rate : The rate shall include the cost of all materials and labour involved in all the operations
described above, including painting of all specials and fittings.
13.26.2.5 Specifications described in 13.22 shall hold good as far as they are applicable.
13.27.1 Oil type wood preservative of specified quality and approved make, conforming to IS 218 shall be
used. Generally, it shall be creosote oil type-I or anthracene oil.
13.27.2.1 Preparation of Surface : Painting shall b e done o nly w hen t he surface i s p erfectly d ry t o
permit of good absorption. All dirt, dust or other foreign matter shall be removed from the surface to be
painted. All roughness shall be sand papered and cleaned.
13.27.2.2 Application : The preservative shall be appl ied liberally with a s tout brush and not daube d
with rags or cotton waste. It shall be applied with a pencil brush at the joints of the wood work. The first
coat shall be allowed at least 24 h ours to s oak in befo re th e se cond (t he f inal) co at is ap plied. The
second c oat shall b e applied in the s ame m anner as t he first coat. T he e xcess of p reservative which
does not soak into the wood shall be wiped off with a clean dry piece of cloth.
13.27.2.3 The specifications described in 13.23 shall hold good in so far as they are applicable.
13.28.1 Coal tar of approved manufacture conforming to IS 290 shall be used. The tar, to every litre of
which 2 00 g m of un slaked l ime ha s b een ad ded, s hall be h eated t ill i t begi ns t o b oil. I t m ust t hen b e
taken off the fire and kerosene oil added to it slowly at the rate of one part of kerosene oil to six or more
parts by volume and stirred thoroughly. The addition of lime is for preventing the tar from running.
13.28.2.1 Preparation of Surface : This shall be done as specified in 13.24.2 except that sand papering is
not necessary. Where iron work is to be painted it shall be free from scales and rust before painting.
13.28.2.2 Application : The mixture shall be applied as hot as possible with a brush. The second coat
shall be ap plied only after the first coat has thoroughly dried up. Where possible, the article to be t arred,
shall be dipped in the hot mixture for better results. The quantity of tar to be used for the first or second
coat shall be not less than 0.16 and 0.12 litre per sqm respectively. Thinning with kerosene oil shall be
suitably done to ensure this.
13.28.2.3 The specifications described in 13.23 shall hold good in all other respects, so far as they are applicable.
33 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
13.28.3 Coal Tarring old Surface
The work shall be done in the same manner as specified in 13.28.2 except that only one coat using
0.12 litre per sqm. area shall be done.
13.29.0 The work shall include a pr iming c oat of ‘Distempering Primer’ or ‘ Cement P rimer’ as specified in
the description of the item. F lat w all P aint shall normally be applied on w alls 12 m onths after their
completion, in which case Distemper primer will suffice. If the walls are to be painted earlier, the primer
coat shall consist of cement primer.
13.29.1 The primer and t he flat wall Paint shall be of approved brand and manufacture and o f the
required shade.
13.29.3 Application
13.29.3.1 Primer Coat : The specified primer shall be painted or sprayed over the surface in an even
and uniform layer.
13.29.3.2 Painting Coats : When t he s urface is dr y, the spray painting with the wall Paint in uniform and
even layers will be done t o the required num ber of coats. Each coat shall b e allowed to dry overnight
and lightly r ubbed with v ery fine grade of sand paper and loose particles br ushed off before the nex t coat
is sprayed.
Spraying s hould b e don e only when dr y c ondition pr evails. D uring s praying t he s pray gun s hall b e he ld
perpendicular t o t he s urface t o b e c oated and shall be p assed over the surface in a un iform s weeping
motion. Different air pressures and fan adjustment s hall be tried so as t o obtain the best application. The Air
pressure shall not be kept too high as otherwise the Paint will fog up and will be wasted.
At the end of the job, the spray gu n shall be cleaned thoroughly so a s to b e free from dirt. Incorrect
adjustments s hall be s et right, as ot herwise t hey w ill r esult in v ariable s pray pat terns, r uns, s ags a nd
uneven coats.
If after the final coat of wall Paints, the surface obtained is not upto the m ark, further one or m ore
coats as required s hall be given af ter r ubbing down the s urface an d du sting of f all loose particles t o
obtain a smooth and even finish.
If the pri mer or wall P aint gets t hickened during the application, i t s hall be t hinned suitably w ith the
thinner recommended by the manufacture.
Adequate v entilation s hall be p rovided t o di sperse spray fumes. F itments and f loor shall be p rotected
from the spray.
13.29.4 The specifications described in 13.23 shall hold good for all other details as far as applicable.
13.30.0 Where t he old Paint i s in sound c ondition, renewal s hall be c arried out as described below,
otherwise the old P aint s hall be completely s tripped and s pray painting s hall be c arried out as over new
work. Such removal shall be paid for separately.
13.30.1 The flat wall Paint shall be of approved brand and manufacture and of required shade.
34 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
13.30.2 Preparation of Surface
The surface shall be washed to remove dust and dirt. A mild detergent solution like soap water shall be
used for washing and the surface shall also be rubbed down lightly with abrasive paper when dry. Any
patches appearing on the surface shall first be touched up with a coat of Paint. These shall be allowed
to dry and then rubbed down lightly.
13.30.3 Application
The Paint shall then be applied with spraying machine in uniform and even layer. A second coat shall be
applied if considered necessary by the Engineer-in-Charge but only after the first coat is complete dry and hard.
Spraying should be don e o nly when dr y condition prevails. During s praying the s pray g un s hall b e
held pe rpendicular to t he s urface to be coated and shall be passed ov er t he s urface in uni form sweeping
motion. D ifferent ai r p ressures and fan ad justment shall be tried so as t o obt ain t he bes t application. The
Air pressure shall n ot be kept too h igh a s otherwise the Paint will fog up and will be wasted. At the e nd
of the job, the spray gun shall be c leaned thoroughly so as to be free from dirt. Incorrect adjustments
shall be set right, as otherwise they result in variable spray patterns, runs, sags and uneven coats.
13.30.4 The s pecifications d escribed i n 13.22 shall hol d g ood f or all ot her details, a s f ar as t hey are
applicable.
13.31.0 The plastic emulsion Paint is not suitable for application on ex ternal, wood and i ron surface and
surfaces which are li able to he avy co ndensation. These Paints ar e to b e used o n int ernal surfaces
except wooden and steel.
13.31.1 Plastic E mulsion P aint a s per I S 5411 of a pproved brand an d m anufacture and of t he requi red
shade shall be used.
13.31.2.2 Application : The number o f coats shall be as s tipulated i n t he i tem. The P aint will be appl ied
in t he usual m anner w ith brush, s pray or rol ler. The P aint dri es by evaporation of t he w ater c ontent and
as s oon a s the w ater has evaporated the film get s har d a nd t he ne xt c oat c an b e applied. T he t ime of
drying varies from one hour on absorbent surfaces to 2 to 3 hours on non-absorbent surfaces.
The thinning of e mulsion i s to be don e w ith w ater and not w ith t urpentine. Thinning with water will be
particularly required for the under coat which is applied on the absorbent surface. The quantity of water to
be added shall be as per manufacturer’s instructions.
The s urface o n f inishing s hall present a f lat v elvety s mooth f inish. If nec essary m ore c oats w ill be
applied till the surface presents a uniform appearance.
13.31.2.3 Precautions
(a) O ld brushes if they ar e to be used with emulsion P aints, should be completely dried of turpentine
or oil Paints by washing in warm soap water.
Brushes should be quickly washed in water immediately after use and kept immersed in water
during break periods to prevent the Paint from hardening on the brush.
(b) I n the preparation of wall for plastic emulsion p ainting, n o oil ba se putties shall b e used in filling
cracks, holes etc.
35 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
(c) S plashes on floors etc. shall be c leaned out without delay as they will be difficult to remove after
hardening.
(d) W ashing of surfaces treated with emulsion Paints shall not be done within 3 to 4 weeks of
application.
13.31.2.4 Other details shall be as specified in 13.23 as far as they are applicable.
13.31.3.1 Preparation of Surface : This s hall be d one, gen erally as s pecified i n 1 3.24.2.1 ex cept that
the s urface bef ore ap plication of P aint s hall be f lattened w ell to get t he pr oper f lat v elvety f inish af ter
painting.
The application shall be as specified in 13.31.2.2 except that thinning with water shall not normally be
required.
13.32.1 Synthetic E namel P aint (c onforming to I S 2933) of approved brand and m anufacture and of t he
required colour shall be u sed for the top coat and an undercoat of ordinary Paint of shade to match the
top coat as recommended by the same manufacturer as far the top coat shall be used.
13.32.2.1 Preparation of surface shall be as specified in 13.24.2 as the case may be.
13.32.2.2 Application : The number of coats including the undercoat shall be as stipulated in the item.
(a) Under Coat : One coat of the specified ordinary Paint of shade suited to the shade of the top
coat, shall be applied and allowed to dry overnight. It shall be rubbed next day with the finest grade of
wet abrasive paper t o ensure a s mooth and ev en surface, f ree f rom brush m arks and all l oose particles
dusted off.
(b) Top Coat : Top coats of synthetic enamel P aint of desired shade shall be applied after the
undercoat is thoroughly dr y. A dditional finishing c oats s hall b e app lied if found n ecessary to en sure
properly uniform glossy surface.
13.32.2.3 Other details shall be as specified in 13.22 as far as they are applicable.
13.32.3.1 Preparation of Surface : Where t he ex isting P aint is firm and s ound i t s hall be c leaned of
grease, smoke et c. and r ubbed with sand paper to remove al l loose par ticles dus ted o ff. A ll pat ches an d
cracks shall then be treated with stopping and filler prepared with the specified Paint. The surface shall
again be rubbed and made smooth and uniform.
If the old pai nt is blistered and f laked i t will be necessary to c ompletely remove the same a s
described in para 13.41. Such removal shall be paid for separately and the painting shall be treated as on
new surface.
36 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
13.32.3.2 Painting : The num ber of coats as s tipulated in the item s hall be applied with s ynthetic
enamel Paint. Each c oat s hall b e a llowed t o dry and r ubbed d own smooth with v ery f ine wet abrasive
paper, to get an even glossy surface. If however, the surface is not satisfactory additional coats as
required shall be applied to get correct finish.
13.32.3.3 Other details shall be specified in 13.22 as far as they are applicable.
13.33.1 Aluminium Paint shall be (conforming to IS 2339) of approved brand and manufacture. The
Paint comes in compact dual container with the paste and the medium separately.
13.33.2.1 Steel Work (New Surfaces) : All r ust a nd scales s hall b e re moved by scraping or brushing
with s teel w ire brushes and t hen smoothened w ith sand paper. The surface shall be t horoughly c leaned
of dust.
13.33.2.2 C.G.S. Sheets (New Surfaces) : The preparation of surface shall be as specified in 13.25.1.1.
13.33.2.3 Steel Work or C.G.S. sheets (Old Surfaces): The specifications shall be as described in
13.25.1.2.
13.33.3 Application
The number of coats to be applied shall be as given in the item. Each coat shall be allowed to dry for
24 h ours and lightly r ubbed dow n w ith fine gr ade s and pape r and du sted o ff be fore the n ext c oat is
applied. The finished surface shall present an even and uniform appearance.
As aluminium paste is likely to settle in the container, care shall be taken to frequently stir the Paint
during used. Also the P aint s hall be applied and laid off quickly, as s urface is otherwise not easily
finished.
13.33.4 Other details shall be as specified in 13.23 as far as they are applicable.
13.34.1 Acid proof Paint of approved brand and manufacture and of the required shade shall be used.
13.34.2 Preparation of surface and application shall be as specified under 13.32 for new/old surface as the
case may be.
13.34.3 Other details shall be as specified in 13.23 as far as they are applicable.
13.35.1 Ready mixed Paint (conforming to IS 158) shall be of approved brand and manufacture. It shall be
black, lead free, acid-alkali-heat-water resistant.
13.35.2 Preparation of surface and application shall be as specified in 13.32 for painting on new or old
surfaces as the case may be.
The drying time between consecutive coats, however, shall be not less than 3 hours.
37 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
13.35.3 Other details shall be as specified in 13.23 as far as applicable.
13.36.1 Floor Paint of approved brand and manufacture and of the required colour shall be used.
It should be not ed that the painting with floor paints shall not be done ov er concrete surfaces less
than two years old.
13.36.3 Application
The number of coats as in the description of the item shall be appl ied. Each coat shall be al lowed to
dry for not less than 24 hours before the next coat is applied. The flooring should not be brought into use for
a week after final coat so that the painted surface can thoroughly harden.
13.36.4 Measurement
Measurements sh all be as p er a ctual l ength and bre adth b eing m easured cor rect to a c m. T he
details given under 13.23.6 shall hold good as far as applicable.
13.37 VARNISHING
13.37.0 Ordinary copal varnish or superior quality spray varnish shall be used. The work includes sizing of
transparent wood filler.
13.37.1 Varnish ( conforming to IS 347 f or the finishing and under coats shall be of the approved
manufacturer.
13.37.2.1 Preparation of Surface : New w ood w ork to be varnished s hall ha ve be en finished s mooth
with a c arpenter’s plane. Knots shall be c ut to a s light depth. Cracks and h oles shall be c leaned of dust.
The knots, cracks etc. shall then be filled in with wood putty made as follows:
On a pi ece of wood say 20 x 15 c m face and on the side where cross grains appear, a s mall
quantity of glue size s hall b e poured and the surface scraped w ith the edge of a fine c arpenter’s
chisel. Very fine wood powder shall be mixed with the glue and the stiff paste thus formed shall be
used for the filling.
The fillings when dry shall be r ubbed do wn with a carpenter’s file and t hen t he entire surface shall be
rubbed down perfectly smooth with medium grained and fine sand papers and wiped with dry clean cloth so
that it presents uniform appearance. In no c ase shall sand papers be rub bed across the grains, as in this
case even the finest marks will be visible when the varnishing is applied.
38 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
13.37.2.2 Sizing or Transparent Wood Filler Coat : The surface s hall t hen be t reated w ith either gl ue
sizing or with transparent wood filler coat as stipulated in the description of item.
(a) Sizing : When sizing is stipulated, an appl ication of thin clean size shall be appl ied hot on t he
surface. When dry, the surface shall be rubbed down smooth with sand paper and cleaned. It shall then be
given anot her ap plication of gl ue s ize nearl y c old. T he s ized w ood w ork s hall agai n be rub bed do wn
smoothly w ith fine s and pap er and c leaned. T he s urface s hall b e pe rfectly dry an d a ll dus t s hall be
removed not onl y from t he surface but also from the edges and joints before varnishing is commenced. If
the wood w ork is to be s tained, t he s taining c olour shall be mixed with t he s econd c oat o f the s ize w hich
must be applied evenly and quickly keeping the colour on the flow.
Any joining up with work already dry will show badly. The object of application of the glue size is to
seal the pores in wood to prevent absorption of the oil in the varnish.
Glue s izing is inad visable on f loors, table tops and o ther ho rizontal s urfaces likely to c arry w et
household untensils which are likely to disturb the size coatings and thus expose bare wood.
Where glue sizing is omitted to be done the rate for the work shall be suitably reduced.
(b) Transparent Wood Filler Coat : Where instead of glue sizing, transparent wood filler application
is stipulated in the item, then the surface prepared as described in 13.37.2.1 shall be given as
application of the filler with brush or rag in s uch a way t hat t he filler fills up all the pores and i ndentations
and levels up the surface. It shall be allowed to dry for 24 hours. Then it shall be cut and rubbed with
emery paper so that the surface of the wood is laid bare, with the filler only in the pores and crevices of
the wood.
13.37.2.3 Application of Varnish : The num ber of c oats t o be appl ied s hall be as s tipulated i n t he
description of the item.
The u ndercoat s hall b e with a f latting v arnish. T his dri es h ard a nd bri ttle a nd w hen cut a nd r ubbed
down t o produce a s mooth s urface enhan ces t he gloss of t he f inishing v arnish. T he t op c oat s hall be
given with stipulated brand of finishing varnish.
The v arnish s hall be applied liberally w ith a f ull b rush and spread ev enly w ith s hort l ight s trokes t o
avoid f rothing. I f t he w ork i s v ertical t he v arnish s hall be c rossed and rec rossed and t hen l aid of f, l atter
being f inished on t he u pstrokes so t hat v arnish, as i t s ets, f lows do wn and e liminates bru sh m arks, t he
above process will c onstitute one coat. I f t he surface i s horizontal, v arnish s hall be w orked i n every
direction, w ith l ight qui ck strokes and f inish i n one def inite d irection s o t hat i t w ill s et w ithout s howing
brush marks, i n handl ing and appl ying v arnish c are should be taken t o av oid f orming froth o r ai r bubbl es.
Brushes and containers shall be kept scrupulously clean.
Rubbing d own an d f latting the s urface s hall be done after e ach c oat e xcept the f inal c oat w ith fine
sand paper.
The w ork s hall be al lowed t o dry aw ay f rom droug hts and dam p ai r. T he f inished s urface s hall t hen
present a uniform appearance and fine glossy surface free from streaks, blister etc.
Any varnish lef t over in the sm all co ntainer shall not be po ured ba ck into the sto ck tin , as it w ill
render the latter unfit for use.
Special fine haired varnishing brushes shall be used and not ordinary Paint brushes. Brushes shall be
well worn and perfectly clean.
13.37.2.4 Other details shall be as specified in 13.23 as far as they are applicable.
39 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
13.37.3 Varnishing on Old Surface
13.37.3.1 Preparation of Surface : If the old varnished surface is firm and sound it shall be cleaned of
grease and dirt with turpentine and then rubbed with wet sand paper until the surface is clean and smooth.
It shall be dried and wiped clean with a soft cloth. Knots, holes and cracks shall be stopped as specified in
13.37.2.1. The entire surface shall then be rubbed down smooth with sand paper and wiped clean.
If the old v arnished surface is peeled or c racked then it w ill be nec essary to remove the entire
varnish as des cribed i n p ara 13. 41 an d s uch removal s hall be pai d f or s eparately out side t he rate f or
varnishing. Further the varnishing itself will have to be done like new work and will be paid for as such.
13.37.3.2 Application : The s pecification s hall be s ame as des cribed i n 13 .37.2.3 as f ar as app licable
except that the coats to be applied will be with the stipulated quality of varnish for finishing coat.
13.37.3.3 Other details shall be as specified in 13.23 as far as they are applicable.
13.38.1 Pure s hellac c onforming t o IS 1 6 v arying from pale o range to l emon y ellow colour, free from
resin o r di rt s hall b e di ssolved in m ethylated spirit at the r ate of 1 40 g m of shellac to 1 litre of s pirit.
Suitable pi gment s hall be added t o get the required s hade. R eady made pol ish c onforming to I S 348 can
also be used.
13.38.2.1 Preparation of Surface : The s urface shall be cleaned. A ll une venness shall be r ubbed do wn
smooth with sand paper and well dusted. Knots if visible shall be covered with a preparation of red lead
and gl ue s ize l aid on w hile hot . H oles and i ndentations on the s urface s hall be s topped w ith gl azier’s
putty. T he s urface s hall t hen b e gi ven a coat of w ood f iller m ade by m ixing w hiting (ground c halk) i n
methylated s pirit at the r ate of 1. 5 K g of w hiting p er litre of s pirit. T he s urface s hall a gain b e r ubbed
down perfectly smooth with glass paper and wiped clean.
13.38.2.2 Application : The number of coats of polish to be applied shall be as described in the item.
A pad of woollen cloth covered by a fine cloth shall be used to apply the polish. The pad shall be
moistened with t he pol ish and r ubbed hard on the wood, i n a series of ov erlapping c ircles appl ying t he
mixture sparingly but uniformly over the entire area to give an even level surface. A trace of linseed oil on
the face of the pad facilitates this operation. The surface shall be allowed to dry and the remaining coats
applied in the same way. To finish off, the pad shall be covered with a fresh piece of clean fine cotton
cloth s lightly da mped with m ethylated spirit and r ubbed l ightly and q uickly w ith circular m otions. The
finished surface shall have a uniform texture and high gloss.
13.38.2.3 Measurements, Rate and other details shall be as specified in 13.23 as far as they are
applicable.
13.38.3.1 Preparation of Surface : If the old p olished surface is not much soiled it shall b e cleaned of
grease and dirt by rubbing with turpentine and then rubbed with fine sand paper.
If t he ol d p olished s urface i s m uch soiled t hen i t will be necessary t o r emove t he e ntire p olish a s
described in 13.41 a nd s uch r emoval shall b e p aid f or s eparately o utside t he r ate o f p olishing. F urther
the polishing itself will have to do done like new work and will be paid for as such.
40 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
13.38.3.2 Application : The specifications shall be same as described in 13.38.2.2 as far as applicable.
13.38.3.3 Measurements, Rate and other details shall be as specified in 13.23 as far as they are
applicable.
13.39.1 The pol ishing s hall be done with bees w axing pr epared locally or with ready m ade w ax pol ish of
approved brand and manufacture, as stipulated in the description of item.
Where bees waxing is to be prepared locally, the following specifications for the same shall apply.
Pure bees wax free from paraffin or stearine adulterants shall be used. Its specific gravity shall be
0.965 to 0.969 and m elting point s hall b e 63 degree C . The polish s hall b e pre pared f rom a m ixture of
bees wax, linseed oil, turpentine and varnish in the ratio of 2 : 1.5 : 1 : 0.5 by weight.
The bees wax and boi led linseed oil shall be heat ed over a s low fire. When the wax is completely
dissolved the mixture shall be cooled till it is just warm and turpentine and varnish added to it in the
required proportions and the entire mixture shall be well stirred.
13.39.2.1 Preparation of Surface : Preparation o f surface s hall be as d escribed in 13 .37.2.1 w ith the
exception t hat k notting, holes and cracks shall be stopped w ith a mixture of fine s aw dus t f ormed of the
wood being treated, beaten up with sufficient bees wax to give it cohesion.
13.39.2.2 Application : The polish shall be applied ev enly with a clean soft pad of cotton cloth in s uch a
way t hat t he surface i s c ompletely an d fully c overed. The surface i s t hen rubbed continuously for hal f an
hour.
When the s urface is quite dry, a s econd c oat s hall be applied in the same m anner and rubbed
continuously for one hour or until the surface is dry.
The final c oat s hall t hen b e applied an d rubbed for two h ours ( more i f nec essary) until the surface
has assumed a uniform gloss and is dry, showing no sign of stickiness.
The f inal p olish depends, l argely o n t he am ount o f r ubbing w hich should b e c ontinuous and w ith
uniform pressure with frequent changes in the direction.
13.39.2.3 Other details shall be as specified in 13.23 as far as they are applicable.
13.39.3.1 Preparation of Surface : The w ood w ork shall be c leaned o f all s moke and grease by
washing with lime water. The surface shall then be washed with soap and completely dried. Then it shall be
prepared smooth as specified in 13.37.2.1.
13.39.3.2 Application : The pol ish s hall be appl ied i n t he m anner s pecified i n 13. 39.2.2. I n this c ase
one or t wo coats shall be applied as necessary to g et uniform gl oss, i nstead of three coats i n the case of
new work.
13.39.3.3 Other details shall be as specified in 13.22 as far as they are applicable.
41 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
13.40 LETTERING WITH PAINT
13.40.1 Black, Colour Paint (conforming to IS 2932) or ready mixed Paint as ordered by the Engineer-in-
Charge s hall be us ed. T he P aint s hall be of a pproved br and a nd m anufacture. O rdinary ready m ixed
Paint shall be of the shade required by the Engineer-in-Charge.
13.40.2.1 Application : The letters and figures s hall b e to the he ights a nd w idth as or dered b y the
Engineer-in-Charge. These shall be s tenciled or d rawn i n penc il and got app roved be fore pai nting. They
shall be of un iform size a nd f inished neatly. The e dges shall be straight or i n pleasant s mooth c urves.
The thickness of the lettering shall be as approved by the Engineer-in-Charge. Lettering shall be vertical or
slanting as required.
Two or more coats of Paint shall be applied till uniform colour and glossy finish are obtained.
13.40.2.2 Measurements : Measurements shall be taken in terms of letter cm (the measurement relates to
the vertical height of the lettering). The letter heights shall be measured correct to a cm.
Dots, dashes, punctuations and other similar marks or lines shall not be measured for payment.
In Devanagari Script Dots & Matras occurring with the letters shall not be measured. Half letter shall be
measured as full letter. The height of letters shall be measured excluding the Matras projecting above the
heading and matras below the letters.
13.40.2.3 Rate : Rate shall include the cost of all labour and materials involved in the operations
described above. The rate per cm height of letter shall hold good irrespective of the width of the letters or
figures or the thickness of the lettering.
The s ame rat e w ill ap ply i rrespective of w hether bl ack J apan or ready m ixed Paint o f any s hade as
required is used.
13.40.3.1 Painting s hall be d one ov er th e e xisting lett ers and sh all a ccurately fol low th eir li nes an d
curves.
One or more coat of Paints shall be applied till a uniform colour and glossy finish is obtained.
13.41.1.1 Patent P aint r emovers s hall c onsist of v olatile org anic l iquids thickened w ith w axes a nd ot her
ingredients t o retard t he evaporation of t he liquid and t o en able a substantial l ayer of remover to be
applied to the surface. The Paint remover shall be of a br and and manufacture approved by the
Engineer-in-Charge. I t s hall be f ree f rom al kaline matter and non -caustic s o t hat it c an be handl ed by
workmen without injury. It shall be of non inflammable quality as far as possible.
13.41.1.2 Application : Paint remover s hall be us ed w here b urning of f w ith blow lamp i s no t suitable.
The Paint remover shall be applied liberally with a brush and allowed to remain on the surface for a
42 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
period depending on the particular brand of remover used and on the thickness of the Paint coating to be
removed. When the Paint film lifts and wrinkles under the action of the remover it shall be stripped with a
sharp i nstrument. If t he film i s not t horoughly r emoved a s econd c oat o f remover may be appl ied i f
necessary over such patches and then the film thoroughly scrapped.
After t he surface h as b een s tripped, i t shall b e washed d own with mineral t urpentine t o re move a ll
traces of par affin w ax, which f orms one of t he i ngredients of pat ent P aint r emover and w hich i f l eft in
place will prevent the Paint from drying.
The cleaned surface shall be suitably prepared for application of Paint or other finish.
13.41.1.3 Precautions : Where the Paint rem over us ed is o f t he i nflammable t ype, s uitable prec aution
against risk of fire shall be taken.
Neighbouring pai nted s urfaces w hich a re not to be t reated should be pr operly protected from c ontact
with Paint remover.
13.41.1.4 Preparation of Surface : The surface shall then be prepared as described in 13.24.2.
13.41.1.6 Rate : Rate shall include the cost of all labour and m aterials involved in all operations
described above.
13.41.2.1 Application : Caustic soda dissolved with 48 t imes its volume of water shall be applied to the
old Paint with a brush and when the Paint film lifts and wrinkles it shall be thoroughly scrapped of in the
same w ay as d escribed in 13.41.1.2. A fter the surface h as b een s tripped thoroughly, i t s hall be ri nsed
with s everal c hances o f clean w ater to remove al l t races o f al kali, w hich i f a llowed to remain a re l iable to
spoil t he n ew P aint applied over i t. A l ittle acetic acid o r vinegar a dded t o t he f inal change of rinsing
water helps to neutralize any remaining alkali.
13.41.2.2 Precautions : Caustic soda as its name implies is a corrosive liquid and care should be taken to
see that no liquid spills over the skin or clothing.
13.41.2.3 Preparation of Surface, Measurements, Rate and other details shall be as specified under
13.41.1.
13.41.3.1 The P aint s hall be removed either w ith a b low l amp o r w ith an a iracetylene e quipment. T he
flame shall be allowed to play upon the Paint just enough to soften it without charring either the Paint or the
background. The s oftened P aint shall t hen be r emoved w ith a s tripping knife f ollowing the flame a s i t i s
moved up the surface.
Burning off shall begin at the bottom of the vertical surface and shall proceed upwards.
13.41.3.2 Precautions : Removal with blow lamp shall not be done on narrow or carved under cut
surfaces or w here there i s r isk o f da mage to neighbouring materials such a s panes i n g lazed
windows.
43 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
13.41.3.3 Preparation of surface, Measurements, Rate and other details shall be as described under
13.41.1.
Neighbouring pai nted s urfaces w hich a re not to be t reated should be pr operly protected from c ontact
with Paint remover.
13.42.3 Materials
13.42.3.1 Stone chippings obtained by crushing hard stone shall be free of dust and deleterious
material. 10 m m no minal size s tone chippings, where s pecified, s hall pass 100% t hrough 12. 5 mm sieve
and f ully ret ained o n 6. 3 mm s ieve. Stone c hippings s hall be t horoughly washed w ith water an d s ieved
before use.
13.42.3.2 Mortar : Cement mortar for under coat and cement mortar to be mixed with stone chippings for
top coat shall be as specified in 3.5.
13.42.4.1 12 mm Under Coat : Under coat of cement mortar 1:4 (1 cement : 4 coarse sand) shall be
applied as specified in 13.1.3 except that the finishing, after the mortar has been brought to level with the
wooden straight ed ge, s hall be done with wooden f loat o nly. The s urface s hall be further r oughened by
furrowing with a scratching tool. Furrowing shall be done diagonally both ways and s hall be ab out 2 mm
deep to provide a key for the top coat. The scratched lines shall not be more than 10 cm apart. The surface
shall be kept wet till top coat is applied.
13.42.4.2 15 mm Top Coat : Top c oat c omprising c ement m ortar and s tone c hippings s hall hav e an
overall proportion of 1:0.5:2 (1 cement : 0.5 coarse sand : 2 stone chippings 10 mm nominal size) or as
specified. The top coat shall be applied a day or two after the under coat has taken the initial set. The
surface of the under coat shall be cleaned and a coat of cement slurry at 2 kg of cement per sqm shall be
applied before the application of coat. The top coat shall be applied in uniform thickness on the under coat
after the application of slurry and sufficiently pressed with wooden float for proper bonding with the under
coat. Vacant space, if any shall be filled with the specified mix.
13.42.5 Finish
The top c oat of pl aster s hall be finished to a true an d pl umb s urface. The s urface shall be tested
frequently as t he work p roceeds w ith a tru e str aight e dge n ot le ss t han 2 .5 m l ong an d w ith pl umb
bobs. A ll hor izontal lines and s urfaces s hall be tested w ith a level a nd a ll jambs and c orners w ith a
plumb bob as the work proceeds. All the corners angles and junctions shall be truly vertical or
horizontal as the case may be. Rounding or chamfering of corners junctions e tc. Where required
shall be true to template.
Finished s urface o f t he t op coat a fter t he mix has t aken the i nitial set, shall b e scrubbed an d washed
with s uitable b rushes an d pl ain w ater. S crubbing and w ashing s hall c ontinue t ill t he s tone c hippings a re
sufficiently ex posed. Stone c hippings which m ay c ome out w hile s crubbing s hall be rep laced us ing t he
specified mortar mix. A sample of the washed s tone grit pl aster s hall be got approved from the Engineer-
in-Charge.
44 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
13.42.6 Grooves
Grooves of size 15 mm x 15 m m or as specified shall be pr ovided as shown on t he drawing or as
required by the E ngineer-in-Charge. T apered w ooden ba ttens to m atch the s ize and s hape of the
grooves shall be fixed on the under coat with nails before the application of the top coat and these shall be
removed carefully s o that t he edges o f the pan els o f top coat a re not dam aged. D amage, if an y, shall b e
made good by the contractor.
13.42.7 Curing
Curing shall be started 24 hours after finishing the plaster. The plaster shall be kept wet for a period of
seven d ays. D uring this per iod, it shall be s uitably pr otected from a ll dam ages a t the contractor’s
expense by such means as the Engineer-in-Charge may approve.
13.42.8 Measurements
13.42.8.1 Length and breadth shall be measured correct to the nearest cm and the area shall be
calculated in sqm correct to two places of decimal.
13.42.8.2 Measurements shall be taken for the work actually done with deductions for all openings and
addition for all j ambs s offits and s ills. However, no deduction i s t o be made for t he grooves provided as
specified in 13.42.6.
13.42.8.3 Washed stone grit plaster on c ircular surfaces not exceeding 6 m in radius and on external
surfaces at a height greater than 10 m shall be measured separately.
13.42.9 Rates
The rates s hall include the cost of al l labour an d materials involved in al l the operations de scribed
above ex cept f or p roviding gr ooves. T he l ength of gr ooves shall be m easured i n r unning m etres a nd
paid for separately.
13.43.3 Materials
13.43.3.1 Premixed l ight w eight pl asters e ssentially consist o f retarded he mihydrate g ypsum pl aster and
light weight aggregate which are characterized by low density, high thermal insulation and sound
absorption pr operties. O ther ad ditions m ay b e i ncorporated to i mpart de sired properties. The ph ysical
and chemical requirements shall conform to IS 2547 (Pt. II).
13.43.3.2 The m inimum recommended water-premixed plaster ratio i s 1:2 as per s tandard pr actice or
as recommended by the manufacturers.
13.43.5 Thickness
Where t he t hickness required, as per des cription of t he i tem i s 12 m m, t he average t hickness of t he
plaster shall not be less than 12 mm whether wall treated is of brick/block/RCC work.
45 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
13.43.6 Finish
The plaster shall be finished as specified in 13.1.7.
13.43.7 Measurement
Measurement of plaster shall be as specified in 13.1.9.1 to 13.1.9.9.
13.43.8 Rate
Rate shall include the cost of all labour & material involved in all the operations described above.
46 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
15.0 :DISMANTLING
AND DEMOLISHING
47 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
CONTENTS
Clause No. Brief Description Page No.
List of Bureau of Indian Standards Codes 048
48 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
15.0 DISMANTLING AND DEMOLISHING
15.0 TERMINOLOGY
(i) Dismantling: The term ‘Dismantling’ implies carefully separating the parts without damage and
removing. This may consist of dismantling one or more parts of the building as specified or
shown on the drawings.
(ii) Demolition : The t erm ‘ Demolition’ implies breaking up. T his s hall c onsist of dem olishing w hole
or part of work including all relevant items as specified or shown on the drawings.
15.1 GENERAL
This chapter relates to buildings only.
15.1.1 Precautions
15.1.1.1 All m aterials obtained f rom d ismantling or dem olition s hall be the p roperty of the Government
unless otherwise specified and shall be kept in safe custody until they are handed over to the Engineer in-
Charge/ authorized representative.
15.1.1.2 The demolition s hall always be well planned before hand and shall g enerally be done i n reverse
order of the one in which the structure was constructed. The operations shall be got approved from the
Engineer-in-Charge before starting the work.
Due care shall be taken to maintain the safety measures prescribed in IS 4130.
15.1.1.3 Necessary propping, shoring and or un der pinning shall be p rovided to ensure the safety of the
adjoining w ork or property bef ore di smantling and demolishing i s t aken up and t he w ork s hall be c arried
out in s uch a w ay that no d amage is c aused to the a djoining w ork o r pr operty. W herever s pecified,
temporary enc losures o r par titions and nec essary s caffolding with s uitable dou ble s caffolding and pr oper
cloth covering shall also be provided, as directed by the Engineer-in-Charge.
15.1.1.4 Necessary pr ecautions s hall be t aken t o keep noi se and dus t nui sance t o t he minimum. A ll
work needs t o b e done u nder t he di rection of Engineer-in-Charge. Helmets, go ggle, s afety b elts etc.
should be used whenever required and as directed by the Engineer-in-Charge.
The demolition w ork shall be proceeded with i n s uch a w ay t hat it c auses the least damage and
nuisance to the adjoining building and the public.
15.1.1.5 Dismantling shall be done in a systematic manner. All materials which are likely to be damaged by
dropping f rom a he ight or by demolishing r oofs, m asonry etc. s hall b e c arefully r emoved f irst. C hisels a nd
cutters may be used carefully as directed. The dismantled articles shall be removed manually or otherwise,
lowered to the ground (and not thrown) and then properly stacked as directed by the Engineer-in-Charge.
15.1.1.6 Where existing fixing is done by nails, screws, bolts, rivets, etc., dismantling shall be done by
taking out the fixing with proper tools and not by tearing or ripping off.
15.1.1.7 Any s erviceable m aterial, obt ained dur ing di smantling o r de molition, s hall be separated out and
stacked pr operly as di rected by t he E ngineer-in-Charge w ithin a l ead of 50 m etres. A ll uns erviceable
materials, rubbish etc. shall be disposed off as directed by the Engineer-in-Charge.
15.1.1.8 The c ontractor s hall m aintain/disconnect existing s ervices, w hether temporary o r p ermanent,
where required by the Engineer-in-Charge.
15.1.1.9 No demolition work should be carried out at night especially when the building or structure t o be
demolished is in an inhabited area.
49 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
15.1.1.10 Screens shall be placed where necessary to prevent injuries due to falling pieces.
15.1.1.11 Water may be used to reduce dust while tearing down plaster from brick work.
15.1.1.12 Safety bel ts shall be us ed b y l abourers w hile w orking at hi gher level to prevent f alling from the
structure.
15.1.1.13 First-aid equipment shall be got available at all demolition works of any magnitude.
15.2.1.1 Temporary bracing s hould be add ed, w here nec essary, t o m aintain s tability. T he end f rame
opposite to the end where dismantling is commenced, or a convenient i ntermediate frame should be
independently and securely guyed in both directions before work starts.
15.2.1.2 On no ac count should the bottom tie of roof trusses be c ut until the principal rafters are
prevented from making outward movement.
15.2.5.1 Expert advice s hould be obt ained and at all stages of the dem olition, the closest supervision
should be g iven by per sons fully ex perienced and c onversant in the type o f w ork to ens ure that the
structure is stable at all times.
15.2.5.2 As much dead load as possible may be removed provided it does not interfere with the stability of
the main arch rings but it should be noted that the load-carrying capacity of many old arches relies on the
filling between the spandrels. On no account should the restraining influence of the abutments be
removed before the dead load of the spandrel fill and the arch rings are removed.
15.2.5.4 Special temporary support shall be provided in the case of skew bridges.
15.2.5.5 A single span a rch. can be de molished b y hand b y c utting nar row segments p rogressively from
each springing parallel to the span of the arch until the width of the arch has been reduced to a minimum
which can then be collapsed (see Fig. 15.2B).
50 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
15.2.5.6 Where i t i s i mpossible t o allow debris t o f all t o t he gr ound b elow, centering designed t o c arry
the load should be erected and the arch demolished progressively. The design of the centering should
make appropriate allowance for impact.
15.2.5.7 Where del iberate c ollapse is f easible t he crown may b e brok en by the dem olition bal l m ethod
working progressively from edges to the centre (see Fig. 15.2C).
15.2.5.9 In multi-span arches before individual spans are removed, lateral restraint should be provided at
the springing level. Demolition may then proceed as for a s ingle span, care b eing taken to dem olish the
spandrels down to the springing line as the work proceeds (see Fig. 15.2D). Where explosives are used it
is preferable to ensure the collapse of the whole structure in one operation to obviate the chance of leaving
unstable portions standing.
15.2.7.2 Attention should be paid to the principles of the structural design to determine which parts of the
structure depend on each other to maintain overall stability.
15.2.7.3 Demolition s hould be commenced by removing pa rtitions and ex ternal no n-load bea ring
cladding. It should be noted that in some buildings the frame may rely on the panel walls for stability.
15.2.7.4 Where hard demolition methods are to be used, the following procedures should be used.
(a) Reinforced Concrete Beams
For bea ms, a s upporting rope s hould be a ttached to the bea m. T hen the c oncrete s hould be
removed from both ends by pneumatic drill and the reinforcement exposed. The reinforcement
should then be cut in such a way as to allow the beam to be lowered under control to the floor
(see Fig. 15.3A).
(b) Reinforced Concrete Columns
For c olumns, t he reinforcement s hould be exposed at the base after restraining wire guy ropes
have been pl aced round the m ember at t he t op. The rei nforcement should then be c ut i n such a
way as to al low th e col umn to b e p ulled do wn to the flo or u nder co ntrol. (see F ig. 15. 3B f or
sequence of operations).
(c) Reinforced Concrete Walls
Reinforced concrete walls should be cut into strips and demolished as for columns (Fig. 15.3C).
15.3 MEASUREMENTS
15.3.1 All work shall be measured net in the decimal system, as fixed in its place, subject to the following
limits, unless otherwise stated hereinafter.
(a) Dimensions shall be measured correct to a cm.
(b) Areas shall be worked out in sqm correct to two places of decimal.
(c) Cubical contents shall be worked out to the nearest 0.01 cum.
51 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
15.3.2 Parts of w ork required t o be di smantled and t hose required to be de molished s hall be m easured
separately.
15.3.3 Measurements of all work except hidden work shall be taken before demolition or dismantling and no
allowance for increase in bulk shall be allowed.
15.3.4 Specifications for deduction for voids, openings etc. shall be on the same basis as that adopted for
new construction of the work.
15.3.6 Roofs
(i) Roof coverings generally including battens boarding, mats, bamboo jaffari or other subsidiary
supports shall be measured in square metres except lead sheet roof covering which shall be
measured in quintals (15.2.3) and stone slab roof covering which shall be measured in cubic
metres.
(ii) R idges, hi ps and v alleys s hall be girthed and included w ith t he r oof a rea. C orrugated or semi
corrugated surfaces shall be measured flat and not girthed.
(iii) Mud phuska on roofs shall be measured in cubic metres.
(iv) Lead s heets i n roofs s hall be m easured i n quintals and hi ps, v alleys, f lashings, l ining t o gutter
etc. shall be included in this weight.
(v) R.B. or R.C.C. roofs shall be measured as specified in 15.3.11.
(vi) Supporting members, such as rafters, purlins, beams joists, trusses etc. of wood shall be
measured in cubic metres and steel or iron sections, in quintals.
15.3.7 Ceiling
(i) The stripping of ceilings shall be measured in square metres.
(ii) Dismantling of supporting joists, beams, etc. shall be measured in cubic metres or in quintals as
specified in 15.3.6(vi).
(iii) Height above floor level, if it exceeds 3.5 m shall be paid for separately.
Vol-2 , 2013
(v) Cleaning stone obtained from demolished/dismantling stone masonry of any description including
ashlar facing dressed stone work, stone slabs or flagging and pre-cast concrete blocks including
all extra handling and disposing off the rubbish as stated shall be measured in cubic metres of
cleaned stone.
(vi) Honey comb works or cavity walls of bricks stone or concrete shall be measured as solid.
Where reinforcement i s required to be s eparated, scraped and c leaned, the work s hall be measured
separately in quintal of salvaged steel.
Boarding including wooden c hajjas and sun s hades al ong with s upports s hall be m easured in s quare
metres in its plane.
Vol-2 , 2013
depth, in un it o f ha lf and one m etre dept h. T he dep th o f the m anhole s hall be the d istance
between the top of manhole cover and invert level of the drain.
(vi) V entilating s hafts, gu lly traps, flushing c isterns and o ther a ppurtenant i tems o f w ork s hall be
enumerated.
15.3.19 Glazing
Taking out any por tion of s erviceable gl ass ex cept pol ished pl ate, from o ld sashes, s kylights, e tc.
(any thickness, weight or size) raking out old putty, etc. shall be measured in square metres.
Irregular c ircular panes s hall be measured a s r ectangle o r s quare e nveloping t he s ame. T he width
and height being measured correct to the nearest 0.5 cm.
15.4 RATES
The ra te s hall i nclude t he c ost of a ll l abour i nvolved and t ools us ed i n de molishing and d ismantling
including scaffolding. The rate shall also include the charges for separating out and stacking the
serviceable material properly and disposing off unserviceable material within a distance of 50 metres.
The rat e s hall al so i nclude f or t emporary s horing f or t he s afety of p ortions n ot requi red t o be pu lled
down, or of adjoining property, and providing temporary enclosures or partitions, where considered
necessary.
54 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
DEMOLITION OF JACK ARCHES
Tie Rod
55 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
DEMOLITION OF MASONRY AND BRICKWORK ARCHES
(1) S Pandrel
Springing
Line
Arch
Ring
Abutments
Fig . 15.2A
Arch
Edge o f
Arch
Fig . 15.2B
Abutments
No te : Order of Demolition
Fig. 15.2 : Demolition of Masonry and Brickwork Arches
56 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
HAND DEMOLITION OF IN-SITU CONCRETE STRUCTURE
Slots c ut on
this Line (2)
Single Storey No person on this side of Wall
Height
Approx 1.0m Wide
57 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
16.0: ROAD WORK
58 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
CONTENTS
Clause No. Brief Description Page No.
List of Mandatory Tests 63
16.0 Terminology 68
16.1 Materials 68
59 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
16.22 Kilometers Stones- DELETED 94
16.23 Surface Dressing on New Surface with Hot Bitumen One Coat 94
16.43 Lime Fly Ash Stabilised Soil Sub Base - DELETED 129
60 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
16.47 Bituminous Macadam 135
16.60 Supplying and Stacking of Hard Stone (for Stone Pitching) 139
61 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
Fig. 16.9 Barbed Wire Fencing (with RCC Post) 140
Fig. 16.13 Broad Details of Cooker for Bitumen Mastic in Wearing Courses 143
62 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
LIST OF MANDATORY TESTS
Material/work Clause Test Field/ Test Mini- Frequency of Testing
Laboratory procedure mum
quan-
tity/
Value
1 2 3 4 5 6 7
3
Coarse 16.1.1 1. Lost Angles Laboratory IS 2386 Per 200 m
Aggregate (Part IV)
2. Abrasion Value or IS 2386
Aggregate Impact Value (Part V)
IS 5640
3. Flakiness Index IS 2386
(Part I)
3
16.1.1 Grading requirement Field IS 2386 Nil Per 100 m
Table 16.2 (Part I)
Fine Aggregate 16.1.2 Deleterious materials Laboratory IS 2386 Nil As required by the
(Part III) Engineer-in-charge
Bitumen 16.1.5 As prescribed in IS 73 Laboratory As Nil As required by the
prescribed Engineer-in-charge
in IS 73
3
Embankment 16.3.1 1. Moisture content Laboratory IS 2720 Nil 250 m
under (O.M.C. 2. Density Field (Part II) Nil 250 m3
conditions) IS 2720
(Part
XXVIII)
16.3.4.4 3. Control test on borrow Laboratory
pits.
(a) Gradation Laboratory IS 2720 Nil One to Two tests per
3
(Part IV) 8000 m
(b) Plasticity Laboratory IS 2720 Nil -Do-
(Part V)
(c) Proctor Test Laboratory IS 2720 Nil -Do-
(Part VIII)
(d) Deleterious content Laboratory Nil As required by the
Engineer- in- charge
3
(e) Moisture contents L aboratory IS 2720 Nil 250 m
(Part II)
Bitumen 16.32 1. Binder Field IS 73 Nil As required by the
Penetration Engineer-in-charge.
Macadam
3
2. Aggregate Abrasion Laboratory IS 2386 Nil Per 100 m of
impact value or Los (Part IV) aggregate as
Angles Value required by the
Engineer-in-charge
3. Flakiness Index Laboratory IS 2386 Nil -Do-
(Part I)
4. Stripping Value Laboratory IS 6241 Nil -Do-
5. Grading of Aggregate Field or IS 2386 Two tests per day
Laboratory (Part I) per plant
3
Bitumen Mastic 16.33 1. Los Angles Abrasion Laboratory IS 2386 Nil For every 100 m
Wearing Course Value/ Aggregate Impact (Part IV)
value
2. Flakiness Index Laboratory IS 2386 -Do-
(Part I)
3. Stripping Value Laboratory IS 6241 -Do-
4. Mix Grading Field/ IS 2386 One set of test on
Laboratory (Part I) individual
constituents and
mixed aggregate
from dryer for each
100 tonnes of mix
subject to minimum
of two sets per plant
per day
Vol-2 , 2013
1 2 3 4 5 6 7
Dense Bitumen 16.46 1. Quality of Binder Laboratory IS 73 Nil As required
Macadam
2. Los Angles Abrasion Laboratory IS 2386 Nil 100 m3
Value/ Aggregate impact (Part IV)
Value
3. Stripping Value Laboratory IS 6241 Nil -Do-
4. Water Absorption -Do- IS 2386 -Do- -Do-
(Part III)
5. Flakiness Index -Do- IS 2386 -Do- One test for 100
(Part I) cum.
6. Sieve Analysis for filler -Do- IS 2386 -Do- One test for each
(Part I) consignment subject
to minimum one test
per 5 cum.
7. Mix Grading -Do- IS 2386 -Do- One set of test on
(Part I) individual constituent
and mixed
aggregates from
dryer for each 100
tonnes of mix subject
to a minimum of two
sets per plant per
day
8. Stability of Mix -Do- ASTM D -Do- Three marshall
1559 specimen per 100
tonnes of mix,
subject to a
minimum of 2 sets
being tested per
plant, per day.
9. Binder Content Field -Do- One test for each
100 tonnes of mix
subject to minimum
of two tests per day
per plant
10. Thickness , Density of Field Appendix -Do- One test of 3
compacted layer ‘B’ samples per 500
sqm.
Same as above except Test Same as Same as Nil Same as for
No. 6 & 7 above above Asphaltic concrete
Cement 16.37.19 Coars e aggregate - Before approval of
concrete 1. Flakiness Index Laboratory IS 2386 the quarry and every
pavement under (Part I) sub-sequent change
controlled in the source of
conditions supply and one test
per 100 cum.
2. Impact Value -Do- IS 2386 - -Do-
(Part IV)
3. Loss Angles abrasion -Do- -D o- - -Do-
Value
4. Deleterious material -Do- IS 2386 - Before approval of
(Part II) the quarry and at
every subsequent
change in the source
of supply
Vol-2 , 2013
1 2 3 4 5 6 7
5. Moisture content -Do- IS 2386 - Regularly as
(Part III) required subject to a
minimum of one test
per day
Fine Aggregate
1. Silt content Field As per - One test per 15 cum.
CPWD
specificati-
on Vol. I.
2. Gradation of sand -Do- IS 2386 - -Do-
(Part II)
3. Deleterious material -Do- IS 2386 - Before approval of
(Part II) the quarry and at
every subsequent
change in the source
of supply
4. Moisture content -Do- IS 2386 - Regularly as
(Part III) required subject to a
minimum of two tests
per day
5. Mix Aggregate Field IS 2386 - One test per 15 cum
(Part I) of concrete
6. Flextural strength Laboratory IS 526 - One test consisting
of 8 specimen for 30
cum. of concrete
Vol-2 , 2013
LIST OF BUREAU OF INDIAN STANDARDS CODES AND IRC STANDARDS
66 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
IRC STANDARDS:
67 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
16.0 ROAD WORK
16.0 TERMINOLOGY
Asphalt : A natural or artificial mixture in which bitumen is associated with mineral matter. The word
‘Asphalt’ should always be qualified by indication of its origin or nature.
Asphalt Mastic : An intimate mixture of mineral fillers, well graded sand and/or stone chippings with a
hard g rade o f bi tumen, c ooked and l aid hot manually b y m eans of w ooden float. The mixture settles to a
coherent, voidless and impermeable solid or semi-solid mass under normal temperature condition.
Bitumen Grade VG-10, 30: A nonc rystalline s olid o r v iscous material, ha ving adhesive pr operties der ived
from petroleum either by natural or refinery processes and substantially soluble in carbon disulphide.
Bitumen-Cutback : Bitumen, the viscosity of which has been reduced by a volatile dilutent when
blended with kerosene or naptha type dilutent or fuel oil, is called, medium or rapid or slow curing cut
backs respectively.
Bitumen-Emulsion : A l iquid pro duct i n w hich a s ubstantial amount of bitumen i s s uspended i n a f inely
divided c ondition i n an aq ueous m edium c ontaining an em ulsifier and s tabiliser. T he em ulsion i s t ermed
‘Anionic’ w hen t he bi tumen particles a re n egatively c harged a nd t he a queous p hase i s al kaline. T he
emulsion is termed ‘cationic’ when the particles are positively charged and the aqueous phase is acidic.
Bitumen Mastic Filler : Inorganic mineral material all of which will pass through specified IS sieve used in
admixture with solid or semi-solid bituminous material.
CRMB: Crumb R ubber M odified Bitumen is manufactured u sing C rumb R ubber from hea vy v ehicle t yres,
which i s Mechanically Partial de -vulcanized and c hemically t reated. A dditives l ike N atural A sphalt and
Natural R ubber l atex ar e added an d flexed at hi gh t emperature u sing hi gh s hear mixing and c ome with
enhanced properties.
PMB : Polymer Modified Bitumen is manufactured with a specially blended feed, making the binder
homogenous and storage stable. It enhanc es t he key p roperties o f asphalt mixes, i .e. de formation
resistance and fatigue l ife. These i mprovements a re the r esult o f three v ital ph ysical c hanges which the
polymer makes in the conventional binder structure: reduced temperature susceptibility, increased stiffness
modulus and enhanced elasticity
Road tar : A product obtained by treating at high temperature coal tar in such a manner that it conforms to a
specification which defines its suitability for road construction.
Tar : A viscous material having adhes ive pr operties and resulting from the distinctive distillation of certain
type of organic material. The term Tar should be preceded by the name of the material from which it is
produced e.g. coal, shale, peat, vegetable matter and its mode of production shall be indicated.
Flash point : The lowest temperature a t w hich the v apour o f a s ubstance can be ignited in a ir by a
flame under specified conditions of test. The substance itself does not continue to burn.
Tack Coat : It s hall consist o f application o f a s ingle coat o f l ow v iscosity liquid bi tuminous material t o an
existing road surface preparatory to further bituminous construction.
16.1 MATERIALS
The stone aggregate s hall conform to the physical requirements set forth i n Table 16.1. The type and
size range of the aggregate shall be specified in the contract.
68 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
TABLE 16.1
Physical Requirements of Coarse Aggregate
Sl. No. Type of Constn. Test for W.B.M. Test method Requirements
The co arse aggregate shall conform to one o f th e gr adings g iven i n T able 1 6.2 as specified. F or
crushable t ype of a ggregates s uch as bri ck m etal, kankar and laterite, grading shall not be regarded as
very important, but the material should generally be within the specified range.
TABLE 16.2
Grading Requirements of Coarse Aggregate for W.B.M.
1. 90 mm to 45 mm 125 mm 100
(Suitable for sub base 90 mm 90 - 100
courses of compacted 63 mm 25 - 60
layer of not less than 45 mm 0 - 15
90 mm thickness) 22.4 mm 0 - 5
2. 63 mm to 45 mm 90 mm 100
63 mm 90 - 100
53 mm 25 - 75
45 mm 0 - 15
22.4 mm 0 - 5
3. 53 mm to 22.4 mm 63 mm 100
53 mm 95 - 100
45 mm 65 - 90
22.4 mm 0 - 10
11.2 mm 0 - 5
69 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
16.1.1.1 Brick Aggregate : Brick aggr egate s hall be br oken f rom ov er-burnt and dens e br ick b ats. I t
shall be hom ogeneous i n t exture, roughly c ubical i n s hape, c lean and f ree f rom di rt and ot her f oreign
matter.
16.1.1.2 Crushed or Broken Stone : When c rushed or br oken s tone i s s pecified as t he c oarse
aggregate, it shall be hard, durable and free from excess of flat, elongated, soft, disintegrated particles, dirt
and ot her obj ectionable matter. The t otal quant ity of s uch del eterious m aterial i ncluding c lay l umps, soft
fragment, foreign material etc. shall not exceed 5% of the weight of the aggregate.
16.1.1.3 Crushed Slag : Crushed s lag shall be m ade f rom air-cooled blast furnace slag. It shall be of
angular shape, r easonably uni form in qual ity and de nsity a nd gener ally f ree from t hin, el ongated and s oft
pieces, d irt or o ther ob jectionable m atter. C rushed s lag s hall not w eigh less than 1120 k g per c ubic
metre and the percentage of glossy material in it shall not be in excess of 20. Water absorption of slag
shall not exceed 10% (IS 2386 Pt.III).
16.1.1.4 Kankar : Kankar s hall be t ough, hav ing a bl ue al most opal escent f racture. I t s hall not c ontain
any clay in the cavities between nodules.
16.1.1.5 Laterite : Laterite shall be hard, compact, heavy and of dark colour. The light coloured sandy
laterite as well as those containing much ochreous clay shall be rejected.
16.1.2 Aggregate-Fine
The f ine aggregate shall be t he f raction p assing 2 .8 m m sieve and retained o n 9 0 m icron s ieve. I t
shall consist of crusher run screenings, natural sand or a m ixture of both. These shall be c lean, hard,
durable, uncoated, dry and free from injurious, soft or flaky pieces and organic or deleterious substance.
The contents of organic and deleterious materials shall not exceed the limits specified in Table 16.3.
TABLE 16.3
Uncrushed Crushed
Coal and lignite 1% 1%
Clay lumps 1% 1%
Material passing through 75 microns (I.S.S.) Sieve 3% 3%
Shale 1% 1%
The s um of t he percentages of all del eterious m aterial s hall not ex ceed 5% . T ests for es timation of
deleterious materials and organic impurities shall be done as per IS 2386 (Pt. II).
Type A (Lowa Type) : The barbs shall have four points and s hall be f ormed by twisting two point
wires, each two turns, tightly around both line wires making altogether four complete turns.
Type B (Glidden Type) : The barbs shall have four points and shall be formed by twisting two point
wires, each two turns, tightly around one line wire making altogether four complete turns.
Vol-2 , 2013
TABLE 16.4
The number of lays between the two consecutive barbs shall very between 2 to 7.
The barbed wire sh all be for med b y t wisting to gether t wo l ine w ires, o ne or b oth containing t he
barbs. T he size of t he l ine a nd point w ires a nd barb spacings shall be as s pecified. T he p ermissible
deviation from the nominal diameter of the line wire and the point wire shall not exceed + 0.08 mm. The
line and poi nt w ires shall be circular i n s ection, free from s cales and ot her defects and shall be uni formly
galvanised. T he l ine w ire, s hall be i n continuous l engths, an d s hall not contain any w elds ot her t han
those in the rod before it is drawn. The distance between two successive splices shall not be less than
15 metres. It shall have the tensile properties as specified in Table 16.5.
TABLE 16.5
Tensile Properties
The number of reels to be selected at random for this purpose shall be in accordance with Table
16.6.
TABLE 16.6
Sampling Criteria
.
71 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
16.1.4 Binding Material
Binding m aterials to p revent ravelling o f w ater b ound m acadam c onstruction shall consist o f a fine
grained m aterial p ossessing pl asticity i ndex v alue of 4 t o 9 w hen t he w ater bou nd m acadam i s t o b e
used as a w earing c ourse, a nd 4 t o 6 w hen W .B.M. i s being adopted a s a s ub-base/base c ourse w ith
bituminous surfacing on top of it. The plasticity index shall be determined in accordance with IS 2720
(Pt.V). The quantity of binding material used in each layer shall be as per direction of Engineer-in-Charge.
Application of binding material may be dispensed with the approval of Engineer-in-Charge, where
screenings c onsisting of crushable t ype m aterial l ike m oorum o r g ravel a re us ed. W here earth cut f or
sub-grade formation is used as binder with the approval of Engineer-in-Charge, no s eparate pa yment
shall be made for collection of this binder material.
16.1.5 Bitumen Straight Run
A range of grades, from a very soft to a very hard consistency, can be produced by varying the
temperature and the rate of flow during distilling process. It shall conform to IS 73. Grades of bitumen for
different uses is given in Table 16.7.
Different Grades of Bitumen
VG-10 Bitumen: VG-10 is widely used in spraying applications such as surface-dressing and paving in very
cold c limate i n l ieu of ol d 80/100 P enetration gr ade. I t i s al so us ed t o m anufacture B itumen E mulsion a nd
Modified Bitumen products.
VG-30 Bitumen: VG-30 is pr imarily used t o c onstruct ex tra heav y du ty Bitumen pa vements t hat ne ed t o
endure substantial traffic loads. It can be used in lieu of 60/70 Penetration grade.
Bitumen of Grade VG-10 or VG-30 of Indian Oil make is to be used in all works wherever specified.
TABLE 16.7
Bitumen Grades
Grade Temperature to which it shall be
heated
I. FOR PAINTING (Surface Dressing)
1. Paving bitumen Grade 177 deg C to 190 deg. C
VG-10
2. Bitumen emulsion min. 50% bitu- (Cold application)
men content:- RS grade IS 8887
3. Cut backs RC-3 (rapid curing) IS 217 —do—
16.1.6 Bricks
Bricks shall be of class designation 75 unless otherwise stated. The specifications of bricks shall be as
sub head brick work as detailed in subhead 6.0.
16.1.7 Filler
The filler, where specified, s hall be an i nert m aterial, t he whole of which passes th rough a 7 10
micron sieve, atleast 9 0 p er c ent pa ssing through a 180 m icron sieve and no t less than 7 0 per c ent
passing t hrough a 90 m icron sieve. T he f iller s hall be cement, stone dust, hydrated lime, lime s tone dust,
flyash or any other non-plastic mineral matter approved by the Engineer-in-Charge.
72 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
.
TABLE 16.8
Aggregate Gradation including Filler
20.0 mm 100 —
12.5 mm 75-100 100
10.0 mm 60-85 75 - 100
4.75 mm 35-55 35 - 55
2.36 mm 20-35 20 - 35
600 micron 10-22 10 - 22
300 micron 6-16 6 - 16
150 micron 4-12 4 - 12
75 micron 2- 8 2-8
16.1.8 Flyash
Flyash shall conform to IS 3812
16.1.9 Lime
Lime shall be of specifications as directed by Engineer-in-Charge.
16.1.10 Moorum
It s hall be obt ained f rom pits of w eathered di sintegrated roc ks. I t s hould pref erably contain s ilicious
material and natural mixture of clay of calcarious origin. The size of moorum shall not be more than 20
mm.
For the whole of their length below the top of the rail the paling shall have a projecting dovetail shape at
the back which shall fit into dovetail grooves in each of the rails. That part of the palings projecting
above the t op r ail s hall be left square to pr event the dropping r ight through t he rails. The posts, rails and
pales shall be free from cracks, twists and such other defects.
73 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
placed ac curately i n pos ition agai nst t he finished end of c oncrete s lab. T he filler s hall r emain 20 mm
below the top surface of the pavement and shall extend upto the sub grade.
16.1.15 Screenings
Screening t o fill v oids in the coarse aggregate s hall g enerally c onsists o f t he same m aterial as t he
coarse aggregate. However, where permitted, predominantly non-plastic material such as moorum or
gravel ( other t han ri ver b orne ro unded m aterial) m ay be u sed f or t his p urpose provided l iquid limit an d
plasticity i ndex of s uch material i s b elow 20 and 6 r espectively and f raction p assing 7 5 m icron s ieve
does not exceed 10 percent.
As f ar as pos sible s creenings s hall c onform t o the gr adings s et-forth i n T able 16. 9. S creenings of
type A sh all b e u sed w ith c oarse aggregate of gr ade I of T able 16.2. Screenings of t ype A o r B as
specified shall be used with coarse aggregates of grading 2. Type B screenings shall be used with
coarse aggregates of gr ading 3. T he use of screenings m ay b e omitted i n t he c ase of soft aggregates
such as brick m etal, k ankar a nd l aterite. F or s creenings l ike moorum or gravel t he gradings given i n
Table 16.9 shall not be binding.
TABLE 16.9
Grading for Screenings
16.1.17 Soil
Soil ha ving a pl asticity index (PI) between 5 and 20 shall be s uitable. At least one t est for 200 c ubic
metre of soil for determining P.I. shall be conducted.
16.1.18 Stones
These shall be clean, hard, sound and durable stones, free from decay and weathering. They shall be
in blocks and hammer dressed on all sides. The size of pitching stones shall be approximately 22.5 cm in
depth and not less than 15 cm in any other direction.
74 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
16.1.19 Stone Chippings For Surface Dressing/Painting
The s tone c hipping s hall consist of f airly c ubical f ragment of c lean, hard, tough and durab le ro ck o f
uniform q uality t hroughout. T hese shall b e obtained by c rushing s tone river g ravel ( shingle) o r other
approved materials. Rounded gravel shall be used only i f s pecifically per mitted by t he Engineer-in-
Charge. T he c hipping shall be f ree of el ongated or f laky p ieces, s oft or di sintegrated s tone, s alt, al kali,
vegetable matter, dust and adherent coatings. They shall conform to the quality requirements of Table
16.10.
However, t he t otal qua ntity of s uch del eterious m aterial i ncluding c lay l umps, s oft f ragments, f oreign
material shall not exceed 5% of the weight of the aggregate.
The aggregate shall be got tested to ensure the requirements specified in Table 16.10.
TABLE 16.10
Physical Requirements of Aggregates for Surface Dressing
The R.C.C. boundary stones shall be cast in cement concrete 1 : 1 ½ : 3 (1 cement : 1 ½ coarse
sand : 3 graded stone aggregate 20 mm nominal size), reinforced with 10 mm diameter tor steel bars or as
directed and f inished smooth with c ement m ortar 1 : 3 ( 1 cement : 3 f ine s and ). T he specifications f or
R.C.C. work shall apply.
75 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
Kilometre stones for every fifth kilometre for National Highways, State highways a nd m ajor di strict
roads shall be of the size 50 x 152.5 x 25 cm. One cm offset shall be provided around the stone slab in
13 c m h eight above t he formation level to s erve a s the pedestal. This k ilometre s tone s hall b e fixed at
right angles to the centre line of carriage way. It shall show the name and distance of the terminal or t he
starting station al so abov e those o f i ntermediate t owns. O n t he side facing the carriage w ay, t he nu mber
of t he kilometre s tone i n continuity of ordinary k ilometre s tone s hall be i nscribed (without the nam e of
any place).
Kilometre stone for other district roads and village roads shall be of the size 35 × 93.5 × 18 cm. One
cm offset shall be provided around the stone slab in 10 c m. height above the formation level to serve as
the pedestal. It s hall be fixed at right ang les to the c entre line of c arriage w ay and s hall indicate the
name and the distance of the next important station. On the side facing the carriage way, the number of
the kilometre stone shall be inscribed (without the name of any place).
The k ilometre s tones shall b e f ixed at t he e dge of t he r oad way o utside t he shoulder o n e specially
erected platforms, if necessary. In cutting these shall be fixed clear of the shoulder and the side drain as per
Fig. 16.7(A). On existing roads the stones shall be fixed on the side of the road other than that on which
miles stones exist. On new roads, these shall be located on left hand side of the road as one proceeds
from the station from which kilometre count starts.
(a) Kilometre Stones in R.C.C. : It shall be cast in cement concrete 1:2:4 (1 cement : 2 coarse sand :
4 gr aded st one a ggregate 20 mm nominal s ize) w ith rei nforcement as d irected a nd f inished
smooth with cement mortar 1 : 3 (1 cement : 3 fine sand) on ex posed s urfaces above the gr ound.
The specifications for R.C.C. work shall apply.
(b) Kilometre Stone Slabs : The stone slabs shall be of red or white sand stone unless otherwise
specified. The slab shall be hard, even, sound and durable. Slabs shall have been sawn or chi-
selled in a plane parallel to the natural bed of the stone. The slabs shall be chisel dressed on the
exposed surfaces above ground facing road side, so that the dressed face shall not be more than
3 mm from a straight edge placed on it. The thickness of the slab shall be u niform and as
specified i n t he item with a per missible t olerance of 1. 5 m m. T he t hickness s hall be m easured
correct to 3 mm.
16.2.0 In s ub-grade composed of c lay, f ine s and or ot her s oils t hat m ay be f orced up i nto t he c oarse
aggregate during rol ling o peration, an i nsulation l ayer of s uitable t hickness of granul ar m aterials or o ver
size b rick a ggregate not l ess t han 10 c m t hick s hall be pr ovided f or bl anketting t he s ub-grade, w hich
shall be paid for separately, unless otherwise specified.
In slushy soils or in areas that are water logged, special arrangements shall be made to improve the
sub-grade and t he t otal pav ement t hickness s hall be des igned af ter t esting t he pr operties of t he s ub-
grade s oil. N ecessary p rovision f or t he s pecial t reatment required s hall be made i n t he proj ect a nd paid
for separately.
Vol-2 , 2013
16.2.2 Consolidation
The sub-grade shall be consolidated with a power road roller of 8 to 12 tonnes. The roller shall run
over the sub grade till the soil is evenly and densely consolidated and behaves as an elastic mass (the
roller shall pass a minimum of 5 runs on the sub grade). All undulations in the surface that develop due
to rolling s hall be m ade good w ith material or quarry spoils as the cases may be and the sub-grade i s
rerolled.
TABLE 16.11
Permissible Tolerances of Surface Evenness of Sub Grade
Where t he s urface i rregularity of t he sub grad e f alls out side t he s pecified t olerances, t he c ontractor
shall be l iable t o rectify these w ith fresh material or quar ry spoils a s t he case m ay be, and the sub-grade
rerolled to the satisfaction of Engineer-in-Charge.
16.2.4 Measurements
The length a nd width shall b e m easured correct t o a cm. The area s hall be worked out in s quare
metre, correct to two places of decimal.
16.2.5 Rate
The rate for pr eparation and c onsolidation o f sub gr ade s hall i nclude the cost o f materials and l abour
involved for all the operations mentioned in above unless otherwise specified.
16.3 SAND PAD FOUNDATION & EMBANKMENTS (UNDER OPTIMUM MOISTURE CONDITIONS)
16.3.1 In t he c ase of ear th w ork c onsolidated under opt imum moisture c onditions eac h l ayer of ear th
shall be carefully moistened to give field moisture content of about +1% to -2% of the optimum moisture
content (O MC). The OMC s hall be determined according t o I S 2720 (Pt.VIII) Methods of Tests f or S oils.
Each l ayer s hall t hen be compacted by M echanical v ibrators i n c ase of S and P ad f oundation and f or
other areas, rolling with 8 to 10 tonnes power road roller and a s heep foot roller if required. The required
amount of water shall be added during consolidation to keep the moisture content of the soil at the optimum
as per test. The density to be achieved for each layer of the material shall be minimum 85% of the density
obtained in the laboratory (Proctor Method).
16.3.2 Each compacted layer shall be tested in the field for density and accepted before the operations for
next layer are begun.
16.3.3 Control on compaction in the field shall be exercised through frequent moisture content and
density det erminations. A s ystematic r ecord o f t hese shall be maintained. A t al l times dur ing c onstruction
the top of the embankment shall b e maintained at s uch cross f all as will s hed water and p revent
ponding.
Vol-2 , 2013
determinations and the average of these 5 determinations shall be treated as the field density achieved.
The determination of density shall be as per IS 2720 (Pt. XXVIII).
16.3.4.2 In general the control at the top 40 cm thickness of the formation shall be more strict with
density m easurements being do ne at t he r ate of on e m easurement f or 2 50 s qm of c ompacted a rea.
Further for the determination of the mean density the number of tests in one measurement shall not be
less t han 10 and t he w ork will be accepted i f t he mean dry dens ity equals or ex ceeds t he specified
density.
16.3.4.3 When dens ity measurements reveal an y s oft a reas i n the e mbankment, t he E ngineer-in-Charge
shall direct that these be compacted further. If inspite of that the specified compaction is not achieved the
material in t he s oft ar eas s hall b e r emoved and r eplaced by a pproved m aterials an d c ompacted to the
satisfaction of the Engineer-in-Charge.
16.3.4.5 Soil s uitable f or c onsolidation under O .M.C. c onditions s hould pr eferably hav e t he f ollowing
characteristics :
16.3.4.6 The Engineer-in-Charge may, however, relax these requirements taking into account availability of
materials, cost of transportation and other relevant factors.
16.3.4.7 Various test required to be conducted on the borrow material with their recommended
frequency are indicated below. All the test need not be stipulated on every project. Depending upon site
condition etc. on ly s ome may be found necessary a t a p articular pro ject. The frequency o f testing
indicated refers generally to the minimum number of tests to be conducted. The rate of testing must be
stepped up a s found nec essary depe nding up on t he v ariability of the materials and compaction methods
employed at a project.
(a) Gradation : At least one t est for each kind of soil. Usual rate of testing 1 t o 2 t ests per 80 00 cum
of soil.
(b) Plasticity : At least one test for each kind of soil. Usual rate of testing 1 to 2 tests per 8000 cum of
soil.
(c) Proctor Tests : At the rate of 1 to 2 tests per 8000 cum of soil.
(e) Moisture contents : One test for every 500 cum of soil.
16.3.4.8 Measurements : The filling shall be measured and quant ity o f ear th w ork computed from c ross
sections of filling or the embankment. No deduction shall be made for voids.
16.3.4.9 Rate shall include the cost of all operations described above including operation mentioned in
16.3 to the extent applicable.
78 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
16.4 SUPPLYING AND STACKING OF MATERIALS: DELETED
16.5.1 Earthwork connected with road construction fall broadly into three categories.
(c) Earthwork in fillings in Sand Pad foundation & embankments (under optimum moisture conditions).
16.5.2 Detailed specifications r elating t o Earthwork a lready described i n s ubhead Earth Work,
Specification so far as the various options in the earthwork for road construction as indicated below shall be
applicable.
16.5.3 In addition to the above, there are certain special requirements of earthwork for road
constructions, especially in embankments and excavations from borrow pits. These shall broadly
conform to.
(a) IRC : 36 Recommended practice for construction of earth embankments for road works.
(b) IRC : 10 Recommended practice for borrow pits for road embankments by manual operations.
16.6.0 In addi tion to w hat is des cribed in 16 .5 above, the following shall apply : m aterials us ed in
embankments shall be e arth m oorum, gravel, a m ixture of t hese or a ny ot her m aterial approv ed by t he
Engineer-in-Charge. Such m aterials s hall be free of l ogs, s tumps, ro ots, rubbish or any ot her ingredient
likely t o det eriorate or affect the stability of the embankment. The work shall b e so planned and ex ecuted
that the best available materials are saved for the top portion of the embankment.
Highly expansive clays exhibiting marked swell and shrinkage properties may be deposited only at the
bottom of the embankment and no such material shall be placed nor permitted to remain in the top 500
mm portion of the embankment below the sub-grade.
79 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
16.6.2 Source of Supply
16.6.2.1 The m aterial used i n embankment s hall be obtained either f rom c utting high ground or from
borrow p its as directed b y t he E ngineer-in-Charge. I n c ase of ro ad em bankments, the borrow pi ts m ay
be ex cavated al ong t he sides of the road s o as t o form road side drains with proper s lopes and sections.
The clear berm width between the toe of the bank and the inner edge of the borrow pits shall be
specified b y t he E ngineer-in-Charge but i t shall not be l ess than 5 metres a fter making due al lowance for
future development.
16.6.2.2 Borrow pits shall be rectangular in shape with one side parallel to the centre line of the road. If
on road land, these shall be dug as near the boundary as possible. Borrow pits shall not be dug
continuously. R idges o f no t le ss t han 8 m etres w idth s hould be left at intervals no t ex ceeding 300
metres. S mall dr ains s hould be c ut t hrough t he r idges t o f acilitate dr ainage. B orrow pi ts s hall be w ell
drained. The bed l evel o f t he bo rrow pi ts, s hall, as far as pos sible, s lope down p rogressively t owards the
nearest cross drain, if any and shall not be lower than the bed of the cross drain. Borrow pits shall not be
dug within 0.8 km of towns or villages. If unavoidable t hese shall not exceed 30 c m in depth and shall be
drained.
16.6.2.3 Where i t be comes necessary t o borrow f illing m aterials f rom t emporarily a cquired cultivable
lands the depth of borrow pits shall not exceed 45 cm. The top soil to a depth of 15 c m shall be stripped
and stacked aside. Thereafter soil shall be dug out to a further depth not exceeding 30 cm and used in
forming the embankment. The top soil shall then be spread back on the land.
16.6.2.4 In case of flood and marginal ban ks, earth shall b e obtained from borrow p its on t he river side
of the b anks. No b orrow pit shall b e excavated o n the l and side of t he bank, u nless permitted by the
Engineer-in-Charge in w riting de pending upon the depth o f bo rrow p its an d he ight o f em bankment.
However the minimum berm width between the toe of the bank and the edge of the borrow pits on the
river side shall be 15 metres and that between the toe of the bank and the edge of the borrow pits on the
land side 25 metres.
16.6.2.5 Guide-banks shall be constructed from material obtained from excavation for laying stone
aprons and f urther bo rrow pi ts ex cavated i f nec essary, ac cording t o t he di rections of the E ngineer-in-
Charge.
16.6.3.2 Embankment material shall be l aid in 20 cm layers which shall be continuous and parallel to the
finished grade. The placing of earth fill shall be done in the full width of embankment including slopes,
and the section of formation shall be kept slightly sloping away from the centre to avoid pools of water
forming due to r ain. The height of f illing i n different s ections shall be uniform as far as pos sible. A ll clods
shall be brok en w hile the ear th is being pla ced. O rganic matter of any kind s hall be rem oved and
disposed off as directed by the Engineer-in-Charge.
16.6.3.3 Joining of old and new embankments shall be done by stepping in an overall slope of about 1 to 5.
16.6.3.5 If the material delivered to the road bed is too wet it shall be dried by aeration and exposure to
the sun, till the moisture content is acceptable for compaction. It shall then be rolled with roller of
minimum 1 /2 tonne w eight, no t less than 5 t imes, till i t gets e venly and dens ely c onsolidated w ith
80 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
wooden or steel r ammers of 7 to 1 0 kg weight h aving a base of 20 cm square or 20 cm diameter. The
labour f or r amming shall be atleast o ne rammer t o s ix diggers. E very t hird l ayer of e arth a nd t he t op
most l ayer s hall b e w ell c onsolidated w ith a po wer r oller of m inimum 8 t onnes w eight, r olled n ot l ess
than 5 t imes, t ill t he s oil behav es as an el astic m aterial and get s c ompressed onl y el astically under t he
load of roller.
16.6.3.6 Dressing : The embankment shall be dressed neatly as per designed section and grade, after it
has b een c ompleted a nd t horoughly c onsolidated. T he t op a nd s lopes s hall be p rotected f rom a ny
damage and maintained, till the work is completed and handed over to the Engineer-in-Charge.
16.6.4.1 To avoid interference with the construction of abutments, wing walls or return walls of
culvert/bridge str ucture, the co ntractor sh all at points to be determined by the E ngineer-in-Charge
suspend w ork on em bankments f orming approaches to such structures, until such time as the
construction of the latter of sufficiently advanced to permit the completion of approaches without the risk of
interference of damage to the bridge works.
16.6.4.2 Unless dir ected oth erwise, t he f illing around cu lverts, br idges and other structures upto a
distance of twice t he h eight of the embankment s hall no t be done. The fill m aterial shall no t be placed
against an y abutment or w ing w all u nless permission ha s be en given b y the Engineer-in-Charge but in
any case not until the concrete or masonry has been in position for 14 days. The embankment shall be
brought up si multaneously i n equal l ayers o n e ach s ide of t he s tructure to av oid displacement a nd
unequal p ressure. T he sequence o f w ork in this regard s hall be go t appr oved from t he Engineer-in-
Charge.
16.6.4.3. Where t he prov ision of a ny f ilter m edium is s pecified behi nd t he ab utment, t he same shall be
laid i n l ayers s imultaneously with t he l aying of f ill m aterial. The m aterial used f or f ilter m aterial shall
conform t o t he requirements f or f ilter m edium as s pecified. P ayment f or p roviding f ilter material s hall be
made separately under relevant items.
16.6.4.4. Where it may be impracticable to use power roller or other heavy equipment, compaction shall be
carried out b y mechanical tempers o r ot her methods appr oved b y t he E ngineer-in-Charge. C are shall be
taken to see that the compaction equipments does not hit or come too close to any structural member so as
to cause any damage to it.
16.6.5.1 When a n ex isting e mbankment is t o be w idened a nd i ts s lope i s s teeper than 4:1 c ontinuous
horizontal be nches ea ch at l east 0.3 m etre w ide, shall be c ut into the ol d s lope f or en suring ad equate
bond with t he f resh e mbankment material t o b e a dded. T he m aterial o btained f rom cutting of benches
could be utilised in the widening of the embankment. However, when the existing slope against which the
fresh m aterial i s t o be pl aced i s f latter t han 4: 1 t he s lope surface may on ly be pl oughed or s carified
instead of resorting to benching.
16.6.5.2 Where t he w idth of t he w idened p ortion is ins ufficient t o pe rmit t he u se o f st andard ro llers
compaction shall be carried out with the help of sheep’s foot roller mechanical tampers or other
approved equipment. End dumping of material from trucks for widening operations shall be avoided
except i n di fficult circumstances w hen t he ex tra width is t oo na rrow t o per mit t he movement o f an y other
type of hauling equipment.
81 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
16.6.6 Cutting
Where t he f ormation l evel of t he road i s l ower t han t he ground l evel, cutting shall be done up t o
formation level. Side slopes except in rock cutting shall be evenly and truly dressed.
16.6.6.1 Disposal of Surplus Earth : Earth f rom cutting s hall be ut ilised f or f illing i n em bankment as
directed b y t he E ngineer-in-Charge. E arth not r equired for e mbankment s hall be di sposed o ff as di rected
by t he E ngineer-in-Charge. The a rea w here the s urplus ear th i s di sposed o ff shall be l evelled and neat ly
dressed..
16.6.6.2 Measurements : The qua ntity of ear th w ork s hall be c alculated b y m easuring t he v olume of
earth e xcavated from the bo rrow pits a nd shall be d one as specified where it is n ot p ossible o r
convenient t o t ake m easurements f rom c utting t he f illing shall be m easured and t he quant ity o f ear th
work c omputed from c ross sections o f the f illing. The qua ntity of ea rth w ork s o c omputed s hall be
reduced by 5% to arrive at the quantity for payment.
For the purpose of taking measurements of earth work in cutting or embankment, ground levels of the
area shall be recorded as specified in 16.5.
16.6.6.3 Rate : It includes the cost of all the operations described above. The lead and lift for depositing
the earth or disposal of uns uitable m aterial s hall be as described in the des cription of item. It als o
includes the Sub Head 2.0 Earth Work.
TABLE 16.12
82 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
TABLE 16.13
16.7.3 The quantity of binding material required for 75 mm (approximate) compacted thickness will be
0.09 cu m/10 s qm in t he case of W .B.M. b ase co urse an d 0.1 3 cu m/10 s qm w hen th e W .B.M. is to
function as a surface course.
Where the existing surface over which the sub base of W.B.M. is to be laid is black topped, to ensure
effective internal dr ainage, furrows 50 m m x 50 m m ( depth o f furrows i ncreased t o reach bottom o f
bituminous layer where necessary) at one metre intervals shall be cut in the existing bituminous surface at
45 degree C to the central line of the carriageway before the W.B.M. is laid.
The p ractice of l aying W.B.M. af ter excavating a t rench s ection i n the f inished f ormation m ust b e
completely avoided.
The s urface of t he aggr egate s pread s hall be c arefully trued up an d a ll high or l ow s pots r emedied b y
removing or adding aggregate as may be required.
83 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
The W .B.M. su b-base shall be normally constructed in layer of 100 mm compacted thickness and
W.B.M. base shall be normally constructed in layers of 75 mm compacted thickness. No segregation of
large or fine par ticles shall be al lowed and t he c oarse aggr egate as s pread shall be o f uni form g radation
with no pockets of fine material.
The coarse aggregate shall n ormally n ot b e spread i n lengths e xceeding t hree d ays a verage work
ahead of the rolling and blending of the proceeding section.
16.7.7 Rolling
Immediately f ollowing at s preading of t he c oarse aggregate, i t s hall be compacted to t he f ull width by
rolling w ith ei ther t he three-wheel-power-roller o f 8 to 10 t onnes capacity or an equivalent v ibratory r oller.
Initially, l ight rolling i s to be done, w hich shall be di scontinued w hen t he aggr egate i s par tially c ompacted
with sufficient void space in them to permit application of screenings.
The rol ling shall beg in f rom t he edges w ith t he rol ler runni ng f orward an d b ackward an d add ing the
screenings simultaneously until the edges have been firmly compacted. The roller shall then progress
gradually f rom t he edg es to t he c entre, p arallel t o t he c entre l ine of t he road and ov erlapping un iformly
each preceding rear wheel track by one half width and shall continue until the entire area of the course
has bee n rolled b y t he rear w heel. R olling s hall continue unt il t he road metal i s thoroughly keyed with no
creeping o f m etal ahea d of the roller. O nly s light sprinkling of w ater m ay be done during ro lling, if
required. O n s uperelevated curves, the rolling s hall pr oceed from the l ower e dge and pr ogress gr adually
continuing towards the upper edge of the pavement.
Rolling of s ub b ase sh all not b e do ne w hen th e s ub-grade i s so ft or yi elding or when t he ro lling
causes a wave like motion in the sub-base or sub-grade. When rolling develops irregularities that
exceed 12 mm when t ested w ith a t hree metre straight edg e, the i rregular s urface s hall be loosened and
then a ggregate added t o or r emoved fr om it as required and t he area rolled until it gi ves a u niform
surface conforming t o t he des ired cross-section an d g rade. The surface shall al so be checked
transversely by template for camber and any irregularities corrected in the manner described above. In no
case shall the use of screenings to make up depressions be permitted.
84 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
16.7.10 Application of Binding Material
After t he application of s creenings and ro lling, a suitable bin ding material s hall be applied at a
uniform and s low rat e i n t wo or m ore s uccessive t hin l ayers. After ea ch appl ication of bi nding m aterial,
the s urface s hall be c opiously s prinkled w ith w ater and t he r esulting slurry s wept i n w ith han d b rooms or
mechanical brooms or bo th s o as t o f ill the v oids properly. T he s urface s hall t hen be r olled by a 8 -10
tonne roller, water being applied to the wheels in order to wash down the binding material that may get
stuck t o t he w heels. The s preading of b inding m aterial, sprinkling of w ater, s weeping w ith br ooms a nd
rolling shall continue until the slurry that is formed will, after filling the voids form a wave ahead of wheels
of the moving roller.
TABLE 16.14
The longitudinal profile shall be checked using a 3 meter long straight edge and graduated wedge at the
middle of each traffic lane along a l ine parallel to the Centre line of the road. The transverse profile shall
be checked with adjustable template at intervals of 10 meters. For base with stone aggregate of size 63
to 45 mm and 53 to 22.4 mm surface evenness to be as per Table 16.15.
TABLE 16.15
15 mm 10 mm
63-45 m m
and
53-22.4 mm 12 mm — 30 8 mm
85 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
The longitudinal profile shall be checked with a three metre long straight edge and graduated wedge at
the middle of each traffic lane along a line parallel to the centre line of the road. The transverse
profile shall be checked with adjustable templates at intervals of 10 metres.
16.7.14 Meaurements
The l ength an d br eadth s hall be m easured to the n earest c entimetre. T he d epth of c onsolidated l ayer
shall be computed to n earest half c entimetre b y taking a verage of depths at the c entre a nd at 30 cm
from t he left a nd right e dges at a cross section t aken at 1 00 metre interval or less as decided b y the
Engineer-in-Charge b y m aking s mall pi ts. T he c onsolidated c ubical c ontents s hall be c alculated i n c ubic
metres correct to two places of decimal. The cubical contents shall be compared with net quantity of stone
aggregates paid (that is stacked quantity - 7.5%). If the cubical contents are within (±) 5% of the paid net
stacked quantity of stone aggregates, the work shall be treated as acceptable. If the cubical contents is
short of net s tacked qua ntity by m ore t han 5% t hen t he pay ment s hall be r estricted t o t he quantities
derived from cubical content.
16.7.15 Rate
The r ate shall i nclude t he c ost of all l abour a nd materials i nvolved i n al l t he operations described
above, except cost of stone aggregate, kankar moorum, screenings and bajri, for which separate
payments shall be made. Where W.B.M. is to be laid over an existing road, scarifying and consolidation of
the aggregate received from scarifying shall be paid for separately.
16.8 WATER BOUND MACADAM WITH BRICK AGGREGATE (OVERBURNT (JHAMA) BRICK AGGREGATE)
16.8.0 Over burnt (jhama) brick aggregate of size 120 mm to 40 mm or 90 mm to 45 mm is used. This is
used w hen s tone aggr egate i s c ostly and ov er bur nt br ick aggr egate i s av ailable at r easonable r ates.
This is also used over soft clayey sub grade with high moisture contents and low CBR values.
16.8.3 For spreading aggregate clause 16.7.6 shall apply except that the quantities of materials shall be as
given above.
16.8.4 The r olling shall b e d one a s s pecified i n 1 6.7.7 except t hat rolling s hall b e d one w ith t he l ight
power roller. T he us e of s creenings s hall al so be om itted. R olling s hall be done 3 t o 5 t imes for eac h
layer.
16.8.5 For r olling with Binding material c lause 16. 7.10 s hall appl y ex cept t hat rolling s hall be done w ith a
light power roller instead of a heavy road roller and water shall not be used during rolling. Rolling shall be
done 3 to 5 times for each layer.
86 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
16.8.6 Surface Evenness rectification of Defective construction, Measurements and Rate shall be as
specified under 16.7.12 to 16.7.15.
In c ase of m ade up soil, ad equate w atering shall be d one so t hat e arth s ettles do wn as m uch a s
possible and t he same rolled up w ith a m inimum three tonnes or light power roller, as di rected by the
Engineer-in-Charge.
16.9.2 Laying and Packing Brick Aggregate : Shall be as s pecified in 16. 7.6 ex cept t hat br ick
aggregate shall be used instead of stone aggregate and laid to 7.5 cm depth unless specified otherwise.
16.9.3 Consolidation : Shall be as specified in 16.7.7 except that rolling shall be done by three tonnes or
light power roller instead of by heavy road roller as directed by the Engineer-in-Charge.
16.9.4 Rolling with Blinding Materials : Shall be as s pecified in 16. 7.10 except t hat r olling s hall b e
done by three tonnes or l ight power roller instead of by heavy road roller as directed by the Engineer-in-
Charge.
16.9.5 Measurements
The finished work shall be measured between the kerb or channel stones or brick edging etc. as the
case m ay be . Length an d breadth shall be m easured, correct to a c m. The are a s hall be c alculated i n
square metres, correct to two places of decimal.
16.9.6 Rate
The rate shall include the cost of materials and labour involved in all the operations described above.
16.10.1 Edging
Trenches of specified width and depth shall first, be made along the edges of the wearing course of the
road to receive the bricks. The bed of trenches shall be c ompacted to a f irm and even surface and then
the bricks shall be laid with its length at right angle or parallel to the side of the road depending upon
the width of edging as specified in the item. The bricks shall be abutting against the wearing course,
true to line, gradient and in camber with the finished road surface at the edge.
16.10.2 Finishing
Berms an d road e dges s hall be restored w ith e xcavated e arth a nd c onsolidated by manually. A ll
surplus earth including rubbish etc. shall be disposed off as directed by the Engineer-in-Charge.
16.10.3 Measurements
Length of the finished work shall be m easured in running metres along the edges of the road correct
to a cm.
16.10.4 Rate
The rate shall include the cost of materials and labour involved in all the operations described above.
87 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
16.11 SCARIFYING METALLED (WATER BOUND) SURFACE
16.11.1 Scarifying
All dirt, dust, cacked up mud, slush, animal droppings, vegetation and all other rubbish shall be
removed from the water bound macadam surface.
The macadam sur face s hall b e sc arified to a de pth of a pproximately 5 c m w ith su ch a dditional
picking of high parts of the road as may be necessary to the required camber and gradient as directed by
the Engineer-in-Charge. Any hollows that remain after picking shall be filled with new aggregate 50 mm
nominal size and well consolidated to bring the surface to template.
16.11.2 Finishing
The scarified aggregate shall be raked to bring smaller stones on the top and surface brought to the
required camber and gradient with tolerance of 12 mm longitudinally as well as transversely.
All rubbish etc. shall be disposed off as directed by the Engineer-in-Charge. Scarifying operation w ill
also include consolidation with road roller the aggregate received from scarifying, although this
aggregate will be consolidated along with aggregate of new wearing course to be paid separately.
16.11.3 Measurements
The finished work shall be measured between the kerb or channel stones or brick edging etc. as the
case m ay b e. Length an d breadth shall be m easured correct to a c m. The area s hall be c alculated i n
square metres correct to two places of decimal.
16.11.4 Rate
The rate shall i nclude t he c ost o f l abour and m aterials i nvolved i n al l t he oper ations des cribed abo ve
except the cost of stone aggregate which shall be paid for separately.
16.12.1 Stones
These s hall b e c lean, har d s tones, free from de cay an d w eathering. They s hall b e in b lock and
hammer dressed on all sides.
The size of the pitching stones shall be approximately 22.5 cm.in depth and not less than 15 cm. in
any other direction.
16.12.3 Pitching
Pitching shall be of 22.5 depth unless specified otherwise. Profiles shall be put up b y means of pegs
and strings or by placing stones, at intervals of not more than 15 cm. Stones shall then be laid closely in
position in bet ween t he pr ofile and firmly em bedded w ith joints staggered and w ith ex posed faces true t o
line, gradient and in uniform slope throughout.
Cross bands of approximately 22.5 cm. w idth through bond s tones equal t o the f ull depth of pi tching
shall be p rovided at an interval o f app roximately 3 m etres centre to c entre both longitudinally and
transversely.
The i nterestices bet ween adjacent s tones s hall be f illed i n w ith s tones of pro per s ize, w ell dri ven i n
with crow bars to ensure tight packing and complete filling of all interstices. Such filling shall be carried on
simultaneously with the placing in position of the large stones and shall in no case be permitted to fall
88 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
behind. F inal w edging s hall be done w ith t he l argest s ized c hip prac ticable, eac h c hip be ing w ell dri ven
home with a hammer so that no chip is possible of being picked up or removed by hand.
16.12.4 Measurements
The m easurements s hall be taken in s qm. T he ar ea o f p itching for dr ains shall be c alculated b y
multiplying t he per imeter ( bed w idth pl us side s lopes) b y t he length o f the pi tching. The l ength, width and
side slope shall be measured correct to a cm.
16.12.5 Rate
The rate s hall i nclude t he c ost of the materials and l abour i nvolved i n all the operations des cribed
above, except pitching stone, if specified, shall be paid for separately.
16.13.1 Bricks shall be all second class unless otherwise specified . The specification of bricks shall be as
per SH 6.00 (Brick work) Specifications.
16.13.2 Preparation of Surface
The sides and bot tom o f earth work to be pi tched, shall be br ought to the required slope and
gradients and shall be compacted to a firm and even surface.
16.13.3 Pitching
Pitching shall b e 1 0 cm. in d epth or in multiples of 10 cm. a s specified. Profiles shall first be put up
by means of pegs and strings or b y placing bricks at intervals not more than 15 cm. Bricks shall then be
laid i n p arallel rows b reaking b ond or H erring -bone bond p attern as di rected. I n t he c ase of d rains,
bricks shall be laid on bed width in parallel rows breaking bond and on sides in either of the above
manner. At the top, the toe and at e very 3 m . intervals, brick courses shall be laid with bricks on en ds.
All bricks shall be l aid closely in position and firmly embedded, true to line, gradient and in uniform slope
through out.
16.13.4 Measurements
Para 1 6.12.4 s hall a pply, exc ept th at t he measurements o f th e d ry pitching 1 0 c m. d eep f or t he
drains shall be taken by adding 10 cm. on either side to the perimeter of the drain so as to allow for the
top 20 c m. c ourses. In this c ase the p erimeter of t he drain (bed w idth plus s ides s lopes) pl us 20 c m.
multiplied with the length of the pitching shall give the area of the pitching in sqm.
16.13.5 Rate
The rate shall include the cost of material and labour involved in all the operations described above.
16.14.1 Cutting
All road c rossings shall be cut i n hal f t he w idth at a t ime and repaired, unl ess ot herwise per mitted b y
the Engineer-in-Charge. Cutting shall be straight and uniform in width. Soling stone and aggregate
obtained f rom c utting macadam s hall b e s tacked s eparately, c lear o f t he ro ad s urface. A ggregate s hall
be screened. Stones of size below 20 mm and with rounded edges shall be discarded and disposed.
16.14.1.2.1 After t he t renches have b een f illed i n w ith excavated earth i n layers of 15 cm t hickness,
watered, w ell consolidated with heavy iron rammers and brought to sub grade level, soling stone
obtained f rom c utting s hall b e l aid a s per existing s oling a nd c onsolidated w ith h eavy i ron rammers.
Where the e arth c onsolidation is w ell d one, no s ettlement n eed oc cur s ubsequently, for this ex cess
watering should be avoided.
89 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
16.14.1.2.2 New aggregate 50 m m nom inal s ize or as required, s hall be a dded t o ol d agg regate an d
spread over to a depth of 7.5 cm as specified in 16.7.6. This shall then be consolidated with hand roller
or h eavy i ron r ammers, as di rected, f irst with l ight s prinkling then w ith s ufficient a pplication of water t ill
the aggr egate has bec ome adequ ately c onsolidated and does not get di splaced. A ll undul ations s hall be
loosened b y hand pi cking, surplus aggregate re moved fr om h igh s pots and d epressions fil led with
surplus and ne w a ggregate an d the s urface c ompacted ag ain. W hen thoroughly c onsolidated, kankar
moorum a nd r ed bajri, f reshly collected s hall b e s pread o ver i t i n 1 2 m m l ayer and c onsolidated with
hand ro ller or h eavy i ron ra mmers, with s ufficient application of sufficient water t ill a uniform s urface i s
obtained.
16.14.2.3 The finished surface shall be in camber and left a little higher than the adjoining road surface to
allow for any settlement on drying.
16.14.1.3 Measurement : Length and width of cutting shall be measured correct to a cm. The area shall be
calculated in square metre, correct to two places of decimal.
16.14.1.4 Rate : The rate shall include the cost of materials and labour involved in all the operations
described above.
16.14.2.1 Cutting, m aking goo d a nd measurements s hall be as s pecified i n 16 .14.1 ex cept the top
bituminous surface shall be finished as per the existing surface or as directed by the Engineer-in-Charge.
The item shall include cutting and restoration of W.B.M. portion as well as Bitumen portion.
16.14.2.2 Rate : The rate shall include the cost of materials and labour involved in all the operations
described above.
16.15.1 Cutting
Cutting shall be straight and uniform in width. Brick aggregate obtained from cutting shall be
screened, aggregates of smaller size discarded and disposed off and rest stacked clear off pathway.
16.15.3 Measurements
Length a nd w idth of c utting s hall b e m easured c orrect to a c m. T he area shall b e c alculated i n
square metre correct to two places of decimal.
16.15.4 Rate
The rate shall include the cost of materials and labour involved in all the operations described above.
16.16 FENCING WITH G.I. BARBED WIRE AND RCC POSTS (FIG. 16.9)
16.16.1 Materials
R.C.C. posts and struts shall be as specified in 16.1.12. G.I. Barbed wire shall be as per IS 278.
90 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
16.16.2 Spacing of Posts and Struts
The spacing of posts shall be three metres centre to centre, unless otherwise specified, or as
directed by t he E ngineer-in-Charge t o suit t he dimensions of t he area t o be f enced. E very 15th, l ast but
one end post and corner posts shall be strutted on both sides and end posts on one side only.
16.16.5 Measurements
Total length of G.I. barbed wire shall be measured in running meter correct to a cm.
16.16.6 Rate
The rate shall include the cost of labour and materials involved in all the operations described above but
excluding the cost of posts, s truts, tu rn buckle, s training bolts and excavation and c oncrete in
foundations for which separate payments shall be made under respective items.
16.17.1 Materials
G.I. Barbed wire shall be as per IS 278 and angle iron shall be as per subhead - 10.00 steel work of
Specifications. The angle shall be of size 40 × 40 × 6 mm.
Vol-2 , 2013
then the di agonal c ross wires and l astly even rows of wires. The barbed wire shall be held b y t earing t he
holes of 1 0 mm d ia in the po st and tied with G.I. wire, turn b uckles and straining bolts shall b e u sed a t
the end post, if so specified.
16.17.5 Measurements
This shall be as per 16.16.5.
16.17.6 Rates
The rate s hall include t he c ost o f labour and materials i nvolved i n al l the oper ations de scribed abo ve
but excluding the cost of post struts turn buckle straining bolts and excavation and concrete in
foundation f or which s eparate pay ments shall be m ade under res pective i tem. A ngle i ron pos t shall be
paid as per similar item of subhead Steel work of Specifications. No ex tra p ayment
shall be made for making holes in angle and nothing shall be deducted on account of holes.
16.18.1 Materials
RCC posts and struts shall be as specified in 16.1.12. Welded steel wire fabric will conform to IS
4948 and shall be of rectangular mesh 75 × 25 mm size weighing not less than 7.75 kg/sqm.
16.18.2 Fixing of RCC posts and struts shall be as described in 16.16.3.
16.18.3 Steel wire fabric 90 cm wide will be fixed to the posts by means of G.I. staple on wooden plugs or
tied t o 6 m m bar ri bs with bi nding w ire. T he s teel fabric s hall be fixed t o l eave 15 c m clearance at t he
bottom and top of the posts.
16.18.4 Finishing
The steel wire fabric shall be painted with two or more coats of approved shade of enamel paint over a
coat of steel primer as for new work.
16.18.5.1 Materials : R.C.C. posts, rails and pales shall be as described in 16.1.11 & 16.1.12.
16.18.5.2 Spacing of Posts : The spacing of post shall be as specified, or as directed by the Engineerin-
Charge to suit the dimensions of the area to be fenced.
16.18.5.3 Fixing Posts : Pits 45 x 45 cm and 70 cm deep or as directed shall first be excavated true to line
and level to receive the posts.
16.18.5.4 Fixing Rails and Pales : The rails shall be slotted into t he slots left in the posts, w hile the
pales shall be simply dovetailed into the rails. The pales shall be fixed by pouring a little grout of 1.2 mix (1
cement : 2 f ine sand) into the dovetails. The fencing shall be s o erected that on completion is truly in line
and level and top of the fence shall then follow approximately the profile of the ground.
16.18.6 Measurements
Fencing t o b e m easured in s quare metre correct t o t wo pl aces of decimal after t aking l ength a nd
width of the finished work in metre.
16.18.7 Rates
As per item No. 16.16.6.
92 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
16.19 ENGRAVING LETTERS IN HARD STONES (FIG. 16.5 & 16.6)
16.19.2 Engraving
Engraving o f the letters to the s pecified he ight and thickness s hall be don e by c utting w ith s nap
incision in V shape, about 12 mm deep or as directed by the Engineer-in-Charge.
16.19.3 Finishing
The engraved po rtion of t he letters shall b e painted with black enamel or as di rected b y the
Engineer-in-Charge.
16.19.4 Measurements
The height of each letter shall be measured correct to a cm.
16.19.5 Rate
The rate shall i nclude t he c ost o f materials and l abour i nvolved i n al l the oper ations des cribed abo ve
except the cost of stones and paint for lettering unless specified otherwise.
16.20.1 Boundary stones shall be as described in 16.1.21 or of size otherwise specified or directed by
the Engineer-in-Charge.
The boundary stones shall be firmly fixed in ground to a depth of 60 cm and the side filling shall be
thoroughly watered and consolidated.
The lower 60 cm portion of the boundary stones shall be encased on all sides by at least 15 cm of
foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) in
case ( a) where w et cultivation abut s the road l and and bou ndary s tones ar e l ikely t o be di splaced dur ing
agricultural op erations (b) w here t he road runs in b uilt up area, a nd (c ) where t he bo undary s tones ar e
intended to serve as permanent land marks.
16.21.1 RCC B oundary s tones s hall be manufactured as per s tandard des ign or a s specified i n i tem and
directed by Engineer-in-Charge.
These s hall be of r einforced c ement c oncrete 1:1 ½ : 3 ( 1 c ement : 1 ½ c oarse s and : 3 gr aded s tone
aggregate 2 0 m m n ominal size), 9 0 cm high and 15 cm dia at t he top a nd 20 cm. dia at bottom with
necessary s teel r einforcement as per s tandard de sign or as di rected by t he E ngineer-in-Charge. T he
precast RCC Stones shall be finished smooth with cement mortar 1:3 (1 cement : 3 fine sand).
93 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
16.22 KILOMETERS STONES :DELETED
.
16.23 SURFACE DRESSING ON NEW SURFACE WITH HOT BITUMEN ONE COAT
16.23.0 This t ype of t reatment s hall c onsist of c leaning t he ex isting w ater bound m acadam k ankar or
gravel s urfaces, a nd a pplying on e co at of h ot bit umen o n the p repared b ase, bli nding it w ith st one
chippings of 12.5 mm nominal size and c onsolidation with a road roller. This ty pe of treatment is
normally done f or a r oad with light density r ubber tyred t raffic and r oads f or temporary construction. T his
treatment i s al so done on ex isting w ater bound m acadam before applying t he f inal s urface treatment. I n
the l atter case, after applying a coat of painting the road i s t hrown o pen to traffic till the r oad i s
consolidated. The f inal treatment is then gi ven after making good the undulations etc . in the road
surface.
16.23.1 Preparation of surface (Repairs and Cleaning) shall be as specified under 16.24.2(a).
16.23.2 Applying bi nder, blinding, c onsolidation, surface f inishing, m easurements and rat es s hall be a s
specified under 16.24 except th at bi nder s hall be appl ied at t he r ate of 2. 25 k g pe r sq m a nd s tone
chippings of size 13.2 mm at 1.65 cum per 100 sqm unless otherwise specified.
16.24.1 Materials
Binder shall be as specified and s hall conform to Table 16.7 and s tone chippings shall conform to
grading as the Table 16.17. Unless otherwise specified or directed by the Engineer-in-Charge the
quantities of m aterials shall be as specified i n Table 16 .17. A pr oper record w ill be kept t o ensure that
the d aily o ut-turn of w ork is c o-related w ith the quantity of bi tumen used as per proforma given i n
Appendix ‘A’.
TABLE 16.17
First 13.2 mm 100 per cent passing through 1.5 cum/100 sqm 1.8 kg
Coat IS sieve 22.4 mm square mesh per sqm
and retained on IS Sieve 11.2 mm
square mesh
Second 11.2 mm 100 per cent passing through 1.0 cum/100 sqm 1.1 kg
Coat IS sieve 13.2 mm square mesh per sqm
and r etained on I S s ieve 5.6 mm
square mesh
94 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
16.24.2 First Coat
For the purpose of repairs the area of pot ho les shall be t aken up to 0.75 sqm and dept h upto 5 cm.
All pot holes, patches and ruts upto 2.5 cm deep shall be repaired and brought to level with premix and
properly consolidated while those of depths greater than 2.5 cm shall be repaired with similar
specifications as adopted originally.
Cleaning : Prior t o t he appl ication o f t he bi nder, a ll dus t, di rt, c aked m ud, animal dung, l oose and
foreign material etc. shall be removed 30 cm on either side, beyond the full width to be treated, by
means of m echanical s weepers and bl owers, i f av ailable or ot herwise w ith wire br ushes, s mall pi cks,
brooms etc. The material so removed shall be disposed off as directed by the Engineer-in-Charge.
For a w ater boun d m acadam s urface, t he i nterstices bet ween t he r oad m etal s hall be ex posed upt o a
depth of about 10 mm by means of wire brushes. The surface shall then be brushed with soft brooms to
remove al l loose aggr egate. Finally t he traces of fine dus t w hich get a ccumulated while brushing shall be
thoroughly removed from the surface by blowing with gunny bags.
The prepared surface shall be closed to traffic and maintained fully clean till the binder is applied.
The binder shall b e applied e venly t o t he c lean dry surface by m eans of a pressure s prayer a t t he
rate specified. The bi nder s hall be appl ied l ongitudinally al ong t he length o f the road and nev er ac ross i t.
The edges of the binder surface shall be defined by wire or a rope stretched in position.
Heating i n c ut out drums and pour ing from per forated tins, cans and s uch ot her methods s hall not be
permitted. E xcept i n the c ase of p etty w orks a nd repairs w ith the specific approval of the E ngineer-in-
Charge.
Excessive dep osits o f bi nder caused b y s topping o r starting o f t he s prayer o r through l eakage o r an y
other reason shall be suitably corrected before the stone chippings are spread.
If a uniform s urface i s a ssured at t his s tage, t he completed surface should be n ormally f ree f rom
undulations and unevenness.
95 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
(d) Consolidation of Blindage
Immediately following t he appl ication o f t he s tone c hippings and l ight br ooming, the r oad s urface
shall be compacted by a power roller of 6 to 8 tonnes, starting at edges and working towards the centre (or
to the outside edge in case of superelevated curve). Each pass of the roller shall uniformly overlap not
less than one t hird o f the track made i n the pr eceding pas s. The r oller shall be w orked or started an d
stopped without j erks a nd s hall n ot b e s topped o r r eversed e ach t ime at t he same l ocation t o c ause
displacement of stone and other irregularities. Consolidation shall be considered complete when the
stone chippings are firmly embedded.
Generally five to six trips shall be made for thorough compaction of the surface or as may be
specified by the Engineer-in-Charge.
Along k erbs, m anholes and all pl aces n ot accessible to the rol ler, c ompaction shall b e s ecured b y
means of steel rammers or hand rollers.
(b) Applying Binder (Hot Bitumen) : The second coat of binder shall be applied immediately after
the blinding has been set and the surface has been cleaned. The binder shall be applied at the
specified rate in the manner specified for the first coat 16.24.2(b).
(c) Blinding or Spreading Stone Chippings : Immediately after the second application of binder,
the stone chippings shall be spread at the specified rate in the manner described in 16.24.2(c).
(d) Consolidation of Blindage : The specifications described in 16.24.2(d) shall apply. Further the
prepared finished surface shall be protected from traffic for 24 hours or such period as may be
specified by the Engineer-in-Charge.
16.24.5 The finished surface shall be thrown open to traffic on the following day. Controlling traffic shall be
done by suitable methods like barricading posting of watchman etc.
16.24.6 Measurements
The l ength a nd width o f the fi nished work shall be measured c orrect t o a cm a long the fi nished
surface of the road. The area shall be calculated in square metre, correct to two places of decimal.
For record purposes, the measurement for binder and stone chippings shall be taken as specified in
16.4.2 and 16.4.3 be fore they ar e ac tually us ed on t he work. P remeasurements of m aterials taken for
record purposes shall simply serve as a guide and shall not form the basis for payment.
16.24.7 Rate
The rate s hall i nclude t he c ost o f materials and labour involved in al l the oper ations des cribed abov e,
except for repairs described under 16.24.2.
96 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
16.25 SURFACE DRESSING ON OLD SURFACE WITH HOT BITUMEN-ONE COAT
16.25.0 This treatment consists of cleaning old painted surfaces and applying a coat of hot bitumen on
the prepared base, blinding with stone chippings and consolidation with road roller.
16.25.1 Materials
Binder s hall be as s pecified and conform to Table 1 6.7 stone chipping s hall conform t o gr ading gi ven
Table 16.17 for 11.2 mm. Unless otherwise specified or directed by the Engineer-in-Charge stone
Chippings of 11.2 mm nominal size shall be used @ 1.5 cum per 100 sqm area and bitumen @ 1.95 kg
per square metre area. A proper record shall b e kept to ensure that the daily turn out of work is
correlated with the quantity of bitumen used as per proforma given in Appendix ‘A’.
16.25.2 Preparation of Surface (Repairs and cleaning) shall be as specified under 16.24.2.
16.25.3 Applying bi nder, Blinding, C onsolidation, S urface Finishing, M easurement a nd R ate s hall be as
specified under 16.24 except that the binder and chippings shall be applied at the rate specified above.
16.26 SURFACE DRESSING ON NEW SURFACE WITH BITUMEN EMULSION-ONE COAT
16.26.0 This treatment consists of c leaning the existing water bound macadam, k ankar gravel or
stabilised bas e and o ther b lack top s urfaces, app lying a c oat o f b itumen emulsion at atm ospheric
temperature, blinding it with stone chippings including consolidation with a road roller.
This t ype of t reatment i s normally ap plied under d amp c onditions a nd f or m inor repai r w orks duri ng
rainy season for roads with medium density, rubber tyred traffic such as service roads. This treatment is
also done on ex isting w ater boun d m acadam bef ore appl ying t he f inal s urface t reatment. I n t he l atter
case, the road is consolidated. The final treatment is then given after making good the undulations
depressions etc. in the road surface.
16.26.1 Materials
Binder shall be as specified and shall conform to RS grade IS 8887. Stone chipping of 13.2 mm size
shall c onform t o Table 16. 17. U nless ot herwise s pecified or di rected b y t he E ngineer-in-Charge 13.2 mm
stone c hippings shall be us ed @ 1. 5 c um per 100 s qm ar ea and bi tumen @ 1. 95 kg/sqm ar ea. A pr oper
record shall be k ept to ensure that the daily out turn of work is correlated with the quantity of bitumen
used as per proforma given in Appendix ‘A’ .
16.26.4 Blinding including consolidation, Measurements and Rate shall be as specified under 16.24
except th at t he st one c hippings s hall b e s pread a t th e s pecified r ate i mmediately after t he bitumen
emulsion on application breaks i.e. changes colour from brown to black.
16.27.0 This treatment consists of cleaning old painted surfaces and a pplying a c oat of bitumen
emulsion o n t he prepar ed bas e, bl inding with s tone c hippings an d c onsolidation w ith a road rol ler. T his
type of treatment is normally done under damp conditions.
97 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
16.27.1 Materials
Binder s hall b e a s specified and shall c onform t o R S grade I S 8887. Unless o therwise specified or
directed by t he E ngineer-in-Charge 11. 2 m m the s tone c hippings s hall be us ed @ 1. 10 c um per 100
sqm area and bitumen @ 1.22 kg per sqm area. A proper record shall be kept to ensure that the daily
out turn of work is correlated with the quantity of bitumen used as per proforma given in Appendix ‘A’.
16.27.2 Preparation of s urface s hall be as s pecified i n 16.24.2 (a) except t hat t he binder used for pat ch
repairs etc. shall be bitumen emulsion.
16.28.0 The rat e of appl ication of binder which s hall be as specified and w hich s hall c onform t o 1 6.1.5
shall depend on the surface on which the premix carpet is to be laid.
(a) 0.75 kg/sqm on W.B.M. surface.
16.28.1 Materials
16.28.3 Cleaning
Prior t o t he appl ication o f bitumen, al l v egetation, l oose sealing c ompound, caked mud, ani mal dung,
dust, d irt and fo reign m aterial s hall be rem oved from the ent ire s urface of the pav ement and from
existing dummy, construction and expansion joints (wherever existing) by means of mechanical
sweepers an d bl owers, ot herwise w ith s teel w ire br ushes, s mall picks, brooms or ot her implements as
approved b y t he E ngineer-in-Charge. T he m aterial so rem oved shall b e di sposed of f as d irected b y t he
Engineer-in-Charge.
16.28.5.1 Heating : Bitumen shall be heat ed in a boi ler to a t emperature of 165 deg. C to 175 deg. C
and maintained at t hat t emperature. Temperature shall be checked at r egular intervals with t he hel p o f a
thermometer.
16.28.5.2 Application of Bitumen : Hot bi tumen s hall be appl ied ev enly t o t he c lean, dry s urface by
means of a pressure sprayer at specified rate. Even and uniform distribution of bitumen shall be
ensured. Bitumen s hall be appl ied l ongitudinally al ong t he l ength of the pa vement and never across it.
Excessive depo sits of bitumen caused b y s topping or s tarting of t he sprayer or t hrough leakage or an y
other reason shall be suitably rectified.
16.28.6 Measurements
Length and br eadth s hall be measured correct to a c m, al ong t he surface o f pavement. A rea s hall be
worked out in sqm correct to two places of decimal.
98 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
16.28.7 Rate
Rate shall include the cost of all materials and labour involved in all the operations described above.
16.29.1 Specification of i tem 16 .28 t o be followed except B itumen emulsion (Rapid S etting) of s pecified
grade and c onsistency t o be u sed at room t emperature i nstead of h ot s traight run b itumen at following
rate.
1. on w.b.m @ 0.4kg/sqm.
2. on bituminous surface @ 0.25 kg/sqm.
16.30.0 This type of treatment is normally applied on r oads where the motor traffic is of medium
intensity, but bullock cart t raffic i s f airly heavy. T his treatment is s uitable f or district roads and for internal
and service road in colonies. The consolidated thickness of this type of treatment shall be 2 c m or 2.5
cm as specified.
This treatment consists of applying a tack coat on the prepared base followed immediately by
spreading aggregates precoated with specified binder to camber and consolidated.
Premix c arpet s hall not b e l aid d uring rainy w eather o r w hen t he b ase c ourse i s da mp o r w et or ,
when the atmospheric temperature in the shade is not more than 16oC.
16.30.2 Materials
Grading of stone chipping shall be as per Table 16.17. Binder shall be as specified and shall conform to
Table 1 6.7. Q uantities o f m aterials s hall be as gi ven i n T able 16. 18. A pro per re cord s hall be k ept t o
ensure that the d aily o ut turn of w ork is c orrelated with the q uantity of bitumen used as per p roforma
given in Appendix ‘A’.
TABLE 16.18
Mixers of approved type shall be employed for mixing the aggregates with the bituminous binder.
99 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
The bi nder s hall be heat ed t o t he t emperature ap propriate t o t he grade of b itumen approv ed by t he
Engineer-in-Charge, in boilers of suitable design avoiding local overheating and ensuring a continuous
supply.
The aggr egates s hall be dr y and suitably heat ed t o a temperature as directed by E ngineer-in-Charge
before these are placed in the mixer. After about 15 seconds of dry mixing, the heated binder shall be
distributed over the aggregates at the rate specified.
The mixing of binder with chippings shall be continued until the chippings are thoroughly coated with the
binder. The mix shall be immediately transported from the mixer to the point of use in suitable
vehicles o r w heel bar rows. The v ehicles e mployed for t ransport s hall be c leaned and be c overed ov er i n
transit if so directed.
When the roller has passed over the whole area once, any high spots or depressions which become
apparent s hall b e c orrected by rem oving or a dding prem ixed materials. Rolling s hall t hen be c ontinued
until the entire surface has been rolled to compaction and all the roller marks eliminated. In each pass of the
roller, preceding track shall be ov erlapped uniformly by at least 1/3 width. The roller wheels shall be kept
damp to prevent the premix from adhering to the wheels and being picked up. In no case shall
fuel/lubricating oil be used for this purpose.
Rollers shall not stand on newly laid material as it may get deformed thereby.
The edges along and t ransverse of t he c arpet, l aid and c ompacted earlier shall be c ut t o t heir f ull
depth so as to e xpose fresh surface w hich s hall be pai nted w ith a thin surface coat o f appr opriate bi nder
before the new mix is placed against it.
Further, t he prepared f inished s urface s hall be pro tected f rom t raffic f or 24 hours or s uch peri od as
may be directed by the Engineer-in-Charge.
Vol-2 , 2013
The l ongitudinal pr ofile s hall be c hecked du ring r olling w ith a t hree m etres l ong s traight edge an d
graduated wedge at the middle of each traffic lane along the road. Similarly the transverse profile shall be
checked with adjustable templates at intervals of 10 metres.
16.30.7 Rectification
Where t he s urface i rregularity f all out side t he s pecified tolerances t he c ontractor s hall be liable to
rectify i t t o t he s atisfaction of E ngineer-in-Charge by addi ng f resh m aterial and r ecompacting t o
specifications where t he surface is low. Where the s urface i s hi gh t he f ull depth of t he l ayer shall b e
removed and replaced with fresh material and compacted to specifications.
16.30.8 Measurements
The l ength a nd width o f the fi nished work shall be measured c orrect t o a cm a long the fi nished
surface of the road. The area shall be calculated in square metre, correct to two places of decimal.
For record purposes, the measurement for binder and stone chippings shall be taken as specified in
16.4.2.2 and 16.4.3.2 before they are actually used on the work. Premeasurements of the materials
taken for record purposes shall simply serve as a guide and shall not form the basis for payment.
16.30.9 Rate
The rate shall include the cost of materials and labour involved in all the operations described above for
the particular item, except for the cost of Repairs described under para 16.24.2(a).
16.31.0 This type of w ork is n ot ordinarily recommended b ut m ay be done in c ase of urgent repairs
under damp conditions.
16.31.1 Materials
Binder s hall be as specified and s hall c onform to R S grade IS 8887 grading of 11.2 m m s tone
chipping s hall be as p er T able 16 .17. Q uantities of bitumen em ulsion and s tone chippings shall b e as
specified in Table 16.20. A proper record shall be kept to ensure that the daily out turn of work is correlated
with the quantity of bitumen used as per proforma given in Appendix ‘A’.
TABLE 16.20
Bitumen Emulsion
16.31.2
Preparation of surface and binder application shall be as specified under 16.26 except that the rate of
application of bitumen for tack coat shall be 0.75 kg per sqm on water bound macadam surface and 0.5 kg
per sqm on black topped surface.
Vol-2 , 2013
16.31.3
Preparation, s preading, consolidating mix, surface finishing, measurements an d r ate shall be as specified
under 16.30 except that the bitumen emulsion shall not be heated but it shall be poured over the
aggregate at atmospheric temperature at the correct rate before spreading on the road surface. The rolling
shall commence 24 hours after spreading the mixture. The surface shall be protected by a suitable
device such as barricading and posting of watchmen for closing the traffic.
16.32.0 Scope
The w ork shall consist of c onstruction o f o ne or m ore l ayers of c ompacted c rushed coarse
aggregates with alternate applications or bituminous binder and key aggregates in accordance with the
requirements of these s pecifications t o be us ed as a bas e c ourse on roads, subject t o the requirements
of t he ov erall pav ement des ign, i n c onformity w ith t he l ines, gr ades and c ross-sections s hown o n t he
drawings or as directed by the Engineer-in-Charge. Thickness of an individual course shall be 50 mm or
75 mm or otherwise as specified.
16.32.1 Materials
16.32.1.1 Bitumen :
The bi nder shall be pav ing bi tumen of s pecified penet ration grade conforming t o
IS 73 or approved cutback satisfying the requirement of IS 217 or 454 as specified in item. The actual
grade of bitumen or cutback to be used shall be as specified in item or as directed by the Engineer-in-
charge.
16.32.1.2 Aggregates:
The coarse ag gregates shall consist of crushed rock, crushed gravel or other hard material retained on
the 2.36 mm IS sieve. They shall be c lean, hard, durable, of cubical shape, free from dust and soft or
friable matter, organic or other deleterious matter. Where the contractors selected source of aggregate
have poor affinity for bitumen, as a condition for approval of the source, the bitumen shall be treated
with app roved anti-stripping a gents, as p er the manufacturers recommendations, w ithout
additional pay ment. B efore app roval of t he s ource t he agg regate s hall be tested f or s tripping. Th e
coarse aggregate shall conforming to Table 16.31. The c oarse and k ey aggregates shall conform to
the grading given in Table 16.21.
The quantities of materials used for this work shall be as specified in Table 16.21.
Vol-2 , 2013
16.32.2.2 Equipment :
The base on which the Penetration Macadam Course is to be laid shall be prepaid, shaped and
compacted to the specified lines, grades and sections as appropriate or directed by Engineer-in-
Charge. A prime coat, where specified shall be applied over the base as directed by the Engineer-in-
charge.
The c oarse aggregate s hall be dry and c lean an d f ree f rom dust, and s hall be s pread uni formly an d
evenly at the rate specified in Table 16.21. I t shall be s pread by a self-propelled or tripper tail mounted
aggregate spreader c apable of spreading aggr egate uni formly at t he s pecified rat es ov er t he requi red
widths. The surface of the layer shall be carefully checked with camber templates to ensure correct line
and l evel an d c ross f all. T he s preading s hall b e c arried out such tha t the rolling and pene trating
operations c an be c ompleted on the s ame day . Segregated aggregates or aggr egates c ontaminated
with foreign material shall be removed and replaced.
TABLE 16.21
Vol-2 , 2013
(1) (2) (3) (4) (5)
Approx. Loose 0-06 0.015 0.09 0.018
aggregate
quantities
cm/m2
Binder Quantity As specified in item As specified in item
(Penetration
Grade)(1) (Kg./m2)
Note : (1) I f c utback bitumen is us ed, ad just binde r quan tity s uch that the res idual bi tumen is
equal to the values in this table.
16.32.2.5 Compaction : After the spreading of course aggregates, dry rolling shall be carried out with an
8-10 tonne smooth steel wheel roller. After initial dry rolling the surface shall be checked with a crown and 3
metre straight edge. The surface shall not vary more than 10 mm from the template or straight edge. All
surface irregularities exceeding the above limit shall be corrected by r emoving or adding aggregate
as required the rolling shall continue until the compacted coarse aggregate has a firm surface, true
to cross-section shown on the plans and has a texture that will allow free and uniform penetration of the
bitumen material.
Bituminous materials shall be laid and compacted in layers which enable the specified thickness,
surface level, regularity requirements and compaction to be achieved.
Compaction of bituminous materials shall commence as soon as possible after laying. Compaction
shall be substantially c ompleted be fore t he t emperature f alls below the minimum rol ling t emperatures
stated in the relevant part of these specifications. Rolling of the longitudinal joints shall be done
immediately behind the paving operation. After t his, rol ling s hall c ommence at the edges a nd progress
towards the centre longitudinally except that on super elevated and unidirectional combered portions, it
shall progress from the lower to the upper edge parallel to the centre line of the pavement. Rolling shall
continue unt il al l ro ller m arks hav e been re moved f rom t he s urface. All def iciencies i n t he s urface af ter
laying s hall be made g ood by t he at tendants behind t he pa ver, bef ore i nitial rolling is c ommenced. T he
initial or breakdown rolling s hall b e d one w ith 8-10 t onnes dead w eight s mooth-wheeled rollers. T he
intermediate rol ling s hall be done with 8 -10 t onnes de ad weight o r v ibratory rol ler or with a pneumatic
tyred roller of 12 to 15 tonnes weight having nine wheels, with a type pressure of at least 5.6 kg/sqcm.
The finish rolling shall be done with 6 to 8 tonnes smooth wheeled tandem rollers.
Bituminus materials s hall be rol led i n a l ongitudinal di rection, w ith the d riven rolls ne arest t he paver.
The roller s hall first compact material adjacent t o joints and then work from t he l ower t o the upper side of
the layer, overlapping on successive passes by at least one-third of the width of the rear roll or, in the
case of a pnueumatic-tyred roller, at least the nominal width of 300 mm.
In port ions w ith s uper-elevated an d uni -directional camber, af ter t he e dge h as been r olled, t he rol ler
shall progress from the lower to the upper edge.
104 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
Rollers should move at a speed of not more than 5 km per hour. The roller shall not be permitted to
stand on pavement which has not been fully compacted, and necessary precautions shall be taken to
prevent dropping of oil, grease, petrol or other foreign matter on the pavement either when the rollers
are operating or standing. The wheels of rollers shall be kept moist with water and the spray system
provided with the machined shall be in good working order, to prevent the mixture from adhering to the
wheels. Only sufficient moisture to prevent adhesion between the wheels of rollers and the mixture
should be used. Surplus water shall not be allowd to stand on the partially compacted pavement.
After i nitial dry rolling, the s urface s hall be c hecked w ith a c rown t emplate and a 3 m etre s traight-
edge. The surface shall not vary more than 10mm from the template or straight-edge. All s urface
irregularity exceeding the above limit shall be corrected by removing or adding aggregates as required.
The rolling shall continue until the compacted coarse aggregate has a firm surface true to the cross
section shown on the plans and has a texture that will allow free and uniform penetration of the bitumen
material.
16.32.2.6 Application of Bituminous Material : After th e c oarse aggregate h as been r olled and
checked, the bit uminous bin der s hall b e ap plied at th e ra te g iven i n T able 16 .21, at a te mperature
directed by Engineer-in-Charge.
At the time of applying the binder, the aggregates shall be surface dry for the full depth of the layer.
In certain c ircumstances, depen ding on the t ype and s ize o f aggr egate us ed, the E ngineer-in-Charge
may direct the placing of a bed of clean sand or quarry fines, not exceeding 10 mm in thickness, on the
prepared foundation b efore pl acing t he c oarse aggregate. The sand o r f ine m aterial shall b e slightly
wetted, jus t s ufficient fo r i t to s lurry up dur ing the c ompaction process. Where c ut bac k is us ed, i f
flooding o f t he binder oc curs it s hould be ap plied i n two operations, o r as di rected by the E ngineer-in-
charge.
16.32.2.7 Application of Key Aggregates : Immediately after the first a pplication of bi tumen, the k ey
aggregates, which s hall b e c lean, dry a nd f ree f rom dus t s hall be spread u niformly ov er t he s urface b y
means of an appr oved m echanical s preader or by appr oved m anual m ethods at t he r ate s pecified i n
Table 16.21.
Where directed by the Engineer-in-charge, the surface s hall be s wept and the quantity of key
aggregate a djusted t o ensure u niform application, w ith all t he s urface voids i n t he c oarse aggregate
being filled w ithout ex cess. T he ent ire s urface s hall then be r olled w ith a 8 - 10 tonnes s mooth s teel
wheel rol ler (or vibrating ro ller opera ting in non-vibratory m ode) in a ccordance w ith the pro cedure
specified in above para 16.32.2.5.
16.32.4 Surfacing
The penetration Macadam shall be provided with a surfacing (binder/wearing course) within a
maximum of forty-eight hours. If there is to be any delay, the penetration macadam shall be covered by a
seal c oat a s s pecified and d irected by E ngineer-in-charge. T he s eal c oat in s uch c ases s hall be
considered incidental to the work and shall not be paid for separately.
Vol-2 , 2013
16.32.5 Arrangements for Traffic
During t he p eriod of c onstruction, arrangements f or t raffic shall be m ade i n accordance w ith t he
provisions of specification and as per direction of Engineer-in-Charge.
16.32.7 Rate
The rate includes the cost of all materials, labours and equipment involved in all the operations
described above.
16.33.1 Definition
The bi tumen m astic i s an i ntimate homogeneous mixture of mineral fillers and w ell grade d f ine a nd
coarse aggregates w ith a hard grade bi tumen, c ooked and l aid hot, troweled and f loated by m eans of a
wooden f loat. T he m ixture s ettles t o a c oherent, v oidless and i mpermeable s olid m ass u nder n ormal
temperature conditions.
The bitumen mastic is normally used as a wearing course. Over the mastic laid surface, hard stone
chips precoated with bitumen are grafted or spread and rolled to provide a skid resistant surface.
Bitumen m astic i s used as a w earing course i n different s ituation of heavy dut y r oad pavements.
However, use of this material is not recommended in places where abundant fuel oil dripping is expected on
the pavement surfaces like bus depots, fuel filling and service stations etc.
16.33.2 Materials
16.33.2.1 The bitumen shall be industrial bitumen conforming to IS 702 of suit able grade consistency
satisfying the requirements of physical properties as given in Table 16.22.
TABLE 16.22
Physical Properties of Bitumen
16.33.2.2 Coarse Aggregates : The c oarse a ggregates s hall consist of clean, har d, durable, c rushed
rock free of disintegrated pieces, organic and other deleterious matter and adherent coatings. They shall be
hydrophobic, of low porosity, and satisfy the physical requirements set forth in Table 16.23.
Vol-2 , 2013
TABLE 16.23
Physical Requirements of Coarse Aggregates for Bitumen Mastic
The pe rcentage an d gr ading of t he c oarse ag gregates to be u sed i n the bitumen m astic d epending
upon t he th ickness of the fi nished c ourse s hall b e a s in T able 1 6.24. T he m inimum and maximum
thickness of the bitumen mastic f or w earing course s hall b e 25 m m and 50 mm res pectively ex cept f or
footpaths of bridges where it shall be 20 mm and 25 mm respectively.
TABLE 16.24
Grading and Percentage of Coarse Aggregates for Bitumen
Mastic in Wearing Course and Footpath
16.33.2.3 Fine Aggregates : The fine aggr egates shall consist o f crushed har d rock o r nat ural sand or a
mixture of bot h. T he grading of f ine aggregates i nclusive of f iller m aterial passing 75 m icron s hall be a s
given in Table 16.25.
TABLE 16.25
Grading of Fine Aggregate I/C Filler
Vol-2 , 2013
16.33.2.4 Filler : The fi ller s hall be limestone p owder p assing 7 5 micron and sh all have a calcium
carbonate content of not less than 80 per cent when determined in accordance with IS 1514.
16.33.3.1 There a re two ways o f preparing a m astic. T he c onventional m ethod is by us ing a m astic
cooker which is dealt with in this specification. The other method using fully mechanized units needed for
large scale work, as is generally practiced in Germany ( Gussasphalt), may f orm t he subject of a
separate document.
16.33.3.2 Mastic c ooker are v ery s imilar t o t ar boi lers. T hese are i nsulated t anks m ounted on w heeled
chassis. T he h eating of t he bi tumen and m aterial i s gen erally don e b y oi l f ired burner s. M astic c ookers
have compartments. The central and main compartment is used for heating bitumen and for preparing
the mix. The s ide poc kets o r c ompartments ar e meant for pr e-heating o f the c oarse and fine aggr egates.
Since heat ing i s b y oi l fired bur ners, the temperature c an be eas ily c ontrolled by c ontrolling the flames or
supply of the fuel.
16.33.3.3 Mastic cookers o f v arious capacities ranging from 1/2 tonne t o 3 t onne a re used depending on
the am ount of work involved. T hese are not being m arketed commercially because it i s not a common
specification but can be easily got made from manufactures of tar boilers.
Fig. 16. 13 i ndicates t he b road d etails of eq uipment and c omponents of c ooker pre sently i n c ommon
use.
16.33.3.4 Apart from mastic cooker, the following equipments are required for transportation and laying.
(1) Wheel barrows a nd flat m ortar pans ( for short di stance ha ul) and small dumpers ( for long
distance haul).
(2) Wooden trowels, heavy wooden floats, suitable hand tools gauge, straight edge and hand level.
(3) Angle irons, required to contain the mastic in desired width and thickness.
16.33.4.1 The m anufacture of bi tumen m astic i nvolves di fferent s tages. Initially the filler alone s hall b e
heated to a temperature o f 175 deg. C t o 210 deg. C i n mechanically agi tated mastic cooker and half the
required quantity of bitumen heated at 175 deg. C to 180 deg. C added. They shall be mixed and cooked for
one hour. A fter t hat t he f ine aggregat es an d t he ba lance bi tumen at 175 deg . C t o 180 deg. C s hall b e
added t o that m ixture in t he c ooker and heated up to 175 de g. C t o 20 0 de g. C a nd f urther mixed f or
another one h our. In the final s tage, the c oarse aggr egates s hall be added and h eating o f m ix s hall
continue for anot her one hour. Thus a t otal per iod o f minimum t hree hour s w ill be neede d t o p repare t he
mastic. During mixing and cooking, care shall be taken to ensure that the contents in the cooker are at no
time heated to a temperature exceeding 210 deg. C.
16.33.4.2 In case the material is not required for immediate use, the bitumen mastic with filler, fine
aggregates and bi tumen shall be cast i nto bl ocks ea ch w eighing abo ut 25 kg. T he bitumen mastic bl ocks
(without c oarse aggr egates) shall s how on a nalysis a c omposition with t he l imits as g iven i n Table 16. 26.
These blocks w hen i ntended t o be us ed s ubsequently s hall be t ransported to s ite, broken i nto pieces of
size not exceeding 60 mm cube and remelted in the cooker at a temperature ranging from 175 deg. C. to
210 deg. C thoroughly incorporating the requisite quantity of coarse aggregates as indicated in Table
16.26 and m ixed c ontinuously f or at l east an ho ur. M ixing shall b e c ontinued unt il t he l aying op erations
are c ompleted s o as t o maintain the c oarse aggr egates i n s uspension. A t any s tage t he t emperature
during the process of mixing shall not exceed 210 deg. C.
Vol-2 , 2013
TABLE 16.26
Composition of Bitumen Mastic Blocks without Coarse Aggregates
16.33.6.1 Preparation of the Base : The base on which bitumen mastic is to be l aid shall be prepared,
shaped and c onditioned t o t he s pecified l evels, gra de and c amber as di rected. I f t he ex isting s urface i s
too irregular and wavy, i t shall be m ade g ood by pro viding a c orrective c ourse of bituminous c oncrete
mix as per I RC:29. T he s urface s hall be t horoughly s wept c lean and m ade f ree of dus t and ot her del e-
terious matter. S pots rich i n bi nder shall be scrapped and repaired. U nder no c ircumstances t he bi tumen
mastic sheet be spread on a base containing a binder which will soften under high application of
temperature. If any s uch spot exists, the same shall be cut out and repaired before t he bitumen mastic i s
laid. To receive and contain the mastic, angle irons of sizes 25 or 50 mm are placed at required spacing
till finish of the job.
16.33.6.2 Transportation of Mix : When the bi tumen mastic, duly pr epared including addi tion of coarse
aggregates at t he m anufacturing poi nt, i s t o be t ransported ov er a l ong di stance and del ivered t o t he
laying site, arrangements f or transport shall be made in a towed mixer transporter with adequate
provision for heating and stirring so as to keep the aggregates and filler suspended in the mix till the time of
laying. However for small works and where the laying site is near the manufacturing point, the mix can be
transported in wheel barrows/flat mortar pans. To prevent the molten material from sticking to the wheel
barrows/pans, t he i nside of t he t ransport m ay b e s prinkled w ith a m inimum quant ity of i norganic fine
material like limestone dust. However, cement, ash or oil shall not be used.
16.33.6.3.1 The bi tumen m astic s hall be di scharged i nto c ontainers sprinkled w ith l imestone du st o r
provided with li me-wash. The bitumen m astic s hall be dep osited di rectly on the prepared ba se
immediately in f ront o f t he s preader where it i s spread u niformly by means o f w ooden fl oats t o t he
required t hickness. T he m ix s hall be l aid i n one m etre w idths c onfined bet ween s tandard ang le i rons o f
size 2 5 m m t o 5 0 mm t o receive a nd c ontain t he mastic of r equired t hickness. T he t emperature of t he
mix at th e ti me of la ying shal l be 175 d eg. C. I n cas e bl owing ta kes pl ace while l aying t he bitumen
mastic, the bubbles shall be punctured while the mastic is hot and t he surface made good. Since mastic
asphalt i s an ex pansive m aterial, ex treme c are s hall be t aken w hile fixing the angle irons and t heir l evel
checked with instrument at suitable intervals.
16.33.6.3.2 Laying Bitumen Mastic Surfacing over Old Existing Bridge Deck : Before laying bitumen
mastic ov er ol d ex isting b ridge d eck, t he ex isting c ross f all/camber, ex pansion j oint m embers and w ater
drainage s pouts s hall be c arefully examined f or t heir proper f unctioning i n t he bri dge dec k s tructure and
any deficiency found shall first be removed. Loose elements in the expansion joint shall be firmly
secured. The cracks in the concrete surface, if any, shall be repaired and filled up properly or replaced by
new concrete of specified grade before laying the bitumen mastic over bridge deck.
16.33.6.3.3 Laying over New Bridge Deck : New concrete bridge deck which is not in camber/cross fall
shall first be provided with required camber and cross fall by suitable concrete or bituminous treatment. In
case of laying over concrete surface, following measures shall be taken:
Vol-2 , 2013
(1) F or proper bond w ith new c oncrete deck, s urface s hall be ro ughened by m eans of s tiff broom or
wire brush and it shall be free from ridges and troughs.
(2) A thin bituminous tack coat (with bitumen of grade 80/100) shall be applied on the concrete deck
before pouring mastic. The quantity of bitumen for tack coat shall not exceed 5-6 kg per 10 sqm.
(3) On surface in longitudinal slope, after applying tack coat, chicken-mesh reinforcement of 1.5 mm
dia steel wire with hexagonal or rectangular openings of 20-25 mm shall be placed and held
properly in position on the concrete surface before pouring mastic.
16.33.7 Joints
All construction joints s hall be properl y and t ruly m ade. T hese joints s hall be m ade by warming t he
existing bi tumen mastic by t he appl ication of an ex cess quantity of hot bi tumen m astic which af terwards
shall be trimmed off to make it flush with surface on the either side.
TABLE 16.27
Vol-2 , 2013
TABLE 16.28
The t raffic may be al lowed a fter c ompletion o f w ork w hen the bi tumen mastic has cooled do wn t o the
ambient temperature.
16.33.9 Controls
16.33.9.1 Sieve analysis of each type of the aggregate used shall be made at least once a day to see
that t he gradation of t he aggregates f ollows t he original gradation as approved. A dditional t ests s hall be
carried out in case of variation in grading or receipt of supply of material from new source. The number
of samples to be tested per day would depend upon the bulk supply of aggregates made in a day at the
plant s ite. Physical pr operties such as aggregate i mpact values, f lakiness i ndex, water a bsorption etc.
shall be de termined a t the r ate o f one test for e very 25 -50 c um o f aggr egates or as d irected by the
Engineer at site.
16.33.9.2 Two sets of test shall be carried out on each lot of supply of bitumen for checking penetration
and softening point as per IS 1203 and IS 1205.
16.33.9.3 For filler material calcium carbonate content and fineness shall be tested at the rate of one set of
tests for each consignment subject to a minimum of one set of test per 5 tonne or part thereof.
16.33.9.4 It s hall b e ensured t hat t he a ggregates are n ot wet b efore h eating, ot herwise it w ould af fect
the out put adv ersely. D uring heat ing t he aggr egate t emperature s hall be r ecorded p eriodically t o s ee
that it does not exceed the limits prescribed.
16.33.9.5 Material in block form shall be sampled by taking approximately equal amount in pieces, from
not less than six blocks chosen at random. The total weight of specimen to be tested shall not be less
than 5 kg. In case the preparation of the mix is at site, then at least one sample of every 10 tonne of
bitumen mastic discharged from the mastic cooker or at least one sample for each cooker per day shall be
collected and following tests done:
(2) B itumen s hall be ex tracted f rom abou t 100 0 gm o f the m astic s ample and b itumen c ontent
determined as specified in Appendix C of IS 1195.
(3) A s ieve anal ysis o f t he aggregates a fter the bi tumen i s extracted, s hall be done and t he gradation
determined according to the procedure laid down in IS 2386 (Pt.I).
16.33.9.6 The temperature of the bitumen mastic a t the time of laying shall n ot exceed 2 10 deg . C an d
shall not be less than 175 deg. C.
.
111 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
16.33.9.7 The longitudinal profile of the finished surface shall be t ested with a s traight edge 3 m long
and transverse profile with a camber template while the mastic laid is still hot. Irregularities greater than
4 mm in the longitudinal and transverse profile shall be corrected by picking up the mastic in full depth and
full area of the affected panel and relaying.
16.33.9.8 Bitumen mastic shall not be laid on a damp or wet surface or when the atmospheric
temperature in the shade is 15 deg. C or less.
16.33.10 Measurements
The l ength & breadth of the ar ea w here bitumen mastic w earing c ourse of specified t hickness ha s
been p rovided s hall be measured c orrect t o a c entimeter an d t he a rea s hall be calculated i n s quare
metres correct to two decimal places.
16.33.11 Rate
The rate per s quare metre shall i nclude cost o f al l t he oper ations des cribed abov e i ncluding ant i-skid
treatment mentioned in para 16.33.1 above.
16.34.0 This t ype of t reatment i s normally done f or garden paths, driveways, f ootpaths and pl aygrounds
and roads. The t reatment i s al so us eful i n pr oviding a t hin wearing course ov er e xisting c ement c oncrete
roads. This i s s ome times capable of standing w ith v ery heavy traffic. This can also be used over worn
out cement concrete p avements, t he c oncrete surface i s ro ughened be fore l aying t he bi nder c oat. It is
also u seful as a corrosion r esistant f looring i n shade a nd godowns f or storing s alt, f ertilizer etc. T his
treatment c onsists of a mixture of c oarse s and and stone chippings w ith bituminous bi nder, s pread a nd
consolidated to a specified thickness on prepared surface after the application of a tack coat.
The consolidated thickness of this type of treatment shall be 2.5 cm or 4 cm, as specified.
The work shall b e c arried ou t o nly when the at mospheric t emperature in shade is 1 6 d eg. C or
above. No bituminous material shall normally be applied when the road surface or material is damp or
when the w eather i s foggy or r ainy, o r dur ing dus t storms. B itumen o f specified gr ade and consistency t o
be used.
TABLE 16.29
Vol-2 , 2013
A proper record shall be kept to ensure that the daily turn out of work is corelated with the quantity of
bitumen used as per proforma prescribed in Appendix ‘A’ .
16.34.2 Preparation of surface and application of binder (tack coat ) shall be as specified under 16.28.2 to
16.30.5.
Any h igh s pots or d epressions which be come ap parent s hall be c orrected b y addi tion or rem oval of
premixed m aterials. The rolling shall c ontinue u ntil t he m aximum c onsolidation t o t he s atisfaction of
Engineer-in-Charge is obtained. The wheels of the roller shall be moistened with gunny bags to prevent the
mixture from sticking to the wheel while rolling.
16.34.4 Surface finishing and rectification shall be as specified under 16.30.6 and 16.30.7.
16.34.6 Measurements
The l ength a nd width o f the fi nished work shall be measured c orrect t o a cm a long the fi nished
surface of the road. The area shall be calculated in square metre, correct to two places of decimal.
For record purposes measurements for binder, stone aggregate, stone chippings and sand as
described unde r 16. 3 s hall be t aken bef ore t hey a re ac tually us ed on t he w ork. P remeasurements s hall
simply s erve as a gui de and s hall not form t he basis f or pay ment. T he t hickness of s urface t reatment
shall be the ruling criterion for payment.
16.34.7 Rate
The rate shall include the cost of materials and labour involved in all the operations described above.
16.35.1 Scope
This work shall consist of the application of a seal coat for sealing the voids in a bituminous surface laid
to the specified levels, grade and cross fall (camber).
16.35.2 Seal coat shall be of either of the two types specified below:
(A) Liquid seal coat comprising of an a pplication of all layer of bituminous binder followed by a c over
of stone chips.
(B) P remixed s eal coat c omprising of a thin ap plication of the a ggregate p remixed with bi tuminous
binder.
16.35.3 Materials
16.35.3.1 Binder : The binder a nd its q uantity s hall be a penetration bitumen of a s uitable g rade as
specified in the item or as directed by the Engineer-in-charge.
113 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
16.35.3.2 Stone Chips for Item 16.41 of D.S.R. 2007 of Seal Coat : The s tone c hips shall c onsist of
angular f rangments of c lean, hard, t ough an d dura ble roc k of uni form quality t hroughout. T hey should
be free of soft or disintegrated stone, organic o r ot her deleterious m atter. S tone chips shall be of 6.7
mm size defined as 100 per cent passing through 11.2 mm sieve and retained on 2.36 mm sieve. The
quantity used for spreading shall be 0. 09 cubic metre per 1 00 square metre area. The stone chips shall
satisfy the quality requirements in Table 16.31 bituminous except that the upper limit for water
absorption value shall be 1 per cent.
TABLE 16.30
Sl. No. I.S. Sieve (mm) Cummulative % passing by weight of total aggregate
1. 0.6 100
2. 0.3 95-100
3. 0.075 85-100
TABLE 16.31
16.35.3.3 Fine Aggregate : The aggr egate shall be s and o r g rit and shall consist o f c lean, hard dur able,
uncoated dry pa rticles and s hall be f ree f rom dus t, s oft or f laky/elongated m aterial, organic m atter or
other del eterious s ubstances. The aggregate s hall pas s 2 .36 mm s ieve and be retained o n 1 80 micron
sieve. The quantity used for premixing shall be 0.06 cubic metres per 100 square metres area. Stones or
fine aggregate shall be used as specified in item.
16.35.4.2 Preparation of Surface : The seal coat shall be appl ied immediately after laying the
bituminous course w hich is required to be s ealed. Before appl ication of seal coat materials, t he s urface
shall be cleaned free of any dust or other extraneous matter.
Vol-2 , 2013
16.35.4.3 Construction of Seal Coat with Stone Chips : Bitumen s hall be he ated t o 150 oC - 163oC
and s prayed a t t he r ate s pecified on t he dry surface i n a u niform ma nner w ith a self-propelled
mechanical sprayer
Immediately a fter t he appl ication o f bi nder, s tone c hips w hich shall be c lean a nd d ry, s hall be s pread
uniformly at the rate specified o n the surface preferably by means of a self -propelled or towed
mechanical grit spreader so a s to cover the su rface c ompletely. If necessary, th e s urface s hall be
brushed to ensure uniform spread of chips.
Immediately af ter t he appl ication o f t he c over m aterial, t he ent ire s urface s hall be rol led w ith a 8 -10
tonne s mooth wheeled s teel r oller, 8-10 tonne s tatic w eight v ibratory r oller, or other equi pment appr oved
by the E ngineer af ter l aying trials i f required. R olling s hall c ommence at the edge s and prog ress
towards t he c entre ex cept i n s uperelevated and uni directional c ambered po rtions w here i t s hall pro ceed
from the lower edge to t he higher edge. Each pas s of the roller shall uniformly overlap not less than one-
third of t he t rack m ade i n t he p roceeding pass. W hile r olling i s i n pr ogress, a dditional c hips s hall be
spread b y ha nd i n nec essary quant ities required t o m ake up irregularities. Rolling s hall continue unt il al l
aggregate particles are firmly embedded in the binder and present a uniform closed surface.
16.35.4.4 Construction of Seal Coat with Premixed Fine Aggregate : A mixer of appropriate
capacity and type approved by the Engineer-in-charge shall be used for preparation of the mixed
material. The plan shall have separate dryer arrangements for heating aggregate.
The bi nder shall be heat ed i n boi lers of suitable de sign, ap proved by t he Engineer-in-Charge t o the
temperature appr opriate t o t he gr ade of b itumen or as di rected by t he Engineer-in-Charge. T he
aggregates s hall be dry a nd s uitably heat ed t o a t emperature bet ween 150 oC and 165 oC or as di rected
by t he Engineer-in-charge before these components are placed in the mixer. Mixing of binder with
aggregates t o the s pecified pro portions s hall b e c ontinued until t he l atter are t horoughly c oated w ith the
former.
The m ix s hall b e im mediately transported from the m ixing plant to the po int of u se and s pread
uniformly on the bituminous surface to be sealed.
As soon as a s ufficient l ength has b een covered with t he premixed material, t he surface s hall b e
rolled with an 8 -10 t onne s mooth-wheeled roller. Rolling shall be continued until the premixed material
completely seals the voids in the bituminous course and a smooth uniform surface is obtained.
16.35.7 Rate
The r ate f or se al c oat s hall be c ost of all m aterials, lab our an d eq uipment inv olved in op eration
described above.
Vol-2 , 2013
16.36 9$&&80'(:$7(5(' CEMENT CONCRETE PAVEMENT
Specifications of item 16.37 to be followed except following :
16.36.1 The c oncrete s labs s hall be f inished by vacuum dewatering i ncluding al l opera tions s uch a s
poker v ibration, s urface v ibration, v acuum processing, f loating a nd t rowelling a s per eq uipment
manufacturer’s recommendation. The equipment to be used shall be subject to ENGINEER's approval.
16.36.2 Measurements
It shall be measured in cubic meteres correct to two place of decimal.
16.36.3 Rate
The rate shall include the c ost of material, labour and machinery inv olved in all the operations
described above.
16.37.1 Materials
16.37.1.1 Cement
(a) Cement used on work shall be as per sub head cement concrete of specifications.
16.37.1.2 Water : Water used on work shall conform to Specification of cement concrete.
16.37.1.3 Coarse Aggregate : These shall be crushed or broken from hard stones obtained from
approved quarry. T hese s hall be c lean s trong, durable of f airly c ubical s hape and f ree f rom s oft, f riable,
thin el ongated and l aminated di sintegrated pi eces. T hese shall al so be free from dirt, organic del eterious
and any other foreign matter and adherent coatings and s hall s atisfy t he phy sical r equirements l aid
down in para 16.37.19 under quality control.
16.37.1.4 Fine Aggregate : This shall be coarse sand conforming to Specification under Aggregate section.
16.37.1.5 Grading of Mixed Aggregates : The gr ading o f al l aggreg ates (c oarse an d f ine aggre gates)
to be u sed in the w ork s hall b e determined i n the laboratory. T he c oarse and f ine a ggregates s hall be
mixed i n s uitable pr oportions so that the gr ading o f t he mixed aggr egates s hall be i n t he range i ndicated
in Table 16.32.
TABLE 16.32
Vol-2 , 2013
16.37.2 Mix Design
16.37.2.1 The mix shall be approv ed by Engineer-in-Charge so as to obtain the following mean strength
that exceeds the minimum specified flexural strength by 1.64 times the designed standard deviation.
16.37.2.2 For t he p urpose of t endering t he contractor s hall b ase hi s rate o n t he a ssumption t hat t he
quantity of c ement used for one cum. of finished concrete s hall be 340 k g. or M - 30. If the actual
quantity of cement required to be used as a result of the laboratory test i s different from that as sumed
above, necessary adjustment in the cost due to short cement used shall be made on the basis of issue
rate of c ement i ncluding s torage c harges pl us 2. 5% f or handl ing c harges. H owever, under no
circumstances the quantity of cement to be used shall either exceed 350 kg./cum or fall below 330 kg. per
cum of finished concrete.
16.37.3 Statistical Field Check
16.37.3.1 Samples of concrete shall be taken at the mixer and work area , made, cured and tested in as
per specifications on cement concrete.
16.37.5.2 The side forms shall have a l ength of at least 3.0 m etres except on c urves of less than 4.5
metres radius w here shorter lengths m ay be used. W hen s et t o grade and stacked in place the
maximum dev iation of the t op s urface of any s ection f rom a s traight line s hall not ex ceed 3 m m. T he
method of c onnection be tween s ections s hall be s uch t hat t he j oint f ormed shall be f ree f rom pl ay o r
movement in any direction. T he us e of bent, t wisted o r w orn ou t forms s hall not be per mitted. A t least
three s take pockets for bracing pins or s takes shall be p rovided for eac h 3. 0 M l ength of forms. Bracing
and s upports m ust be am ple t o prev ent t he s pringing of f orms under pres sure of c oncrete or w eight or
thrust of the m achinery ( like sc reed vibrator) o perating on th e f orms. S upport to th e f orms shall b e
sufficiently rigid to hold them in position during the entire operation of laying and compacting and
finishing and t hat they shall not at any time d eviate m ore than 3 m m from s traight edge 3 m etres in
length. F orms w hich s how a v ariation from t he r equired rigidity o f t he al ignment and levels shown on t he
plans shall be reset or removed as directed. The length and number or pins or stakes shall be such as to
maintain the forms at the correct line and grade.
Vol-2 , 2013
16.37.5.3 The supply of forms shall be s ufficient to permit their remaining in place for at least 12 hr s.
after the concrete has been placed or longer, if in the opinion of the Engineer-in-Charge, it is necessary.
16.37.5.4 The top line of the forms is not to vary from the correct level or alignment and the levels and
alignment o f the forms a re t o be checked and corrected as nec essary i mmediately pr ior to t he pl acing of
concrete. T he t op edges and f aces of t he f orms a re t o b e c arefully c leaned a nd m aintained i n c lean
condition.
16.37.5.5 While removing the steel forms, care shall be taken to withdraw them gradually, any damage to
the bull nosed edges shall be made good while the concrete is still green.
(b) Forms shall be set for at least 50 metres in advance of the point where the concrete is being laid
and shall not be removed until at least 12 hrs. of placing of the concrete or longer if in the opinion
of Engineer-in-Charge is necessary.
(c) After setting, the working faces shall be thoroughly oiled by using approved oil before concrete is
placed against them.
(d) The pavement joints of overlay layer would overlap with the joints of underlay cement concrete
16.37.8.1 Compaction shall be carried out by electrically (or) d iesel ope rated need le and s creed
vibrators as s tipulated he reafter. N eedle v ibrator s hould be us ed al l ov er the ar ea f or obt aining initial
compaction of concrete. These should be of diameter not less than 4.5 cm. If the vibrator are pneumatic
the p ressure m ust not be be low 4 k g/sq.cm. If el ectrically ope rated, they should have a m inimum
frequency of 3500 impulses per minute.
16.37.8.2 There should be at least three needle vibrators w orking in any bay. A v ibrating s creed
consisting of a steel or timber section weighing not less than 15 kg. per metre with a tamping edge of not
less t han 7 cm width and ha ving a vibrator mounted t hereon shall f ollow n eedle vibrators t o o btain f ull
compaction. The face of the wooden tamping edg e of the screed s hall be l ined with M .S. Plate rigidly
fixed by m eans o f c ounter s unk s crew. W here s creed v ibrators are us ed f or compaction, a s tandby un it
shall always be m aintained r eady f or use, s hould t he other one go out o f o rder. Where el ectrically dr iven
vibrators ar e em ployed, a s tandby di esel pneum atic uni t s hall be k ept ready f or us e i n case of pow er
failure. A t t he di scretion of the E ngineer-in-Charge, f or c ompaction at edges and joints, v ibrators may be
supplemented by hand tamping and rodding for securing satisfactory results. Under no circumstances,
honey combing of concrete at joints or elsewhere shall be permitted.
16.37.8.3 When us ing s creed v ibrator for c ompaction i t should not be dr agged ov er the c oncrete. D uring
the initial pas ses i t s hall be l ifted to t he ad jacent forward pos ition i n short s teps, subsequently, i t s hall be
slowly slided over the surface with its axis slightly tilted away from the direction of sliding and the operation
repeated until a close, dense surface is obtained.
16.37.8.4 Concreting s hall be c arried out in one ope ration bet ween the ex pansion joints and construction
joints without any break at the dummy joints.
Vol-2 , 2013
16.37.8.5 Concrete shall be deposited on the base as near the joints as possible without touching them. It
shall t hen be s hoveled ag ainst t he s ides, m aintaining equal pr essure and d eposited app rox. 5 0 mm
higher than the depth of the j oints, care being taken that it is worked well around the joints. The concrete
shall not be dumped from the bucket directly upon or against the joints.
16.37.8.6 Workmen shall not be allowed to walk on freshly laid concrete and proper cat walk shall be
provided with independent supports beyond concreting bays.
16.37.9.1 During compaction, any low or high spots shall be made up by adding or removing concrete.
After longitudinal floating has been completed but while concrete is still plastic, the slab surface shall be
tested f or t rueness w ith a 3 m s traight edge. A ny depressions or high spots showing departure from the
true s urface s hall be i mmediately r ectified. H igh spots s hall be c ut dow n and r efinished. D epressions
shall be enlarged to about 8-10 cm and filled up with fresh concrete, compacted and finished.
16.37.9.2 The straight edge testing the refloating is to continue until the entire surface:
(c) shall conform to the specified surface when the concrete has hardened.
16.37.9.3 The foregoing work is to be carried out while the concrete is still plastic and workable.
16.37.10 Belting
16.37.10.1 Just bef ore c oncrete becomes non-plastic, t he s urface s hall be belted w ith a t wo pl y c anvas
belt not less than 20 c m wide and at least 1 m etre longer than the width of the slab. Hand belts shall
have suitable handles to permit controlled uniform manipulation. The belt shall be operated with short
strokes transversed to the centre line of the pavement and with rapid advance parallel to the centre line.
16.37.11 Brooming
16.37.11.1 After belting and as soon as the surplus water, if any, has risen to the surface, the pavement
shall be gi ven a broom finish with an appr oved s teel or fiber broom not less than 45 cm wide. The broom
shall be pul led gent ly ov er t he s urface of t he pav ement f rom edge t o edge. A djacent s trokes s hall b e
slightly o verlapped. B rooming shall be per pendicular to t he c entre l ine o f t he pav ement and s o ex ecuted
that the corrugations formed shall be uniform in character and width and not more than 1.5 mm deep.
16.37.11.2 Brooming s hall b e completed b efore t he c oncrete r eaches such a s tage t hat t he s urface i s
likely t o be torn or unduly roughened by the operation. The broomed s urface shall be free from porous or
rough spots, irregularities, depressions, an d small pockets such as may be caused by accidental
disturbing of pa rticles of coarse aggr egates em bodied near the s urface. T he b rooming s hall be of
uniform pattern all through.
16.37.11.3 Edging : After belting/brooming has been completed but before the initial setting of concrete, the
edges of the slab shall be carefully finished with an edge r of 6 m m radius, and the pavement edges shall
be left smooth and true to line.
Vol-2 , 2013
16.37.12 Honey Combing
16.37.12.1 The s ide forms shall not be r emoved un til 12 hour s o r such l onger period a s t he E ngineer-in-
Charge may decide after the laying of concrete.
16.37.12.2 As soon a s t he s ide f orms are r emoved, a ny m inor honey combed area shall b e f illed w ith
mortar composed of one part of cement and two parts of fine aggregate. Major honey combing areas or
segregated c oncrete or o ther def ective w ork o r ar eas da maged b y r emoval of t he f orms o r c oncrete
damaged b y r ain or due t o any ot her reason whatsoever shall be c onsidered a s def ective w ork and shall
be r emoved and replaced b y t he contractor at hi s ow n ex pense. The total ar ea o f hone y combed s urface
shall not exceed 4 per cent of the area of the slab side. However, no individual honeycomb patch shall
exceed 0 .1 s qm. E ngineer-in-Charge’s decision as t o w hether t he c oncrete is defective or no t shall be
final and binding.
16.37.13.1 After the c oncrete has s ufficiently har dened a fter about 12 hour s and not l ater than 24 hours,
the surface s hall be t ested again for high s pots. A ll high s pots s hall be m arked a nd those ex ceeding 3
mm shall be ground down immediately. Care shall be taken to see that the grinding does not in any way
damage the concrete surface.
16.37.13.2 The final surface finish is to be such that when tested with a profilograh/roughness
indicator/or a 3 metre long straight edge or an equivalent mechanical unevenness indicator placed
anywhere within t he s ame or adjoining s lab i n a ny di rection o n t he surface, t here shall be n o variation
greater than 3 mm.
6.37.13.3 If the surface irregularity exceeding 3 mm still remains despite grinding as per para
16.37.13.2 the concrete shall be removed to its full depth. The area of concrete to be removed shall be
complete s lab be tween the n earest joints, w here t he de fective s lab is less than 4 .5 m etres from the
expansion joint, the whole area upto the expansion joint shall be removed to the full depth. The concrete so
removed shall not be reused in the work. Fresh concrete shall be laid in the manner already described
in above paras and shall again be subject to test for surface accuracy and other quality control measures.
Nothing extra shall be paid on this account.
16.37.13.4 Every s lab s hall bear an i mpression not ex ceeding 3 m m i n depth c omprising t he num ber
allotted to t he s lab and the dat e on w hich i t is l aid. T his impression s hall be f ormed by t he c ontractor
when the concrete is green so as to leave permanent mark on setting.
16.37.13.5.1 Immediately after completion of the finishing operations, the surface of the pavement shall be
entirely c overed w ith w etted bur lap, c otton or j ute m ats. T he m ats us ed s hall be of s uch l ength ( or
width) that as laid they shall extend at least 45 cm b eyond the e dges of the slab. T he mats shall be
placed so that the entire surface and both edges of the slab are completely covered. This covering shall be
placed as soon as, in the judgment of the Engineer-in-Charge the concrete has set sufficiently to
prevent d amage t o t he s urface pri or t o bei ng pl aced, t he m ats s hall be t horoughly saturated w ith water
and s hall be placed w ith t he w ettest side down. T he mats shall b e s o pl aced and weighed down a s t o
cause them to remain in intimate contact with the surface covered, and the covering shall be maintained full
wetted and in position for 24 hours after the concrete has been placed or until the concrete is
sufficiently h ard t o be walked on w ithout suffering da mage. Water shall be gent ly s prayed s o as t o av oid
damage t o t he f resh c oncrete. I f i t bec omes nec essary t o remove a m at f or any reason, t he c oncrete
slab shall not be exposed for a period of more than half an hour.
Vol-2 , 2013
16.37.13.5.2 Worn burlap or burlap w ith holes s hall not be per mitted. B urlap reclaimed f rom previous
use ot her t han c uring c oncrete s hall be t horoughly w ashed pri or t o us e f or c uring purpos es. I f burl ap i s
obtained in strips, shall be laid to overlap by at least 150 mm.
16.37.14 Burlap s hall b e pla ced f rom s uitable bridges. W alking o n fr eshly lai d c oncrete to facilitate
placing burlap shall not be permitted.
16.37.15.1 Upon t he removal of t he burlaps, t he slab shall be t horoughly w etted and t hen cured as
follows:-
All j oints s hall be f illed with f iller i n order t o prevent t he edges of j oints f rom get ting dam aged and
entry of clay materials into the joints during final curing. Exposed edges of the slab shall be bank ed with
a s ubstantial b erm of e arth. U pon t he slab shall t hen be l aid a system of t ransverse a nd l ongitudinal
dykes of c lay about 50 m m hi gh immediately c overed w ith a bl anket of s andy s oil free f rom stones to
prevent the drying up and cracking of clay. The rest of slab shall then be covered with sufficient sandy
soil so a s to pr oduce a bl anket of earth not l ess than 40 mm deep a fter w etting. The ea rth covering shall
be thoroughly wetted while it is being placed on the surface and against the sides of the slab and kept
thoroughly saturated with water for 21 days and thoroughly wetted down during the morning of the 22nd
day and shall thereafter remain in place until the concrete has attained the required strength and
permission is g iven by the E ngineer-in-Charge. T hereafter the c overing s hall be rem oved and the
pavement c leaned an d s wept. I f the ea rth c overing bec omes di splaced d uring t he c uring period, i t s hall
be replaced to the original depth and resaturated.
16.37.15.2 Contractor shall appoint chowkidars at his expense to prevent workmen, cattle, etc., straying
on the pavement concrete.
16.37.15.3 Concrete shall not be s ubjected to any load or w eight of any plant until at least 28 day s after
laying.
16.37.16.1 Construction j oints s hall be pr ovided a s s hown in the dr awing and a lso a t p laces w here
concreting i s s topped d ue t o unf oreseen c ircumstances. T he j oints s hall be s traight and vertical t hrough
the f ull t hickness of t he s lab. W hile c oncrete i n ad jacent bay i s s till green, f lats of s uitable s ize s hall be
drawn along the e dge a nd a groove of size 10 m m × 2 5 mm deep shall b e ne atly formed a nd finished.
The edges of the groove shall be f ull nosed. After curing of concrete is complete, this groove shall be
thoroughly cleaned o f all s and dust and s hall be p erfectly dried an d f illed with ho t poured s ealing
compound c onforming to grade B of I S 1834. B efore f illing with sealing c ompound t he f aces of c oncrete
of the joint shall be coated with primer of approved brand to a depth of 25 mm at the rate of 2.6 liters per
10 square meters. Bitumen emusion shall not be used as primer.
16.37.17.1 The joints shall be 10 mm wide and shall extend vertically from the surface of the slab to a
depth equal to 1/3rd of the thickness of the slab but not less than 4 cm in any case. The joint may be
formed by depressing into the soft but compacted concrete a hi gh tensile M.S. or ot her approved Tee of
flat bar of depth not less than required depth of the joint plus 25 mm. The bar used for forming the
groove shall be coated with soft soap or other suitable lubricant to facilitate its removal when the steel
Tee or flat i s r emoved j oints s hall b e n eatly f ormed with proper t ools a nd mortar/fine material f rom the
slab itself. No additional cement mortar (rich or otherwise) shall be used.
Vol-2 , 2013
16.37.17.2
Cutting or s awing by a saw m ounted o n a m ovable frame and driven m echanically s hall also be
permitted as a method for making t he joint. I n t his c ase the w idth may b e reduced to 6 mm. an y other
method for making joints can be followed with the prior approval of the Engineer-in-Charge.
16.37.17.3
In all cases, except where cutting is done with saw, the joint edges shall be bullnosed. Care should
be taken to see that the edges of the grooves are not damaged.
16.37.17.4
The gr ooves s hall be filled w ith hot poured s ealing c ompound c onforming to Grade B o f
IS:1834. P rior t o filling w ith s ealing compound, t he joints shall be c leaned b y compressed ai r and pr imed
with Shalijet primer or equivalent at the rate specified in Para 16.37.16.1
16.37.17.5
All joints shall be sealed as soon as practicable after 28 days of casting of cc pavement.
Joints s hall be sealed f lush with t he adjacent pav ement s urface i n s ummer and 3 -4 m m bel ow f inished
concrete surface i n winter. The pav ement s hall be opened t o t raffic onl y a fter joint sealing over t he ent ire
pavement. T o prev ent t ackiness or pi ckup under t raffic, t he e xposed s urfaces of t he s ealing c ompound
shall be dus ted with hy drated l ime, i f di rected by Engineer-in-Charge, f or which n othing extra shall b e
paid to the contractor.
16.37.17.6
In case of sudden rain or storm, the work can be concluded at the dummy joints but these will then
be formed as construction joints.
16.37.17.7
Before sea ling of jo ints, it m ay b e en sured t hat the gr oove e xtends fu lly acr oss th e ba y
between c onsecutive l ongitudinal j oints, i n the case of t ransverse j oints and is c ontinuous i n t he case of
longitudinal joints. Any concrete or other foreign matter must be removed from the groove.
16.37.18.1
To prevent damage to freshly laid concrete during monsoon, or s udden rains, the contractor shall
provide an adequat e s upply of tarpuolines or ot her w ater pr oof c overing m aterial. A ny c oncrete
damaged by rain s hall be removed an d replaced b y t he c ontractor at hi s o wn c ost as di rected by t he
Engineer-in-Charge.
The f ollowing qual ity c ontrol t ests s hall be c arried out at f requencies s pecified agai nst eac h as i n
Table 16.33.
Vol-2 , 2013
TABLE 16.33
Vol-2 , 2013
1 2 3 4 5
(iv) Slump test IS 1199 At least once in 50 batches Not more than 25 mm
of concrete at each mixer or more
frequently if di rected b y t he
Engineer-in-Charge
(v) Flexural IS 516 One test of sample consisting As per para 16.37.3.5.
strength of eight specimen for every
30 cum of concrete
(vi) Surface As prescribed Regularly As per para 16.37.13
accuracy
16.37.20 Equipments
16.37.20.1
16.37.20.2
The Engineer-in-Charge reserves t he ri ght t o test any part of concrete l aid regardi ng q uality
soundness, compactness, thickness, strength and finish of the concrete, at any time before the expiry of the
“Defect l iability period” not w ithstanding t hat n ecessary t ests ha d b een c arried o ut a nd f ound
satisfactory at the time of execution.
16.37.20.3
All defective unsound sub-standard work and concrete of sub-standard strength and quality
etc. as established vide paras 16.37.3 shall be r ejected and s hall be r eplaced by the contractor at his
own e xpense i n t he m anner as d etailed i n para 16 .37.3. Where due t o oper ational or any ot her re ason
such replacement does not become possible (decision of Engineer-in-Charge in this respect being final
and b inding on the c ontractor), the c ost o f r emoval a nd r eplacement of s uch r ejected w ork s hall be
recovered from t he contractor w hether s uch rejected w ork i s s ubsequently replaced by the G overnment
or not.
16.37.21 Measurements
16.37.21.1
For t he purpos e of as certaining t he quant ity of c oncrete i n t he pav ement, t hickness s hall b e
measured by m eans of a s cale c orrect t o t he nearest 2 m m. T he t hickness of t he c oncrete pav ement
slabs s hall be t aken o n ei ther s ide of t he pav ement at eac h dum my j oint at f our c orners of t he s lab
Vol-2 , 2013
Note : The quantity of concrete in the pavement slab shall be worked out by multiplying the area of
the slab and its average thickness or specified thickness whichever is less. No deduction
shall be made for any joints in the concrete slab.
16.37.22 Rate
The rate of the item for concrete in pavement s hall include the c ost of all m aterials and labour
including c harges f or m achinery t ools & p lants req uired i n al l t he op erations des cribed abov e. T he rat e
also includes all cost of setting up the laboratory at site and carrying out the quality control
measures/tests enumerated above b y t he c ontractor at hi s own c ost i n t he pr esence of E ngineer-in-
Charge or his au thorized r epresentative and submission of t est results o n c ompletion o f t ests t o t he
Engineer-in-Charge thereof.
16.39.0 Materials
Premoulded Joint Filler in Expansion Joint : It shall conform to IS 1838 (Pt. I). The thickness shall be 25
mm w ith t olerance 1. 5 m m. and s hall be o f t he m aximum av ailable s tandard l ength not l ess t han on e
lane width. T he f iller b oard s hall b e p ositioned v ertically with t he pr efabricated joint a ssemblies along
the line of the joint within tolerance o f + 10 mm from the intended line of the joint. T he d epth of b oard
shall be 25 m m less than thickness of slab within a tolerance of ± 3mm so that the top of the board shall
be below the surface or will not impead the passage of the finishing straight edge or oscillating beam of
the paving machine.
Bitumine Hot Sealing Compound : The j oint s ealing compound s hall be f uel a nd h eat re sistant t ype
complying to g rade B o f IS 1834. It shall be c apable of adhering to the c oncrete w ithout cracking,
spalling and disintegration.
16.40.1 Expansion joints s hall be provided as s hown i n t he drawing and as per di rections of Engineer-in-
Charge. A ll j oints s hall be c onstructed t rue t o l ine w ith t heir f aces pe rpendicular t o t he surface of the
pavement. The joint shall be 20 mm wide. The depth of the non-extruding filler pad shall be 25 mm less
than the depth of the concrete slab.
16.40.2 Before the provision of ex pansion joint, the face of the already laid concrete s lab s hall be
painted w ith primer at t he rate of 2.6 liters per 10 s quare m etres. T he ex pansion pad s hall b e properly
cut to shape and shall then be placed in position abutting the painted face of the al ready l aid c oncrete
slab. T he adj acent s lab s hall t hen be c oncreted. T he f ace of t he pad against w hich t he new c oncrete
slab i s t o be l aid s hall also be pai nted w ith primer bef ore l aying t he c oncrete, w hile c oncreting a neat
groove of size 20 mm x 25 mm as per drawing shall be formed on top of the pad taking care that the
Vol-2 , 2013
edges ar e abs olutely s traight and that the gr oove s o m ade does no t ge t f illed w ith any m aterial like
concrete, mortar and other rubbish.
16.40.3 Before t he c uring process i s s tarted, t he t op of expansion joint shall be f illed w ith bitumen sand
mixture in order t o ensure t hat no f oreign m aterial used in c uring enters i nto the j oint. T his f illing shall be
removed before filling the joints with sealing compound.
16.40.3.1 For sealing the joints following operations shall be carried out :—
(a) The joints are cleared of any foreign matter to the full depth upto the top of expansion pad with
steel spatula.
(d) Priming is done with spray gun @ 2.6 liters per 10 sqm of the surface to be primed.
(e) The primer is allowed to dry completely before pouring the sealing compound.
(f) The sealing compound grade ‘A’ is heated to the required temperature ranging between 155 deg.
C to 165 deg. C or to the temperature range specified by the manufacturer. Over heating shall be
avoided. Pouring shall be done from vessel with spout in such a manner that the material will not
get spilled on the exposed surface of the concrete, any excess filler on the surface of the
pavement shall be removed immediately and the pavement surface cleaned.
(g) The filling shall be worked into the joints with hot flats to ensure escape of trapped air.
(h) The filling is then ironed with hot iron. It is recommended that while in summer the joints may be
sealed flush with the adjacent pavement surface, in winter the sealing compound may be filled to
a depth 3-4 mm below the surface.
(i) The edges of the joints are then cut and trimmed to ensure neat and straight line finish.
(j) To prevent tackiness or pick up under traffic, the exposed surfaces of the sealing compound shall
be dusted with hydrated lime, if directed by Engineer-in-Charge (Nothing extra shall be paid for
the same).
16.40.4 Rate
Rate for the item shall include the cost of all m aterials, plant, m achinery an d labour involved in all
operations described above, including all cartages and lifts.
16.41.1 Materials
The paver blocks shall have the following properties:
Crushing Strength: 40 MPa (Minimum) tested as per BS:15658.
Water absorption: 3% maximum tested as per BS:1881.
Abrasion resistance: As per IS:2386.
Thickness: 80 mm.
Vol-2 , 2013
All paver blocks shall be factory made using Automatic moulding and curing machine. All moulds and
machines shall be open for inspection of IOC. The handmade paver blocks shall not be accepted.
The pavers shall be manufactured as mono-layer only. The paver blocks shall be steam cured
The ingredients of the paver blocks shall comply with following:
Cement: Shall comply with IS:8112 for high strength ordinary portland cement or IS:12330 for Sulphate
resisting cement. The minimum cement content shall be 300 kg/m3.
Aggregates: Aggregates shall comply with IS:383. The Los Angles abrasion test limits shall not be more
than 35%.
Sand: The s and shall be p referably nat urally obt ained sand. Crushed stone sand may al so be us ed
complying with IS:383 requirement. The sand shall be in grading zone II or zone III.
Sand for cushioning
The sand used f or l aying the paver blocks shall be natural s and c omplying with I S:383. T he s and
from sea bed may also be used in this case.
Kerbing :The kerbing for pavers shall be made out of concrete cast-in-situ or pre-cast as directed
by site engineer
16.41.2 LAYING
The concrete pavers shall have perpendicular ties. The surface shall be anti-skid and anti-glare type.
The pavers shall have uniform special champers to facilitate easy drainage of surface run-off. The pavers
shall hav e uniform interlocking space of 2 to 3 mm to ensure compacted sand filling. The paver blocks
shall be tested one out of every 1000 pieces and the test result shall be produced to ENGINEER/IOC. All
these t esting s hall be at the c ost o f CONTRACTOR/VENDOR. The s ub bas e s hall be p repared t o the
required grade, level and camber. It shall be cleaned of all dust, dirt, and other extraneous matter. Any
ruts, soft yielding places or any pot holes shall be corrected by filling with good earth and well compacted
by mechanical vibrator. Form edge restrains before compacting blocks. Do not vibrate the paver until the
edge beam t ogether w ith an y c oncrete haunc hing has gai ned sufficient strength. The s and shall be
spread uniformly and evenly upon the prepared base in required quantities. It shall be spread in such a
manner that a fter compacting t he c onsolidated thickness w ill be 50mm. H owever, the s and l aid for
bedding should be un-compacted and surface vibrator shall be used after the pavers are laid.
Paving uni ts s hould be pl aced on t he pr epared l aying course so t hat t he s urface l evels ar e
within t he tolerance. The paver bl ocks shall be laid on t he s and c ushion and s hall be closely
interlocked. All design pat terns a s instructed b y I OC/ENGINEER with one or more different colours
shall be followed. The laying pat tern shall be her ringbone pat tern and c hecked w ith a s tring line. The
first row of paving units should be aligned against a straight section of the edge restraint. Paving units
should be laid with a joint width typically within the range of 2 mm to 5 mm.
Fully c ompact t he pav er us ing a pl ate compactor w ith a pl ate a rea o f not l ess than 0. 25 m2
transmitting an effective force not less than 75 KN/m2 of plate at a frequency of vibration in the range
75 Hz to 100 Hz. After compaction of the paver, spread sand of the grading in Table A(given below) as
joint filling. The paver shall be again vibrated to ensure complete filling of the block-to-block joint by the
surface applied sand preferably dry.
The paved area should be covered with full sized paving units, where paving units need to be
trimmed sizes smaller then a quarter of the original size of the unit should be avoided. Trimming has to
be carried by machine cut by hydraulic splitter to retain the perpendicular edges.The pavers used near
the kerbing shall be machine cut by hydraulic splitter to retain the perpendicular edges. The jointing
sand shall be spread over the pavers to ensure that the same is deposited uniformly in the joints. The
finished job shall be vibrated by means of surface vibrator so that all the blocks are properly interlocked.
Then the ex cess s and on the pav er bl ocks s urface c oming out due to v ibration s hall be r emoved b y
brooming.
Vol-2 , 2013
16.41.3 Measurement & Rates
Area provided with paver block to be measured in sqm. correct upto two places of decimal. The rate
include the cost of the material, labour, tools etc. required in all the operations described above.
16.42.2 Materials :The material t o be us ed for the work s hall be natural sand, c rushed gravel, crushed
stone, or combination t hereof depending upon t he g rading r equired. T he material shall be f ree f rom
organic o r o ther del eterious constituents and shall c onform to t he qual ity standards a s p rescribed i n t he
specifications for C ement C oncrete.Table 16.34 prescribes four gr adings for G ranular S ub-Base (GSB).
Gradings I and I I in Table are w ell gr aded gr anular s ub-base materials. These c an be us ed at l ocations
where drainage requirement are not predominant. Gradings III and IV are gap graded and addresses to the
concern of the drainage requirements. These can be used at location experiencing heavy rainfall, flooding
etc. C ases where G SB i s to be pr ovided i n t wo l ayers,it i s recommended t o adopt ei ther gr ading I II o r
grading I V for l ower layer and ei ther g rading I or gr ading I I f or upper layer. Minimum t hickness o f l ower
layer at l ocations w here dr ainage requirements a re p redominant shall not be l ess than 200 mm. The
grading to be adopted for a project shall be as desired by Engineer in Charge.
16.42.3 Physical requirements: The material shall hav e a 10 pe rcent fines v alue o f 50kN o r more ( for
sample in soaked condition) when tested in compliance with IS:2386 (Part IV) 1963. The water absorption
value of the c oarse aggregate shall be det ermined as per I S:2386 ( Part 3) . If this v alue i s gr eater than 2
percent, t he soundness t est shall be carried out on the material del ivered to site as per I S:383. F or
Gradings II and IV materials, the CBR shall be determined at the density and moisture content likely to be
developed in the field.
Note: The material passing 425 micron (0.425 mm) sieve for all the gradings when tested according t o
IS:2720 (Part 5) shall have liquid limit and plasticity index not more than 25 and 6 percent respectively.
Vol-2 , 2013
16.42.4 Construction Operations
16.42.4.2 Spreading and compacting : The sub-base material of grading specified in the Contract shall be
spread on t he pr epared s ubgrade with t he he lp of a motor gr ader of adequat e c apacity, i ts bl ade having
hydraulic controls suitable for initial adjustment and for maintaining the required slope and grade during the
operation or other means as approved by the Engineer. When the sub-base material consists of combination
of materials mentioned, mixing shall be done mechanically. Mixing shall be done in a separate yard by pugmill
or ot her a pproved m echanical m eans s o as t o issue hom ogenous & u niform mix. Moisture c ontent of t he
loose m aterial s hall be c hecked i n ac cordance with I S:2720 (Part 2) an d s uitably adjusted b y s prinkling
additional water from a truck mounted or trailer mounted water tank and suitable for applying water uniformly
and at controlled quantities to variable widths of surface or other means approved by the Engineer so that, at
the t ime of compaction, i t i s f rom 1 Percent abov e t o 2 per cent bel ow t he optimum moisture c ontent
corresponding to IS:2720 (Part 8). While adding water, due allowance shall be made for evaporation losses.
After water has been added, the material shall be processed by mechanical or other approved means until the
layer is uniformly wet.
Immediately thereafter, rolling shall start. If the thickness of the compacted layer does not exceed 100 mm, a
smooth wheeled roller of 80 to 100 kN weight may be used. For a compacted single layer upto 200 mm the
compaction shall be done with the help of a vibratory roller of minimum 80 to 100 kN static weight with plain
drum or pad foot-drum or heavy pneumatic tyred roller of minimum 200 to 300 kN weight having a minimum
tyre pressure of 0.7 MPa or equivalent capacity roller capable of achieving the required compaction. Rolling
shall c ommence at t he l ower edge and proceed t owards t he up per edge l ongitudinally f or por tions h aving
unidirectional crossfall and super-elevation shall commence at the edges and progress towards the centre for
portions having crossfall on both sides.Each pass of the roller shall uniformly overlap not less than one-third
of the track made in the preceding pass. During rolling, the grade and crossfall (camber) shall be checked
and any high spots or depressions which become apparent, corrected by removing or adding fresh material.
The speed of the roller shall not exceed 5 km per hour. Rolling shall be continued till the density achieved is at
least 85 percent of the maximum dry density for the material determined as per IS:2720 (Part 8). The surface
of an y layer of material on c ompletion of c ompaction s hall be well c losed, free f rom movement un der
compaction equipment and from compaction planes, ridges, cracks or loose material. All loose, segregated or
otherwise defective areas shall be made good to the full thickness of layer and re-compacted.
16.42.6 Rate
The rate for granular sub-base shall be payment in full for carrying out the required operations ncluding full
compensation for:
i) furnishing all materials to be incorporated in the work including all royalties, fees, rents where applicable
with all leads and lifts;
ii) all labour, tools, equipment and incidentals to complete the work to the Specifications;
iii) carrying out the work in part widths of road where directed
Vol-2 , 2013
16.45 CONCERTINA COIL FENCING
16.45.1 Material :
Concertina coil f encing shall be dia 6 10 m m ( having 15 nos r ound p er 6 mtre. length), s pring c ore
(2.5 mm thick) wire of high tensile strength of 165 kg./sq.mm with tape (0.52 mm thick) and weight
43.478 gm/metre.
16.45.4
Fixing Concertina coil fencing shall be fixed on angle iron shaped with 9 horizontal reinforced
barbed t ape (RBT) s tud t ied w ith G I s taples and G I clips t o retain hor izontal i ncluding nec essary bol ts or
GI bar bed w ire t ied t o angl e i ron al l c omplete as p er di rections of E ngineer-in-Charge w ith r einforced
barbed tape.
16.45.5 Measurements
The length of fencing shall be masured correct to a cm. for finished work.
16.45.6 Rate
The rate shall include the cost of labour and materials involved in all the operation described above
but excluding the cost of M.S. angle and excavation and concrete in foundation for which separate
payment shall be made under respective items.
Vol-2 , 2013
16.46 DENSE BITUMINOUS MACADAM
16.46.1 Scope
Dense B ituminous M acadam (DBM) i s us ed mainly f or i n b ase/binder an d p rofile c orrective c ourses.
DBM is also used as road base material. T his work s hall consist of construction i n a s ingle or m ultiple
layers of DBM on a previously prepared base or sub-base. The thickness of a single layer shall be
50 mm to 100 mm.
16.46.2 Material
16.46.2.1 Bitumen : The bi tumen shall be pav ing b itumen o f penet ration G rade o f s pecified c onsistency
and content conforming to IS 73 or as otherwise specified in the item.
16.46.2.2 Coarse Aggregates : The c oarse aggr egates shall c onsist o f c rushed rock, crushed gr avel or
other hard m aterial retained on t he 2.36 m m I S S ieve. T hey s hall be clean, ha rd, durable, o r c ubical
shape, free from dust and soft or friable matter, organic or other deleterious substance. Before approval of
the source, the aggregates shall be tested for stripping. The aggregates shall satisfy the physical
requirements specified in 16.35, for dense bituminous macadam.
Where c rushed gr avel i s proposed for us e as aggregate, not l ess than 90% b y weight o f the c rushed
material retained on the 4.75 mm IS Sieve shall have at least two fractured faces.
16.46.2.3 Fine Aggregates : Fine aggr egates s hall c onsist of c rushed or n aturally oc curring m ineral
material, or a c ombination o f the two, pas sing the 2.36 m m IS S ieve an d retained o n the 75 m icron
sieve. They shall be c lean, hard, durable, dry and free from dust and soft or friable m atter, organic or
other deleterious matter.
The fine aggregate shall have a sand equivalent v alue of not less than 50 when tested in ac cordance
with the requirements of IS 2720 (Part 37).
The plasticity i ndex o f t he fraction pas sing t he 0 .425 mm I S S ieve s hall not ex ceed 4, w hen t ested i n
accordance with IS 2720 (Part 5).
TABLE 16.35
Physical Requirements for Coarse Aggregate for Dense Bituminus Macadam
Vol-2 , 2013
(The elongation test to be done only on non-aggregate in the sample)
3. IS 2368 Part 4*
4. IS 2368 Part 4*
5. IS 2386 Part 5
6. IS 2386 Part 3
7. IS 6241
8. AASHTO T283**
* Aggregate may satisfy requirement of either of these two tests.
** T he water sensitivity test is on ly required if the minimum retained coating in the stripping test is less
than 95%.
16.46.2.4 Filler : Filler shall consist of finely divided mineral matter such as rock dust, hydrated lime or
cement approved by the Engineer-in-Charge.
The filler shall be graded within the limits indicated in Table 16.36.
TABLE 16.36
Grading Requirements for Mineral Filler
The f iller shall be f ree f rom o rganic i mpurities and ha ve a pl asticity i ndex n ot g reater t han 4. T he
Plasticity Index requirements shall not apply if filler is cement or lime.
16.46.2.5 Aggregate Grading and Binder Content : When tested in accordance with IS 2386 Part 1
(wet sieving method), the c ombined grading of t he c oarse and f ine aggregates and added filler f or t he
particular mixture shall fall within the limits shown in Table 16-37 for dense bituminous macadam.
TABLE 16.37
Composition of Dense Graded Bituminous Macadam Pavement Layers
Grading 1
Nominal aggregate size 25 mm
Layer Thickness 50-75 mm
IS Sieve1 (mm) Cummulative % by weight of tatal aggregate passing
37.5 100
26.5 90-100
19 71-95
13.2 56-80
4.75 38-54
2.36 28.42
0.3 7-21
0.075 2-8
Bitumen content % by mass of 5% or as specified in the item
total mix2 (Marshal method)
Bitumen grade VG-30 grade or as specified in the item
Note: The combined aggregate grading shall not vary from the low limit on one sieve to the high
limit on the adjacent sieve.
Vol-2 , 2013
16.46.3 Mixture Design
16.46.3.1 Requirement for the Mixture: The mixture shall meet the requirements as given in Table
16.38.
TABLE 16.38
Requirements for Dense Bituminous Macadam
The requirements for minimum percent voids in mineral aggregate (VMA) are given in Table 16.38.
TABLE 16.39
Minimum Percent Voids in Mineral Aggregate (Vma)
Nominal Maximum Particle Minimum VMA, Percent Related to Design Air voids, Pe rce nt2
s ize 1 (mm)
3.0 4.0 5.0
9.5 14.0 15.0 16.0
12.5 13.0 14.0 15.0
19.0 12.0 13.0 14.0
25.0 11.0 12.0 13.0
37.5 10.0 11.0 12.0
Note:
1. T he n ominal maximum p article size is o ne size larger than the first sieve to re tain more than 10
percent.
2. I nterpolate minimum voids i n t he mineral aggregate (V MA) f or design ai r v oids values between
those listed.
16.46.3.2 Binder Content : The binder content shall be optimized by using Marshall method for
determining the op timum bi nder c ontent s hall b e adopted as de scribed i n the A sphalt Institute M anual
MS-2, replacing t he aggregates retained on t he 26.5 m m s ieve by t he aggregates pas sing t he 26. 5 mm
sieve and retained on the 22.4 mm sieve.
16.46.3.3 Job Mix Formula : The c ontractor s hall i nform t he E ngineer-in-Charge i n w riting, at l east 20
days before the start of the work, of the job mix formula proposed for use in the works, and shall give the
details of Source and location of all materials, their sizes, grading and test results.
Approval o f the job mix formula s hall be bas ed on i ndependent testing b y t he Engineer-in-Charge f or
which sa mples of all ingredients of the m ix sh all be furnished by th e Contractor as re quired by th e
Engineer-in-Charge.
Job m ix formula shall be revised if there is a c hange in source of m aterial and be got approved by
Engineer-in-Charge.
Vol-2 , 2013
16.46.3.4 Plant Trials - Permissible Variation in Job Mix Formula: Once t he laboratory jo b mix
formula is approved, the Contractor shall carry out plant trials at the mixer to establish that the plant can be
set up t o produce a uniform m ix conforming to t he ap proved job mix formula. Th e pe rmissible
variations of t he i ndividual percentages of t he various i ngredients i n t he actual m ix f rom t he j ob mix
formula to be used shall be within the limits as specified in Table 16.40.
TABLE 16.40
Permissible Variations from the Job Mix Formula
16.46.3.5 Laying Trials : Once t he pl ant t rials ha ve been s uccessfully c ompleted and appr oved, t he
Contractor s hall c arry out l aying t rials, t o dem onstrate t hat t he pr oposed m ix c an be s uccessfully l aid
and compacted.
16.46.4.1 Prime Coat : Where the m aterial on w hich the dense bituminous m acadam is to be laid is
other t han a bi tumen bou nd l ayer, a p rime c oat s hall be appl ied, as s pecified, i n ac cordance w ith t he
provisions, or as directed by the Engineer-in-Charge.
16.46.4.2 Tack Coat : Where the m aterial on which the d ense bituminous macadam is to b e p laced is
bitumen bound surface, a tack coat shall be applied as specified, in accordance with the provisions, or as
directed by the Engineer-in-Charge.
16.46.4.3 Mixing and Transportation of the Mixture : The provisions are as specified in item and
Morth specification.
16.46.4.4 Spreading : Morth s pecification shall a pply. T he p aver f inisher shall b e f itted with electronic
sensor device.
16.46.4.5 Rolling : The compaction process shall be carried out as per MORTH Specification.
16.46.4.6 Opening to Traffic : The newly laid surface shall not be open to traffic for at least 24 hours
after laying the completion of compaction, without the express approval of the Engineer-in-Charge in
writing.
16.46.4.7 Surface Finish and Quality Control of Work : The surface finish of the completed
construction s hall c onform t o t he re quirements of 1 6.32.3. T he materials an d w orkmanship s hall c omply
with the provisions set out in Table.
16.46.4.8 Arrangement for Traffic : During the period of construction, arrangements for traffic shall be
made in accordance with the provisions 16.32.5.
Vol-2 , 2013
16.46.5 Measurement
Dense B ituminous M aterials shall b e m easured a s fini shed work i n cu bic meters,correct t o t wo
places of decimal.
16.46.6 Rate
The rate include the cost of all materials, labour and equipment, in all the operation described above.
16.47.1 Bituminous M acadam (BM) is more open graded than DBM and consists of single course or
multiple courses of compacted crushed aggregates premixed with bituminous binder.
16.47.2 Material
16.47.2.2 Course A ggregates s ame as 16. 46.2.2 excepting s trength w hich s hall be max 40% for L os
Angeles Abrassion value and aggregate impace value of max 30%.
16.47.2.4 Aggregate grading and binds content ag gregate gr ading, quantity of bitumen and ap propriate
thickness are as per table 16.41.
TABLE 16.41
Composite Of Bituminous Macadam
16.47.2.5 Measurement : BM sh all b e m easured as fu rnished w ork i n c ubic m eters cor rect to t wo
places of decimal.
16.47.2.6 Rate : The ra te i ncludes t he c ost of all m aterial l abour a nd e quipments i n a ll t he op erations
described.
16.48 DENSE BITUMINOUS CONCRETE
16.48.1 Scope
Dense Bituminous C oncrete (D BC), i s us ed i n w earing an d prof ile corrective c ourses, in a s ingle or
multiple l ayers on a pr eviously p repared bo und s urface. A s ingle l ayer shall be 2 5 m m t o 10 0 m m i n
thickness.
16.48.2 Materials
16.48.2.1 Bitumen: CRBM or PMB as specified.
16.48.2.2 Coarse Aggregates : The coarse aggregates shall be generally as specified in Table 16.23.
Vol-2 , 2013
16.48.2.3 Fine Aggregates : The fine aggregates shall be all as specified in 16.33.2.3.
16.48.2.4 Filler : Filler shall be generally as specified in 16.33.2.4.
16.48.2.5 Aggregate Grading and Binder Content : When tested i n a ccordance w ith IS 2386 p art 1
(wet grading method), the combined grading of the coarse and fine aggregates and added filler shall fall
within the limits shown in Table No. 16.41 for grading 1 or 2 specified in the contract.
16.48.3 Mixture Design
16.48.3.1 Requirements for the Mixture : Apart from conformity with the grading and quality
requirements f or individual ingredients, t he mixture shall meet t he re quirements s et out in T able 1 6.39
except l oss of s tability of immersion i n water at 60 °C. T he requirements f or minimum percent v oids in
mineral aggregate (VMA) are as per 16.46.3.1.
16.48.3.2 Binder Content : The Marshall m ethod for det ermining the o ptimum bi nder content shall b e
adopted as described in the Asphalt Institute Manual MS-2, replacing the aggregates retained on the 26.5
mm Sieve and retained on the 22.4 mm Sieve, where approved by the Engineer-in-Charge.
16.48.3.3 Job Mix Formula : The p rocedure f or formulating the job m ix formula shall be generally as
specified in 16.46.3.3.
16.48.3.4 Plant Trials - Permissible Variation In Job Mix Formula : The requirements for plant trials
shall be as specified in 16.46.3.4.
16.48.3.5 Laying Trials : The requirements for laying trials shall be as specified in 16.46.3.5.
16.48.4 Construction Operations
Grading 1 2
Nominal aggregate size 19 mm 13 mm
Layer Thickness 50-65 mm 30-45 mm
IS Sieve1 (mm) Cumulative % by weight of total aggregate passing
45 - -
37.5 - -
26.5 100
19 79-100 100
13.2 59-72 79-100
9.5 52-79 70-88
4.75 35-55 53-71
2.36 28-44 42-58
1.18 20-34 34-48
0.6 15-27 26-38
0.3 10-20 18-28
0.15 5-13 12-20
0.075 2-8 4-0
Bitumen content % by mass of total 5.5% or specified in item or 5.5% or specified in item or
mix2 directed otherwise directed otherwise
Bitumen grade (pen) Specified in item or directed Specified in item or directed
otherwise otherwise
Note:
1. The combined aggregate shall not vary from the low limit on one sieve to the high limit on the
adjacent sieve.
2. Determined by the Marshal method.
136 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
16.48.4.1 Tack Coat : Where specified in the Contract, or otherwise required by the Engineer, a tack
coat shall be applied.
16.48.4.2 Mixing and Transportation of the Mixture : The provisions as specified i n i tem and MO RTH
specification shall apply.
16.48.4.5 Opening to Traffic : The newly laid surface shall not be open to traffic for at least 24 hour
after l aying and c ompletion of c ompaction, without t he e xpress ap proval of t he Engineer-in-Charge i n
writing.
16.48.4.6 Surface Finish and Quality Control : The surface finish of the completed construction shall
conform to the requirements of “Clause 9.2 and provisions set out in Section 900 of MORTH
specification”.
16.48.4.7 Arrangements for Traffic : During the period of construction, arrangements for traffic shall be
made in accordance with the provisions of 16.46.4.8.
16.48.4.8 Measurement for Payment : DBC m easured as finished w ork i n cubic m eters, correct to t wo
places of decimal.
16.48.4.9 Rate : The rate include the cost of material, labour and equipments, involved in all the
operations described above.
16.57 DELETED
Vol-2 , 2013
16.58 KERB STONE (PRECAST)
16.58.1 Laying
16.58.1.1 Trenches shall first be made along the edge of the wearing course of the road to receive the
kerb stones of c ement concrete of specified grade. The bed of the trenches shall be compacted
manually w ith s teel r ammers to a firm an d ev en s urface and then the s tones s hall be s et in c ement
mortar of specified proportion.
16.58.1.2 The kerb s tones with top 20 cm. wide shall be laid with their l ength running parallel to t he road
edge, true in line and gradient a t a distance of 30 cm. from the road e dge to a llow for the channel and
shall project about 12.5 cm. above the latter. The channel stones with top 30 cm. wide shall be laid in
position i n c hamber w ith finished road s urface and with s ufficient s lope t owards t he road gul ly chamber.
The j oints of kerb and c hannel s tones shall be s taggered and s hall be not more t han 10 mm. W herever
specified all joints shall be filled with mortar 1:3 (1 cement : 3 coarse sand) and pointed with mortar 1:2 (1
cement: 2 fine sand) which shall be cured for 7 days.
16.58.1.3 The ne cessary drainage openings of specified sizes shall be m ade through the kerb as p er
drawings or as directed by the Engineer-in-Charge for connecting to storm water drains.
16.58.2 Finishing
Berms and road edges shall be restored and all surplus earth including rubbish etc. disposed off as
directed by the Engineer-in-charge. Nothing extra shall be paid for this.
16.58.3 Measurements
It shall be measured in cubic meters with Length of the finished work (for specified width and height of
stone) shall be measured in running metre along the edge of the road correct to a cm.
16.58.4 Rate
The rate shall include the cost of all the materials and labour involved in all the operations described
above.
16.59 G.I. CHAIN LINK FABRIC FENCING
16.59.1 Material
G.I. Chain link fabric fencing of required width in mesh size 50 x 50 or 25 x 2 5 mm or specified
otherwise of a pproved br and an d m ade of s pecified dia G I w ire P VC c oated of s pecified t hickness / o r
not as specified in item of required colour or shade to be used.
16.59.1.1 Fixing : GI chain l ink shall be s tretched and fixed i n specified w idth, strengthening w ith 2 mm
dia w ire or nut s bol ts & washers as required t o be done c omplete as per the di rection of E ngineer-in-
Charge.
16.59.1.2 Measurements : The length and w idth shall be measured correct to a c m. The area s hall be
calculated in square metre, correct to two places of decimal.
16.59.2 The rate shall include the cost of material and labour involved in all the operations described as
above.
Specification for supplying, stacking and measurement to be same as for item no. 16.3.
Vol-2 , 2013
AP PENDIX B
A known w eight o f dr y s tandard sand, pas sing 710 m icron I .S. S ieve and r etained on 355 micron I.S.
sieve, is taken in the sand pouring cylinder. The cylinder is kept directly over the hole and the shutter of
the cylinder is released without any jerk and closed when the hole is filled with the sand. The quantity of
the residual sand in the cylinder as well as the quantity filling the cone of the cylinder are weighed.
A, d
Density: gmpercc
W−(W1+W2)
Vol-2 , 2013
BARBED WIRE FENCING (WITH R.C.C. POST)
Sub Head : Road Work
Clause : 16.16
100
125
125
G.I. or M.S. 125
Barbed Wire
125
125 1200
125
125
1800
125
G.L. 140
150
165
C.C. 1:5:10
100
600
150 150
150
450 450
INTERMEDIATE POST
Details of Reinforcement
125
In Post Vertical 6 Dia B ars 4 Nos.
Stirrups 6 Dia Bars 9 Nos. 125
G.L. 140
500 600
Cement Concrete1:5:10
C.C. 1:5:10
150
150
450
700
Vol-2 , 2013
FENCING WITH R.C.C. POST RAILS, PALES
Sub Head : Road Work
Clause : 16.18.6
150 150
110
90
1300
900
1850
90
110
100 100
450
450
C.C. 1:5:10
150 150
ELEVATION
30
130 75
25
130 130
2120
PLAN
A A 130
1250
Chamfer
10 x 10
90
75 50 75
50 75
SECTION A-A
B
DETAIL OF PALE
PART PLAN
DETAIL OF RAIL
Vol-2 , 2013
KERB & CHANNEL STONES
Sub Head : Road Work
Clause : 16.1.20
Kerb Stone
(of Material as Specified)
20 CM
12.5 CM 30 CM
10 CM WBM
Base Course
7.5 CM
Channel
(of Material as Specified)
Vol-2 , 2013
BROAD DETAILS OF COOKER FOR BITUMEN MASTIC IN WEARING
COURSES
Sub Head : Road Work
Clause : 16.33.3
Oil Tank
457
1600
710
760
1830
58
457
FRONT ELEVATION
915
845
SIDE VIEW
300
2640
PLAN
Fig. 16.13 : Broad Details of Cooker for Bitumen Mastic in Wearing Courses
Vol-2 , 2013
17.0 : SANITARY
INSTALLATIONS
Vol-2 , 2013
CONTENTS
Clause No. Brief Description Page No.
List of Bureau of Indian Standards (BIS) Codes 147
Vol-2 , 2013
Appendix A Standard Weights and Thickness of C.I. Pipes 170
Fig. 17.16 Typical Vertical Section of Wash Basins (Waste Pipe Open to View) 185
Fig. 17.17 Typical Vertical Section of Wash Basin (Waste Pipe Concealed from 186
View)
Vol-2 , 2013
LIST OF BUREAU OF INDIAN STANDARDS (BIS) CODES
S. IS No. Subject
No.
1. IS 771 (Pt.1) Specification for glazed fire clay sanitary appliances: Part 1: General
requirements.
2. IS 771 (Pt.-2) Specification for glazed fire clay sanitary appliances: Part 2: Specific
requirements of kitchen and laboratory sink.
3. IS 772 Specific action for general requirements for enameled cast iron sanitary
appliances.
4. IS 774 Flushing cisterns for water closets and urinals (Other than plastic
cistern)-Specifications.
5. IS 1300 Phenolic moulding materials.- Specifications
6. IS 1703 Water fittings- copper alloy float valves (horizontal plunger type) -
Specification.
7. IS 1729 Cast iron /Ductile Iron Drainage Pipes and pipe fittings for Over ground
non-pressure pipe line Socket and Spigot Series.
8. IS 1795 Specification for pillar taps for water supply purposes.
9. IS 2267 Polystyrene moulding and extrusion materials - Specifications
10. IS 2326 Specification for Automatic Flushing Cisterns for Urinals (Other than
plastic cisterns)
11. IS 2548 (Part-1) Plastic seats and covers for water closets Part 1: Thermo set seats and
covers - Specifications
12. IS 2548 (Part-2) Plastic seats and covers for water closets Part 2: Thermoplastic seats
and covers.- Specifications
13. IS 2556 Vitreous sanitary appliances (vitreous china) -Specifications
14. IS 2556 (Part-1) Part-1: General requirements.
15. IS 2556 (Part-2) Part-2: Specific requirements of wash-down water closets.
16. IS 2556 (Part-3) Part-3: Specific squatting pans.
17. IS 2556 (Part-4) Part-4: Specific requirements of wash basins.
18. IS 2556 (Part-5) Part-5: Specific requirements of laboratory sinks.
19. IS 2556 (Part-6) Part-6: Specific requirements of Urinals & Partition plates
20. IS 2556 (Part-7) Part-7: Specific requirements of accessories for sanitary appliances
21. IS 2556 (Part -14) Part-14: Specific requirements of integrated squatting pans.
22. IS 2556 (Part -15) Part-15: Specific requirements of universal water closets.
23. IS 2963 Specification for Copper alloy waste fittings for wash basins and sinks.
24. IS 3076 Specification for low density polyethylene pipes for potable water
supplies.
25. IS 3389 Urea formaldehyde moulding materials. - Specifications
26. IS 3989 Specification for centrifugally cast (spun) iron spigot and socket soil,
waste and ventilating pipes fittings and accessories.
27. IS 4827 Specification for electroplated coating of nickel and chromium on
copper and copper alloys.
28. IS 4984 Specification for high density polyethylene pipes for potable water
supplies.
29. IS 4985 Unplasticised P.V.C. pipes for potable water supply - Specifications.
30 IS 7231 Plastic flushing cisterns for water closets and urinals - Specifications.
31. IS 13983 Stainless steel sinks for domestic purposes -Specifications.
.
147 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
17.0 SANITARY INSTALLATIONS
17.0 TERMINOLOGY
Bend
Length of pipe bent or cast into an angle shape.
Bib Tap
A tap with a horizontal inlet and nozzle bent to discharge in a downward direction.
Blister
A r aised p ortion of t he s urface pr otruding n ot more t han o ne millimeter a bove t he s urface and n ot
greater than 3 mm in its greatest dimension.
Box Union
A device for joining two threaded pipes.
Caulking
(a) The process of d riving, pouring o r forcing lead, oakum, plastic or other material into a j oint to
make it leak proof.
Caulked Joint
A s pigot and s ocket j oint i n w hich t he j ointing m aterial i s c ompacted by m eans of c aulking t ool an d
hammer.
Chase
A continuous recess in wall, floor or ceiling for the purpose of holding pipes and conduits.
Vol-2 , 2013
Collar
A pipe-fitting in the form of sleeve for jointing the spigot ends of two pipes in the same alignment.
Craze or Crazing
Fine cracks in the glaze.
Cross
A pipe fitting used for connecting four pipes at right angles.
Fittings
Coupling, f lange, b ranch, ben d, t ee, el bow, uni on, w aste w ith pl ug, P o r S trap w ith v ent, f errule,
stop ta p, bib ta p, pillar t ap, globe ta p, ball va lve, cist ern, s torage t ank, b aths, water closets, boiler
geyser, pum ping s et w ith m otor a nd accessories, m etre, h ydrant v alve a nd any other article u sed i n
connection with water supply, drainage and sanitation.
Flush Bend
A bend located at the bottom of low level flushing cistern for the purpose of flushing pedestal type
water closet and similar fixture.
Gasket
A piece of compressible material used to make a joint between two flat surfaces.
Oakum
Hemp or old hemp rope soaked in oil to make it water proof.
Pinhole
A hole in the body, less than 1.5 mm, in its maximum dimension.
Reducer
A pi pe-fitting w ith i nside threads l arger at one end t han at t he ot her. A ll s uch f ittings hav ing m ore
than one size are reducers because of the custom of stating the larger size first.
Vol-2 , 2013
Socket
The female part of spigot and socket joint.
Soil Pipe
A pipe which conveys to drain the discharge from a water closet or urinals. In ‘One pipe’ and ‘single
stack’ syst em the so il p ipe a lso conveys t o a dr ain t he di scharges f rom bath, w ash bas ins, s inks and
similar appliances.
Speck
Area of the finished surface with contrasting colour less than one millimeter maximum dimension.
Spigot
The male part of a spigot and socket joint.
Stack
A main vertical discharge or ventilating pipe.
Trap
A f itting or dev ice s o des igned and c onstructed as t o provide, w hen properly v ented, a liquid s eal
which w ill p revent the bac k passage of ai r w ithout m aterially affecting t he flow o f sewage or w aste w ater
through it.
Union
A pipe fitting used for joining the ends of two pipes neither of which can be turned.
Valve
A device used for controlling the flow of liquid in a line of pipe.
Warpage
Distortion of original shape during manufacturing process.
Water Seal
The depth of water which should be removed from a fully charged trap before air can pass through
the trap.
Waste Pipe
A pipe used to convey liquid waste not containing human excreta.
Waste Stack
A vertical pipe used to convey liquid waste not containing human excreta.
150 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
17.1 APPLIANCES AND FITTINGS
17.1.0 All vitreous sanitary appliances (Vitreous China) shall conform to IS 2556 (Part-I) general
requirements.
Cisterns shall be of following type ( i) Vitreous China (IS 774) f or F lushing type (ii) A utomatic
Flushing Cistern (IS 2326) and (iii) Plastic cisterns (IS 7231).
17.1.1.1 Vitreous Chine Cisterns : The thickness of the body including cover shall be not less than 6mm
for v itreous C hina c isterns. T he o utlet of each s yphon o r s tand pipe s hall be securely c onnected t o the
cistern by m eans of l ock nut. T he cistern s hall b e f ree from m anufacturing f aults a nd o ther d efects
affecting their utility. All working parts shall be designed to operate smoothly and efficiently. Cistern shall be
mosquito proof. A cistern shall be considered mosquito proof only if there is no clearance any where
which would permit a 1. 6 m m wire to pass through in the permanent position of the cistern i.e. in the
flushing position or filling position.
The breadth of a l ow level cistern, from front to back shall be s uch that the cover or s eat, or bot h, of
water closet pan shall come to rest in a stable position when raised.
The c istern s hall be s upported on t wo c ast i ron b rackets of s ize as appr oved by t he E ngineer-in-
Charge and embedded i n c ement c oncrete 1: 2:4 block 100 x 75 x 15 0 mm. These shall be pr operly
protected b y suitable i mpervious pa int. A lternatively the c isterns s hall have t wo ho les in the b ack s ide
above t he ov erflow l evel for s crewing i nto t he w all, s upplemented by t wo cast i ron w all s upports. A 5
litres cistern, however, may be supported by larger brackets cast on the body of the cistern.
The c istern shall h ave a removable c over w hich s hall fit closely on it and be secured against
displacement. I n designs where t he operating mechanism i s at tached t o t he c over t his m ay be m ade in
two s ections, but t he section supporting t he mechanism s hall be s ecurely bol ted or screwed t o t he bod y.
The outlet fitting of each cistern shall be securely connected to the cistern. The nominal internal
diameter of cistern outlet shall be not less than 38 ± 1mm for low level cisterns respectively. The length of
the outlet of the cistern shall be 37 ± 2 mm.
Ball valve shall be of screwed type 15 mm in diameter and shall conform to IS 1703. The float shall be
made of polyethylene as specified in IS 9762. (The design shall permit the cistern to fill in rapidly and close
effectively when the level of water reaches the working water level.)
In the case of manually operated cisterns the siphonic action of the flushing cistern shall be capable of
being rapidly br ought i nto action b y t he oper ating l ever, but shall not self siphon or leak. When tested
according to IS 774 the discharge rate shall be 10 ± 0.5 litre in 6 seconds and 5 ± 0.5 litre in 3 seconds for
cisterns of capacities 10 litre and 5 litre respectively. The cisterns shall be so designed that there is not
appreciable v ariation i n t he f orce of f lush du ring t he di scharge of t he required qu antity of w ater. T he
cistern shall have a discharge capacity of 5 & 10 litres as specified. When required to give a full flush,
they shall respectively discharge 5 litres and 10 litres with variation of ± 0.5 litres.
The flush pipe shall be of (a) medium quality galvanised iron having internal diameter of 38 ± 1 mm
for low level cistern. The flush pipe shall be of suitable length with bends etc. as required for fixing it with
front or back inlet W.C. Pan. (b) Polyethylene pipes low density conforming to IS 3076 or high density
(c) U nplasticised P VC p ipes. For h igh d ensity p olyethylene a nd un plasticised P VC p ipes, the o utside
diameter o f the pipes shall be 40 mm. When PVC p lumbing pipes are u sed the outside diameter o f the
pipe shall be 40 mm for high level cisterns and 50 mm for low level cisterns.
Vol-2 , 2013
In case of low level cistern the flush pipe shall be a vertical pipe 30 cm long and having a nominal
internal dia 38 ± 1 mm (except plastic flush pipes).
The invert of the ov erflow pipe in the c ase of high level and low level cisterns s hall be 19 m m
minimum above the w orking w ater level. In case of overflow due to any reason w ater should drain
out through the over flow pipe and not through the siphon pipe.
(b) T he plastic ov erflow pipes s hall be m anufactured from h igh de nsity p olyethylene c onforming to IS
4984 or unplasticised P.V.C. conforming to IS 4985.
Inlet and Overflow Holes: The c istern s hall be provided w ith inlet and ov erflow hol es, situated o ne at
each e nd w hich s hall b e c apable of a ccommodating an ov erflow pi pe of n ot less t han 2 0 m m n ominal
bore and a 15 mm size ball valve. The holes shall be cleanly cast or drilled and the adjacent surfaces
shall be smooth.
17.1.1.2 PVC Cisterns : Plastic flushing cisterns for WC and Urinals shall be as per IS 7231.
TABLE 17.1
Materials for Various Components of Flushing Cisterns
Vol-2 , 2013
(1) (2) (3) (4)
3. Cover Same material as that of the body
4. Chain Hot-dip galvanized steel wires -
Or
Inter-locked non-ferrous metal
Or
Any other corrosion resistant material
5. Overflow pipe High density polyethylene IS 4984
Or
Unplasticised PVC IS 4985
Or
Any other corrosion-resistant material
6. Siphon/Valve High density polyethylene IS 7328
Or
Polystyrene, high impact IS 2267
Or
Polypropylene
Or
Acrylonitrile- butadiene-styrene -
Or
Glass fibre reinforced plastic (GRP) -
7. Operating Non-ferrous metal or any other corrosion- -
Mechanism/ Lever resistant material
8. Float valve As specified in IS 1703
Or
IS 12234
Or
IS 13049
9. Polyethylene float As specified in IS 9762 -
for float valve
10. Coupling nut and Non-ferrous metal, -
lock-nut Or
Hot-dip galvanised steel
Or
Hot-dip galvanised malleable iron
Or
Any other non-corrosive metal
Or
Injection-moulded HDPE/polyacetal
Note: Where the requirements for the material of any component or the relevant Indian Standard
designation for any material are not specified, these shall be as directed by the Engineer-in-
Charge.
The t hickness o f the bod y including cover at an y poi nt shall not be l ess t han 2 mm for GRP, and not
less than 3 m m f or other plastic materials. The cistern shall be free from manufacturing f aults and other
defects a ffecting i ts ut ility. All w orking pa rts shall be des igned so a s t o oper ate smoothly an d e fficiently.
The c istern s hall b e m osquito-proof. I t s hall be deemed t o b e m osquito proof o nly w hen t here i s no
clearance a nywhere in it which would permit a 1.6 m m diameter wire to p ass t hrough. The o utlet of
each siphon or stand pipe or flush valve shall be securely connected to the cistern by means of a lock
nut. In the case of plastic siphon, it shall be provided with suitable means of ensuring and maintaining
watertight and airtight joint to the cistern.
Vol-2 , 2013
The c istern s hall be pr ovided w ith a r emovable cover w hich s hall f it c losely and s hall be s ecured
against di splacement. I n des igns, where the operating mechanism is at tached to t he c over, t he c over
may b e m ade i n two s ections, t he s ection s upporting t he mechanism being s ecurely fixed or b ooked t o
the body.
The flush pipe (except plastic flush pipe) shall have an internal diameter of 32 + 1 mm for high level
cistern and 38 + 1 mm for low level cistern. The steel flush pipe shall be not less than 1 mm thick
whereas the l ead f lush pi pe s hall have a minimum t hickness of 3 .5 m m. F or hi gh den sity p olyethylene
pipes, t he o utside diameter of t he pi pes shall be 4 0 m m. For unplasticised PVC plumbing pipes the
outside diameter of the pipe shall be 4 0 mm for high level cisterns, and 50 mm for low level cisterns. I n
the case of high level flushing cisterns, a pipe clip fitted with a rubber buffer shall be fixed to the flush
pipe to prevent damage either to the pipe or to the seat when the seat is raised. N o flush pipe is
required for coupled cisterns.
Note: The minimum thickness specified is for normal conditions of service. Where highly corrosive
atmospheres are expected, greater thicknesses are required to be provided as per nomenclature
of the item.
The screw threads for connection to the flush pipe shall not be less than size 1½ of IS 2643
(Part 3). In the c ase of polyethylene and unplasticised P VC f lush pi pes, t he upper end of the f lush pipe
shall b e pro vided w ith s uitable m eans of e nsuring an d m aintaining a w atertight an d ai rtight j oint to t he
flushing cistern. W hen o rdered f or u se w ith a f lush pi pe, t he outlet connection m ay b e s upplied w ith
coupling nut made o f c opper bas ed al loy or ot her non -corrodible material and a pl ain tail pi ece hav ing a
minimum l ength of 60 mm. T he c entre of t he o utlet h ole s hall b e g enerally c entral t o t he l ength o f t he
cistern. T he length of t he out let s hall be 37±2 mm i n c ase of i nterchangeable siphon; h owever, where
integral siphon is provided, the outlet length shall be 20±2 mm.
Note: The length of the cistern outlet shall be the dimension from the bottom surface of the cistern to
the end of the outlet after the cistern with siphon/stand pipe has been duly fitted with all washers,
lock-nuts, etc.
Float Valve
The float valve shall be 15 mm nominal size and shall conform to IS 1703 or IS 12234 or IS 13049.
In the case of low-level cisterns, where the mechanism is handle operated, the handle, whether
situated on the front or at the en d of the cistern, shall be within the projection limit. Particular attention
shall be given to the case of operation of the handle.
Vol-2 , 2013
String (Chain)
The string (chain) shall be of such strength as to sustain a dead load of 500 N without any apparent or
permanent deformation.
The s tring (c hain) s hall terminate i n a suitable handle or pu ll m ade o f a m oulding in any
heatresisting an d no n-absorbent plastic or a ny other e qually suitable m aterial. T he f inish shall be
smooth and all burrs which are liable to cause injury to the hand when gripped shall be removed.
Overflow Pipe
The ov erflow p ipe s hall be of not l ess t han 20 m m nom inal b ore an d s hall i ncorporate a
noncorrodible m osquito-proof de vice sec ured in a manner which will per mit it to be readily cle aned
or renewed when necessary. No provision shall be made whereby the overflow from the cistern shall
discharge directly into the water-closet or soil pipe without being detected.
The invert of the overflow pipe in the case of high-level and low level cisterns and the top edge of
the overflow pipe in the case of coupled cistern shall be 19 mm (Min) above the working water level. In
case of ov erflow du e to a ny reason, w ater should dra in out t hrough t he o verflow pi pe a nd not t hrough
the siphon pipe.
Finish
The surface of the cistern including cover shall be free from blisters and delamination, and
reasonably f ree f rom f low lines, s treaking or c olour variations. The cistern and cover shall be opaq ue to
light.
Discharge Capacity
When t ested i n a ccordance w ith I S 723 1, c istern o f 5 litres and 10 l itres capacities, when required t o
give a full flush, shall respectively discharge 5 l itres and 10 l itres with v ariation of ± 0 .5 l itres. D ual-flush
cistern of 10 litres capacity shall discharge alternatively a short flush of 5 ± 0.5 litres. Dual flush cistern
of 6/3 litres capacity shall discharge 6 ± 0.5 litres and alternatively a half flush of 3 ± 0.5 litres.
Discharge Rate
When tested in accordance with IS 7231, the discharge rate shall be 10 ± 0.5 litres within 6 seconds
and 5 ± 0.5 litres within 3 seconds for cistern of capacities 10 litres and 5 litres and 6 ± 0.5 litres within 6
second and 3 ± 0.5 litres within 3 second for cistern of 6/3 litres capacity respectively. The cistern shall
Vol-2 , 2013
be so des igned t hat t here is no appr eciable v ariation i n t he force o f the flush during t he di scharge o f t he
required quantity of water. For coupled cisterns, this test shall not be applicable.
Special Requirements
Distortion Resistance Test
The c isterns, c omplete with i ts fittings, s hall be installed and f illed with w ater t o t he m arked w ater
line and observed for any distortion. The cistern shall not budge more than 6 mm and the cover shall not be
dislodged.
Impact Test
The c istern, complete with its fittings, w hen i nstalled and filled a s des cribed i n IS 7231 s hall show no
defect after one i mpact. Repeat the test but with the cistern em pty. T he cistern shall show no def ect
after the further impact.
PVC shelf as per manufacturer’s specifications and size as specified shall be provided.
17.1.5 Mirror
The mirror shall be of superior glass with edges rounded off or beveled, as specified. It shall be free
from flaws, specks or bub bles. The size of the mirror shall be 60 x 45 cm unl ess specified otherwise and
its thickness shall not be less than 5.5 mm. It shall be uniformly silver plated at the back and shall be
free from s ilvering defects. S ilvering s hall ha ve a p rotective uniform covering o f red lead paint. W here
beveled edge mirrors of 5.5 mm thickness are not available, fancy looking mirrors with PVC
Vol-2 , 2013
beading/border or aluminium beading or s tainless steel bea ding/border based on manufacture’s
specifications b e pr ovided not hing e xtra sh all b e paid on t his account. Backing of mirrors sh all b e
provided with environmentally friendly material other than asbestos cement sheet.
TABLE 17.2
Minimum Finished Weights of Pillar Taps
Casting shall be sound and free from laps, blow hole and pitting. External and internal surfaces shall be
clean, smooth and free f rom sand and be neatly dressed. T he body, bonnet and other parts shall be
machined true so that when assembled, the parts shall be axial, parallel and cylindrical with surfaces
smoothly finished.
The area of waterway through the body shall not be less than the area of the circle of diameter equal to
the bore of t he s eating of t he t ap. T he s eating of pi llar t ap s hall be i ntegral with t he bod y and edge s
rounded to avoid cutting of w asher. P illar t aps s hall be ni ckel c hromium plated and t hickness of c oating
shall not be less than service grade No. 2 of IS 4827 and plating shall be capable of taking high po lish
which shall not easily tarnish or scale.
Every pi llar t ap, c omplete w ith i ts c omponent par ts s hall w ithstand an i nternally appl ied hy draulic
pressure of 20 Kg/sq. c m m aintained f or a peri od of 2 m inutes d uring w hich peri od i t s hall nei ther l eak
nor sweat.
17.1.8 Sand Cast Iron or Centrifugally Cast (Spun) Iron Pipes and Fittings
Sand cast iron spigot and socket soil, waste and ventilating pipes, fittings and accessories shall
conform t o IS 1 729. C entrifugally cast (Spun) i ron s pigot a nd s ocket s oil, w aste a nd v entilating pipes,
fittings and accessories shall conform to IS 3989.
The f ittings shall c onform t o t he s ame I .S. s pecifications t o which t he p ipe i tself conforms i n which
they are connected.
The p ipes shall h ave s pigot a nd socket ends , w ith he ad on s pigot end in c ase o f sand c ast iron
pipes and without head on spigot end in case of cast iron (Spun) pipes. The pipes and fittings shall be
Vol-2 , 2013
true t o s hape, s mooth and cylindrical, th eir in ner an d outer s urface b eing as n early as pr acticable
concentric. T hey s hall be s ound and s hall be f ree from c racks, t aps, p inholes and o ther i mperfections
and shall be neatly dressed and carefully fettled. All pipes and fittings shall ring clearly when struck with a
light hand hammer.
The ends of pi pes and f ittings s hall be reasonably s quare t o t heir axis. T he sand c ast i ron pi pes
shall be 1.5/1.8/2.0 metre in length including socket ends, cast iron (Spun) pipes shall be
1.5/1.75/2.0/2.5/3.0 metre i n l ength ex cluding s ocket ends, unl ess shorter lengths ar e ei ther specified o r
required at junctions etc. The pipe and fittings shall be supplied without ears, unless s pecified or
directed otherwise.
All pi pes and f ittings s hall be c oated i nternally and ex ternally w ith t he s ame m aterial at t he f actory,
the f itting be ing preheated pri or t o t otal i mmersion i n a bath containing a un iformly heated c omposition
having a tar or other suitable base. The coating material shall have good adherence and shall not scale
off. In all instances where the coating material has tar or similar base it shall be smooth and tenacious
and hard enough not to flow when exposed to a temperature of 77 degree centigrade but not so brittle
at a temperature of 0 degree centigrade as to chip off when scribed lightly with a pen knife.
The standard weights and thicknesses of pipes and their tolerances shall be as prescribed in
Appendix A.
The t hickness of f ittings a nd t heir s ocket and s pigot di mensions shall c onform t o t he t hickness an d
dimensions s pecified f or t he c orresponding sizes of s traight p ipes. T he t olerance i n weights &
thicknesses shall be the same as for straight pipes.
The a ccess d oor fittings s hall b e designed s o a s to avoid dead s paces i n which f ilth may
accumulate. Doors s hall be prov ided w ith 3 m m ru bber i nsertion pac king a nd w hen c losed and bol ted,
these shall be water tight.
17.1.9 Plastic Seat and Covers for Water Closet (Fig. 17.6)
The s eat a nd c over s hall be of t hermosetting or t hermoplastic conforming t o I S 2 548 as specified.
Unless otherwise specified these shall be of closed pattern.
17.1.9.1 Thermosetting plastic used shall conform to grade 2 or 3 of IS 1300 when it is phenolic plastic or
IS 3389 when of urea formaldehyde.
17.1.9.2 The hi nging dev ice shall be b ronze or b rass w ith ni ckel chromium p lating confirming to I S 106 8
and the seat shall have not less than three rubber or plastic buffers of size 25 mm x 40 mm x 10 mm for
closed front seats and not less than four for open front seats, which shall be securely fixed to the under
side o f the s eat unless ot herwise specified. The cover s hall be fitted with t he same nu mber o f bu ffers as
provided for the seat.
Vol-2 , 2013
17.1.9.3 Seats shall have a s mooth finish and shall be non absorptive and free from cracks and
crevices. They shall be capable of being easily cleaned and shall not be adversely affected by common
solvents or household cleanser.
17.1.9.4 Strength: The s eats shall withstand without per manent di stortion o f the seat o r hi nge fittings or
damage to any finish, a load of 1150 N for 30 minutes applied in the manner prescribed in IS 2548.
17.1.10.1 Stainless s teel k itchen s ink s hall be o f sizes a s specified and s hall be c onforming t o IS 13983
(Fig. 17.7).
17.1.13 Urinals
17.1.13.1 Bowl Type Urinals (Fig. 17.9 & 17.10) : Urinal bas ins shall be of flat back or corner wall t ype
lipped i n front. These shall be of white v itreous china conforming to IS 2556-(Part 6). The ur inals shall of
one pi ece c onstruction. E ach u rinal s hall be p rovided with not l ess than two f ixing hol es o f minimum di a
6.5mm o n e ach s ide. E ach uri nal s hall h ave an i ntegral f lushing ri m o f s uitable t ype an d i nlet o r s upply
horn for connecting the flush pipe. The flushing rim and inlet shall be of the self draining type. It shall
have a weep hole at the flushing inlet of the urinals.
At the b ottom of the urinal a n outlet h orn for c onnecting to an outlet pipe s hall be provided. T he
exterior of t he out let hor n s hall no t be g lazed and the s urface s hall be pr ovided w ith gr ooves at r ight
angles to the axis of the outlet to facilitate fixing to the outlet pipe. The inside surface of the urinal shall be
uniform and smooth throughout to ensure efficient flushing. The bottom of pan shall have sufficient slope
from the front towards the outlet such that there is efficient draining.
17.1.13.2 Half Stall Urinals (Fig. 17.11) : They shall be of white vitreous China conforming to IS 2556
(Part 6 ). They shall be of one piece construction with o r without an integral flushing box rim a nd
provided w ith s lots or al ternative f ixing arrangement at t he flat bac k end. T hey s hall be pr ovided w ith
ridges w here integral flushing rim is not provided in the sides of t he i nterior of the b owl, to divert t he
water t owards t he f ront line of t he urinal w here i ntegral f lushing box rim is specified, w ater s preaders
provided s hall conform to IS 2556 P art-6 (Fig. 17.13). T hese s hall be vitreous C hina of one piece
construction w ith i ntegral f lush i nlet. T he t olerance o f ± 4 per c ent m ay b e allowed on the d imensions
specified.
17.1.13.3 Urinal Partition Slabs : Urinal Partition slabs shall be provided, as specified in the item of work.
17.1.13.4 Squatting Plate Urinal (Fig. 17.12) : The plates shall be of white vitreous china conforming to
IS 2556 (Part-1) and IS 2556 (Part-6) with internal flushing rim with front or side inlet. Squatting Plate shall
be of one piece construction. Each urinal shall have integral longitudinal flushing pipe of suitable type
which may be connected to flush pipe. These shall be 100 mm dia white glazed vitreous china channel
with stop and outlet piece in front.
Vol-2 , 2013
17.1.14 Wash Basins (Fig. 17.14, 17.15, 17.16, 17.17 & 17.18)
Wash bas ins s hall be of w hite v itreous c hina c onforming t o I S 2556 ( Part-I) and I S 2556 ( Part-4).
Wash basins either of flat back or angl e back as specified shall be o f one pi ece construction, including a
combined overflow. All internal angles shall be designed s o as to f acilitate cleaning. Each b asin s hall
have a rim on a ll sides, e xcept sides in c ontact with the w alls and s hall h ave a s kirting at the bac k.
Basins s hall be p rovided w ith s ingle o r do uble t ap hol es as s pecified. T he t ap h oles s hall be 2 8 mm
square or 30 m m rou nd o r 25 m m round f or pop u p hole. A suitable tap h ole button shall be s upplied if
one t ap hole is not required i n installation. Each basin shall have c ircular waste hole to which t he i nterior
of basin s hall drain. The waste hol e shall be ei ther rebated or bev eled internally with di a meter of 65 mm
at top. Each basin shall be pr ovided with a non -ferrous 3 2 m m waste fitting. Stud slots to receive the
brackets on the underside of the wash basin shall be suitable for a bracket with stud not exceeding 13
mm diameter, 5 mm high and 305 mm from the back of basin to the centre of the stud. The stud slots
shall be of depth sufficient t o take 5 mm s tud. E very bas in s hall hav e an i ntegral soap hol der recess or
recesses, which shall fully drain into the bo wl. A slot type of overflow having an area of not less than 5
sq. cm, shall be provided and shall be so designed as to facilitate cleaning of the overflow.
Where oval shape or round shape wash ba sins are r equired t o be fixed t hese s hall be fixed
preferably in R CC pl atform w ith l ocal av ailable s tone topping ei ther fully s unk in s tone top or t op f lush
with the stone topping as directed by Engineer-in-Charge.
The wash basins shall be one of the following patterns and sizes as specified (Fig. 17.14).
(a) Flat back: 660 x 460 mm (Surgeon’s Basin)
630 × 450 mm
550 × 400 mm
450 × 300 mm
(b) Angle back: 600 × 480 mm
400 × 400 mm
White gl azed pedes tals f or w ash bas ins, w here s pecified shall be p rovided. T he qu ality of the
glazing of the pedestal shall be exactly the same as that of the basin along with which it is to be
installed. It s hall be c ompletely r ecessed a t the bac k to ac commodate s upply and w aste p ipes an d
fittings. I t shall be capable of supporting the bas in rigidly and ade quately a nd s hall be s o des igned as t o
make the height from the floor to top of the rim of basin 75 to 80 cm as shown in Fig. 17.14, 17.15,
17.16, 17.17 & 17.18. All the waste fittings shall be brass chromium plated, or as specified.
17.1.15 Waste Fittings for Wash Basins and Sinks (Fig. 17.8)
The waste f ittings shall b e of n ickel c hromium plated brass, with t hickness of p lating not l ess t han
service grade 2 of IS 4827 which is capable of receiving polish and will not easily scale off. The fitting
shall conform in all respect to IS 2963 and shall be sound, free from laps, blow holes and fittings and
other manufacturing defects. External a nd i nternal s urfaces shall b e c lean and s mooth. T hey s hall be
neatly dressed and be truly machined so that the nut smoothly moves on the body.
Waste fitting for wash basins shall be of nominal size of 32 mm. Waste fittings for sinks shall be of
nominal size 50 mm.
17.1.16 Water Closet (Fig. 17.19, 17.20, 17.21, 17.22 & 17.23)
17.1.16.1 Squatting Pans (Indian Type W.C.) ( Fig. 17.19, 17.20 & 17.21) : Squatting pans shall be of
white vitreous c hina c onforming to I S 2 556 Part-I f or General Requirements an d r elevant I S codes f or
each pattern as described below:
(i) Long pattern-conforming to IS 2556 (Part-3).
(ii) Orissa pattern-conforming to IS 2556 (Part-3).
(iii) Integrated type conforming to IS 2556 (Part-14).
Preferably Orissa type pan should be used.
Vol-2 , 2013
Each p an s hall ha ve an i ntegral f lushing rim of suitable t ype. I t s hall al so h ave an i nlet o r s upply
horn for c onnecting the flush pi pes, as s hown i n Fig. 17.19, 17 .20 & 17 .21. T he flushing rim a nd i nlet
shall be of the self draining type. It shall have weep hole at the flushing inlet to the pan. The flushing
inlet s hall be i n t he front, unl ess ot herwise specified or or dered b y t he E ngineer-in-Charge. The i nside of
the bottom of the pan shall have sufficient slope from the front towards the outlet and the surface shall
be uni form and s mooth t o enabl e eas y and quick di sposal w hile f lushing. The ex terior s urface of t he
outlet bel ow t he flange shall be an ungl azed s urface w hich s hall hav e g rooves at right angl es t o the a xis
of the outlet. In all cases a pan s hall be pr ovided with a ( 100 mm) S.C.I. trap ‘P’ or ‘S’ type with
approximately 50 mm water seal and 50 mm dia vent horn, where required by the Engineer-in-Charge.
17.1.16.2 Wash Down Type (European Type W.C.) ( Fig. 17.22 & 17.23) : Water c losets s hall be of
white vitreous china conforming to IS 2556 (Part-1) and 2556 (Part-2), as s pecified an d shall be of
“Wash down type”. The c losets s hall be ei ther of the two patterns (Pattern I & P attern I I) an d sizes as
shown in Fig. 17.22 & 17 .23 as specified. The closets shall be of one pi ece construction. Each water
closet shall have not less than two holes having a m inimum diameter of 6.5 m m for fixing to floor and
shall h ave an integral flushing rim of suitable t ype. It shall al so ha ve a n inlet or supply h orn for
connecting t he f lushing pipe of di mensions as s hown i n t able i n F ig. 17. 20 & 17. 21 t he f lushing rim
may be box ed or open t ype. I n t he c ase of box ri ms adequat e nu mber of h oles, on eac h s ide t ogether
with a s lot oppos ite the inlet s hall be pr ovided. T he f lushing rim and i nlet shall be of the s elf draining
type. T he w ater closet s hall hav e a w eep hole at the flushing inlet. E ach w ater closet s hall hav e an
integral trap with ei ther ‘ S’ or ‘ P’ out let with at least 50 mm water seal. For P trap, the slope of the out let
shall b e 14 de g. bel ow t he hori zontal. Where req uired t he w ater c loset s hall hav e an a ntisiphonage 5 0
mm di a v ent horn on t he outlet s ide of t he t rap w ith di mension c onforming t o t hose gi ven i n F ig. 17. 22
and on either right or left hand or centre as specified set at an a ngle of 45 d eg. and invert of vent h ole
not below the central line of the outlet. The inside surface of water closets and t raps shall be uni form
and smooth in order to enable an efficient flush. The serrated part of the outlet sh all not be gl azed
externally. The water closet, when sealed at the bottom of the trap in line with the back plate, shall be
capable o f h olding not le ss th an 15 l itres o f w ater bet ween the no rmal water level and th e hi ghest
possible water level of the water closet as installed.
17.2.1 The w ork s hall be c arried c ut, c omplying i n al l r espects w ith t he r equirements of r elevant
byelaws of the local body in whose jurisdiction the work is situated.
17.2.2 Any damage caused to t he building, o r t o el ectric, sanitary, water supply o r ot her, i nstallations
etc. therein, either due to negligence on the part of the contractor, or due to actual requirements of the
work, shall be made good and t he bui lding or the i nstallation shall be restored to i ts o riginal condition b y
the contractor. Nothing extra shall be paid for such restoration works except where otherwise specified.
17.2.3 For making good the damage to the under mentioned items of work, the specifications as given in
the following paras shall apply, unless directed otherwise.
(a) Masonry Work: The masonry work shall be made good by using the same class of bricks, tiles
or stones as was damaged during the execution of the work. The mortar used shall be cement
mortar 1:5 (1 cement: 5 fine sand) or as directed by the Engineer-in-Charge.
(b) Plain Concrete Work : Concrete work for sub-grade of the flooring, foundations and other plain
concrete works shall be cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone
aggregate 40 mm nominal size). A coat of neat cement slurry shall be applied at the junction with
old work, before laying fresh concrete.
(c) Cement Concrete Flooring and R.C.C. Work : Cement concrete 1:2:4 (1 Cement : 2 Coarse
sand : 4 graded stone aggregate 20 mm nominal size) shall be us ed after appl ying a coat of neat
cement s lurry a t t he j unction w ith old w ork, and the s urface f inished t o match w ith the
surrounding surface.
Vol-2 , 2013
(d) Plastering: Cement plaster 1:4 (1 cement: 4 sand) shall be used. The sand shall be fine or
coarse, as used in the original work. The surface shall be finished with two or more coats of
white wash, colour wash, distemper or painting as required, but where the surface is not to be
white washed, colour washed, distempered or painted, it shall be finished as required to match
with the surrounding surface.
(e) Other Items: Damage t o an y o ther i tem s hall b e m ade good as directed b y the E ngineer-in-
Charge.
17.2.4 All exposed G .I., C .I. or lead pipes and fittings shall be painted with approved qual ity of pai nt and
shade as specified. The painting work shall conform to specification described under SH: Painting.
17.2.5 All sanitary and plumbing work shall be carried out through licensed plumbers.
17.2.6 On completion of the work the site shall be cleaned and all rubbish disposed off as directed by
the Engineer-in-Charge.
17.2.7 Various sanitary fittings described under 17.1 including fixing shall be enumerated individually or in
combination un der r elevant i tems of w orks a s d escribed below. W hen us ed i n c ombination,
specifications a s des cribed under rel evant paras shall appl y but not hing e xtra s hall b e pai d f or m aking
connections required for successful functioning of the combination.
17.3.1 Fixing
One end of the board shall rest on s ink and the other end shall be supported on C.I. bracket
embedded in cement concrete (1:2:4) block 100 × 75 × 150 mm. The b rackets u sed shall be of
cantilever type or wall fixed type as for the sink.
17.3.2 Painting
The brackets shall be painted with two or more coats of approved paint.
17.3.3 Measurements
Draining board shall be measured in numbers.
17.3.4 Rate
The rate shall include the cost of all materials and labour involved in all operations.
17.4.1 Fixing
17.4.1.1 Low Level Cistern: The c istern s hall be f ixed on C .I. c antilever brac kets w hich s hall be f irmly
embedded in the wall in cement concrete (1:2:4) bl ock 100 x 75 x 150 mm. Connection between cistern
and closet s hall be m ade by m eans of 40 m m dia flush bend with rubber or G .I. inlet c onnection as
specified.
17.4.1.2 Automatic Cistern: Clause 1 7.4.1.1 s hall ap ply exc ept th at C P B rass sto p co ck s hall b e
provided for cistern ha ving a c apacity of m ore than 5 l iter. The m ain & distribution flush pipe shall be
fixed to the wall by means of standard pattern holder bat clamp shown in Fig. 17.5.
17.4.2 Painting
The br ackets shall b e p ainted, i f specified, with t wo or more coats o f p aint of a pproved s hade a nd
quality.
162 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
17.4.3 Measurements
Cistern, including all fittings, shall be measured in numbers.
17.4.4 Rate
The r ate s hall i nclude the c ost of al l materials and l abour i nvolved i n al l t he oper ations des cribed
above.
17.5.1 Fixing
The m irror shall be mounted on bac king w ith en vironmentally f riendly m aterial other t han as bestos
cement sheet shall be fixed in p osition b y means o f 4 C .P. brass screws and C.P. bra ss washers, o ver
rubber washers and w ooden pl ugs f irmly e mbedded i n w alls. C .P. b rass clamps w ith C .P. b rass sc rews
may b e an alternative m ethod of fixing, w here so d irected. U nless s pecified otherwise the longer s ide
shall be fixed horizontally.
17.5.2 Measurements
Mirror shall be measured in numbers.
17.5.3 Rate
Rate s hall i nclude t he c ost of al l t he m aterials and l abour i nvolved i n al l t he operations d escribed
above.
17.6.0 The s pecifications de scribed i n s ub-head 1 2.0 s hall a pply, a s f ar a s applicable, except t hat t he
joint shall be l ead caulked. A ll soil pipes shall be c arried up abov e the roof and shall have sand cast iron
terminal guard.
The pipes abov e the p arapet s hall be s ecured to the w all by m eans of M .S. stay and clamps a s
specified in 17.1.6.
The c onnections bet ween t he m ain pi pe and br anch pi pes s hall be m ade by us ing br anches and
bends w ith ac cess door s for cleaning. The w aste from lavatories, kitchen, bas ins, s inks, bat hs and o ther
floor t raps s hall b e s eparately connected to res pective waste s tack of up per f loors. T he waste s tack of
lavatories s hall be c onnected d irectly to m anhole w hile the w aste s tack o f othe rs s hall s eparately
discharge ov er gul ly t rap. W here s ingle stack system is p rovided, t he c onnection shall be made di rect to
the manhole.
17.6.2 Jointing
The interior o f the s ocket and ex terior o f the s pigots s hall be thoroughly c leaned and dried. T he
spigot end shall be inserted into the socket right u p to the ba ck o f the socket and carefully centered by
two or three laps of treated spun yarn, twisted into ropes of uniform thickness, well caulked into the back of
the socket. No piece of yarn shall be shorter than the circumference of the pipe. The jointed pipe line shall
be at required levels and alignment.
Vol-2 , 2013
The leading of pipes shall be made by means of ropes covered with clay or by using special leading
rings. The lead shall be melted so as to be thoroughly fluid and each joint shall be filled in one pouring.
The following precautions shall be taken for melting lead:
(a) The pot and the ladle in which lead shall be put shall be clean and dry.
(c) Any scum or dross which may appear on the surface of the lead during melting shall be skimmed
off.
After the l ead has been run i nto the joint the lead shall b e thoroughly caulked. Caulk ing of joints
shall be done after a convenient length of the pipes has been laid and leaded.
The leading ring shall first be removed and any lead outside the socket shall be removed with a flat
chisel and t hen the joint cau lked ro und three times wi th caulking too ls of increasing th ickness and
hammer 2 t o 3 kg. weight. The joints sh all not be co vered ti ll the pipe line has been tes ted under
pressure.
Use of collars for joint ing is n ot p ermitted in any co ncealed or embedd ed loca tion. Howe ver, in
exposed locations where full length pipes cannot be fixed due to site constraints, collars (and n ot loose
sockets) may be used subject to the following:
(a) No two consecutive joint shall be with the use of collars.
(b) The joint of collar with the cut/spigot end of the pipe shall be made on the ground in advance and
tested against leakage before fixing.
(c) Cut/spigot end of the pipes shall be inserted in the collars u p to the projection inside the col lar
and jointing shall be done as in the case of socket and spigot joint. The jointed pipe line shall be
at required level/slope and alignment.
a a
e d
c
Collar
Loose Socket
Note: The dimensions of loose sockets shall correspond to those of appropriate nominal size of pipe.
Vol-2 , 2013
17.6.3 Testing
In order to ens ure that ad equate lead i s pour ed pr operly i nto the joints and to control waste in use of
lead, at the beginning of work three or four s ample joints shall be m ade and the quantum of lead per
joint appr oved b y t he Engineer-in-Charge. A ll sand c ast i ron/cast i ron (Spun) pi pes and fittings i ncluding
joint s hall be tested b y s moke test t o the satisfaction o f the E ngineer-in-Charge and l eft i n w orking or der
after completion. The smoke test shall be carried out as under:
Smoke shall be pumped into the pipes at the lowest end from a smoke machine which consists of a
bellow an d burner. The m aterial u sually burnt is gre asy cotton w aste which gives out a c lear p ungent
smoke which is easily detectable by sight as well as by smell, if there is leak at any point of the drain.
17.6.4 Painting
All sand cast iron/cast iron (Spun) pipes and fittings shall be painted with shade to match the colour of
the background as directed by the Engineer-in-Charge.
17.6.5 Measurements
17.6.5.1 The pipes s hall b e measured net w hen f ixed i n p osition ex cluding al l fittings a long its l ength,
correct to a cm.
17.6.5.2 When collars are used for jointing SCI pipes these shall be measured as fittings and shall be
paid for separately.
17.6.5.3 No allowance s hall be made f or the p ortions of t he pipe l engths e ntering the s ockets of the
adjacent pipes or fittings. The above shall apply to both cases i.e. whether the pipes are fixed on wall
face or embedded in masonry.
17.6.5.4 No deduction shall be made in the former case from the masonry measurement for the volume of
concrete blocks embedded therein. Similarly no d eduction shall be made for the volume occupied by the
pipes from the masonry when the former are embedded in the later.
17.6.6 Rates
The r ate s hall i nclude the c ost of al l l abour and materials i nvolved in al l t he oper ations des cribed
above, e xcluding f ittings, l ead c aulk j ointing, t he supply a nd f ixing M .S. holder bat clamps a nd M.S.
stays and clamps, floor trap and painting, which shall be paid for separately.
17.7.1 Fixing
The seat shall be fixed to the pan by means of two corrosion resistant hinge bolts with a minimum
length of shank of 6 5 mm a nd t hreaded t o w ithin 25 m m of t he f lange supplied by the m anufacturer
along w ith the s eat. E ach bol t s hall be pr ovided w ith two s uitably s haped w ashers of r ubber o r ot her
similar materials for ad justing t he l evel o f the s eat w hile fixing i t to t he pans . In addi tion, one non -ferrous
or s tainless steel w asher shall be pr ovided w ith eac h bo lt. T he m aximum ext ernal diameter of t he
washer f ixed on t he underside of t he pan shall not be great er t han 25 m m. Alternative hinging de vices
as s upplied b y t he manufacturer o f t he s eat c an al so be us ed for fixing w ith t he appr oval o f E ngineer-in-
Charge.
17.7.2 Measurements
Seat with cover shall be measured in numbers.
17.7.3 Rate
Rate s hall i nclude t he c ost of al l t he m aterials and l abour i nvolved i n al l t he operations d escribed
above.
165 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
17.8 INSTALLATION OF SINK
17.8.0 The installation shall consist of assembly of sink C.I. brackets, union and G .I. or P.V.C. waste
pipe.
17.8.1 Fixing
The s ink s hall be supported on C .I. c antilever brackets, e mbedded i n c ement c oncrete (1:2:4) bl ock
of size 100 x 75 x 1 50 mm. Brackets shall b e fixed in p osition b efore the dado work is d one. T he C.P.
brass or P.V.C. union shall be c onnected to 40 mm nominal bore G.I. or PVC waste pipe which shall be
suitably b ent t owards the w all and shall di scharge into a floor t rap. C .P. br ass trap and uni on and w aste
shall be paid separately. The height of front edge of sink from the floor level shall be 80 cm.
17.8.2 Measurements
The sinks shall be measured in numbers.
17.8.3 Rate
Rate shall include the cost of all materials and labour involved in all the operations described above
but shall not included the cost of waste fitting and brackets which shall be paid for separately.
17.9 INSTALLATION OF URINAL LIPPED, HALF STALL (SINGLE OR RANGE) (FIG. 17.9 & 17.11)
17.9.0 Urinal i nstallation s hall c onsist of a l ipped uri nal (S ingle or range), an automatic f lushing c istern,
G.I. flush and waste pipe. The capacity of flushing cistern and relevant size of flush pipe for urinals in a
range shall be as prescribed in Table 17.3.
Waste pipe shall be of 32 mm nominal bore G.I. pipe and shall be paid separately.
17.9.1 Fixing
Urinals shall be f ixed in position by using wooden plugs and s crews. It shall be at a hei ght of 65 c m
from the standing level to the top of the lip of t he uri nal, u nless ot herwise directed by the E ngineer-in-
Charge. The size of wooden plugs shall be 50 mm × 50 mm at base tapering to 38 mm × 38 mm at top
and of l ength 5. 0 cms. These s hall be f ixed i n the w all i n c ement mortar 1:3 (1 c ement: 3 fine sand).
After the plug fixed in the wall, the mortar shall be cured till it is set.
TABLE 17.3
17.9.2 Measurements
Urinals shall be measured in numbers.
17.9.3 Rate
Rate shall include the cost of all the materials and labour involved in all the operations described above.
Vol-2 , 2013
17.10 INSTALLATION OF STALL URINAL (SINGLE OR RANGE)
17.10.0 The i nstallation shall c onsist of s tall u rinal (single or r ange), a utomatic f lushing cistern, C .P.
brass s tandard flush p ipes, C .P. br ass s preader and C .I. trap w ith tail pi ece and outlet gra ting of C .P.
brass. C apacity of f lushing c istern a nd r elevant s ize of f lush pi pe, C .I. t rap shall be as prescribed i n
Table 17.4.
TABLE 17.4
17.10.1 Fixing
The floor slab shall be suitably sunk to receive the stall urinal. Where the floor slab is not sunk, the
stall urinal s hall be pr ovided ov er a platform. T he l ip of t he s tall urinal s hall be f lush w ith t he f inished
floor level adjacent to it. The stall urinal shall be laid over a fine sand cushion of average 25 mm
thickness. A s pace o f not l ess t han 3 mm shall be pr ovided al l-round, i n front, sides and filled w ith w ater
proofing pl astic c ompound. C are s hall be t aken t hat af ter t he s ub-grade f or t he f loor i s c ast, one week
should lapse before urinals are installed. The trap and fittings shall be fixed as directed by the Engineerin-
Charge. Payment for the floor and its sub-grade shall be made separately.
17.10.2 Measurements
Stall urinals shall be measured in numbers.
17.10.3 Rate
The rate s hall i nclude the c ost o f al l t he materials and labour i nvolved i n al l the oper ations described
above.
17.11 INSTALLATION OF WASH BASIN (FIG. 17.14, 17.15, 17.16, 17.17 & 17.18)
17.11.0 The installation shall c onsist o f an a ssembly of w ash bas in, pi llar taps, C .I. br ackets, C .P. b rass
or P .V.C. uni on, as specified. The w ash bas in s hall be p rovided w ith one o r t wo 15 mm C .P. br ass pi llar
taps, as specified. The height of top of the rim of wash basin from the floor level shall be w ithin 750 mm
to 800 mm.
17.11.1 Fixing
The basin s hall be s upported o n a pai r of C .I. c antilever b rackets c onforming to I S 77 5 an d be
embedded in c ement concrete (1:2:4) block 100 x 75 x 150 m m. U se of M .S. angle or Tee section as
bracket is not per mitted. B rackets shall be fixed in pos ition before dado work is done. The brackets hav e
been shown i n Fig. 17.15. The wall pl aster on the rear shall be cut t o rest over the top edge of the basin
so as not to l eave an y gap for water t o seep through between wall pl aster & skirting of basin. After fixing
the bas in, pl aster shall be m ade go od an d s urface finished m atching w ith t he ex isting one. S.C.I. f loor
traps conforming to IS 1729 having 50 mm water seal (minimum 35 mm in two pipe systems with gully
trap) should be used. Waste pipes laid horizontally should have gradient not flatter than 1 in 50 and not
steeper than 1 in 10.
The w aste w ater from w ash basin s hall be di scharged di rectly t o v itreous s emi-circular open drain,
discharging to a floor trap and finally to the v ertical stack (Fig.17.15) on u pper floors and in c ase of
ground floor, t he w aste w ater shall be discharged ei ther di rectly to the gul ly t rap or through the floor trap
(Fig. 17.16). C.P. brass trap and union are not to be used in such situations.
167 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
If w aste pipe i s c oncealed or c rosses t he wall, w aste w ater s hall be di scharged t hrough non f errous
trap like P VC E ngineering plastic or C.P. brass and union (Fig. 17.17) to vertical stack. The C.P. brass
trap and union shall be paid for separately.
Where so specified a 20 mm G.I. puff pipe terminating with a perforated brass cap screwed on it on the
outside of the wall or connected to the antisyphon stack shall be provided.
17.11.2 Measurements
Wash basins shall be measured in numbers.
17.11.3 Rate
The rate s hall i nclude the c ost o f al l t he materials and labour i nvolved i n al l the oper ations described
above.
17.12.0 The installation shall consist of squatting pan, flushing cistern, flush pipe and a pair of foot rests.
17.12.1 Fixing
The pa n s hall be sunk into the floor an d em bedded in a cushion of av erage 15 c m thick c ement
concrete 1: 5:10 (1 C ement : 5 fine s and : 1 0 gra ded brick ballast 40 m m n ominal s ize). The concrete
shall be left 115 mm bel ow t he top level of the pan so as to allow flooring and its bed concrete. The pan
shall be provided with a 100 mm S.C.I., P or S type trap with an approximately 50 mm seal and 50 mm dia
vent h orn, where requi red by t he Engineer-in-Charge. T he joint bet ween t he pan an d t he t rap s hall be
made leak proof with cement mortar 1:1 (1 cement : 1 fine sand).
17.12.2 Measurements
The squatting pans shall be measured in numbers.
17.12.3 Rate
Rate s hall i nclude t he c ost of al l t he m aterials and l abour i nvolved i n al l t he operations d escribed
above. Cost of concrete shall be paid separately.
17.13.0 Installation shall consist of water closet with seat and cover, flushing cistern and flush bend.
17.13.1 Fixing
The closet shall be f ixed to the f loor by means of 75 mm long 6.5 mm diameter counter-sunk bolts
and nuts embedded in floor concrete.
17.13.2 Measurements
Water closets shall be measured in numbers.
17.13.3 Rate
Rate s hall i nclude t he c ost of al l t he m aterials and l abour i nvolved i n al l t he operations d escribed
above.
17.14.2 Measurements
Pair of foot rests shall be measured in numbers.
168 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
17.14.3 Rate
Rate s hall i nclude t he c ost of al l t he m aterials and l abour i nvolved i n al l t he operations d escribed
above.
17.15.0 The installation shall c onsist o f an assembly of s quatting plates (single or range), v itreous C hina
channel, automatic flu shing cistern, flu sh pipe with fi ttings s preader and C.I. t rap. T he c apacity of
flushing cistern and relevant size of flush pipes shall be as specified in Table 17.5.
TABLE 17.5
17.15.1 Fixing
The floor slab shall be suitably sunk to receive the squatting plate. Where the floor slab is not sunk, the
plates s hall be prov ided over a p latform. T he t op edge o f t he s quatting pl ate s hall b e f lush with t he
finished floor level adjacent to it. It shall be embedded on a layer of 25 mm thick cement mortar 1:8 (1
cement: 8 fine sand) laid over a bed of cement concrete 1:5:10 (1 cement: 5 fine sand: 10 graded brick
aggregate 20 mm nominal size).
There s hall b e 100 m m d ia, w hite gla zed v itreous C hina c hannels w ith s top and ou tlet p ieces
suitably f ixed i n t he f loor i n c ement m ortar 1: 3 (1 cement : 3 c oarse s and) and j oint f inished w ith w hite
cement. The squatting plate shall have 1200 high and half brick thick wall in front and on either side of
the squatting plate. The brick work for the walls shall be paid separately. The exposed surface of walls
shall be l ined with white glazed tiles with proper corners and a ngles set in neat cement mortar, the face
of the joints shall be gone over with whiting so as to match with the colour of the tiles. The tiles shall be
15 mm square. S pace if any, left between the side w alls and squatting plate shall be finished w hite t o
match the colour of the squatting plate. The trap and fittings shall be fixed as directed by the Engineerin-
Charge. The vitreous China channel shall discharge into 65 m m diameter standard urinals, C.I. trap with
vent arm having 65 mm C.P. brass outlet grating.
17.15.2 Measurements
Squatting plates shall be measured in numbers.
17.15.3 Rate
The rate shall i nclude the c ost o f al l t he materials and l abour i nvolved i n al l the oper ations des cribed
above.
17.16.1 Measurements
Tower rails shall be measured in numbers.
17.16.2 Rate
Rate s hall i nclude t he c ost of al l t he m aterials and l abour i nvolved i n al l t he operations d escribed
above.
169 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
AP P ENDIX A
STANDARD WEIGHTS AND THICKNESS OF C.I. PIPES
(Clause 17.1.8)
Vol-2 , 2013
PIPE SYSTEMS AND PARTS
Sub Head : Sanitary Installations
Clause : 17.1
Cowl
F.L F.L
Antisyphonage
Pipe
F.L F.L
F.L. F.L
Branch
W.C. B ranch S
Max Length 1500 WB
FT
FL
S
WC WB
Bath FT
FL S
38 ø WC WB
FT
FL S
WC WB
Swept Entry 50 Radius FT
FL S
WC WB
FT
FL
WC S. = Sink
W.B. = Wash Basin
F.T = Floor Trap
W.C. = Water Closet
F.L. = Floor Level
Large Radius Bends
Vol-2 , 2013
FLUSHING CISTERNS
Cover
Inlet
AUTOMATIC TYPE
Siphon
Body
Cover
Operating Lever
Overflow Pipe
this side Inlet and Ball Valve
Float
CURVED SI PHON TYPE Chain
Syphon
Pipe
Pull
Body
Lock Nut
Flush Pipe
Cover
Overflow Pipe
Bell
Inlet and Ball Valve
BELL TYPE
Pull
Flush Pipe
Vol-2 , 2013
FOOT REST
330
20 75
250
15 Min
ELEVATION
250 (Min)
125
(Min)
PLAN
Vol-2 , 2013
M.S. STAYS AND CLAMP
Terminal Guard
Socket
Top of Parapet
Pipe C.C 1:2:4
100
Parapet
ELEVATION
M.S. Clamp
30 x 1.5
PLAN
Vol-2 , 2013
PLASTIC SEAT AND COVER
Rubber Knob
3 mm Min. 10 mm Min.
Rubber or Plastic
Buffer
COVER
50 to 100 mm Width of
Position of opening for open front
Cover Seat
G
C D
F F
E B Cover
A 10 mm Seat
min.
3 mm min.
Rubber or
Seat Bolt Plastic Buffer
SEAT
(1) (2)
(i) Distance from centre line of hinge bolts to extreme 445 475
edge of rim at front, A
(ii) Length of opening at longest point, B 250 290
(iii) Width of opening at widest point, C 215 240
(iv) Overall width at widest point, D 380
(v) Distance between inner and outer rims, E 55
(vi) Centre-to-centre distance of seat bolt holes, F 145 175
(vii) Distance from centre line of hinge bolts to inner rim 85
of seat at the back, G
(viii) Thickness of seat at thinnest point 3
(ix) Thickness of cover at thinnest point 3
Note : Some hinging devices are made so as to provide adjustment in the longitudinal
direction. This is not precluded by these figures.
Vol-2 , 2013
KITCHEN & LABORATORY SINKS
Overflow
(Optional) C
for
Laboratory
Sinks
B
D 2
b f
b f
e
e
d a
d a d
Vol-2 , 2013
WASTE FITTINGS FOR W.B. & SINKS
88 mm φ +0
-2
58 mm φ 64 mm φ +0
-2
3 mm
Flange 40 m m φ
Chamfered 15 mm Min Flange
3 mm
27 m m Chamfered
3 mm
15 mm Min
3 mm
A A Slot Area 25 m m
-5 cm2 Min.
90 m m +2 A
-0 3 mm 75 m m +2
-0
50 m m Parallel 3 mm
Pipe Thread 50 m m Parallel
Pipe W idth
Recess for end of Recess f or end
Hex Width A/F tail piece Hex Width A/F of tail piece
65 m m 45 m m
83 m m 60 m m
Vol-2 , 2013
URINAL BOWL TYPE
c1
W
b
320
Flushing Rim
H 2 Holes ∅ 65 mm
on each side
85°
Slope
f K
e1
c2
SIDE FIXING
e2
Note : Where a closed channel with overflow is not provided a domed grating with perforating starting from the base and the
crown of which shall be 25 mm, minimum above surface shall be provided which may be integral or otherwise.
Vol-2 , 2013
URINAL BOWL TYPE (Contd.)
c1
b
2 Holes, ∅ 6.5 min
on each side
85°
Slope
K
e1
e2
c2
Vol-2 , 2013
URINAL – HALF STALL
e
10° m in 1
c
2
a b1) c1 c2 d e1 e2 f, Min
8_3DJH+2&LYLO6SHFLILFDWLRQV9ROXPH
Vol-2 , 2013
URINAL SQUATTING PLATE
∅ 13 Hole at
H1
e Three Places d2
W2 d1
W1 W1 H3
L H2
Vol-2 , 2013
SPREADER FOR URINAL
12
6
20 55
95
40 X
15
70 C/C
25
7.5 6.5
95 Elevated
13R Hole
6 mm Min 55
45 22 X
55
SECTION X-X
Vol-2 , 2013
WASH BASINS
200
50
110 460
750-800
Above 200 Min
460 Floor
610
660
SURGEONS BASIN
C A C
A
B B
ANGLE BACK
FLAT BACK
A g g4
2
f
g
1
SECTION A-A
d 1 A d
1
f 2
Vol-2 , 2013
FIXING ARRANGEMENT OF WASH BASIN
(ELEVATION OF WASH BASIN)
Semicircular
Channel
Floor Level
Slope Slope
F.T.
Waste Pipe Leading
to Vertical St ack Lean Conc. Filling
65
265 to 270
75 to 80
Vol-2 , 2013
TYPICAL VERTICAL SECTION OF WASH BASIN
(WASTE PIPE OPEN TO VIEW)
Plaster/Wall Finish
Brick Wall
Supporting
Bracket
Waste Hole
R.C.C. Slab
Filling/Lean Conc.
Water proofing layer
Localised depressed R.C.C. slab
portion of 250 mm to 325 mm
deep. (Also refer para 4.0 of
Q.C.T.A Circular No. 2 of 1992).
Fig. 17.16 : Typical Vertical Section of Wash Basin (Waste Pipe Open to View)
Vol-2 , 2013
TYPICAL VERTICAL SECTION OF WASH BASIN
(WASTE PIPE CONCEALED FROM VIEW)
Plaster/Wall Finish
Brick Wall
Supporting
Bracket
Waste H ole
Waste Fitting 32 mm
Elbow
P.V.C. Bottle Trap
32 mm Waste Pipe
750 to 800
Floor Level
Rich Conc. of m in. 50 m m
Thickness Alround
Floor Trap (75 m m/ 100 mm Outlet)
R.C.C. Slab
Water Proofing Layer
Filling/Lean Conc.
Fig. 17.17 : Typical Vertical Section of Wash Basin (Waste Pipe Concealed from View)
Vol-2 , 2013
ANGLE BACK WASH BASIN
(PATTERN-2)
SOAP
RECESS
200
200
MAX.
SECTION - X-X
Notes :
(1) Tap hole provisions are not shown. However provision shall be made for 1 or 2 Tap holes in any suitable position.
(2) Stud provisions are not shown but suitable provision shall be made for fixing purposes.
(3) Provision of soap recess need not be central in the case of single tap hole.
(4) Drawing not to scale.
(5) All dimensions are in mm.
Vol-2 , 2013
LONG PATTERN SQUATTING PAN, TYPE I
Flange
Optional
A
B C
L
M
G
K
Vol-2 , 2013
ORISSA PATTERN SQUATTING PAN
Flange Optional
H
J
B
C
D
L
F
M
G
K
Note : Footrest may be flushed or raised, clearance permissible between raised footrest and rim opening.
Vol-2 , 2013
INTEGRATED SQUATTING PAN
430
730
680
550 130
500 30 50 φ Main
50
45°
77°-80° 104°
320
Flange
Optional 50
140
Vol-2 , 2013
PATTERN 1 AND PATTERN 2 WATER CLOSETS
O
F E
D1
A
D D2/2
B
H R
C1
θ
K
P-TRAP
Q L
W2 J N
W1
0 F
E
G
A
B
D
S D1 C2
D2
S - TRAP 2
FUNCTIONAL DIMENSIONS CONNECTING DIMENSIONS
Pattern-1 Pattern-2
Vol-2 , 2013
PATTERN 3 WATER CLOSET WITH HORIZONTAL P-TRAP
F
E
D2 /2
S G
O B
D D1
C1 R1
∅
A
H
∅M
T
L
N
W1
W2 P J
F
E
G
Q D2
D1 B
K
D
FUNCTIONAL DIMENSIONS
CONNECTING DIMENSIONS
Vol-2 , 2013
18.0 : WATER SUPPLY
Vol-2 , 2013
CONTENTS
18.5 Laying and Jointing of Cast Iron Pipes and Fittings (External Work) 211
18.11 Making Connection of G.I., Distribution Branch with G.I. (Main) 225
Vol-2 , 2013
18.13 Fixing Ferrules 226
Fig. 18.6 Masonry Chambers and Surface Boxes (for Fire Hydrant and Water 245
Meter)
Fig. 18.7 Masonry Chambers and Surface Boxes (for Stop Cock and Sluice Valves) 246
Vol-2 , 2013
LIST OF BUREAU OF INDIAN STANDARDS (BIS) CODES
Vol-2 , 2013
18.0 WATER SUPPLY
18.1 TERMINOLOGY
Air Gap: The unob structed v ertical di stance t hrough t he f ree at mosphere be tween t he l owest op ening
from any pipe or fitting supplying water to a tank or other device and the flood level rim of the receptacle in a
water supply system.
Air Valve: A valve that releases air from a pipe line automatically without loss of water, or introduces air into
a pipe line automatically if the internal pressure becomes less than that of the atmosphere.
Available Head: The head of water available at the point of consideration due to main’s pressure or
overhead tank or any other source of pressure.
Back Flow: The f low of w ater i nto t he di stributing pi pes of w ater s ystem f rom any s ource or s ources
other than its intended source.
Back Siphonage: The flowing ba ck of us ed, c ontaminated or p olluted w ater from a p lumbing fitting or
vessel into a water supply system due to a lowering of pressure in such system.
Ball Cock (Fig. 18.1): A f aucet opened or c losed by t he f all or rise of a bal l f loating on t he s urface of
water.
Branch (Fig. 18.2): (i) A s pecial form of c ast iron pipe used f or m aking connections t o water m ains. T he
various types are called T, Y, T-Y, double Y, and V branches, according to their respective shapes.
Capacity: The storage capacity of storage or flushing cistern or a tank when filled up to the water line.
Non Return Valve (Fig. 18.4): A device provided with a disc hinged on one edge so that it opens in the
direction of normal flow and closes with reversal of flow.
Collar: A pipe fitting in the form of a s leeve for jointing the spigot ends of two pipes in the same
alignment.
Coupling: A pipe fitting with inside threads only, used for connecting two pieces of pipe.
Cross (Fig. 18.2): A pipe fitting used for connecting four pipes at right angles.
Elbow (Fig. 18.2): A pipe fitting for providing a sharp change of direction in a pipe line.
Ferrule (Fig. 18.2): A pipe fitting for connecting a service pipe to a water main.
Fitting: Anything fitted or fixed in connection with the supply, measurement, control, distribution,
utilization or disposal of water.
Fire Hydrant (Fig. 18.5): A device connected t o a w ater main and provided w ith necessary valve and
outlets, to w hich a fire hos e m ay b e attached for discharging w ater at a high rate for the purpose of
extinguishing fires, washing down streets, or flushing out the water main.
Flange (Fig. 18.2): A projecting flat rim on the end of a valve, pipe etc.
Flanged Pipe (Fig. 18.2): A pipe pro vided w ith flanges so that th e ends can be joined together b y
means of bolts.
Vol-2 , 2013
Float Valve: A valve in which the closure to a n op ening such as a pl ug or gat e is actuated by a f loat to
control the flow into a tank.
Sluice Valve (Gate Valve) ( Fig. 18.4) : A valve i n w hich t he flow of w ater is cut off by means of a
circular disc., f itting against m achine-smoothed faces, at right angles to t he direction of f low. T he di sc i s
raised or lowered by means of a t hreaded stem connected to the handle of the valve; the opening in the
valve is usually as large as the full bore of the pipe.
Nipple (Fig. 18.2): A tubular pipe fitting usually threaded on both ends and less than 300 mm long used for
connecting pipes or fittings.
Offset: A combination of elbows or bends which brings one section of the pipe out of line but into a line
parallel with the other section in a piping system.
Reflux Valve (Fig. 18.4): A non return valve used in a pipe line at a rising gradient to prevent water that is
ascending the gradient from flowing back in the event of a burst lower down.
Spigot (Fig. 18.2): The male part of a spigot and socket joint.
Stop Cock (Fig. 18.3): A control valve fixed at the end of a communication pipe which controls t he
supply from the water main.
Storage Tank: A tank or a cistern for storage of water which is connected to the water main by means of a
supply pipe.
Service or Supply Pipe: Pipe through which supply is drawn from water mains.
Union (Fig. 18.2): A p ipe fitting used f or j oining t he ends of t wo pi pes n either of w hich c an be t urned.
Valve: A device used for controlling the flow of water in a pipe line.
18.2.1 Any damage caused to the building, or to electric, sanitary water supply or other installations etc.
therein either due to negligence on the part of the contractor, or due to actual requirements of the work,
shall be made good and the building or the installations shall be restored to its original condition by the
contractor. Nothing extra shall be paid for it, except where otherwise specified.
18.2.2 All water supply installation work shall be carried out through licensed plumbers.
18.2.3 It i s m ost i mportant t o ens ure t hat wholesome w ater supply pr ovided f or dr inking and c ulinary
purposes, i s i n no w ay l iable to c ontamination from any less satisfactory water. There s hall, t herefore, b e
no c ross connection w hatsoever between a pipe or f itting f or c onveying or c ontaining w holesome w ater
and a p ipe o r fi tting for c onveying o r c ontaining impure w ater or water li able to c ontamination or of
uncertain qual ity of w ater w hich has been us ed f or any purpose. T he provision of reflux or non -return
valves or closed and sealed v alves shall not be c onstrued a per missible s ubstitute for c omplete abs ence
of cross-connection.
18.2.4 Where a supply o f wholesome w ater is required a s a n alternative o r standby to s upply of less
satisfactory water or is required to be mixed with the latter, it shall be delivered only into a cistern, and by
a pipe or fitting discharging into the air gap at a height above the top edge of the cistern equal to twice
its nominal bore, and in no case less than 15 cm.
Vol-2 , 2013
18.2.5 No piping shall be laid or fixed so as to pass into, through or adjoining any sewer, scour outlet or
drain or any manhole connected therewith nor through any ash pit or manure-pit or any material of such
nature that can cause undue deterioration of the pipe.
18.2.6 Where the l aying of a ny pi pe through fouled s oil or pr evious m aterial is unavoidable, t he p iping
shall be pro perly pro tected from c ontact w ith such s oil or m aterial by be ing c arried t hrough an ex terior
cast iron tube or by some other suitable means. Any piping or f itting laid or f ixed which does not comply
with the above requirements, shall be removed and re-laid in conformity with the above requirements.
18.2.7 The design of the pipe work shall be such that there is no possibility of backflow towards the
source of s upply from a ny cistern or appliance whether by siphonage or o therwise, and re flux or
nonreturn valves shall not be relied upon to prevent such back flow.
18.2.8 All pi pe work s hall be s o des igned, laid or fixed, and m aintained s o t hat i t r emains c ompletely
watertight, t hereby av oiding w astage o f w ater, da mage t o pro perty an d t he ri sk of contamination of t he
water conveyed.
18.2.9 In designing and pl anning the layout of the pipe work, due at tention shall be gi ven to the
maximum rate of di scharge, requi red ec onomy i n labour and m aterials, prot ection aga inst dam age a nd
corrosion, protection from frost, if required, and to avoidance of airlocks, noise transmission and
unsightly arrangement.
18.2.10 To reduce f rictional l osses, pi ping s hall be as s mooth as po ssible i nside. M ethods of j ointing
shall be such as t o av oid i nternal roughness and pr ojection at t he joints, whether o f t he jointing materials
or otherwise.
18.2.11 Change in d iameter an d in d irection s hall preferably be g radual r ather than a brupt to av oid
undue loss of he ad. N o be nd o r curve in pi ping s hall be made s o a s to materially r educe or al ter the
cross-section.
18.2.12 Underground piping shall be laid at such a depth that it is unlikely to be damaged by frost or
traffic loads and v ibrations. I t s hall not be laid i n gr ound l iable t o s ubsidence, but w here s uch gr ound
cannot be avoided; special precautions shall be taken to avoid damage to the piping. Where piping has to
be l aid ac ross r ecently di sturbed gr ound, the g round shall be thoroughly c onsolidated so as to pr ovide a
continuous and even support.
18.2.14 In flats and tenements supplied by a common service pipe a stop valve shall be fixed to control
the each br anch separately. In large bui ldings a sufficient num ber o f stop v alves shall be fixed on br anch
pipes, and t o c ontrol gr oups of bal l v alves and d raw off taps, s o as t o minimize i nterruption of t he s upply
during r epairs, al l s uch s top v alves s hall be f ixed in ac cessible pos itions and pr operly pr otected f rom
being tampered with, they may be of the gate type to minimize loss of head by friction.
18.2.15 Water for drinking or for culinary purposes as far as possible shall be on branch pipes
connected directly to the service pipe.
18.2.16 Pumps shall not be allowed on the service pipe as they cause a d rop of pressure on t he suction
side thereby a ffecting the s upply to the a djoining properties. In c ases w here pum ping is r equired, a
properly protected storage tank of adequate capacity shall be provided to feed the pump.
199 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
18.2.17 Service pipes shall be so designed and constructed as to avoid air-locks, so that all piping and
fittings abov e gr ound c an be c ompletely e mptied o f w ater t o facilitate r epairs. T here s hall be dr aining
taps or draw-off taps (not underground) at the lowest points, from which the piping shall rise
continuously to draw-off taps, ball valves, cisterns, or vents (where provided at the high points).
18.2.18 Service pi pes s hall be des igned s o as t o reduce t he production an d t ransmission of noise as
much as p ossible. A ppliances w hich create noise s hall b e i nstalled as far di stant as possible from the
living r ooms of t he house. H igh v elocity of water i n pi ping and f ittings s hall be avoided.Piping shall b e
confined, as f ar as pos sible, t o room s w here ap pliances are f ixed, i t s hall ha ve eas y ben ds, and w here
quietness i s p articularly desired, holder b ats or clamps s hall be i nsulated f rom t he piping by suitable
pads.
18.2.19 The rising pipe to the storage cistern, if an y, or t o any feed cistern shall be t aken as directly a s
possible to the cistern and shall be fixed away from windows or ventilators.
18.2.20 All pipe work shall be planned so that the piping is accessible for inspection, replacement and
repair. T o avoid it s being unsightly, it i s usually possible to arrange it in or adjacent to c upboards,
recesses, et c. pro vided t here i s s ufficient s pace t o work on t he pi ping with t he us ual t ools. Piping s hall
not b e bu ried in w alls o r solid fl oors. W here u navoidable, pipi ng may be buried f or sh ort d istances
provided t hat adequate protection i s gi ven against damage and t hat no j oints are buried. I f pi ping i s laid
in ducts or chases, these shall be roomy enough to facilitate repairs and shall be so constructed as to
prevent t he ent ry of v ermin. T o f acilitate removal of pi pe c asing, f loor boards c overing piping s hall be
fixed with screws or bolts.
18.2.21 When it is nec essary for a pi pe t o pass through a wall or floor, a sleeve shall be fixed therein for
insertion of t he pi pe and to al low f reedom for ex pansion, c ontraction and other m ovement. P iping l aid in
wood floors shall, where possible, be parallel with the joists.
18.2.22 Where s torage t anks are prov ided t o m eet ov erall requ irements of water c onnection of s ervice
pipe with an y di stributing pipe s hall not be per mitted ex cept one di rect connection for culinary or d rinking
requirements.
18.2.23 No service pipe shall be c onnected to any water closet or urinal. All such supplies shall be f rom
flushing cisterns which shall have supply from storage tank.
18.2.24 No service or s upply pipe shall be c onnected directly to any h ot-water s ystem or to a ny
apparatus used for heating other than through a feed cistern thereof.
18.3 MATERIALS
18.3.0 The standard s ize of brass or gun metal fittings s hall be designated by t he nom inal bore of t he
pipe outlet to which the fittings are attached. A sample of each kind of fittings shall be got approved from the
Engineer-in-Charge and all supplies made according to the approved samples.
All c ast ir on fittings shall be sound a nd free f rom lap s, blow holes and p itting. B oth in ternal a nd
external surfaces shall be clean, smooth and free from sand e tc. B urning, pl ugging, s topping or pa tching
of t he c asting shall not be permissible. The bodies, bonnets, spindles and other parts shall be truly
machined so t hat w hen assembled the parts shall be ax ial, par allel and cylindrical w ith surfaces
smoothly finished. The area of the water way of the fittings shall not be l ess than area of the nom inal
bore, chromium plating wherever specified shall be of 0.3 micron. The chromium shall never be
deposited o n brass u nless a h eavy c oating of nickel i s i nterposed. I n t he c ase of i ron a t hick coat o f
copper shall first be applied, then one of nickel and finally the chromium. In finish and appearance the
plated ar ticles w hen i nspected s hall be f ree f rom plating def ects s uch as b listers, pi ts r oughness and
unplated areas and shall not be s tained or discoloured. Before fitting is plated, the washer plate shall be
removed from the fittings, the gland packing shall be protected from the plating solution.
200 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
18.3.1 Ball Valve (Brass)
The ball valve shall be of Brass or Gunmetal as specified conforming to IS 1703 (Fig. 18.1). The ball
valve shall be of following two classes:—
(a) High Pressure: High pr essure f loat v alves are indicated by t he a bbreviation ‘ HP’ and are
designed for use on mains having pressure of 0.175 MPa or above.
(b) Low Pressure: Low P ressure f loat v alves a re indicated by t he abb reviation ‘ LP’ and are
designed for use on mains having a pressure up to. 0.175 MPa.
The ball valves shall be of following nominal sizes 15 mm, 20 mm, 25 mm, 32 mm, 40 mm and 50
mm. T he nom inal s ize s hall c orrespond w ith t he n ominal bore of t he i nlet s hanks. P olyethylene f loats
shall conform to IS 9762.
The bi b t ap and s top v alve s hall be pol ished br ight. T he m inimum f inished w eights of b ib t ap and
stop valve shall be as specified in Table 18.1.
TABLE 18.1
Minimum Finished Mass of Bib Taps and Stop Valves
In case t hese are required to be ni ckel plated, t he pl ating shall be of the first qu ality with a good thick
deposit of silvery whiteness capable of taking high polish which will not easily tarnish or scale.
Vol-2 , 2013
18.3.4 Fire Hydrants (Fig. 18.5)
The hydrant shall conform to IS 909 and shall consist of the following components:
The body, bonnet, gland, outlet cap and spindle cap and shall be of good quality cast iron grade FG
200 of IS 210. Outlet, seat for valve, valve, spindle nut, check nut shall be made of copper alloy as per
IS 909.
In choosing the material for piping and fittings, account shall be taken of the character of the w ater to
be c onveyed through it, the nature of the ground in w hich the pipes are to be laid and the relative
economics.
18.3.10.1 The spun iron pipes shall conform to IS 15 36. The s pun iron pi pes shall be of c ast iron cast
centrifugally an d v ary in di ameters from 80 mm to 750 mm. T hese s hall b e of class LA, c lass A an d
class B, as specified. Pipes shall be t ested hydrostatically at the pressure specified in table 18.2 & 18.3.
Tolerances on specified dimensions shall be as prescribed in Appendix A.
Vol-2 , 2013
18.3.10.2 Specials: The specials s hall c onform t o I S 1538. T he hy draulic t est pressure of ea ch c lass
shall be as det ailed in Table 18. 4. Tolerances on specified dimensions s hall be as prescribed in
Appendix B of sub head- 18.
TABLE 18.2
Hydrostatic Test pressure for centrifugally cast socket & spigot pipes in
MPa
Hydrostatic Test pressure for works in MPa
Class Up to DN 600 DN 700 & above
LA 3.5 1.5
A 3.5 2.0
B 3.5 2.5
TABLE 18.3
Hydrostatic Test pressure for centrifugally cast pipes with screwed on flanges in MPa
Class Up to DN 600 DN 700 & above
B 2.5 1.6
TABLE 18.4
18.3.11.2 Galvanising shall conform to IS 4736 : The zinc coating shall be uniform adherent,
reasonably smooth and free from such imperfections as flux, ash and dross inclusions, bare batches,
black s pots, pi mples, l umping runs, r ust s tains, bul ky white deposits and blisters. T he pipes and s ockets
shall be c leanly f inished, well gal vanised i n and out and f ree from c racks, surface f laws l aminations and
other d efects. A ll s crew t hreads shall b e clean a nd w ell c ut. T he e nds shall be cut c leanly and square
with the axis of the tube.
Vol-2 , 2013
18.3.11.3 The di mensions and w eights of pi pes and s ockets and t olerances s hall be as prescribed i n
Appendix ‘C’.
18.3.11.4 All s crewed t ubes a nd s ockets s hall ha ve pipe threads c onforming to the re quirements of IS
554. Screwed tubes shall have taper threads while the sockets shall have parallel threads.
18.3.11.5 All tubes shall withstand a test pressure of 50 Kg/sq.cm without showing defects of any kind.
18.3.11.6 Fittings : The f ittings s hall b e of m ild s teel tubular or w rought steel f ittings conforming to IS
1239 ( Part-2) o r a s s pecified. T he f ittings s hall be des ignated b y t he respective nominal b ores of t he
pipes for which they are intended.
The valve shall be marked with an arrow to show the direction of turn for closing of the valve.
The C .I. s urface box es s hall be c oated with a bl ack bi tuminous c omposition ex cept i n c ase of f ire
hydrants where t he c over of th e sur face b ox s hall be p ainted with tw o co ats o f rus t res isting bright
luminous yellow paint for clear visibility during night.
18.3.15.1 Water meters s hall be selected ac cording to flow t o be measured a nd not nec essarily t o s uit a
certain size of main. The following points shall govern the selection of meters:
(a) The maximum flow shall not exceed the nominal capacity of the meter.
(b) The continuous flow shall be not greater than the continuous running capacity rating.
(c) The minimum flow to be measured shall be within minimum starting flows.
18.3.15.2 Inferential w ater m eter h as t he same a ccuracy a s t he s emi-positive t ype at higher flows; i t
passes unfiltered water better than a semi-positive meter and is lower in cost.
18.3.15.3 Special c are i s necessary i n s electing t he m ost s uitable m eter where l arge rat es of f low m ay
exist f or short periods. The normal w orking f low s hall b e well w ithin t he c ontinuous running capacity
specified in IS 779, as high rates of flow over short period may cause excessive wear if the meter
chosen is too small for the duty.
Vol-2 , 2013
18.3.15.4 Owing to the f ine clearances in t he working parts of meters, t hey a re not suitable for
measuring w ater containing sand or similar foreign m atter, and in s uch c ases a filter or dirt box of
adequate e ffective a rea s hall be fitted on the ups tream side o f t he meter. S ee Fig. 18. 4. It shall be not ed
that the normal strainer fitted inside a m eter is not a f ilter and does not prevent the entry of small
particles, such as sand.
18.3.15.5 Water meters and their parts, especially parts coming in continuous contact with water shall be
made of m aterials r esistant to corrosion and shall be non -toxic and non -training. U se o f di ssimilar metals
in contact under water shall be avoided as for possible in order to minimise electrolytic corrosion.
18.3.15.6 Body : The b ody of w ater meter s hall be m ade either f rom Type A or T ype B m aterials a s
specified below:—
Type A : The body of water m eters shall be m ade from bronze, brass or any other corrosion resistant
material e.g. Grey iron castings, blackheart malleable iron, pherodial graphite iron casting.
Type B: The bod y of t he water m eters s hall be m ade f orm s uitable pl astics.
Note: Plastics shall have following qualities:
(ii) Elongation, 15 per cent, Min. on a specimen of length 150 mm (for procedure of
determination of elongation).
(iii) W ater abs orption on i mmersion f or 24 hour s s hould not ex ceed 0. 6 per c ent by w eight
(for procedure of determination of water absorption).
18.3.15.7 Registration Box: Registration box of w ater m eters of T ype A s hall be m ade f rom b ronze,
brass, al uminium al loy or s uitable plastics. R egistration box of w ater m eters of T ype B s hall be m ade
from suitable pl astics o r al uminium al loys. The registration box o f d ry di al water meters shall be pr ovided
with one or two escape holes for minimising the accumulation of condensed water.
18.3.15.8 Cap: Cap of w ater m eters of T ype A s hall be m ade f rom brass, bronze, al uminium al loy or
suitable pl astics. The c ap o f w ater meters o f Type B shall be made o f pl astics or al uminium alloy. Where
the cap and registration box are integral, the materials for cap may be the same as used for registration
box. The cap shall be so designed and fixed to the registration box as to avoid entry of water and dirt.
The t ransparent window which covers the d ial shall be inserted from the inside into the cap. The
protective lid shall be secured by a robust hinge or other suitable method of robust construction.
18.3.15.9 Locking Arrangement: Provision s hall also be m ade t o l ock t he l id. T he pr ovision s hall b e
such t hat t he l ock i s conveniently operated f rom t he t op. Where t he provision i s designed f or use i n
conjunction with padlocks, the hole provided for padlocks shall be of a diameter not less than 4 mm.
18.3.15.10 Wiper: Where so required f or dry-type w ater meters t he transparent window c overing the dial
shall be provided with a wiper on the inner side for wiping off condensed water.
18.3.15.11 Connecting Arrangements: The m eter c asing s hall be f itted i n the pi pe l ine by m eans o f
two c onical or cylindrical ni pples or tail pi eces w ith connecting n uts which s hall be provided w ith ea ch
meter. The nipples of water meters of Type A shall be made of the same materials as specified for body.
Vol-2 , 2013
Nipples of water meters of Type B shall be made of the same materials as specified for the body where
they ar e integral w ith the body o f the water m eters; w here they a re s eparate, they s hall be made o f
malleable i ron, gal vanized s teel or s uitable pl astics. T he nut s s hall be of t he same m aterial as us ed f or
nipples. The internal diameter of the nipple where it connects the pipe line shall be equal to that
corresponding t o t he nominal s ize of t he m eter. T he t hreads on t he c onnection s hall c onform t o I S 779.
The minimum length of the threads shall be as given in Table 18.5.
18.3.15.12 Strainers: Water m eters s hall be p rovided w ith s trainers. S trainers s hall be of a material
which i s not s usceptible t o el ectrolytic c orrosion. T hey s hall be of pl astics or ot her c orrosion-resistant
materials for both Type A and Type B meters. They shall be rigid, easy to remove and clean, and shall
be fitted on the inlet side of the water meter. It shall be possible to remove and clean the strainer in such
a way as not to permit disturbing the registration box or tampering with it. The strainer shall have a total
area of h oles n ot l ess t han t wice the area of t he n ominal i nlet bore of t he pipe t o w hich t he meter i s
connected however, in the case of meters provided with internal strainer involving opening of the
registration box f or c leaning, an addi tional ex ternal strainer s hall be f itted on t he i nlet s ide s atisfying t he
above requirements.
TABLE 18.5
Minimum Length of Thread on Connections
TABLE 18.6
Overall Dimensions of Water Meters
18.3.15.13 Capacity on Short Period Rating or Nominal Capacity: The no minal capacity of t he w ater
meters shall be as specified in Table 18.7. The meters shall be capable of giving minimum discharges as
stated in the table without the head loss exceeding 10 m within the meters.
Vol-2 , 2013
18.3.16 Yarn (Spun)
Spun yarn shall be of clean hemp and of good quality. It shall be soaked in hot coal tar or bitumen
and cooled before use.
18.4.1 Unloading
18.4.1.2 Unloading (except where mechanical handling facilities are available) : Pipes weighing up
to 60 k g shall be ha ndled by two persons by h and passing. Heavier pipes s hall be unl oaded from the
lorry or wagon by holding them in loops, formed with ropes and sliding over planks set not steeper than
45 degree. T he pl anks shall b e s ufficiently rigid and t wo r opes s hall al ways b e u sed t o roll t he pi pes
down the planks. The ropes should be tied on the side opposite the unloading. O nly one pipe s hall be
unloaded at a time.
TABLE 18.7
Nominal Capacity of Water Meters
18.4.1.3 Under no c ircumstances s hall t he pipes be t hrown down f rom t he c arriers or be d ragged or
rolled along hard surfaces.
18.4.1.4 The pipes shall be checked for any visible damage (such as broken edges, cracking or spalling of
pipe) while u nloading and shall be sorted out for reclamation. A ny pipe which s hows sufficient
damage to preclude it from being used shall be discarded.
18.4.2 Storing
18.4.2.1 The pi pes and s pecials shall be handled w ith sufficient care to avoid dam age to them. T hese
shall be lined up on one side of the alignment of the trench, socket facing upgrade when line runs uphill
and upstream when line runs on level ground.
18.4.2.2 Each s tack s hall contain p ipes o f same c lass and s ize, c onsignment or b atch num ber and
particulars of suppliers, wherever possible, shall be marked on the stack.
18.4.2.3 Storage shall be done on firm, level and c lean ground. Wedges shall be pr ovided at the bottom
layer to keep the stack stable.
18.4.3 Cutting
18.4.3.1 Cutting of pi pes may be nec essary when pipes are to be laid in lengths s horter t han t he lengths
supplied, such as while replacing accessories like tees, bends, etc. at fixed position in the pipe lines.
Vol-2 , 2013
18.4.3.2 A line shall be m arked around the pipe with a c halk piece at the point where it is to be c ut. The
line shall be s o m arked that the cut is truly at right angle to the longitudinal axis of the pipe. The pipe
shall be rigidly held on two parallel rafters nailed to cross beams, taking care that the portion to be cut
does not overhang and t he cut mark is between the two rafters. The pipe shall be neat ly cut at the chalk
mark w ith carpenter’s s aw o r ha cksaw h aving a long blade, by s lowly rotating the p ipe a round i ts
longitudinal ax is s o as to ha ve the un cut po rtion on top for c utting. C utting of the pi pe at the ov erhang
should, as far as possible, be avoided, as an overhanging and is liable to tear off due to its weight before
the cutting is complete.
18.4.4 Trenches
18.4.4.1 The trenches shall be so dug that the pipes may be laid to the required alignment and at
required depth.
18.4.4.2 Cover shall be measured from top of pipe to the surface of the ground.
18.4.4.3 The bed of the trench, if in soft or made up earth, shall be well watered and rammed before
laying t he pi pes and t he d epressions, i f any, shall be p roperly filled with ear th and consolidated i n 20 cm
layers.
18.4.4.4 If the trench bottom is extremely hard or rocky or loose stony soil, the trench shall be excavated at
least 150 m m bel ow t he trench grade. Rocks, s tone or ot her hard s ubstances f rom t he bot tom of t he
trench shall b e re moved an d t he t rench b rought back t o t he re quired gr ade by f illing with selected f ine
earth or sand (or fine moorum if fine soil or sand is not available locally) and compacted so as to provide a
smooth bedding for the pipe. Where excavation requires blasting operation, it shall be ensured that no pipes
have been stacked in the vicinity and completed pipe line in the vicinity has already been covered before
starting of blasting operations; this is necessary to prevent damage to the exposed pipes in the vicinity by
falling stones as a result of blasting.
18.4.4.5 After the excavation of the trench is completed, hollows shall be cut at the required position to
receive the socket of the pipes and t hese hollows s hall be of sufficient depth to ensure that the barrels of
the pi pes shall re st t hroughout t heir e ntire l ength on t he s olid gr ound a nd t hat s ufficient spaces l eft f or
jointing t he u nderside of t he pipe j oint. T hese s ocket h oles s hall b e ref illed with s and a fter j ointing t he
pipe.
18.4.4.6 Roots of trees within a distance of about 0.5 metre from the side of the pipe line shall be
removed or killed.
18.4.4.7 The e xcavated m aterials s hall n ot b e pl aced w ithin 1 m etre or ha lf of t he d epth of the trench,
whichever is greater, from the edge of the trench. The materials excavated shall be separated and
stacked s o that i n r efilling they may be re-laid and c ompacted in t he same or der t o t he satisfaction of the
Engineer-in-Charge.
18.4.4.8 The t rench shall be k ept f ree f rom w ater. S horing and t imbering s hall be pr ovided w herever
required. Excavation below water table shall be done after dewatering the trenches.
18.4.4.9 Where the pipe line or drain crosses an existing road, the road crossing shall be excavated half at
a t ime, t he 2nd ha lf being c ommenced a fter t he pi pes h ave be en l aid i n t he f irst hal f an d the t rench
refilled. N ecessary sa fety m easures f or tr affic a s dire cted s hall b e ad opted. All t ypes, water mains
cables, et c. met within t he course o f e xcavation s hall be carefully pr otected an d s upported. C are s hall be
taken n ot to di sturb the e lectrical and c ommunication c able m et w ith duri ng course of ex cavation,
removal of which, if necessary, shall be arranged by the Engineer-in-Charge.
Vol-2 , 2013
18.4.5 Laying
18.4.5.1 The pipes shall be l owered into the trench by means of suitable pulley blocks, sheer legs chains
ropes etc. In no case the pipes shall be rolled and dropped into the trench. One end of each rope may
be tied to a w ooden or s teel p eg driven into the g round a nd the other end he ld by m en w hich w hen
slowly r eleased w ill lower the pi pe i nto t he trench. A fter lowering, t he pi pes s hall be ar ranged so t hat the
spigot of one pipe is carefully centered into the socket of the next pipe, and pushed to the full distance
that it can go. The pipe line shall be laid to the levels required. Specials shall also be l aid in their proper
position as stated above.
18.4.5.2 Where so di rected, the pi pes and s pecials may be l aid on masonry or concrete pillars. The pi pe
laid on the level ground, shall be laid with socket facing the direction of flow of water.
18.4.5.3 The pipes shall rest continuously on the bottom of the trench. The pipes shall not rest on lumps of
earth or on t he j oints. F our m etre l ong w ooden t emplates m ay be us ed t o c heck t he l evel of t he be d.
Clearance of approximately 100 mm in depth and width equal to length of the collar plus 30mm on both
sides shall be provided at the joint which shall be refilled from sides after the joint is made.
18.4.5.4 In unstable s oils, such as soft soils and dry lumpy soils it shall be checked whether the soils can
support the pipe lines and if required suitable special foundation shall be provided.
18.4.5.5 Some clayey soils (for example black cotton soil) are drastically affected by extremes of
saturation a nd dryness. I n ch anging fr om saturated t o a d ry c ondition, th ese soils a re s ubjected t o
extraordinary s hrinkage w hich i s us ually s een i n t he f orm of w ide and deep c racks i n t he eart h s urface
and m ay res ult i n dam ages t o under ground s tructures, i ncluding pi pe m aterials. T he c lay f orms a t ight
gripping bond with the p ipe, s ubjecting i t t o e xcessive s tresses as the clay shrinks. It i s r ecommended
that in such cases an envelope of a minimum 100 mm of tamped sand shall be made around the pipe
line to avoid any bonding.
18.4.5.6 In places where rock is encountered, cushion of fine earth or sand shall be provided for a depth of
150 mm by excavating extra depth of the trench, if necessary, and the pipes laid over the cushion.
Where t he gr adient of the bed s lopes i s more than 30 degr ee i t may be nec essary t o anchor a few pipes
against sliding downwards (Fig. 18.8).
18.4.6.1 Thrust blocks shall be installed wherever there is a change in the direction/size of the pipe line or
the pressure line diagram, or w hen the pipe line ends at a dead end. If necessary, thrust blocks may be
constructed at valves also.
18.4.6.2 Thrust bl ocks s hall be c onstructed t aking i nto ac count t he pi pe s ize, w ater pr essure, t ype of
fitting, gravity co mponent when l aid on s lopes and th e typ e o f soi l. T he l ocation of th rust bl ocks f or
various types’ fittings is given in Fig. 18.8.
18.4.6.3 When a fitting is used to make a vertical bend, it shall be anchored to a concrete thrust block
designed t o have enough weight to resist the upw ard and outward t hrust. S imilarly at j oints, deflected in
vertical plane, it shall be ensured that the weight of the pipe, the water in the pipe and the weight of the soil
over the pipe provide resistance to upward movement. If it is not enough, ballast or concrete shall be placed
around the pipe in sufficient weight to counteract the thrust.
18.4.6.4 When the l ine is under pressure there is an out ward thrust at each coupling. Good soil, properly
tamped is usually sufficient to hold pipe from side movement. However, if soft s oil conditions are
encountered, i t m ay be n ecessary t o pr ovide s ide thrust bl ocks of ot her m eans of anc horing. I n s uch
cases only pipe on each side of the deflected coupling shall be anchored without restricting the coupling.
209 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
18.4.6.5 Pipes on slopes need be anchored only when there is a possibility of the back fill around the
pipe sloping down the hill and carrying the pipe with it. Generally for slopes up to 30 degree good well
drained soil carefully tamped in layers of 100 mm under and over the pipe, right up to the top of trench will
not require anchoring.
18.4.6.6 For steeper slopes, o ne out of e very three pipes shall b e h eld by straps fastened to vertical
supports anchored in concrete.
18.4.7.2 The s oil un der the pi pe an d coupling s hall be s olidly tamped to pr ovide firm an d continuous
support for the pipe line. Tamping shall be done either by tamping bars or by using water to consolidate the
back fill materials.
18.4.7.3 The initial back fill material used shall be free of large stones and dry lumps. In stony areas the
material fo r init ial b ack fi ll can be s haved fro m th e sid es o f th e tre nches. In bo gs and marshes, th e
excavated material i s u sually little m ore t han v egetable m atter a nd t his s hould not be us ed f or bedd ing
purposes. In such cases, gravel or crushed stone shall be hauled in.
18.4.7.4 The initial back fill shall be placed evenly in a layer of about 100 mm thick. This shall be
properly consolidated and this shall be continued till there is a cushion of at least 300 mm of cover over
the pipe.
18.4.7.5 If it i s desired to observe the joint or coupling during the testing of mains they shall be left
exposed. S ufficient bac k fill s hall be pl aced on t he pi pe t o resist t he movement due t o pressure w hile
testing.
18.4.7.6 Balance of the back fill need not be so carefully selected as the initial material. However, care
shall be t aken to avoid back filling with large stones which might damage the pipe when spaded into the
trench.
18.4.7.7 Pipes in trenches on a slope shall have extra attention t o make c ertain t hat the new ly placed
back f ill w ill not be come a bl ind drai n in ef fect b ecause unt il bac k f ill be comes c ompletely consolidated
there is a t endency f or ground or s urface w ater to move along t his lo oser soi l r esulting in a lo ss of
support to the pipe. In such cases, the ba ck fill shall be t amped with extra care and t he tamping
continued in 100 mm layers right up to the ground level.
(a) Pressure t est at a pressure of at l east double t he m aximum working p ressure-pipe a nd j oints
shall be absolutely water tight under the test.
(b) Leakage test (to be conducted after the satisfactory completion of the pressure test) at a
pressure to be specified by the authority for duration of two hours.
18.4.8.2 Hydrostatic Tests: The portions of the line shall be tested by subjecting to pressure test as t he
laying progresses before the entire line is completed. In this way any error of workmanship will be f ound
immediately and can be corrected at a minimum cost. Usually the length of the section to be tested shall not
exceed 500 m.
Vol-2 , 2013
18.4.8.3 Where any section of a main is provided with concrete thrust blocks or anchorages, the
pressure test shall not be made until at least five days have elapsed after the concrete is cast. If rapid
hardening c ement has been used i n t hese blocks or anchorages, test shall n ot be made until at least t wo
days have elapsed.
18.4.8.4 Prior to testing, enough b ack fill as d escribed in 1 8.4.7 shall be pl aced o ver the pipe line t o
resist up ward t hrust. All t hrust bl ocks f orming part of t he f inished l ine s hall h ave been sufficiently c ured
and no temporary bracing shall be used.
18.4.8.5 The open end of the section shall be s ealed temporarily w ith an end c ap hav ing an out let w hich
can serve as an air relief vent or for filling the line, as may be required. The blind face of the end cap shall
be properly braced during testing by screw jacks and wooden planks or steel plate as shown in Fig. 18.6.
18.4.8.6 The section of the line to be tested shall be filled with water m anually or by a low pressure
pump. A ir s hall be v ented from al l h igh s pots in the pipe line b efore m aking the pressure s trength test
because ent rapped ai r g ets c ompressed and c auses di fficulty i n r aising t he r equired pressure f or t he
pressure strength test.
18.4.8.7 The test pressure shall be gr adually raised at the rate of approximately one K g./sq. cm./min.
The dur ation o f the test per iod i f not specified s hall be s ufficient to make a careful check on t he pi pe line
section.
18.5 LAYING AND JOINTING OF CAST IRON PIPES AND FITTINGS (EXTERNAL WORK)
18.5.0 Specifications described in 18.4 shall apply, as far as applicable.
TABLE 18.8
Test Pressure for Pipes
18.5.1 Trenches
18.5.1.1 The gradient is to be set out by means of boning rods and the required depth to be excavated at
any poi nt of t he t rench s hall be r egarded a s di rected b y t he E ngineer-in-Charge. T he d epth of t he
trench s hall not be less t han 1 metre measured from the top of the pipe to the surface of the ground
under roads and not less than 0.75 metre elsewhere.
18.5.1.2 The width of the trench shall be t he nominal diameter of the pipe plus 40 c m but it shall not be
less than 55 cm in case of all kinds of soils excluding rock and not less than 1 metre in case of rock.
18.5.2 Laying
Any deviation either i n plan or e levation l ess t han 11 .25 d egrees shall be effected by l aying t he
straight pi pes ar ound a flat curve o f s uch radius t hat minimum thickness o f lead at t he face o f the socket
shall not be reduced bel ow 6 mm or the openi ng b etween spigot and socket increased beyond 12 mm at
any joint. A d eviation o f a bout 2.25 degree can be effected at ea ch joint in this way. At the en d of e ach
day’s w ork t he l ast pi pe l aid s hall h ave i ts o pen e nds s ecurely c losed w ith a w ooden plug t o p revent
entry of water, soil, rats and any other foreign matter into the pipe.
Vol-2 , 2013
18.5.3.2 The approximate depth and w eights of pig lead for various diameters of C.I. pipes and s pecials
shall be as given in Table 18.9.
TABLE 18.9
Lead for Different Sizes of Pipes
Note: 1. The quantity of lead given in the table is on average basis and a variation of 10 per cent is
permissible.
2. B efore pipes a re j ointed on l arge s cale, t hree or f our sample j oints s hall be m ade and t he
average consumption of lead per joint shall be got approved by the Engineer-in-Charge.
Only required quantity of spun yarn shall be put so as to give the specified depth of lead in the joint.
18.5.4.2 The approximate w eights and dept hs of lead wool o r l ead yarn required for ea ch joint o f v arious
dia. of C.I. pipes and specials shall be as given in Table 18.10. Just sufficient quantity of spun yarn shall be
put so as to give specified depth of lead wool.
18.5.4.3 Jointing: The s pun y arn s hall f irst be i nserted and c aulked i nto t he socket as d escribed under
jointing with pig lead. Lead wool or yarn shall then be introduced in the joint in strings not less than 6 mm
thick and t he caulking shall be repeat ed with each turn of lead wool or y arn. The whole of the lead wool
or yarn shall be compressed into a dense mass. The joint shall then be finally finished flush with face of
the socket.
Vol-2 , 2013
TABLE 18.10
Diameter of Weight of lead wool Depth of lead wool
pipe (mm) or lead yarn (kg) or lead yarn (mm)
80 0.80 19
100 0.90 19
125 1.25 20
150 1.60 23
200 2.05 23
250 2.95 25
300 3.50 25
350 4.65 29
400 5.70 31
450 6.70 32
500 8.30 33
600 10.00 35
700 11.80 36
750 13.60 38
800 15.40 40
900 16.80 40
Note: An allowance of five per cent variation in the specified weights and depths is permissible.
18.5.5.2 Each bol t s hould be t ightened a l ittle at a t ime t aking c are to tighten di ametrically opp osite bol ts
alternatively. The practice of fully tightening the bolts one after another shall not be allowed.
18.5.5.3 Several pr oprietary f lexible joints ar e av ailable for j ointing c ast i ron pi pes and t hese may b e
used with the specific approval of the authority, however, they shall be used strictly in accordance with the
manufacturer’s instructions.
18.5.5.4 For joints i n small d iameter cast i ron p iping, c opper-alloy s crewed un ions or f errules shall be
used, and for large dia. The joints shall be made by flanged connecting pieces.
18.5.6 Hydrostatic
The procedure for testing for leakage under pressure shall be as described in Appendix D of Chapter
18 which is to be read in addition to 18.4.8. The joints of pipes and specials have to be repaired till the
leakage in the portion under test is within the specified limit indicated in Appendix-D.
18.5.7 Measurements
18.5.7.1 The net length of pipes as laid or fixed, shall be measured in the running metres correct to a
cm. s pecials shall be excluded and enumerated and paid for separately. T he portion of the pipe within
the collar at the joints shall not be included in the length of pipe work.
18.5.7.2 Excavation, re filling, shoring and t imbering i n t renches masonry or concrete pillars and t hrust
blocks, wherever required, shall be measured and paid for separately, under relevant items of work.
18.5.7.3 Lead caulked joints shall be measured and paid for separately.
18.5.8 Rate
The rate shall i nclude t he c ost of materials and l abour i nvolved i n al l the oper ations des cribed abo ve
except for the items measured/enumerated separately under Para 18.4.7.1, 18.4.7.2, 18.4.7.3 which
shall be paid for separately.
Vol-2 , 2013
18.6 LAYING AND JOINTING OF G.I. PIPES (EXTERNAL WORK)
18.6.0 The specifications described in 18.4 shall apply, as far as applicable.
18.6.1 Trenches
The galvanised iron pipes and f ittings shall be l aid in trenches. The w idths and dept hs of the
trenches for different diameters of the pipes shall be as in Table 18.11.
TABLE 18.11
At j oints t he t rench w idth s hall be w idened w here necessary. T he work of excavation and r efilling
shall be done t rue to line and g radient i n a ccordance w ith gene ral specifications for ea rth w ork in
trenches.
When ex cavation is done in rock, it s hall be c ut dee p e nough to permit the pipes to be laid on a
cushion of sand minimum 7.5 cm deep.
18.6.3 Jointing
The pipes shall be cleaned and cleared of all foreign matter before being laid. In jointing the pipes,
the inside of the socket and the screwed end of the pipes shall be oiled and rubbed over. Teflon Tape
should be used on threads i nstead of ‘Dhaaga/ Safeda’. T he end shall t hen be s crewed i n t he s ocket,
Tee etc. with the pipe wrench. Care shall be t aken that all pipes and f ittings are properly jointed so as to
make the joints completely water tight and pipes are kept at all times free from dust and dirt during fixing.
Burr f rom t he j oint s hall be r emoved af ter s crewing. A fter l aying, t he op en end s of t he pipes s hall be
temporarily plugged to prevent access of water, soil or any other foreign matter.
18.6.5 Painting
The pipes shall be painted with two coats of anticorrosive bitumastic paint of approved quality.
Vol-2 , 2013
have bee n recalibrated be fore the t est. The t est pum p hav ing been s topped, t he t est pr essure should be
maintained without loss for at least half an ho ur. The pipes and fittings shall be t ested in sections as the
work of l aying pr oceeds, hav ing t he j oints e xposed f or i nspection d uring t he t esting. P ipes o r f ittings
which are found leaking shall be replaced and joints found leaking shall b e redone, without extra
payment.
18.6.8 Measurements
The l engths s hall be m easured i n running m etre c orrect t o a c m f or t he f inished w ork, w hich s hall
include G .I. pi pe and G .I. f ittings such as bends , tees, el bows reducers, crosses, pl ugs, sockets, ni pples
and nu ts, bu t ex clude b rass or gu n m etal ta ps (c ocks), v alves, un ions, lead connection p ipes and
shower rose. A ll pi pes an d fittings shall be c lassified according t o t heir diameters, m ethod of j ointing and
fixing s ubstance q uality and f inish. I n c ase of f ittings of a n e qual bo re t he pipe s hall be described as
including all cuttings and wastage. In case of fittings of unequal bore the largest bore shall be measured.
Note: G.I. unions shall be paid for separately in external work as well as in internal work.
Digging an d ref illing of t renches shall ei ther be m easured s eparately a s s pecified in t he appro priate
clauses of excavation and earth work or clubbed with main item.
18.6.9 Rate
The rate s hall i nclude t he c ost o f l abour and materials involved i n al l the oper ations des cribed abo ve.
The rate shall not include excavation in trenches, painting of pipes and sand filling all round the pipes,
unless otherwise specified.
18.7.0 For internal work the g alvanised iron pipes an d fittings s hall run o n the s urface of the w alls o r
ceiling (not i n c hase) unl ess ot herwise s pecified. T he f ixing s hall be done by means of s tandard pat tern
holder bat c lamps, ke eping th e pi pes ab out 1.5 cm cle ar o f the wall. W hen it is fo und ne cessary t o
conceal t he pi pes, c hasing m ay be adopt ed or pi pes fixed i n t he d ucts or re cess et c., prov ided t here i s
sufficient s pace to work on the pipes with the usual tools. The pi pes shall not ordinarily be bu ried i n walls
or solid floors. Where unavoidable, pipes may be buried for short distances provided adequate
protection i s gi ven agai nst dam age and where s o r equired j oints are not buri ed. W here d irected b y t he
Engineer-in-Charge, a M .S. tube sleeve shall be fixed at a place the pipe is passing through a w all or
floor for reception o f t he pi pe and t o al low freedom for ex pansion and c ontraction and ot her movements.
In c ase t he pi pe i s em bedded i n w alls or f loors i t should be pa inted w ith an ticorrosive bi tumastic pai nts
of approved quality. The pipe shall not come in contact with lime mortar or lime concrete as the pipe is
affected by time. Under the floors the pipes shall be laid in layer of sand filling as done under concrete
floors.
All pipes and fittings shall be fixed truly vertical and horizontal unless unavoidable. The pipes shall be
fixed to walls with standard pattern holder bat clamps of required shape and size so as to fit tightly on the
pipes when tightened with screwed bolts, these clamps shall be embedded in brick work in cement mortar
1:3 (1 cement: 3 coarse sand), and shall be spaced at regular intervals in straight lengths as shown in
Table 18.12.
The clamps shall be fixed at shorter lengths near the fittings as directed by the Engineer-in-Charge.
For G.I. pipes 15 mm diameter, the holes in the walls and floors shall be made by drilling with chisel
or j umper and not by dismantling t he brick w ork o r c oncrete. H owever, f or bigger dimension pipes t he
215 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
holes shall be carefully made of the smallest size as directed by the Engineer-in-Charge. After fixing the
pipes the holes s hall be m ade go od with c ement m ortar 1: 3 ( 1 c ement: 3 c oarse sand) an d p roperly
finished to match the adjacent surface.
TABLE 18.12
Dia. of Pipe Horizontal length Vertical length
(mm) m m
15 2 2.5
20 2.5 3
25 2.5 3
32 2.5 3
40 3 3.5
50 3 3.5
65 3.5 5
80 3.5 5
Unions w ill be provided to f acilitate connections additions and al terations as well as f or m aintenance
and f or change of pi pes. The l ocations w here uni ons a re t o be pr ovided will b e dec ided w ith pr ior w ritten
approval of the Engineer-in-Charge.
18.7.1 Measurements
The l engths s hall be m easured i n running m etre c orrect t o a c m f or t he f inished w ork, w hich s hall
include G.I. pi pe and G .I. f ittings such as bends , tees e lbows, reducers, crosses, pl ugs, sockets, nipples
and nu ts, but exclude b rass or gun m etal tap s (c ocks), v alves, un ions, lead connection p ipes and
shower rose. A ll pi pes and fittings shall be c lassified according to t heir diameters, m ethod of j ointing and
fixing s ubstance, qual ity and f inish. I n c ase of f ittings of an equal bor e t he pi pe s hall be des cribed as
including all cuttings and waste. In case of fittings of unequal bore, the largest bore shall be measured.
Pipes l aid i n t renches (or without s upports) and pi pes f ixed t o w alls, c eilings, et c. w ith s upports s hall be
measured separately.
18.7.2 Rate
The rate s hall i nclude t he c ost of l abour and m aterial i nvolved i n all t he operations described above.
The rate shall include the cost of cutting holes in walls and floors and making good the same. This shall not
however, i nclude c oncealed pi pe work i n w hich c ase cutting o f c hase and m aking good s hall be pai d
separately. I t shall not i nclude pai nting o f pipes and prov iding s leeves, unl ess s pecified otherwise. I t w ill
also not include union which shall be paid for separately.
Vol-2 , 2013
quantity o f c olour m aster bat ches. T he c olour m aster bat ch s hould be uni form t hroughout t he
pipe s urface. T he s tandard di mension r atio ( SDR) i .e. r atio of the nom inal outer di ameter of a
pipe to its nominal wall thickness should be 7.4/11 as given in the item.
18.8.2 Fittings
Plain fittings, Chrome plated brass threaded fittings and Valves shall be as per nomenclature of item or
as directed by engineer- in- charge.
(a) The plain fittings shall be Polypropylene Random Copolymer and comply with all the
requirements of the pipes. The plain fittings shall comprise of Socket, Elbow, Tee, Cross,
Reducer socket, Reduction Tee, End Cap, Crossover, Omega, Threaded Plug and wall clamps in
available sizes.
(b) The Chrome Plated Brass threaded fittings shall be Chrome Plated Brass threaded piece molded
inside Polypropylene random copolymer fitting. The maternal shall comply with all the
requirements of the pipes. The Chrome plated Brass threaded fittings shall comprise of Socket,
Elbow and Tee (Male & Female) in available sizes. These are the fittings for C.P. connections
and for continuations from existing Galvanized Irion Pipes and fittings.
(c) The valves shall be Polypropylene Random Copolymer Valves. The valves comprise of Gate
Valve, Ball Valve, Concealed stop valve and Chrome Coated Valve in available sizes.
However, the other Brass/Bronze Valves can be connected to Polypropylene Random pipes using
C.P. Brass threaded fittings of desired sizes.
18.8.4 The out s ide diameter of pi pes, t olerance i n t he s ame a nd o vality o f pi pe s hall b e a s gi ven i n
Table 18.13 below.
TABLE 18.13
Outside Diameter, Tolerance and Ovality of Pipes
Vol-2 , 2013
(1) (2) (3) (4) (5)
(ii) 20 20.0 0.3 1.2
(iii) 25 25.0 0.3 1.2
(iv) 32 32.0 0.3 1.3
(v) 40 40.0 0.4 1.4
(vi) 50 50.0 0.5 1.4
(vii) 63 63.0 0.6 1.6
(viii) 75 75.0 0.7 1.6
(ix) 90 90.0 0.9 1.8
(x) 110 110.0 0.9 2.2
1. T he values specified for tolerance o n o utside diameter have been calculated as 0.009DN,
rounded off to the nex t higher 0.1 mm s ubject to minimum of 0.3 mm. No negative tolerances are
allowed.
2. The basis for the values specified for ovality is:
(a) F or nom inal out side d iameters≤ 75 mm, the tolerance equals (0.008 DN+1.0) mm, rounded
to the next higher 0.1 mm, with a minimum value of 1.2 mm.
(b) F or nom inal outside d iameters≥ 75 mm and ≤ 250 mm, the tolerance equals 0.20 DN,
rounded to the next higher 0.1 mm.
(c) F or nom inal out side di ameter > 250 m m, t he t olerance equa ls 0. 35 DN, r ounded t o t he ne xt
higher 0.1 mm.
18.8.5 Wall Thickness
The minimum and maximum wall thickness of pipes shall be as given in Table 18.14 below:-
TABLE 18.14
Vol-2 , 2013
and t he f itting i s removed f rom t he w elding m achine and the t wo pi eces c onnected together by applying
a little pressure w ithout tw isting. T he joint is allowed to c ool dow n for a few s econds. T he w elding
process is that safe because the properly heated part of Polypropylene create a homogeneous
connection.
Guidelines for Welding PP-R Pipes and Fittings (DVS Guideline 2207, Part II)
The same procedure shall be adapted for exposed as well as concealed fittings. The Crossovers
may be us ed w herever the ov erlapping o f the P P-R pipes i s r equired. The fixing s hall be done b y means
of Wall Support Clamps keeping the pies about 1.5 cm clear of the wall where to be l aid on t he surface.
Where it is specified to conceal the pipes, chasing may be adopted. For pipes fixed in the shafts, ducts
etc. t here s hould be sufficient s pace t o work on t he pipes w ith t he usual t ools. P ipe s leeves s hall be
fixed at a place the pipe is passing, through a wall or floor for reception of the pipe and allow freedom for
expansion and c ontraction and other movements. F ixed s upports pr event a ny m ovement of t he pi pe by
fixing it a t s ome points. F ittings a re us ed in c reating the fixed points. F ixed supports m ust n ot but
installed at bendi ng par ts and t he di rection c hanges must be done i n t he pi pe itself. I n bet ween t he fixed
supports some arrangements must b e do ne to c ompensate any p otential el ongation o r shrinkage i n t he
pipe l ength. F or exposed s traight pi pes having l ength more t han 5 meters, to c ompensate the ex pansion
an expansion piece must be used.
18.8.8 Testing
All water s upply s ystem shall be tested t o H ydrostatic p ressure test. Max imum operating pressure at
varying degree of temperature is given in Table 18.15:
Vol-2 , 2013
TABLE 18.15
Sl. No. Temperature SDR 11 SDR 7.4
Pressure MPa Pressure MPa
(i) 10 1.91 3.02
(ii) 20 1.63 2.58
(iii) 30 1.37 2.17
(iv) 40 1.15 1.84
(v) 50 0.98 1.55
(vi) 60 0.82 1.28
(vii) 70 0.62 0.98
(viii) 80 0.39 0.62
(ix) 95 0.27 0.4
The p ressure t est i s p erformed i n 3 steps being preliminary t est, m ain t est an d f inal t est. F or t he
preliminary t est a pre ssure w hich i s 1. 5 times hi gher t han t he pos sible w orking pres sure i s appl ied a nd
this is repeated two times in 30 minutes with intervals of 10 minutes. After a test period of 30 minutes,
the test pressure must no t be dropp ed more than 0 .6 bar and no leak must occur. Main test follows the
preliminary t est. Test t ime i s t wo hours, i n d oing so t he t est pressure t aken f rom t he preliminary t est
must not have fallen more than 0.2 bar. After completion of these tests, the final test comes which has to be
done under a test pressure of 10 bars and 5 bar in the interval of 15 minutes. Between the respective test
courses, pressure has to be removed.
All l eaks a nd def ects i n joints re vealed duri ng the testing s hall be rec tified and got approved at s ite
by retest. Piping required subsequent to the above pressure test shall be retested in the same manner.
After commissioning o f t he water s upply system, c ontractor s hall t est each valve by closing and
opening i t a number of times to observe if it is working efficiently. V alves which ar e not w orking efficiently
shall be replaced by new ones.
18.8.9 Measurements
The n et length o f pipes as laid or f ixed shall b e measured in ru nning m eters correct to a cm for the
finished w ork, w hich s hall i nclude P P-R pi pe and fittings i ncluding pl ain fittings and C hrome P lated B rass
Threaded fittings. Deductions for the length of valves shall be made. The cost includes cutting chases in the
masonry wall and making good the same, trenching, refilling and testing of joints. The cost of gate
valves/ wheel valves/union shall be paid for separately.
18.9.1 CPVC pipes & fi ttings u sed i n h ot & cold pot able w ater dis tribution system sh all co nform to
requirement of IS 15778. T he material f rom w hich th e pipe is pr oduced shall co nsist of chlorinated
polyvinyl c hlorides. T he polymer f rom w hich t he pi pe c ompounds a re t o b e m anufactured s hall h ave
chlorine content n ot l ess than 6 6.5%. Test C ertificates covering v arious t est mentioned i n following t ables
should be submitted.
The i nternal and ex ternal s urfaces of t he pi pe s hall be s mooth, c lean and f ree f rom g rooving and
other defects. T he pi pes s hall not ha ve any detrimental e ffect on the c omposition of the w ater flowing
though it.
Diameter and wall thickness of CPVC pipes are as per given in Table 18.16 below.
220 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
TABLE 18.16
(b) For pipes of minimum wall thickness greater than 6mm, the permissible variation of wall
thickness shall again be positive in the form of +y, where y would be applied in two parts.
(c) The average wall thickness shall be determined by taking at least six measurements of wall
thickness round the pipe and including both the absolute minimum and absolute maximum
measured values. The tolerance applied to this average wall thickness from these measurements
shall be within the range 0.1 eMin+0.2 mm (see Table 18.16).
Vol-2 , 2013
(d) The maximum wall thickness at any point shall be within the range 0.15eMin (see Table 18.16).
(e) The results of these calculations for checking tolerance shall be rounded off to the next higher
0.1 mm.
18.9.2.4 Effective Length (Le) : If the length of a pipe is specified, the effective length shall not be less
than t hat s pecified. T he preferred eff ective length of pi pes s hall b e 3, 5 or 6 m . T he pipes m ay b e
supplied in other lengths where so agreed upon between the manufacturer and the purchaser.
18.9.4.1 Visual Appearance : The c olour of t he pi pes shall be off-white. S light variations i n t he
appearance of the colour are permitted.
The i nternal an d ex ternal surface of t he pi pe s hall b e s mooth, c lean an d f ree f rom gr ooving a nd ot her
defects.
18.9.4.2 Opacity : The wall of the plain pipe shall not transmit more than 0.1 per c ent of the visible light
falling on it when tested in accordance with IS 12235 (Part 3).
18.9.4.3 Effect on Water : The pipes shall not have any determinate effect on the composition of the
water flowing through them, when tested as per 10.3 of IS 4985.
18.9.4.4 Reversion Test : When tested by the method prescribed in IS 12235 (Part 5/ Sec 1 and Sec 2), a
length of pipe 200 ±20 mm long shall not alter in length by more than 5 per cent.
18.9.4.5 Vicat Softening Temperature : When t ested by t he method pr escribed i n I S 12235 ( part 2) ,
the Vicat softening temperature of the specimen shall not be less than 110°C.
18.9.4.6 Density : When tested in accordance with IS 12235 (Part 14), the density of the pipes shall be
between 1450kg/m3 and 1650kg/m3.
18.9.5.1 Hydrostatic Characteristics : When s ubject t o i nternal h ydrostatic p ressure test i n ac cordance
with t he procedure given i n I S 12235 (part 8/Sec 1), t he pi pe s hall n ot f ail during t he p rescribed t est
duration. T he temperatures, du ration and hy drostatic ( hoop) s tress for the test s hall conform to the
requirements given in Table 18.17. The test shall be carried out not earlier than 24 h after the pipes have
been manufactured.
Vol-2 , 2013
TABLE 18.17
Requirements of Pipes for Internal Hydrostatic Pressure Test
(Clause 18.9.5.1)
18.9.5.2 Thermal Stability by Hydrostatic Pressure Testing : When s ubject t o i nternal hy drostatic
pressure t est i n ac cordance w ith t he p rocedure gi ven i n I S 12235 ( Part 8 /Sec 1 ) and as per requirement
given in Table 18.17, Sl. No. (iv), the pipe shall not burst or leak during the prescribed test duration.
18.9.5.3 Resistance to External Blow at 0°C : When tested by the method prescribed in IS 4985, with
classified striker mass and drop h eight as given in Table 18.18, the pipe shall have a t rue impact rate of
not more than 10 per cent.
TABLE 18.18
Classified Striker Mass and Drop Height Conditions for the Falling Weight Impact Test
(Clause 18.9.5.3)
18.9.5.4 Flattening Test : When tested by the method prescribed in IS 12235 (part 19), pipe shall show
no signs of cracking, splitting and breaking.
18.9.5.5 Tensile Strength : When t ested by t he m ethod prescribed i n I S 12235 (Part 19), t he t ensile
strength at yield shall not be less than 50 MPa at 27 ± 2°C.
Vol-2 , 2013
18.9.7. Marking
18.9.7.1 Each pi pe s hall be c learly an d i ndelibly m arked i n i nk/paint or hot e mbossed on w hite bas e a t
intervals of not more than 3 m. The marking shall show the following:
(a) Manufacturer’s name or trade-mark
(b) Outside diameter,
(c) Class of pipe and pressure rating, and
(d) Batch or lot number
18.9.7.2 BIS Certification Marking : Each pipe may also be marked with the Standard Mark.
18.9.8 Fittings
The fittings shall be as follows:
(a) Plain CPVC solvent cement fittings from size 15 mm to 160 mm.
(b) Brass threaded fittings.
(c) Valve from size 15 mm to 160 mm
(d) Brass Threaded Fittings: All types of one end brass threaded male/female adaptors in various
fittings like coupler, socket, elbow, tee are available for transition to other plastic/metal piping
and for fixing of CP fittings. Ball, Gate valves in CPVC are available in all dimensions. All
fittings shall carry the following information:
(1) Manufacturer’s name/trade mark.
(2) Size of fitting
18.9.9.1 Concealed Piping: Pipes can be c oncealed in chases. The pi pes an d fitting ar e t o be pr essure
tested prior t o concealing the c hases. To maintain alignment of C P f ittings w hile j oining, all al ignment of
fittings and p ipe shall be done c orrectly. DO N OT U SE N AILS F OR H OLDING O F P IPES IN THE
CHASES.
18.9.9.2 External Installations: For pipes fixed in the shafts, ducts etc. there should be sufficient space to
work on the pipes. Pipes sleeves shall be fixed at a place the pipe is passing through a wall or floor so as to
allow freedom for expansion and contraction. Clamping of the pipe is done to support it while allowing
the freedom for movement.
All pi pes ex posed t o s unlight s hall b e pai nted w ith a w ater bas ed ac rylic pai nt em ulsion t o enhan ce
UV p rotection. P ipes i n trenching s hall be l aid i n ac cordance t o the G ood P lumbing pr actices followed for
Metal piping.
18.9.9.3 Expansion LOOP: CPVC systems, like all piping materials, expand and contract with changes
in temperatures. CPVC pipes shall expand 7.5 cm per 30 m length for a 400C temperature change.
224 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
Expansion does not v ary w ith P ipe size. T hermal e xpansion c an be generally be ac commodated at
changes in direction. On a long straight run, an offset or loop based on the following chart is required.
18.9.10 Testing
All water supply s ystems shall b e t ested t o h ydrostatic pres sure t est. T he pr essure t ests are similar
to t he te st pressure u sed f or other plastic/metal pipes. S ystem m ay b e t ested in sections a nd s uch
section s hall be entirely checked on c ompletion of connection t o t he o verhead t ank or pumping system
or mains.
18.9.11 Measurements
The n et length o f pipes as laid or f ixed shall b e measured in ru nning m eters correct to a cm for the
finished work, which shall include CPVC pipe and fittings including plain and Brass threaded fittings and
jointing solvent cement.
The pipes & f ittings af ter t hey ar e laid s hall be t ested t o h ydraulic pr essure of 6 kg./sq.cm. (60 m ).
The pi pes s hall be s lowly and c arefully c harged w ith w ater al lowing al l a ir t o es cape an d av oiding al l
shock of w ater hammer. T he draw of l aps and stop cocks shall then be closed and specified hy draulic
pressure shall be appl ied gr adually. P ressure gaug e must be ac curate and p referably s hould hav e bee n
recalibrated be fore the t est. The test pu mp hav ing been s topped, t he t est p ressure should be maintained
without loss for at least h alf an h our. The pi pes an d fittings s hall b e tested in sections a s the w ork of
laying proceeds, having the joints exposed for inspection during the testing.
Vol-2 , 2013
18.11.4 Finishing
The portion of the pipe in the pit shall be painted with bitumastic paint and encased with sand 15 cm
all-round. The pit shall be filled with earth in level with the original ground surface watered, rammed and
the area dressed.
18.11.5 Measurements
The work of making connections shall be enumerated.
18.11.6 Rate
The rate shall include the cost of labour and materials involved in all the operations described above.
18.12.0 The fitting s hall b e fully examined and c leared o f al l foreign matter be fore bei ng fixed. The fitting
shall be f itted in the pipe l ine i n a w orkman like m anner. T he j oints b etween f ittings an d pipes s hall be
leak-proof when t ested t o a pr essure o f 17. 5 kg/sq.cm. The de fective fittings and joints s hall be r eplaced
or redone.
18.12.1 Measurements
Fittings shall be enumerated.
18.12.2 Rate
The r ate s hall inc lude co st of all t he m aterial an d labo ur in volved in all th e op eration de scribed
above.
18.13.1 For fixing ferrule the empty main shall be drilled and tapped at 45 degree to the vertical and the
ferrule screwed in. The ferrule must be so fitted that no portion of the shank shall be left projecting within the
main into which it is fitted.
18.13.2 Measurements
Ferrule shall be enumerated.
18.13.3 Rate
The rate shall include the cost of all materials and labour involved in fixing the ferrule.
18.16 INSTALLATION OF WATER METER AND STOP VALVE (FIG. 18.3 and 18.4)
18.16.0 The G .I. line s hall be c ut to the re quired length at t he po sition w here the m eter a nd s top cock
are required to be fixed. The ends at the pipe shall then be threaded. The meter and stop cock shall be
fixed in position by means of connecting pipes, G.I. jam nut and s ocket etc. The stop cock shall be f ixed
near the inlet of the water meter. The paper disc inserted in the nipples of the meter shall be removed
and t he m eter i nstalled e xactly hori zontal or v ertical i n t he f low l ine i n t he d irection s hown b y t he arro w
cast on the body of the meter. Care shall be taken that the factory seal of the meter is not disturbed.
Wherever the m eter shall be f ixed to a newly fitted pipe line, the pipe line shall have to be c ompletely
washed before fitting the meter. For this purpose a piece of pipe equal to the length of the meter shall be
fitted i n th e p roposed p osition of t he meter in t he ne w pi pe line. The w ater sh all be allowed t o fl ow
completely to w ash th e pip e lin e an d the n th e m eter i nstalled a s de scribed a bove by r eplacing t he
connecting piece.
Vol-2 , 2013
18.16.1 Testing of Joints
Testing of joints shall be done as described in 18.6.6.
18.16.2 Measurements
The w ork of fixing m eters and s top cocks s hall b e c ounted i n numbers s eparately ac cording to the
diameters.
18.16.3 Rate
The rate shall i nclude t he c ost o f l abour and m aterials i nvolved i n al l t he oper ations des cribed abo ve
excluding the cost of stop cock and water meter.
18.17.3 Rate
The rate s hall i nclude t he c ost o f materials and labour involved in al l the oper ations des cribed abov e,
except the ex cavation i n saturated soil, s oft or decomposed and hard rock i f m et w ith. T he di fference of
cost, bet ween ordi nary s oil and s aturated s oil or s oft or dec omposed or hard roc k as t he c ase m ay be ,
shall be paid for separately.
18.18.1 Material
Polyethylene used for manufacture of tanks and manhole lids may be high density (HDPE), low
density (LDPE) or l inear low density ( LLDPE) and s hall c onform t o I S 101 46. Polyethylene shall be
compounded with carbon black so as to m ake the tank resistant to ultra violet rays from the sun. The
percentage of c arbon bl ack c ontent i n polyethylene s hall b e 2. 5 ± 0. 5 p ercent an d i t s hall be u niformly
distributed. The materials us ed f or t he manufacture of tank, m anhole l id and f ittings shall be s uch t hat
they neither contaminate the water nor impart any taste, colour, odour or toxity to water.
Vol-2 , 2013
18.18.5 Installation and Fittings
The flat base of the tank shall be f ully supported over its whole bottom area on a dur able rigid flat
and l evel platform s ufficiently s trong to s tand w ithout deflection the w eight of the tank w hen fully filled
with w ater. D epending upon the c apacity an d location tanks m ay be s uitably anc hored as per the
directions of t he E ngineer-in-Charge. For i nlet, o utlet and ot her connections fully threaded G I, H DPE or
PVC c onnections w ith hex agonal c heck nu ts and w ashers on ei ther s ide of the ta nk w all s hall be
provided. Holes for threaded connections shall be drilled and not punched. Pipes entering of leaving the
tank shall be p rovided w ith u nions a nd s uitably s upported on a firm base to a void dam age to the tank
walls.
18.18.7 The tank and its components shall conform to the local bye-laws for preventions of mosquito menace.
18.18.8 Measurements
Dimensions shall be measured to the nearest cm. and weight of the empty tank shall be recorded to
the nearest 100g. Capacity of the tank as defined in 18.18.3 shall be calculated to the nearest litre.
TABLE 18.23
18.18.9 Rates
The rate shall include the cost of the tank, manhole lid, carriage and delivery at the place specified.
Hoisting, installation, fittings, platform and anchoring shall be payable separately.
Vol-2 , 2013
18. 20 CUTTING HOLES IN WALL UPTO 30 × 30 CM
18.20.2 Finishing
Cement m ortar i n 1:4 m ix ( 1 cement: 4 s and) s hall be u sed f or plastering or p ointing, as m ay b e
required. S and shall be fine or c oarse, as u sed in t he original w ork. The s urface s hall b e finished w ith
two or more coats of white wash, colour wash, distemper or painting as required but where the surface is
not to be white w ashed, col our w ashed, distempered o r p ainted; i t s hall be f inished smooth with a
floating coat of neat cement or as required to match with the surrounding surfaces.
18.20.3 Measurements
The holes shall be enumerated.
18.20.4 Rate
The r ate s hall i nclude the c ost of l abour and materials required f or all t he op erations described
above.
18.21.0 Square holes of size as specified shall be cut in R.C.C. floor and r oofs for passing drain pipe
etc. A ny d amage to the adjoining portion o r t o any ot her item s hall b e m ade good a s directed b y t he
Engineer-in-Charge. All the dismantled material shall be removed from the site.
18.21.2 Measurements
Holes shall be enumerated.
18.21.3 Rate
The rate shall include the cost of labour and material required for all the operations described above
except the pipe which shall be paid for separately.
I. Cutting of chases in one brick thick and above load bearing walls :
Vol-2 , 2013
(i) As far as possible services should be planned with the help of vertical chases. Horizontal
chases should be avoided.
(ii) The depths of vertical chases and horizontal chases shall not exceed one third and one
sixth of the thickness of the masonry respectively.
(iii) W hen narrow stretches of m asonry (or short lengths of walls) such as between doors an d
windows, cannot be avoided, they should not be pierced with openings for soil pipes orwaste
pipes o r t imber j oints, e tc. Where t here i s a possibility of l oad c oncentration, s uch narrow
lengths of walls shall be checked for stresses and high strength bricks mortar or concrete walls
provided, if required.
(iv) H orizontal c hases w hen unav oidable s hould be l ocated i n t he upper o r l ower one t hird of
height of storey and not more t han three chases should be permitted i n any stretch of a wall.
No continuous horizontal chase shall exceed one metre in length. Where unavoidable,
stresses in the affected area should be checked and kept within the permissible limits.
(v) Vertical chases should not be closer than 2 m in any stretch of a wall. These shall be kept
away f rom bea rings of beam s and l intels. I f u navoidable, s tresses in the affected area
should be checked and kept within permissible limits.
(vi) Masonry directly above a recess, if under than 30 cm (Horizontal dimension) should be
supported on l intel. H oles i n m asonry m ay be pr ovided up t o 30 c m w idth x 30 c m hei ght
without any lintel. In the case of circular holes in masonry, no lintel should be provided up to
40 cm in diameter.
No chase shall be permitted in a half brick load bearing wall and as such no recessed conduits
and concealed pipes shall be provided in half brick thick load bearing walls.
In c ase of non load be aring h alf br ick w alls services should be pl anned w ith the help of v ertical
chases. Horizontal chases should be provided only when unavoidable.
The provision (i) to (vi) under Sl. No. I are equally applicable to stone masonry walls also.
Note:
1. No inclined chase shall be permitted in brick masonry or stone masonry walls. In case inclined
chases are unavoidable these shall be cut with written approval of the Engineer-in-Charge, and
shall be repaired properly to his satisfaction. However, in half brick masonry wall, no inclined
chase will be permitted.
2. Chases shall be made by chiseling out the masonry to proper line & depth. Any damage to the
adjoining portion or to any other item shall be made good, as decided by the Engineer-in-Charge,
for which no extra payment shall be made. All dismantled material shall be removed from site.
Vol-2 , 2013
AP P ENDIX A
Note : (1) f is the caulking space of the joint in millimeters and is equal to 9 + 0.003 DN.
(2) T he j ointing t olerances a pplicable t o r ubber j oints (m echanical o r p ush i n j oints) s hall be as
specified by their manufacturer and shall be within the tolerances specified above.
Tolerance on Thickness
Dimensions Tolerance in mm
(a) Wall thickness - (1 + 0.05 e)
(b) Flange thickness ± (2 + 0.05 b)
Tolerance on Length
Vol-2 , 2013
AP P ENDIX B
Tolerances in Diameter
Tolerances on Thickness
Dimension Tolerance in mm
Wall thickness - (2 + 0.05 e)
Flange thickness ± (3 + 0.05 b)
Tolerance on Lengths
Vol-2 , 2013
AP P ENDIX C
A) Thickness
4. For quantities per load of 10 tonnes, min (medium and heavy series) ± 7.5 percent
Vol-2 , 2013
AP P ENDIX D
PROCEDURE FOR PRESSURE TEST
(Clause 18.5.6)
1. Each valved section of the pipe shall be slowly filled with water and all air shall be expelled from the
pipe through hydrants and blow-offs. If these are not available at high places, necessary tapping may
be m ade at points of highest elevation before the test is m ade and pl ugs inserted after the tests have
been completed.
2. If t he t rench has b een pa rtially back-filled the s pecified pr essure ba sed on the el evation of the
lowest point of the line or section under test and c orrected to the elevation of the test gauge, shall be
applied by means of a pump connected to the pipe in a manner satisfactory to the Engineer-in-Charge.
The duration of the test shall not be less than 5 minutes.
3. Examination under Pressure: All ex posed pipes, f ittings, valves, h ydrants and j oints s hould b e
carefully e xamined d uring th e op en-trench t est. When t he j oints a re made w ith le ad, all such jo ints
showing visible l eaks s hall be recaulked u ntil t ight. W hen t he j oints a re made w ith cement a nd show
seepage o r s light l eakage, s uch j oints s hall be c ut out and r eplaced as di rected by t he aut hority. A ny
cracked or defective pi pes, fittings, v alves or hy drants di scovered i n c onsequence of t his pres sure t est
shall be removed and replaced by sound m aterial and t he test shall be repeated until s atisfactory to t he
Engineer-in-Charge.
4. If the trench has been back-filled to the top, the section shall be first subjected to water pressure
normal t o t he a rea an d t he e xposed pa rts s hall be c arefully e xamined. I f any d efects a re f ound, t hey
shall be repaired a nd t he pr essure t est r epeated until no defects are f ound. T he du ration of t he f inal
pressure tests shall be at least one hour.
5. Leakage is defined as the quantity of water to be supplied into the newly laid pipe, or any valved
section thereof, nec essary t o maintain t he s pecified leakage t est pressure after t he pipe has b een f illed
with water and the air expelled.
No pipe installation shall be accepted until the leakage is less than the number of cm3/h determined by
the formula:
ND P
ql =
3.3
Where ql = the allowable leakage in cm3/h.
N = number of joints in the length of the pipe line.
D = diameter in mm, and
P = the average test pressure during the leakage testing kg/cm 2.
6. Variation from Permissible Leakage: Should any test of pipe laid in position discloses leakage
greater than that specified in Para 5 the defective joints shall be repaired until the leakage is within the
specified allowance.
Vol-2 , 2013
AP P ENDIX E
E-1 STORAGE
CPVC pi pes of all sizes are pac ked in pol yethylene packing rolls and both the ends of the packed roll
are sealed w ith ai r bubbl e film cap i n or der to pr ovide pr otection dur ing handl ing and transportation. A fter
packing, the w hole bunch of pi pes is tightened w ith polypropylene/ H DPE s trapping. E ach role i s t hen
marked w ith size/type o f t he p ipe, lot number and quantity. The p acked p ipe r olls are s tored in their
respective ra cks in properly c overed storage area. A part f rom providing protection duri ng handling and
transportation, the packing rolls also protect the pipe from ultra violet rays.
E-2 INSTALLATION GUIDELINES
E-2.1 Visually i nspect pipe ends before making t he j oint. U se of a c hamfering t ool w ill help i dentify and
crakes, as it will catch on to any crack.
E-2.2 Pipe m ay be c ut qui ckly and ef ficiently by s everal m ethods. W heel t ype pl astic t ubing c utters are
preferred. Ratchet t ype c utter o r f ine tooth s aw ar e a nother o ptions. However, when u sing t he r atchet
cutter be certain to score the exterior wall by rotating the cutter blade in circular motion around the pipe. Do
this be fore appl ying s ignificant dow nward pr essure t o finalize t he c ut. This step l eads to a s quare cut. In
addition, m ake s ure rat chet c utter bl ades are s harp. C utting t ubing as squarely as po ssible prov ides
optimal bonding area within a joint.
E-2.3 Burrs a nd f ilings can prevent proper contact be tween t he tube a nd f ittings during t he a ssembly,
and s hould be removed f rom t he out side and i nside of t he t ube. A c hamfering t ool i s preferred, but a
pocket knife or file is also suitable for this purpose.
E-2.4 Use only CPVC cement jointing. Use CPVC cement, which is fully recommended by the
manufacturer.
E-2.5 When using adhesive solution/solvent cement be certain of proper ventilation.
E-2.6 When making a j oin, ap ply a he avy, e ven c oat of cement to t he pipe en d. Use the same
applicator w ithout ad ditional c ement t o ap ply a t hin coat i nside t he f itting s ocket. T oo m uch c ement c an
cause c logged w aterways. D o not al low ex cess c ement t o puddl e i n t he f itting and pi pe as sembly. T his
could result in a weakening of the pipe wall and possible pipe failure when the system is pressurized.
E-2.7 Rotate pipe one -quarter to one -half turn while inserting it into the fitting socket and remove the
excess adhesive solution/solvent cement from the joint with clean rag.
E-2.8 When m aking a t ransition c onnection t o m etal t hreads, us e a s pecial t ransition f itting or C PVC
male threaded adapter whenever possible. Do not over-torque plastic threaded connections. Hand tight
plus one-half turn should be adequate.
E-2.9 Hang o r strap C PVC s ystems l oosely t o al low f or t hermal e xpansion. D o not use m etal s traps
with sharp edges that might damage the tubing.
E-2.10 CPVC stub outs for lavatories, closets and sinks are appropriate. However, on areas where there is
a likelihood that movement or impact abuse will occur, metal pipe nipples may be amore appropriate stub-
out material. Showerheads, tub spouts and outside still cocks are examples.
E-2.11 When connected to a gas water heater, CPVC tubing should not be located within 50 cm of the
flue. F or w ater heaters l acking rel iable t emperature c ontrol, t his di stance may be i ncreased up t o 1 m a
metal ni pple or f lexible appliance c onnector s hould be ut ilized. T his measure eliminates t he pot ential f or
damage to plastic piping that might result from excessive radiant heat from the flue.
Vol-2 , 2013
AP P ENDIX F
F-1.2 Lot
All CPVC pipes in a single consignment of the same class, same size and manufactured under
essentially similar conditions shall constitute a lot.
F-1.3 For ascertaining conformity to the requirements of the specification, samples shall be tested for
following requirement at manufacturer place.
TABLE F-1
Scale of Sampling of Visual Appearance and Dimensional Requirements
(Clause F-1.4.1 and F-1.4.3)
F-1.4.2 These pipes shall be s elected at random from the lot a nd in order to ensure the ra ndomness of
selection, a r andom num ber t able s hall be us ed. F or gui dance and us e of random num ber t ables, IS-
4905 may b e referred t o. I n t he a bsence of a r andom n umber t able, t he f ollowing procedure m ay be
adopted:
Starting from any pipe in the lot, count them as 1, 2, 3, etc, up to r and so on, where r is the integral
part of N/n, N being the number of pipes in the lot, and n t he n umber of p ipes in the sample. Every r th
pipe so counted shall be withdrawn so as to constitute the requires sample size.
F-1.4.3 The number of pipes given for the first sample in col. 4 of Table F-1, shall be t aken from the lot
and examined f or v isual and di mensional requirements gi ven i n T able 18.16 and 18. 9.4.1. A pi pe f ailing
to s atisfy any o f t hese re quirements s hall b e c onsidered as def ective. T he l ot s hall be deemed t o h ave
satisfied these requirements, if t he nu mber o f de fectives found i n the firm sample is l ess than or equal to
the corresponding acceptance number given in col. 6 of Table F-1. The lot shall be deemed not to have
met these req uirements, if the n umber of de fectives found in the first sample is greater than or equ al to
the corresponding r ejection n umber given i n col. 7 of T able F-1. I f, how ever, t he num ber of defectives
found in the first sample lies between the corresponding acceptance and rejection numbers given in
Vol-2 , 2013
cols. 6 and 7, a s econd sample of the size given in col. 4 shall be taken and examined for the
requirements. The lot shall be considered to have satisfied these requirements. The lot shall be
considered t o hav e s atisfied t hese r equirements i f t he c umulative s ample i s l ess t han or e qual t o t he
corresponding acceptance number given in col. 6, otherwise not.
F-1.5.2 For this purpose, the number of pipes given for the first sample in col. 4 of Table F-2 shall be
taken from t he l ot. The sample pi pe f ailing t he reversion t est shall be considered as defective. The lot
shall be d eemed t o ha ve m et t he requirements gi ven i n this s pecification f or t he r eversion t est, i f t he
number of defectives f ound i n t he f irst s ample i s l ess t han o r e qual t o t he corresponding a cceptance
number given in col. 6. T his lot shall be deemed not to have m et these requirements, if the number of
defectives found in the first sample is greater than or equal to the corresponding rejection number given in
col. 7 i f, h owever, t he number of d efectives i n t he f irst s ample l ies b etween t he c orresponding
acceptance an d rejection numbers gi ven in c ol. 6 an d col. 7, a second s ample of size gi ven in c ol. 4
shall be taken and ex amined for the r equirements. T he lot s hall be c onsidered to hav e s atisfied the
requirements, if the number of d efectives f ound i n the cumulative sample is less t han or e qual to t he
corresponding acceptance number given in col. 6, otherwise not.
TABLE F-2
Scale of Sampling for Reversion, Vicat Softening Temperature and Density Test
(Clause F-1.5.2, F-1.6.2 and F-1.7.2)
F-1.6.2 For t his p urpose, t he p rocedure a dopted f or sampling a nd criteria f or conformity shall be t he
same as that for reversion under F-1.5.2 using Table F-2 at manufacturer place .
F-1.7 Density
F-1.7.1 The lot, having satisfied the visual and dimensional requirements, shall be tested for density as
given in 18.9.4.6 at manufacturer place .
F-1.7.2 For t his p urpose, t he p rocedure a dopted f or sampling a nd criteria f or conformity shall be t he
same as that for reversion under F-1.5.2 using Table F-2 at manufacturer place.
Vol-2 , 2013
F-1.8.2 For t his purpose, t he pr ocedure adopted f or sampling and criteria f or conformity s hall be as
specified in Table 18.18 and Table F-3.
TABLE F-3
Scale of Sampling for Resistance to External Blow at 0°C
TABLE F-4
Scale of Sampling for Internal Hydrostatic Test
(Clause F-1.9.1 and F-1.9.3)
Sl. No. Number of pipes in the lot Sample size Acceptance number
(1) (2) (3) (4)
(i) Up to 3000 2 0
(ii) 3001 to 10000 3 0
(iii) 10000 & above 5 0
F-1.9.2 The pipes shall be taken at random from the lot. In order to ensure the randomness of
selection, procedures given in IS 4905 may be followed.
F-2.1.2 Opacity
For t his test, the manufacturer or t he s upplier s hall furnish t o the testing authority one sample of t he
pipe of the thinnest wall section, selected preferably from a regular production lot.
Vol-2 , 2013
F-2.1.2.1 The sample so selected shall be tested for compliance with requirements for opacity as given in
18.9.4.2.
F-2.1.2.2 If the sample passes the requirements of the opacity test, the type of the pipe under
consideration s hall be c onsidered t o b e el igible f or ap proval, w hich s hall b e v alid f or a period of o ne
year.
F-2.1.2.3 In case the sample fails in the test, the testing authority, at its d iscretion, may call for a fresh
sample and subject the same to the opacity test. If the sample passes the r epeat test, the type of pipe
under c onsideration s hall be c onsidered e ligible for ap proval. I f t he sample fails i n t he repeat t est, t he
type of pipe shall not be ap proved. T he m anufacturer or t he s upplier may be a sked to i mprove t he
design and re-submit the product for type approval.
F-2.1.2.4 At the end of the validity period (normally one y ear) or earlier, if necessary, the testing
authority may call for a fresh sample for opacity test for the purpose of type approval.
F-2.1.3.1 Three s amples s o s elected s hall be t ested f or c ompliance w ith t he requi rements f or ef fect o n
water as given in 18.9.4.3.
F-2.1.3.2 If all three samples pass the requirements for effect on water, the type test of the pipe under
consideration shall be c onsidered to be el igible f or approval, w hich hall be n ormally valid f or a period of
one year.
F-2.1.3.3 In case an y of the samples fails in this test, the testing a uthority, at its d iscretion, may call for
fresh samples not exceeding the original number, and subject them to the test for effect on water. If, in
the repeat t est, no s ingle f ailure oc curs, t he t ype o f pi pe under c onsideration s hall be c onsidered el igible
for type approval. If any of the samples fails in the repeat test, the type of pipe shall not be approved.
The manufacturer or t he supplier may be as ked to improve the design and re submit the product for type
approval.
F-2.1.3.4 At the end of the validity period (normally one y ear) or earlier, if necessary, the testing
authority may call for fresh samples for effect on water test for the purpose of type approval.
F-2.1.4 Internal Hydrostatic Pressure Test (Type Test) and thermal Stability
For this type test, the manufacturer or t he supplier shall furnish to the testing authority, three samples of
pipes of different diameters and different classes (selected preferably from a regular production lot).
F-2.1.4.1 Three s amples so selected s hall be t ested f or compliance with t he r equirements of t ype t est
given in Table 18.9.4.3.
F-2.1.4.2 If a ll the th ree samples pas s the requirements of the qua lity tes t, the type of p ipe under
consideration s hall be c onsidered to be e ligible for type a pproval w hich s hall be nor mally v alid for a
period of one year.
F-2.1.4.3 In case any of the samples fail in this test, the testing authority, at its discretion, may call for
fresh samples not exceeding the original number and subject them to the type test. If, in the repeat test, no
single failure occurs, the type of pipe shall be considered for type approval. If any of the samples fails in the
repeat tests, the type of pipe shall not be approved. The manufacturer or the supplier may be asked to
improve the design and resubmit the product for type approval.
239 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
F-2.1.4.4 At the end of the validity period (normally one y ear) or earlier, if necessary, the testing
authority may call for fresh samples for type test for the purpose of type approval.
F-2.1.5.1 Five s amples so s elected shall b e t ested f or compliance w ith t he r equirements of t ype t est
given in 18.9.5.4.
F-2.1.5.2 If all the five samples pass the requirement of the quality test, the type test of pipe under
consideration s hall be c onsidered to be e ligible for type a pproval w hich s hall be nor mally v alid for a
period of one year.
F-2.1.5.3 In case an y of the samples fails in this test, the testing a uthority, at its discretion, may call for
fresh samples not exceeding the original numbers and subject them to the type test. If, in the repeat test no
single failure occurs, the type of pipe shall be considered for type approval. If any of the samples fail in the
repeat tests, the type of pipe shall not be approved. The manufacturer or the supplier may be asked to
improve the design and resubmit the product for type approval.
F-2.1.5.4 At the end of the validity period (normally one y ear) or earlier, if necessary, the testing
authority may call for fresh samples for type test for the purpose of type approval.
Vol-2 , 2013
BALL VALVE (ASSEMBLY)
Sub Head : Water Supply
Clause : 18.3.1
Cap Body
Washer X
Air Hole
Inlet
Piston
Lever
Back Nut 30°
X SECTION XX
Outlet Hole for Split
Cotter Pin
Note : The shapes of the component parts are only illustrative but the dimensions and minimum requirements, where
specified, are binding.
Vol-2 , 2013
FITTINGS & SPECIALS
Sub Head : Water Supply
Clause : 18.3.9
CROSS
SOCKET / SPIGOT
FLANGE
ELBOW NIPPLE
BRANCH 'Y'
Outlet
Body Cap
Inlet
FERRULE
(Clause 18.3.3)
Vol-2 , 2013
BIP TAP & STOP VALVE
Sub Head : Water Supply
Clause : 18.3.2
A A A
Handle
B Spindle B B
C Gland C
D C
Gland Packing D D
E Bonnet E F
G Bonnet Joint G E
F G
Washer F
J Washer Plate J
J
Washer
H K K
L H K H
M L L
M M
N N W N W
PU P U V
T T
P Q T Q T T T
Q
P
P S R Body R S P S R S P S
Overall Length Washer Plate Nut Overall Length Overall Length
BIB TAP EXTERNALLY THREADED
INTERNALLY THREADED
STOP VALVE
STOP VALVE
All dimensions in millimetres
Dimensions Lift of
A B C D E F G H J K L M N P Q R S T U V W Washer
Nominal + 0.0 Plate
Sizes –0.5 (with
Washer
in
Position,
Min. Min. Min. Min. Min. Min. Min. Min. Min. Min. Min. Min. Min. Min. Min. Min. Min. Min. Min. Min. Min. Min.)
8 47.8 13.3 7.8 16.5 6.3 2.0 7.9 7.0 3.8 10.0 M 20x 1.5 14.3 2.8 6.5 2.4 11.0 4.7 1.6 15.2 19.5 7 3.5
10 54.0 14.0 9.4 18.7 7.5 2.0 9.5 9.5 4.7 11.5 M 20 x 1.5 15.9 3.2 9.0 3.2 11.4 7.9 2.0 20.8 23.3 7 4
15 54.0 14.0 9.4 19.0 7.5 2.0 9.5 11.0 5.6 11.5 M 24 x 1.5 19.0 3.2 13.0 4.1 15.0 9.5 2.0 25.6 28.3 9 4.5
20 60.4 15.7 10.9 20.1 8.9 2.5 11.1 12.5 6.4 13.5 M 30 x 1.5 25.4 4.0 18.0 4.9 16.3 10.3 2.0 30.5 33.0 10.5 6
25 66.8 18.0 12.5 23.0 10.1 2.5 12.7 13.0 7.1 17.0 M 39 x 1.5 33.3 4.0 23.0 4.9 19.1 11.0 2.8 37.6 42.4 11.5 7
32 74.6 20.5 14.1 30.9 11.4 2.5 14.3 16.0 7.8 19.0 M 48 x 1.5 40.1 4.3 30 5.9 21.4 12.7 3.2 47.2 52.1 13.5 9.5
40 82.5 22.0 15.7 33.3 12.7 2.5 15.9 17.5 8.6 20.5 M 56 x 1.5 47.7 5.5 36 6.6 21.4 14.3 3.2 56.4 58.5 13.5 11
50 95.0 25.3 17.3 35.9 14.0 2.5 17.4 17.5 12.5 26.0 M 72 x 1.5 63.5 6.3 46 8.3 25.1 15.9 4.0 70.1 71.5 16.5 14.5
Vol-2 , 2013
COCKS VALVES & METER
Sub Head : Water Supply
Clause : 18.3.15
Water Meter
10 d Min Filter
10 d Min
Dirt Box
By Pass
Valve L
Vol-2 , 2013
MASONRY CHAMBERS & SURFACE BOXES
Sub Head : Water Supply
Clause : 18.3.14
Masonry Chamber
500
750 One Brick Thick One Brick Thick
75
100 C.C. 1:5:10
600
100 C.C. 1:5 :10 75 75
SECTION C D
SECTION X Y
75 75
1 Bk 600 1 Bk
75 600 75
75
1 Bk 75
1 Bk
600
X Y 450
C D
1 Bk One Brick
75 75
PLAN PLAN
SURFACE BOX
550
450 SURFACE BOX
350
550
A A B B
650
200
750
280
30 440
45 30 10
155 165 10
15
10 200
410
50
SECTION A A 6
400
480
SECTION B B
Vol-2 , 2013
MASONRY CHAMBERS & SURFACE BOXES (Contd.)
Sub Head : Water Supply
Clause : 18.3.14
Surface Box
FOR STOP COCK R.C.C. 1:2:4
Masonry
750 Chamber
500
75 600 75
300 75
75
A B 600
X Y
300
PLAN 75
PLAN
185
360 Pin 10 dia
75
30 45
20
160 x 160
112 x 112
230
13
75 6
10
100 x 100 160
280
SURFACE BOX FOR STOP COCK SURFACE BOX FOR SLUICE VALVE
Vol-2 , 2013
THRUST BLOCKS
Sub Head : Water Supply
Clause : 18.4.6
Soil
Concrete
Clamp
Vol-2 , 2013
HYDROSTATIC TESTS
(END CLOSURE FOR PIPES)
Wedge
Screw Jack
One or Two Wooded Sleeper
Depending Upon dia of Pipe
Wooden Packing
Vol-2 , 2013
19.0 : DRAINAGE
Vol-2 , 2013
CONTENTS
Clause No. Brief Description Page No.
List of Bureau of Indian Standards (BIS) Codes 252
Vol-2 , 2013
Fig. 19.6 Manhole (Contd.) 279
Vol-2 , 2013
LIST OF BUREAU OF INDIAN STANDARDS (BIS) CODES
5. IS 1729 Cast Iron /Ductile Iron Drainage Pipes and Pipe Fittings Socket and Spigot
Series for Over-ground Non-pressure Pipe Line.
Vol-2 , 2013
19.0 DRAINAGE
19.0 TERMINOLOGY
Benching (Fig. 19.8): The sloped floor of a manhole or an inspection chamber on both sides and above the
top of the channel.
Channel: The open waterway through which sewage, storm water or other liquid waste flow at the invert of
a manhole or an inspection chamber.
Cleaning Eye (Fig. 19.8): An access ope ning having a rem ovable cover t o e nable obstructions t o be
cleared by means of a drain rod.
Connections: The junction of a foul water drain, surface water drains with public sewer, cesspool soakway
or other water courses.
Dispersion Trench: A t rench i n w hich open j ointed pi pes s urrounded by coarse ag gregate m edia a nd
overlaid by fine aggregate, are laid. The effluent from septic tank gets dispersed through the open joints
and is absorbed in the surrounding soil.
Depth of Manhole: The v ertical di stance f rom t he top of t he m anhole t o t he outgoing i nvert of t he m ain
drain channel.
Drain: A l ine o f pi pes including al l fittings and equi pment, such as manholes traps, gul lies and floor traps
used for the drainage of a building, or a number of buildings or yards appurtenant to the buildings, within the
same cartilage. Drain shall also include open channels used for conveying surface water.
Drainage: The removal of any liquid by a system constructed for the purpose.
Drop Connection (Fig. 19.8): A br anch dr ain of w hich t he l ast l ength o f pi ping of t he i ncoming dr ain,
before connection to the sewer, is vertical.
Drop Manhole (Fig. 19.8): A manhole incorporating a vertical drop for the purpose of connecting a
sewer or drain at high level to one at lowers level.
Effluents
(a) Tank Effluent: The supernatant liquid discharge from a septic tank.
Gully Chamber (Fig. 19.2): The chamber built of masonry around a gully trap, for housing the same.
Gully Trap (Fig. 19.2): A t rap w ater s eal prov ided i n a drai nage system i n a suitable pos ition t o collect
waste water from the scullery, kitchen sink, wash basins, baths and rain water pipes.
Haunching (Fig. 19.11): Concrete bedding with ad ditional c oncrete at t he s ides of t he pipe.
Invert: The lowest point of the interior or a sewer or drain at any cross action.
Inspection Chamber: A water t ight c hamber c onstructed i n any hous e d rainage s ystem w hich t akes
wastes from gully traps and disposes off to manhole with access for inspection and maintenance.
253 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
Interceptor Manhole (Interceptor Chamber): A m anhole incorporating a n i ntercepting t rap, an d pr oviding
means of access thereto and equipped with a fresh air inlet on the upstream side of the trap.
Manhole (Manhole Chamber): Any c hamber constructed on a dra in or s ewer s o as t o pro vide a ccess
thereto for inspection testing or the clearance of obstruction.
Rest Bend (Duck Foot Bend): A bend supported in a vertical position by a foot formed at its base.
Saddle: A purpose m ade fitting, s o shaped as t o f it over a hole cut i n a s ewer or drain, and us ed to form
connections.
Soffit: The highest portion of the interior of a sewer or drain at any cross-section.
Soil Waste: The di scharge from water c losets, ur inals, s lope sinks, stable o r cowshed gul lies and similar
appliances.
Soil Pipe: Which receives the discharges from soil fitments, such as water closets urinals, and slope sinks.
Sullage Waste Water: Spent w ater from bat hs, w ash bas ins kitchen sinks, a nd similar appl iances w hich
does not contain human or animal excreta.
Sewer: A closed drain carrying night soil and other water borne waste.
Surface Water Drain: A drain conveying surface water including storm water.
Surface Water: The run off from precipitation, other water that flows over surface of the ground.
Sub Soil Water: Water occurring naturally below the surface of the ground.
Soak Pit (Seepage Pit Soak Way) (Fig. 19.17) : A pit through which effluent is allowed to seep or leach into the
surrounding soil.
Septic Tank (Fig. 19.15 & 19.16) : A water tight single storied tank in which sewage is retained sufficiently
long t o per mit s edimentation of s uspended s olids and par tial di gestion of s ettled s ludge by anaer obic
bacteria.
Scum: The greasy and other substances floating on the surface of sewage.
Vent Pipe: A pipe line installed to provide flow of air to or from a drainage system or to provide circulation of air
within such system to protect trap seals from siphonage and back flow.
Waste Water: The di scharge from w ash basins, sinks and similar a ppliance, w hich doe s not contain hu man
excreta.
19.1.2 The d ischarge o f water th rough a dom estic d rain is intermittent and limited in quan tity and
therefore, small ac cumulations of s olid m atter are l iable t o f orm in t he dra ins bet ween t he b uilding a nd
the publ ic s ewer. Ther e is us ually a gradual s hifting of these depos its as discharges take pl ace.
Gradients shall be sufficient to prevent these temporary ac cumulations bui lding up an d bl ocking the
drains.
254 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
19.1.3 Normally, t he sewer shall b e designed for discharging t hree t imes t he dry weather f low f lowing
half-full w ith a m inimum self c leansing v elocity of 0.75 m etre per s econd. The appr oximate gr adients
which gi ve this velocity for the s izes of pi pes l ikely to be used i n building drainage and the corresponding
discharges w hen flowing h alf-full are gi ven in T able 19.1. T he s izes and s lopes s hall c onform t o L ocal
Municipal Bye-laws.
19.1.4 In c ases, where it i s practically not pos sible to conform to the minimum gradients, a f latter
gradient m ay be used bu t the m inimum v elocity in such cases s hall on no a ccount be less than 0. 61
metres per second.
19.1.5 On t he other h and, i t i s u ndesirable t o employ gradients giving v elocity of f low greater than 2. 4
metres per second. W here it i s unavoidable, c ast i ron p ipes s hall be used. T he a pproximate g radients
which g ive a v elocity o f 2 .4 m etres per s econd for the v arious s izes o f p ipes and the c orresponding
discharge when flowing half-full are given in Table 19.1.
TABLE 19.1
Gradients for Sewers
Minimum Gradient Maximum Gradient
Diameter Gradients Discharge Gradients Discharge
mm cum/Min. cum/Min.
100 1 in 57 0.18 1 in 5.6 0.59
150 1 in 100 0.42 1 in 9.7 1.32
200 1 in 145 0.73 1 in 14 2.4
230 1 in 175 0.93 1 in 17 2.98
250 1 in 195 1.10 1 in 19 3.60
300 1 in 250 1.70 1 in 24.5 5.30
TABLE 19.2
Stoneware Pipes
Internal Diameter (mm) Mean Thickness of the Barrel and Socket (mm)
100 12
150 15
200 16
230 19
250 20
300 25
350 30
400 35
450 37
The length of pipes shall be 60, 75, 90 cm exclusive of the internal depth of the socket. The pipes
shall be handled with sufficient care to avoid damage to them.
Vol-2 , 2013
19.2.1.1 S.W. Gully Trap (Fig. 19.2): Gully traps shall conform to IS 651. T hese s hall be sound, free
from visible defects such as fire cracks, or h air cracks. The glaze of the traps shall be f ree form crazing.
They shall give a sharp clear tone when struck with light hammer. There shall be no broken blisters.
Each g ully t rap s hall hav e one C .I. grat ing of s quare s ize c orresponding t o t he di mensions of i nlet of
gully trap. It will also have a w ater tight C.I. cover with frame inside dimensions 300 x 300 m m the cover
weighing not less than 4.50 Kg and the frame not less than 2.70 Kg. The grating, cover and frame shall be
of sound and good casting and shall have truly square machined seating faces.
19.2.1.2 Laying and Jointing Stone Ware Pipes : For al l s ewers and drains, gl azed s toneware pi pes
shall be us ed as f ar as p ossible i n preference t o o ther t ypes of pi pes. T hese are s uitable, particularly
where acid effluents or acid sub-soil conditions are likely to be encountered.
The trench shall be so dug that t he pipe can be l aid to the r equired al ignment and at t he required
depth. W hen the pi pe line is u nder a roadway, a m inimum c over of 9 0 c m i s recommended for
adoption, bu t it m ay be m odified to s uit l ocal c onditions. T he trench s hall be e xcavated o nly s o
far in ad vance o f p ipe laying a s s pecified by the E ngineer-in-Charge. T he trench s hall be s o
shored an d dr ained t hat the w orkmen m ay w ork therein s afely and efficiently. T he d ischarge of
the trench dewatering pumps shall be conveyed either to drainage channels or to natural drains.
The ex cavation shall be carried out with manual l abour o r with s uitable mechanical equi pment as
approved by the Engineer-in-Charge.
Unless otherwise specified by the Engineer-in-Charge, the width at bottom of trenches for
different diameters of pipes laid at different depths shall be as given below:—
(a) For all diameters, up to an average depth of 120 cm, width of trench in cm = diameter of
pipe + 30 cm.
(b) For all diameters for depths above 120 cm, width of trench in cm = diameter of pipe + 40 cm.
(c) N otwithstanding (a) and (b) t he total width of trench shall not be l ess than 75 c m for depths
exceeding 90 cm.
The width of trench in the upper reaches shall be increased as described in sub-head
‘Earthwork’.
(ii) Laying (Fig. 19.11) : Where the pipes are laid on soft soil with maximum water table lying at
invert level of the pipe, the pipes shall be bedded in cement concrete with thickness and mix as
specified, projecting on each side of the pipe to the specified width of the trench (Fig. 19.11(i)).
The pipes with their crown level at 1.20 m depth and less from ground shall be covered with 15 cm
thick. Concrete above the crown of the pipe and sloped off to meet the outer edges of the
concrete, to give a minimum thickness of 15 cm all-around the pipe (Fig. 19.11 (iii)). Pipes laid at a
depth greater than 1.20 m at crown and maximum water table level rising above the invert level of
pipe, shall be concreted at the sides up to the level of the centre of the pipe and sloped off from
the edges to meet the pipe tangentially (Fig. 19.11(ii)).
The p ipe s hall b e c arefully l aid t o the a lignments, l evels and g radients s hown o n t he plans and
sections. Great ca re s hall be ta ken to pr event s and et c. fro m e ntering th e pip es. T he p ipes
between two manholes shall be laid truly in a straight line without vertical or horizontal
256 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
undulation. The pipes shall be laid with socket ends facing upstream. The body of the pipe shall for
its entire l ength rest on an even bed of concrete and pl aces shall be excavated in the
concrete to receive the socket of the pipe.
Where pipes are not bedded on concrete, the trench floor shall be left slightly high and carefully
bottomed up as pipe laying proceeds, s o tha t the pi pe ba rrels re st on f irm an d und isturbed
ground. I f t he excavation has been carried t oo l ow, t he desired l evels shall be made up with
concrete 1 :5:10 ( 1 c ement: 5 fine s and: 10 g raded s tone aggr egate 40 m m n ominal s ize) for
which no extra payment shall be made.
If t he f loor of t he t rench c onsists of r ock or v ery hard gr ound t hat c annot easily be ex cavated t o
smooth surface the pipe shall be laid on a levelling course of concrete as desired.
When S.W. pipes are used for storm water drainage, no concreting will normally be necessary. The
cement mortar for jointing will be 1:3 (1 cement: 3 fine sand). Testing of joints will also not be done.
(iii) Jointing : T arred ga sket or he mp yarn soaked in thick c ement s lurry shall first be pl aced round
the spigot of each pipe and the spigot shall then be slipped home well into the socket of the pipe
previously laid. The pipe shall then be adjusted and fixed in the correct position and the gasket
caulked tightly home so as to fill not more than 1/4th of the total depth of the socket.
The remainder of the socket shall be filled with stiff mixture of cement mortar in the proportion of
1:1 (1 cement: 1 fine sand). When the socket is filled, a fillet shall be formed round the joint with a
trowel forming an angle of 45 degree with the barrel of the pipe.
After a d ay’s w ork a ny extraneous material s hall be removed f rom t he i nside of t he pipe. The
newly made joints shall be cured for at least seven days.
(iv) Testing of Joints : Stoneware pipes used for sewers shall be subjected to a test pressure of 2.5 m
head of w ater a t t he hi ghest p oint o f t he s ection u nder te st. B efore commencing test, the
pipeline shall be filled with water and maintained full for 24 hours under head of 0.6 m of water.
The test shall be carried out by suitably plugging the lower end of the drain and the ends of the
connection if any and f illing the system with water. A knuckle bend s hall be t emporarily jointed in
at the top end and a sufficient length of vertical pipe jointed to it so as to provide the required test
head, or the top may be plugged with a connection to a hose ending in a funnel which could be
raised or lowered till the r equired h ead i s obtained and f ixed suitable f or obs ervation. The
tolerance of two liters per centimeter of diameter per kilometer may be allowed during a period of 10
minutes.
If an y leakage is visible, the defective p art of the work shall b e cut o ut and m ade g ood. A slight
amount of sweating which is uniform may be overlooked, but excessive sweating from a
particular pipe or joint shall be watched for and taken as indicating a defect to be made good.
Any j oint f ound l eaking o r s weating, s hall b e re ctified or e mbedded i nto 15 cm l ayer of cement
concrete (1:2:4) 30 cm in length and the section retested.
(v) Refilling : In cases w here pipes are not bedded on concrete special care s hall be taken in refilling
trenches to prevent the displacement and subsequent settlement at the surface resulting in
uneven street surfaces and dangers to foundations etc. The backfilling materials shall be packed by
hand under and around the pipe, and rammed with a shovel and light tamper. This method of filling
will be c ontinued up t o t he t op of pi pe. T he r efilling s hall r ise ev enly on bot h s ides of t he pipe
continued up to 60 cm above the top of pipe so as not to disturb the pipe. No tamping should
be done within 15 cm of the top of pipe.
257 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
(vi) Measurements : The lengths of pipes shall be measured in running metres nearest to a cm as
laid or f ixed, f rom i nside of one m anhole t o t he i nside of t he ot her m anhole. T he l ength s hall be
taken along the centre line of the pipes over all fittings such as bends, junctions, etc. which shall
not be measured separately.
Excavation, r efilling, s horing and timbering i n t renches, and cement c oncreting w herever r equired
shall be measured separately under relevant items of work.
(vii) Rate : The rate shall inc lude the cost of materials and labou r inv olved in all the operations
described above excluding the cost of concrete which shall be paid for separately.
(ii) Fixing : The gully traps shall be fixed on cement concrete foundation 65 cm square and not less
than 10 cm t hick. The mix for t he concrete will be 1:5:10 (1 cement: 5 fine s and: 10 graded stone
aggregate 40 m m nominal s ize). T he j ointing of gully o utlet t o t he branch drain shall b e d one
similar to jointing of S.W. pipes described above.
(iii) Brick Masonry Chamber : After fixing and testing gully and branch drain, a brick masonry
chamber 300 x 300 mm (inside) in brick work of specified class in cement mortar 1:4 (1 cement: 4
fine s and) s hall be built w ith a hal f bri ck t hick bri ck work ro und t he gul ly t rap from t he t op of t he
bed concrete up t o ground l evel. T he s pace between t he chamber walls a nd t he t rap s hall be
filled i n w ith c ement c oncrete 1: 5:10 (1 c ement: 5 f ine s and: 10 grade d s tone aggregat e 40 m m
nominal size). The upper portion of the chamber i.e. above the top level of the trap shall be plas-
tered i nside w ith c ement mortar 1: 3 ( 1 c ement: 3 c oarse s and), f inished w ith a f loating c oat of
neat cement. T he corners and bottom of t he chamber shall be rounded off s o as t o slope towards
the grating.
C.I. cover with frame 300 × 300 mm (inside) shall then be fixed on the top of the brick masonry
with c ement concrete 1: 2:4 ( 1 cement: 2 c oarse sand: 4 gr aded s tone aggr egate 20 mm no minal
size) and rendered smooth. The finished top of cover shall be left about 4 cm above the adjoining
ground level so as to exclude the surface water from entering the gully trap.
(iv) Measurements : The work shall be enumerated. Excavation shall be measured separately under
relevant item of earth work.
(v) Rate : The rate shall include the cost of materials and labour involved in all the operations
described above, except earth work which shall be paid for separately.
Concrete used for the m anufacture of un -reinforced and reinforced concrete pipes and collars
shall no t b e leaner than 1 :2:4 (1 c ement: 2 c oarse s and: 4 g raded stone ag gregate). The m aximum
size of aggregate should not exceed one third of the thickness of the pipe or 20 mm whichever is
Vol-2 , 2013
smaller for pipes above 250 mm internal diameter. But for pipes of internal diameter 80 to 250 mm, the
maximum size of aggregate should be 10mm. The reinforcement in the reinforced concrete pipes shall
extend throughout t he l ength of t he pi pe. The c ircumferential an d l ongitudinal rei nforcements s hall be
adequate to withstand the specified hydrostatic pressure and f urther b ending stresses due t o the weight
of water when running full across a span equal to the length of pipe plus three times its own weight.
The minimum clear cover for reinforcement in pipes and collars shall be as given in Table 19.3.
TABLE 19.3
Note : An effective means shall be provided for maintaining the reinforcement in position and for
ensuring correct cover during manufacture of the unit. Spacers for this purpose shall be of rust
proof material or of steel protected against corrosion.
(ii) Loading, t ransporting and unl oading of c oncrete pi pes s hall be d one w ith care. H andling shall be
such as to avoid impact. Gradual unloading by inclined plane or by chain pulley block is
recommended. A ll pi pe s ections and c onnections s hall be inspected carefully before bei ng l aid.
Broken or defective pipes or c onnections s hall not be us ed. P ipes shall be lowered into the
trenches carefully. Mechanical appliances may be used. Pipes shall be laid true to line and grade as
specified. Laying of pipes shall proceed upgrade of a slope.
(iii) If the pi pes h ave spigot and s ocket joints, t he socket e nds s hall f ace u pstream. In t he case of
pipes with joints to be made with loose collars, the collars shall be slipped on before the next pipe is
laid. Adequate and proper expansion joints shall be provided where directed.
(iv) In case w here foundation c onditions a re unus ual such as i n t he pr oximity o f t rees or hol es, under
existing or pr oposed t racks m anholes et c. t he pi pe s hall be enc ased al l-around i n 15 c m t hick
cement concrete 1: 5:10 ( 1 c ement : 5 fine sand : 10 graded stone aggregate 40 mm nominal
size) or compacted sand or gravel.
(v) In c ases w here the na tural foundation is inadequate the p ipes s hall be laid e ither in c oncrete
cradle supported on proper foundations or on any other suitably designed structure. If a concrete
cradle bedd ing is u sed the depth of concrete below the bottom of the pipe shall be at least 1/4th
of the internal dia of the pipe subject to the min. of 10 cm and a maximum of 30 cm. The concrete
shall extend up the sides of the pipe at least to a di stance of 1/ 4th of the o utside di ameter of
pipes 300 mm and over in dia. The pipe shall be laid in this concrete bedding before the concrete
has set. Pipes laid in trenches in earth shall be bedded evenly and firmly and as far up the
259 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
haunches of the pipe as to safely transmit the load expected from the backfill through the pipe to
the bed. This shall be do ne either by excavating the bottom of the trench to fit the curve of the
pipe or by c ompacting the earth under around the curve of the pipe to form an ev en bed.
Necessary provision shall be made for joints wherever required.
(vi) When the pipe is laid in a trench in r ock hard clay, shale or ot her hard material the space below
the pipe shall be excavated and replaced with an equalising bed of concrete, sand or compacted
earth. In no place shall pipe be laid directly on such hard material.
(vii) The method of bedding and laying the pipes under different conditions are illustrated in Fig. 19.9.
(viii) When t he p ipes ar e l aid completely above t he gr ound t he f oundations s hall be made e ven and
sufficiently compacted to support the pipe line without any material settlement. Alternatively the
pipe l ine s hall be s upported on r igid f oundations at i ntervals. S uitable arrangements shall be
made to retain the pipe line in the proper alignment, such as by shaping the top of the supports to
fit the lower part o f the p ipe. T he d istance be tween the s upports s hall in no c ase ex ceed the
length of the pipe. T he pipe shall b e supported as far as possible close to the joints. In n o case
shall the joints come in t he c entre of the s pan. C are s hall be taken to s ee that super imposed
loads greater than the total load equivalent to the weight of the pipe when running full shall not be
permitted.
Suitably de signed a nchor b locks at c hange o f d irection and g rades f or pressure l ines shall be
provided where required.
(ix) Jointing: Joints are generally of rigid type. Where specified flexible type joints may also be
provided.
(b) Rigid Collar Joint (Fig. 19.10): The two ad joining pipes shall b e butted against each other
and adj usted i n correct p osition. T he c ollar shall t hen be slipped ov er t he j oint, c overing
equally both the pipes. The annular space shall be filled with stiff mixture of cement mortar
1:2 (1 cement: 2 f ine sand) which shall be r ammed with caulking fool. After a day ’s work
any extraneous materials shall be removed from the inside of the pipe and the newly made
joint shall be cured.
(c) Semi Flexible Spigot and Socket Joint (Fig. 19.10): Deleted
(d) Semi Flexible Collar Joint: This is made up of a loose collar which covers two specially
shaped pi pe ends as s hown i n t he Fig. 19. 10. E ach end s hall be f itted with a rubber ring
which w hen c ompressed between t he s pigot and t he c ollar, s eal t he joint. Stiff m ixture of
cement m ortar 1: 2 (1 c ement: 2 f ine s and), s hall then be f illed into the remaining annul ar
space an d ra mmed w ith a c aulking t ool. A fter day ’s w ork, a ny ex traneous m aterial s hall be
removed from the inside of the pipe and the newly made joint shall be cured.
(e) Internal Flush Joint (Fig. 19.10): This joint is generally used for culvert pipe of 60 c m dia
and o ver. The en ds of the pi pe are s pecially s haped to form a s elf c entering joint w ith a n
internal j ointing s pace 1.3 cm w ide the f inished j oint is f lush with bo th i nside and outside
with the pipe wall as shown in Fig. 19.10.
Vol-2 , 2013
The jointing space is filled with cement mortar 1:2 (1 cement: 2 fine sand) mixed sufficiently
dry t o rem ain i n po sition w hen f orced w ith a trowel or r ammer. A fter d ay’s w ork, any
extraneous material s hall be removed from the inside of the pipe and the newly made joint
shall be cured.
(f) External Flush Joint : This joint is suitable for pipes which are too small for jointing from
inside. This j oint i s c omposed of s pecially s haped pi pe en ds as s hown i n Fig. 19. 10. E ach
end s hall be b utted against eac h ot her and adj usted i n c orrect pos ition. T he j ointing s pace
shall then be fill ed with ce ment m ortar 1:2 (1 ce ment: 2 fine sand) su fficiently dry a nd
finished of f flu sh. Great care sh all b e tak en t o e nsure th at t he pr ojecting end s are not
damaged as no repairs can be readily affected from inside the pipe.
(x) In all pressure pipe lines the recess at the end of the pipe line shall be filled with jute braiding
dipped i n hot bi tumen or ot her s uitable approved c ompound. P ipes s hall be s o j ointed t hat t he
bitumen r ing of one p ipe shall s et i nto t he r ecess of t he n ext p ipe. T he ri ng s hall b e t horoughly
compressed by jacking or by any other suitable method.
The number of pipes that shall be jacked together at a time shall depend on the diameter of the
pipes and the bearing capacity of the soil, for small pipes up to 25 cm diameter, six pipes can be
jacked together at a time.
The q uantity of jute a nd bitumen in t he ring s hall be j ust s ufficient to fill the recess in t he pipe
when pressed h ard by j acking or by an y other suitable m ethod. B efore an d d uring jacking c are
shall be taken to see that there is no offset at the joint.
(xi) Testing: For pressure pipes, the completed pipeline shall be tested for pressure (Known as site
test pressure) which shall not be less than the maximum pipeline operating pressure
F or non - Pressure pipes to be used for carrying liquid, the joints shall be tested as per procedure
laid down under Para 19.2.1.2 (iv).
(xii) Refilling of Trenches: The specification described in 19.2.1.2 (v) shall apply. In case where pipes
are not bedded on concrete s pecial c are s hall be tak en in re filling, tr enches to prev ent th e
displacement and subsequent settlement at the surface resulting in uneven street surfaces and
dangers t o f oundations et c. T he bac kfilling m aterials s hall be pac ked by han d under a nd aro und
the pipe and rammed with a shovel and light tamper. This method of filling will be continued up to
the top of pi pe. The refilling shall rise evenly on bot h sides of the pipe and continued up to 60 cm
above the top of pipe so as not to disturb the pipe. No tamping shall be do ne within 15 c m of the
top of pipe. The tamping shall become progressively heavier as the depth of the backfill
increases.
(xiii) Measurements : The lengths of pi pes shall be measured i n ru nning m etres ne arest to a cm a s
laid or f ixed, f rom inside of one m anhole t o the i nside of t he other m anhole. T he l ength shall be
taken al ong t he c entre l ine of t he pi pes o ver all f ittings s uch a s b ends, c ollars, j unctions, e tc.
which shall not be measured separately. Excavation, refilling, shoring and timbering in trenches, and
cement concreting wherever required shall be measured separately under relevant items of work.
(xiv) Rate: The rate shall include the cost of materials and labour involved in all the operations
described above.
Vol-2 , 2013
19.2.3 Cast Iron (Centrifugally Cast) Pipes and Specials
Cast iron (centrifugally cast) pipes and specials shall conform to the specifications described in
18.3.10.
The chamber shall be of brick masonry, 12 mm dia, round bar shall be fixed in cement concrete block at
the bottom. The bars at the top shall be welded or riveted to M.S. flat 40×6 mm as shown in Fig. 19.14.
The details of typical road gully chamber of brick masonry with horizontal and vertical grating shall be as
given in Fig. 19.14.
(ii) They shall be cleanly cast and shall be free from air and sand holes, cold shuts and warping.
(iii) Covers shall have on its operative top a raised chequered design to provide for an adequate
no-slip grip. The rise of chequers shall be not less than 4mm.
(iv) Key holes, keys and lifting devices shall be provided in the manhole covered to facilitate their
placement in the frames and their operative maintenance.
Vol-2 , 2013
(v) Manhole covers and frames shall be coated with materials having base with a black
bituminous composition. The coating shall be smooth and tenacious. It shall not flow when
exposed to temperature of 63°C and shall not be so brittle as to chip off at temperature of
0°C.
(vi) Size and shape and performance requirement of manhole covers and frames shall conform
to IS 1726.
(vii) Each manhole covers and frame shall have cast on them the following information:
(a) Manufacturer’s name or trade-mark
(b) Grade designation
(c) Date of manufacturer
(d) The words SWD or ’Sewer’ to denote ‘storm water drain’ or ‘sewer’ respectively
(e) Identification marks as required by Engineer-in-Charge.
(ix) The sizes of covers specified shall be taken as the clear internal dimensions of the frame.
(x) The approximate weight of the various type of manhole covers and frames shall be as per IS
1726.
(xi) The cover shall be capable of easy opening and closing and it shall be fitted in the frame in
workmanship like manner.
19.3.2.1 Materials
Cement: Cement used for the manufacture of pre-cast c oncrete m anhole covers shall be 4 3 gr ade
Portland cement conforming to IS-8112.
Aggregates: The aggrega tes us ed s hall be clean a nd f ree f rom de leterious matter and s hall conform to
the r equirements o f IS-383. The aggr egates s hall be w ell graded and t he no minal maximum s ize of
coarse aggregate shall not exceed 20 mm.
Concrete: The mix proportions of concrete s hall be determined b y t he manufacturer and shall be such a s
will pro duce a d ense concrete w ithout voids, h oney c ombing et c. The m inimum cement content i n the
concrete shall be 410 kg/m3 with a maximum water cement ratio of 0.45. Concrete weaker than grade M-
30 (design mix) shall not be used. Compaction of concrete shall be done by machine vibration.
Reinforcement
(a) The reinforcement steel shall conform to IS 1786. Reinforcement shall be clean and free from
loose mill scale, loose rust, and mud, oil, grease or any other coating which may reduce or
destroy the bond between the concrete and steel. A light film of rust may not be regarded as
harmful but steel shall not be visibly pitted by rust.
(b) Fibers Steel: The diameter/equivalent diameter of steel fibers where used, shall not be greater
than 0.75 mm. The aspect ratio shall be in the range of 50 to 80. The minimum volume of fibers
shall be 0.5 percent of the volume of concrete.
Vol-2 , 2013
The reinforced concrete manhole cover and frame shall be designed in accordance with the
provisions of IS 456. Clear cover to reinforcement shall not be less than 15 mm.
19.3.2.2 Shapes and Dimensions: Shape, d imensions a nd t olerance of pr e-cast c oncrete m anhole
covers and frames s hall conform to IS 12592. O utside dim ension o f c over at top s hall m atch with
corresponding f rame s o that t he m aximum c learance at t op bet ween t he f rame and t he c over a ll rou nd
the periphery is not more than 5 mm and the top surface of the frame and covers, is in level within a
tolerance of +5 mm.
For f acility of removing t he c over f rom t he f rame, s uitable t aper m atching with t aper gi ven f or t he
frame shall be provided to the periphery of the cover.
19.3.2.3 Lifting Device: The minimum diameter of mild steel rod used as lifting device shall be 12 mm
for l ight and m edium dut y c overs and 16 m m f or h eavy a nd e xtra hea vy d uty c overs. T he l ifting de vice
shall be protected from corrosion by hot galvanising or epoxy coating or any other suitable treatment.
19.3.2.4 Finishing & Coating: To prevent any possible damage from corrosion of steel the underside of the
covers shall be treated with anticorrosive paint. The top surface of the covers shall be given a
chequered finish.
In order to protect the edges of the covers from possible damage at the time of lifting and handling it is
necessary t hat t he manhole c overs s hall be c ast w ith a pr otective mild s teel s heet o f minimum 2. 5 mm
thickness a round t he per iphery of t he c overs. E xposed surface o f mild s teel sheet shall be gi ven s uitable
treatment with an ticorrosive pai nt or co ating. To pre vent the top outer ed ge of frame fro m po ssible
damages, it shall be protected by 25 mm X 3 mm mild steel flat as part of the frame.
(b) Load Test: The breaking l oad of i ndividual un its w hen t ested i n a ccordance w ith t he m ethod
described in IS 12592 shall be not less than the values specified in Table 19.4.
TABLE 19.4
19.3.2.6 Fixing: The frames o f manhole shall be firmly e mbedded t o correct al ignment and l evel i n R CC
slab or plain concrete as the case may be on the top of masonry which shall be paid as extra unless
specified otherwise.
19.3.2.7 Measurements: The manhole covers shall be enumerated under relevant items.
19.3.2.8 Rates: The rate s hall i nclude t he cost of m aterials and l abour i nvolved i n all t he operation
described abov e ex cept f ixing o f f rames a nd covers w hich shall be pa id as ex tra un less specified
otherwise in the item.
Vol-2 , 2013
19.3.2.9 Foot Rests: Foot rests shall be of 20 mm M.S. square or round bars as specified.
Manholes of di fferent t ypes a nd sizes a s s pecified s hall be c onstructed i n t he s ewer l ine at s uch
places and t o s uch l evels and dimensions a s s hown i n the drawings or a s di rected b y t he Engineer-in-
Charge. The size specified shall indicate the inside dimensions between brick faces of the manholes.
Where the diameter of the drain is increased, the crown of the pipe shall be fixed at the same level
and nec essary slope g iven in the invert o f the m anhole c hamber. In e xceptional c ases and w here
unavoidable, the crown of the branch sewer may be fixed at lower level but in such cases the peak flow
level of the two sewers shall be kept the same.
Sewers of un equal sectional area shall not be jointed at the same invert in a manhole. The invert of
the smaller sewer at its junction with main shall be at least 2/3 the diameter of the main above the invert of
the m ain. T he branch s ewers shall deliver s ewage i n t he m anhole in t he direction of m ain f low and the
junction must be made with care so that flow in main is not impeded.
No dr ain from hous e fittings, e .g. gu lly trap or s oil pipe, e tc. to m anhole s hall nor mally ex ceed a
length of 6 m unless it is unavoidable.
Manholes 90 × 80 cm are generally constructed within compound for house drainage only and near the
buildings for house drainage. Manholes 1.2 m × 90 cm are general ly constructed for main drainage work
for depths less than 1.5 m.
Manhole 1 .4 m × 9 0 c m i s of t he arc hed t ype a nd is general ly c onstructed f or m ain drai nage w orks
where dept h i s 1.50 m o r m ore. The width of manholes shall be i ncreased more t han 90 cm on bends or
junctions or pipes with diameter greater than 450 mm and that the benching width on either side of the
channel is minimum 20 cm.
Manholes 1.4 m internal diameter are generally constructed for main drainage works where depth is
2.45 m or more as an alternative to manholes of arch type. The diameter shall be i ncreased suitably, for
pipes with diameter greater than 450 mm in the same manner as in the case of rectangular manholes.
Before deciding s ize of m anholes, Loc al M unicipal Bye Law s s hall be consulted. A s a gen eral guide
some t ypical t ype des igns o f manholes f ollowed in D elhi have be en shown in F ig. 19 .4 t o 19.7. When
manholes are constructed on f oot path, t hese s hall be prov ided with cover of m edium dut y c asting a nd
when built within the width of t he r oad under vehicular traffic, t hese shall be provided with cover of heav y
duty casting.
19.4.1 Excavation
The excavation for manhole shall be true to dimensions and levels shown on the plans or as directed by
the Engineer-in-Charge.
Vol-2 , 2013
19.4.3 Brick Work
The brick w ork s hall be w ith c lass 75 br icks i n c ement m ortar 1: 4 (1 c ement: 4 c oarse s and). T he
external joints of the br ick masonry shall be finished smooth, and the joints of the pipes with the masonry
shall be made perfectly leak proof. For arched type and c ircular m anholes, brick m asonry i n arches and
arching over the pipes shall be i n cement mortar 1.3 (1 c ement: 3 f ine sand). In the case of manholes of
circular type the excess shaft shall be corbelled inwardly on three sides at the top to reduce its size to
the cover frame to be fitted.
The walls shall be built of one brick thickness for depths up to 4.25 m. Below a depth of 4.25 m in
ordinary subsoil the wall thickness shall be increased to one and half brick and at 9.75 m below ground two
brick thick walls shall be built.
For ea rth w ork e xcavation, bed c oncrete br ick w ork, plaster and poi nting, R .C.C. w ork and r efilling o f
earth, respective specifications shall be followed.
19.4.5 Benching
The c hannels a nd benching s hall b e d one i n c ement c oncrete 1:2:4 (1 c ement: 2 c oarse sand: 4
graded s tone a ggregate 20 m m n ominal s ize) an d r endered s mooth w ith ne at c ement. T he d epth of
channels and benching shall be as given in Table 19.5.
TABLE 19.5
Sizes of drain Top of channel at the centre Depth of benching at side walls
above bed concrete above bed concrete
mm cm cm
100 15 20
150 20 30
200 25 35
250 30 40
300 35 45
350 40 50
400 45 55
450 50 60
266 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
Foot rests which shall b e of 20 × 2 0 Sq. M.S. bars as shown in Fig. 1 9.8 shall be f ixed 40 c m ap art
vertically and staggered l aterally and shall pr oject 10 cm beyond the surface of the wall. The top foot rest
shall be 45 cm below the manhole cover.
Foot r ests s hall be p ainted w ith c oal t ar, the por tion embedded in the c ement c oncrete bl ock b eing
painted with thick cement slurry before fixing.
19.4.8 Measurements
Manholes s hall be en umerated unde r relevant i tems. T he dept h of t he m anhole s hall be reckoned
from the top level o f C.I. cover to the invert level of channel. The depth shall b e measured correct to a
cm. The extra depth shall be measured and paid as extra over the specified depth.
19.4.9 Rate
The rate shall include the cost of materials and labour involved in all the operations described above
but excludes t he c ost o f (i) excavation, (ii) M. S. foot rests and ( iii) 12 mm thick cement pl aster w ith w ater
proofing material appl ied at t he ex ternal surface o f t he manhole i f required. These i tems shall be pai d for
separately under relevant items of work.
Payment for extra depths of manholes shall be made separately under relevant items of work.
For 150 and 250 mm main line, if the difference in level between the water line (peak flow level) and
the invert level of the branch line is less than 60 cm, a drop connection may be provided with in the
manhole by gi ving suitable ramp. If the difference in level is more than 60 cm, the drop s hall be provided
externally.
The main lines up to 350 mm dia, are designed for half depth of flow, from 350 mm to 900 mm for 2/3
depth of flow and beyond 900 mm for 3/4 depth of flow.
19.5.1 Excavation
The excavation shall be done for the drop connection at the place where the branch line meets the
manhole. T he excavation shall b e carried u p to the bed concrete of the manhole and t o the full width o f
the branch line.
19.5.2 Laying
At t he end of branch sewer line S .C.I. cross shall be fixed to the line which shall be extended through
the w all of the m anhole by a hor izontal piece of S .C.I. pi pe to form a n inspection or c leaning e ye. The
open end shall be provided with chain and lid. T he S .C.I. drop pipe shall be c onnected to the cross at
the top and to the S.C.I. bend at the bottom. The bend shall be extended through the wall of the
manhole by a p iece o f C .I. pipe w hich s hall d ischarge into the c hannel. N ecessary c hannel s hall b e
made w ith c ement c oncrete 1: 2:4 (1 c ement: 2 c oarse s and: 4 g raded s tone aggre gate 20 m m no minal
size) a nd f inished smooth t o c onnect t he m ain c hannel. T he j oint b etween S.C.I. p ipe and f ittings shall
be lead caulked as described in 18.5.3. The j oint between S.C.I. cross and S.W. branch line shall be
made with cement mortar 1:1 (1 cement: 1 fine sand). The exposed portion of the drop connection shall
267 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
be encased al l-around w ith minimum 15 c m thick c oncrete 1: 5:10 ( 1 c ement: 5 fine s and: 10 g raded
stone aggregate 40 mm nominal size) and cured. For encasing the concrete around the drop
connection, the nec essary centering and shuttering s hall be provided. The hol es made in the w alls o f t he
manhole s hall be made good w ith b rick w ork in cement m ortar 1: 4 (1 c ement: 4 c oarse sand) a nd
plastered w ith c ement m ortar 1 :3 ( 1 c ement: 3 c oarse s and) on the inside of the m anhole w all. T he
excavated earth shall be back filled in the trench in level with the original ground level.
19.5.3 Measurements
Drop co nnection shall b e enumerated. T he de pths be yond 60 cm shall be m easured in running
metres correct to a cm under relevant items.
19.5.4 Rate
The rate shall include the cost of labour and materials involved in all the operations described above
but excluding the cost of excavations and refilling.
The size of the drain as specified shall be the width of the drain at the top, measured between the
masonry walls. The drain shall be given, as far as possible, uniform slope from the starting point to the
discharge point.
19.6.1 Measurements
The drains shall be measured in running metres, correct to a cm.
19.6.2 Rate
The rate sh all inc lude th e cost of la bour an d materials re quired for all the operations des cribed
above, suitable deduction or extra payment, per cm basis shall be made in case there is a variation in
average depths from those stated above.
Vol-2 , 2013
19.7.2 Road Gully Chamber with Vertical Grating (Fig. 19.14)
The chamber shall be of brick masonry 12 mm dia round bar shall be fixed in cement concrete block
at the bottom. The bars at the top shall be welded or riveted to M.S. flat 40 × 6 mm as shown in Fig.
19.14. The specifications shall be same as described in 19.7.1.
19.7.4 Measurements
Road gully chambers shall be enumerated.
19.7.5 Rate
The rate shall include the cost of materials and labour involved in all the operations described above
except the cost of excavation and connection pipes.
19.8.1 Measurements
Grease traps shall be enumerated.
19.8.2 Rate
The ra te shall i nclude t he c ost of l abour a nd m aterials required fo r a ll t he o perations d escribed
above.
Surface and s ub-soil w ater s hould b e ex cluded f rom f inding w ay i nto t he s eptic t ank. W aste w ater
may be passed into the septic tank provided the tank and the means for effluent disposal are designed to
cope up with this extra liquid. Depending on the location of the water table and the nature of the
strata, the type of disposal for the effluent from the septic tank shall be decided.
19.9.1 Dimensions
Septic tanks shall have minimum width of 75 cm, minimum depth of one metre below water level and a
minimum liquid capacity of the one cubic metre. Length of tanks shall be 2 to 4 times the width.
Suitable sizes of septic tanks for use of 5, 10, 15, 20 and 50 persons based on certain assumptions are
given in Appendix II.
Vol-2 , 2013
The ventilating pipe shall extend to a height which would cause no smell nuisance to any building in the
area. Generally the ventilating pipe may extend to a height of about 2 m , when the septic tank is at least
15 m away from the nearest building and to a height of 2 m. above the top of the building when it is located
closer than 15 metres. The ventilating pipe may also be connected to the normal soil ventilating system of
the building where so desired.
19.9.5 Testing
Before the t ank i s commissioned for us e, it s hall be tested for water-tightness by filling it with water an d
allowing it to stand f or 24 hours. I t s hall t hen be topped up, if necessary, and allowed to stand f or a further
period of 24 hours during which time the fall in the level of the water shall not be more than 1.5 cm.
19.9.8 Measurements
Septic tank shall be enumerated.
19.9.9 Rate
The rate shall include the cost of materials and labour involved in all the operation, except
SubSurface absorption system which shall be paid for separately.
19.10.3 Measurements
Soak pit shall be enumerated.
19.10.4 Rate
Rate shall include the cost of labour and material involved in all the operations described above.
Vol-2 , 2013
19.11 SOAK PIT 1.2 × 1.2 × 1.2 M
19.11.1 Construction
The earth excavation shall c onform to t he general s pecifications f or earth w ork. A fter t he ex cavation
is complete the soak pit shall be filled with brick bats. The brick bats shall be from properly burnt bricks.
10 cm w ide and 10 cm de ep b rick edgi ng w ith br icks o f class designation 75 s hall be pr ovided r ound the
soak pit.
19.11.2 Measurements
Soak pits shall be enumerated.
19.11.3 Rate
Rate shall include the cost of labour and materials involved in all the operations.
19.12.1 Construction
Dispersion trenches shall be 50 to 100 cm deep and 30 to 100 cm wide, excavated to a slight
gradient and shall be pr ovided w ith 15 t o 25 cm o f washed gr avel or c rushed stones. Open jointed pi pes
placed inside the trench shall be made of u nglazed earthenware clay or concrete and shall have
minimum i nternal di ameter of 75 t o 100 mm. E ach d ispersion t rench s hould not be l onger t han 30 m and
trenches should not be placed closer than 1.8 m.
The c overing f or t he pi pes on t he t op s hall be w ith c oarse aggregate of uniform s ize t o a dept h of
approximately 15 c m. T he aggr egate abov e t his l evel m ay be gr aded w ith aggr egate 12 t o 15 m m to
prevent i ngress of top soil w hile t he f ree f low of w ater is n o w ay retarded. T he trench m ay be covered
with about 30 cm of ordinary soil to form a mound and turned over. The finished top surface may be kept at
least 15 cm above ground level to prevent direct flooding of the trench during rains.
19.12.2 Measurements
The length of dispersion trench shall be measured in running metres nearest to a cm.
19.12.3 Rate
The rate shall include the cost of materials and labour involved in all the operations described above.
Desludging s hall pr eferably be carried out by hydrostatic h ead or by using a portable pump. Manual
handling of sludge shall be discouraged.
Vol-2 , 2013
AP P ENDIX — ‘I’
Note:
1. I f the mild steel is used for spiral reinforcement, the weight specified under col. 7 s hall be
increased by a factor 140/25.
2. S oft gra de m ild s teel w ire may be u sed a s reinforcement for c ollars of p ipes of n ominal internal
diameter up t o 250 m m only, by i ncreasing t he w eight by a f actor 140/84. Where onl y s oft grade
mild s teel w ire i s u sed f or m aking c ollar c ages, t he w eight of rei nforcement s hall be t otal w eight
or col. 6 and 7 multiplied by 140/84. This is allowed as a process requirement.
3. I nternal di ameter of collar t o s uit t he ac tual di ameter of pi pes with minimum c aulking s pace as
given in col. 2
Vol-2 , 2013
AP P ENDIX — ‘II’
RECOMMENDED SIZES OF SEPTIC TANKS
(Clause 19.9)
RECOMMENDED SIZES OF SEPTIC TANKS FOR 5-20 USERS
Notes :
1. The capacities are recommended on the assumption that discharges from only WC will be
treated in the septic tank.
2. A provision of 300 mm should be made for free board.
3. T he sizes of s eptic t anks a re b ased o n c ertain as sumptions, w hile c hoosing t he s ize of s eptic
tank exact calculation shall be made.
Notes :
1. A provision of 300 mm should be made for free board.
2. The sizes of the septic tank are based on certain assumptions while choosing the size of septic
tank, exact calculation shall be made.
3. F or po pulation over 100, the tank may be divided into independent parallel chambers for ease of
maintenance and cleaning.
Vol-2 , 2013
FLUSHING TANK
Water Inlet
G.L. C.I. Cover C.C. 1:2:4
G.L.
Vol-2 , 2013
GULLY TRAP
75
B 1 B rick
B
A A
300
1 B rick
PLAN 75
PLAN
A
D 92½ ° ± 2½° C.I. Cover 300 x 300
Typ e S ize A C d D D E F F G
Vol-2 , 2013
MANHOLE
C.I. cover
R.C.C. 1:2:4
150 150
150 150
12 cement plaster
50
200 C.C. 1:4:8
75 1200 75 75 900 75
1 Bk 1 Bk 1 Bk 1 Bk
SECTION AA SECTION BB
B C.I. Cover
75 150 R.C.C. 1:2:4
1 Bk 150
A 20 cover
A
1200
1 Bk 1 Bk
560
900
C C
c
1 Bk
75 560
a
75 75
1200
1 Bk 1 Bk
b
B
d
PLAN
Vol-2 , 2013
MANHOLE (Contd.)
C.I. Cover
R.C.C. 1:2:4
150 150
One b rick
wall
M.S. Foot
Rest.
Cement
Plaster
M.S. Foot
Rest.
C.C. 1:2:4
50
75
200 Cement Conc.
1: 4 : 8
75 1200 75 75 1 Bk 900 1 Bk 75
1 Bk 1 Bk
SECTION B-B
SECTION A-A
C.I. Cover R.C.C. 1:2:4
150
B
500
1 Bk 1200 1 Bk
A 75
1 Bk SECTION C-C
A A
900 C
C c
a
1 Bk b
d
75
75 1200 75
1 Bk 1 Bk
B
500
PLAN
PLAN
Vol-2 , 2013
MANHOLE (Contd.)
1 Brick Thick
C.C. 1:2:4
75 75
50
200 C.C. 1 : 4: 8 200
900 800
75 1 Bk 75
1 Bk SECTION A-A
SECTION B-B
B
610
75
1 Bk C.I. cover 610 x 455
A 455 A 150
800 900
1 Bk 1 Bk
SECTION C-C
1 Bk
75
75 1 Bk 1 Bk b
900
75
B
c
C C
PLAN
d a
b
Vol-2 , 2013
MANHOLE (Contd.)
Cement Pointing
300
M.S. foot
rest
Cement
Plaster
Wall
Wall
H Height of
springing
Channel and
Benching
C.C. 1:2:4 250 min.
50
200
W W W W
150 1400 150 900
150 150
SECTION AA
SECTION B-B
C.I. Cover
B
150
150 R.C.C. 1:2:4
W 1 Brick
900
1 Bk 1 Bk
A A SECTION CC
900
b
W a
150 C C
PLAN
500
PLAN
Vol-2 , 2013
MANHOLE (Contd.)
Sub Head : Drainage
Clause : 19.4
MUNICIPAL CORPORATION DELHI DESIGN
H2 T2
T2 T2 H2
d T2
150 150
dc
D
H3 T3
SECTION B B
T3 400 C.C.
C.I. foot rest
T4 T4
H4 B B
T5
T5
2/3 d+80 12 C ement
Plaster in C.M.
H5 1:4 1:4 1: 4
PLAN
150
PLAN
(1500 & 1800 ø)
Vol-2 , 2013
MANHOLE
(With Drop Connections)
G.L. G.L.
150
200
300 2050
300 300
Cleaning eye
More than 1 Bk
2450
A A 300
C.I. Pipe
1 /2 Bk
1
C.C. 1:5:10
SECTION A A SECTION B B
B
Bent up 40 mm min.
C.C. 1:5:10
M.S. Bar 20 x 20
200
A A
100
B 110
1400 DETAIL OF BENCHING
M.S. FOOT REST
PLAN
Vol-2 , 2013
BEDDING OF PIPES
Thoroughly Tampted
Bt Bt
BC
BC
05 BC Min 07 BC F
A C
BC 200
PBC D
GL BC GL BC
BC BC/4 min
BC/10 min. BC/10 min
X D/4 Min
B
D G
PBC
P. M ax 07 Thoroughly Tampted Earth
BC
3 BC/10 Min
BC/10 min Accurately shaped to fit pipe
D = Internal Diametre
Fig. Bedding Load Factor
BC = Horizontal B readth O utside of the P ipes i n metres
(i.e., external diametre in case of a circular pipe) A Ordinary 1.5
Bt = Horizontal Width of Trench immediately below the
top of the pipe in metres B –do– –
H = Height of fill above top of pipe in metres C First Class 1.9
x = Min 200 for ‘H’ < 5000 when ‘H’ > 5000, 10 for every
250 of ‘H’. D –do– –
E –do– –
F Concrete Craddle 2.25 to 3.4
G –do– –
Vol-2 , 2013
JOINTS OF CONCRETE PIPES
Int. Dia
C.M (1:2)
Barrel Thickness
Internal Dia
(EXTERNAL) (INTERNAL)
FLUSH JOINTS
Vol-2 , 2013
BEDDING/ENCASING STONEWARE PIPES
MWL
1
/4D
(i) CONCRETE T
BEDDING
X/2 Dø
MWL
X/2
X/2
(iii) CONCRETE W
ALLROUND
Vol-2 , 2013
BRICK MASONRY OPEN SURFACE DRAINS
200
C.C. 1:2:4
100
C.C. 1:5:10
75 75
200
C.C. 1:2:4
75 75
300
C.C. 1:2:4
75 75
Vol-2 , 2013
ROAD GULLY CHAMBER
SECTION AA
X – SECTION
75 450 75
1Bk 1 Bk 75
One Bk
75
A 150 A
500
150
75
One Bk
75
75 450 75
WITH HORIZONTAL GRATING 1bk 1bk
R.C.C. 1:2:4
Cement Plaster Horizontal 450
Gully Grating
75
175 100 C.C. 1:2:4
1 Bk 150
200
Wall A A
600
500
450
S.W.
Pipe 100
1 B k.
150 150
75 75
C.C. 1:5:10 450 200 450 1 B k 75 75
1 Bk
1100
1 Bk
1 Bk
PLAN
SECTION AA
Vol-2 , 2013
SEPTIC TANK
L
Y
X X
L/5
Brick wall
SECTIONAL PLAN ZZ
900
50ø min Y
Ventilating P ipe 40 t hick B affle Conc. or Conc. Roof of Precast
Stone Slab Conc. S labs
G.L. G.L.
Z 450 Z
30
20 to 70 600–750
0-4D max.
D
100ø pipe 75 ø pipe
Cast I ron S tep
12 Cement
Mortar Finish
C.C. 1:2:4 Baffle Conc. or Brick in
Cement Mortar
SECTION XX
Bucket
SECTION YY
Vol-2 , 2013
SEPTIC TANK (Contd.)
Vol-2 , 2013
SOAK PIT
Brick E dging
Brick Bats
Brick B allast 50 t o
80 normal size
Brick Ballast 40
Nominal S ize
450
1200
1800
2500
SECTION AB
A B
PLAN
Vol-2 , 2013
DISPERSION TRENCH
300 to 1000
300 Max.
Distribution
Chamber
900
1 Brick Wall
Baffle 1000
1800
Tight
Joint Open Joints
150 Max GL
300 to 1000
Vol-2 , 2013
20.0 : PILE WORK
Vol-2 , 2013
CONTENTS
Clause No. Brief Description Page No.
List of Bureau of Indian Standards (BIS) Codes 293
Vol-2 , 2013
LIST OF BUREAU OF INDIAN STANDARD CODES
Vol-2 , 2013
20.0 PILE WORK
20.0 TERMINOLOGY
Allowable Load: I t is l oad w hich i s a pplied t o a p ile af ter t aking i nto account its ul timate l oad c apacity,
pile s pacing, O verall be aring c apacity of t he g round, t he allowable s ettlement, ne gative s kin f riction
including reversal of loads.
Bearing Pile: A pi le formed i n t he gr ound for transmitting l oad o f a structure t o the soil b y t he resistance
developed at its tips and or along its surface. It is either vertical or batter pile. It may be ‘End bearing
pile’ or friction pile if it supports the load primarily along the surface.
Board Compaction Pile: It i s bored c ast-in-situ w ith or w ithout bul b. I n t his c ompaction of s urrounding
ground and f reshly f illed concrete i n pi le, bor e i s simultaneously ac hieved by s uitable method. A pi le
with a bulb is called a “ under-reamed b ored c ompaction pile”. Under-reamed pile with more than one
bulb is called Multi-under-reamed pile.
Constant Rate of Penetration (CRP) Test: The ul timate bear ing c apacity o f pr eliminary pi les and pi les
which are not used as working piles.
Constant Rate of Uplift (CRU) Test: The ultimate c apacity i n t ension of preliminary pi les and piles
which are not used as working piles.
Cut of Level: It is t he l evel where t he installed p ile is c ut of f t o support t he pile c aps or b eams.
Draft Bolt: A metal rod driven into hole bored in timber, the hole being smaller in diameter than the rod.
Drop of Stroke: The distance through which the driving weight is allowed to fall for driving the piles. Factor
of Safety: It is the ratio of the ultimate load capacity of a pile to the safe load of a pile.
Follower Tube: A t ube w hich i s u sed f ollowing t he m ain c asing t ube a nd i t r equires t o be extended
further. The i nner di ameter o f the follower t ube should be the same a s t he inner di ameter o f c asing. The
follower t ube s hall preferably b e a n o utside g uide a nd sh ould be w ater t ight when driven i n
waterbearing strata or soft clays.
Initial Test: This test is c arried ou t w ith a v iew to de termine ul timate lo ad c apacity and s afe l oad
capacity.
Raker or Batter Pile: The pi le w hich i s installed a t an angl e to t he v ertical. R aker pi les ar e nor mally
provided where vertical piles cannot resist the required applied horizontal forces. The maximum rake to be
permitted in piles shall not exceed -
1 in 8 for cast-in-situ piles of large diameter viz. 750 mm dia,. and above.
1 in 4 pre-cast piles.
Routine Test: It i s carried o ut with a v iew t o c heck whether pile is c apable of t aking the working l oad
assigned to it.
Safe Load: It is the load arrived at by applying a factor of safety to the ultimate load capacity of the pile.
Vol-2 , 2013
Set: The net di stance by which t he pi le penet rates in t he ground due t o s tated num ber of b lows of t he
hammer.
Spliced Pile: A pile composed of two or more lengths secured together, end to end to form one pile.
Test Pile: A p ile w hich i s s elected f or l oad t esting and which i s s ubsequently l oaded f or t hat p urpose.
This pile m ay form working pile itself if subjected to a rout ine load test with u p to on e an d half time the
safe load.
Total displacement (Gross): The total movement of the pile under a given load.
Total Elastic Displacement: This is the magnitude of the displacement of the pile due to rebound
caused at the top after removal of given test load. This comprises two components as follows:
(a) Elastic displacement of the soil participating in load transfer; and
(b) Elastic displacement of the pile shaft.
Trial Piles: These ar e i nstalled i nitially to as sess the load c arrying c apacity, i t i s either t ested to ul timate
bearing capacity or twice the estimated safe load.
Ultimate Load Capacity: The maximum load which a pile can carry before failure of ground (when the soil
fails by shear) or failure of pile materials.
20.1.2 Equipment
The equipment and accessories used for driven cast-in-situ piles shall depend on type of sub-soil
strata, ground water conditions, type of founding material and penetration etc.
Commonly used plants are as per Appendix ‘F’ and few more are given below:
Dolly: A c ushion of hard wood or s ome s uitable m aterial pl aced o n t he t op of t he c asing t o re ceive t he
blows of the hammer
Kent Ledge: Dead weight used for applying a test load to a pile.
Shoe: Pile Shoe should be of material as specified in the item. The pile shoes may be either cast iron or
mild steel. Cast i ron pi le shoes s hall be m ade f rom c hill hardened i ron as used f or m aking grey i ron
casting c onfirming to IS 210 . T he c hilled iron po int shall b e free from b low ho les and o ther s urface
defects. Cast steel piles shoe shall be of steel conforming to IS 2644. Straps or ot her fastenings to cast
pile shoes shall be of steel conforming to IS 1079 and shall be cast into the point to form an integral part of
shoe. Different types of pile shoes are shown in Fig. 20.1
Vol-2 , 2013
Square Pile Shoe Round Pile Shoe Pile Shoe with Wedge Shape
Drop Hammer (or Monkey): Hammer, ram or monkey raised by a winch and allowed to fall under
gravity.
Single or Double Acting Hammer: A ha mmer oper ated b y steam compressed ai r or i nternal
combustion, t he energy of i ts blows being derived m ainly f rom source of motive p ower a nd n ot f rom
gravity along.
Pile Frame (or Pile Rig): A movable steel structure f or d riving piles in the correct position and
alignment by means of a hammer operating in the guides or (leaders) of the frame.
(ii) In case of a single pile under a column, the positional deviation should not be more than 50 mm
or D /4 w hichever i s l ess ( 100 m m i n c ase of p iles having d iameter m ore t han 600 m m. G reater
tolerance may be prescribed for piles driven over water and for raking piles.
20.1.3.3 Sequence of Installation: Normal sequence of installation of pile group is from the centre to the
periphery of the group or from one side to the other. Particular care shall be taken t o avoid
damaging t he al ready c ast pi le w hile driving a f resh t ube nearby before t he c oncrete has s ufficiently
set. The possibility of the pile getting damaged is more in compact soils than in loose soils.
Vol-2 , 2013
(iii) In case of very soft soil it is advisable to start driving the bore hole from outside to inside so that
the soil gets restrained from flowing out during operation.
(ii) T hese pi les m ay be c ast i n metal s hells which may remain permanently in pl ace or t he c asing
may be withdrawn which may be termed as uncased driven cast-in-situ cement concrete piles.
(iii) T he m etal casing s hall be of sufficient t hickness and strength t o ho ld i n original f orm an d s how
no harmful distortion when the adjacent casing is driven and the driving core if any is withdrawn.
(iv) Driven c ast-in-situ concrete pi les s hall be i nstalled us ing a pr operly des igned det achable s hoe at
the bottom of the casing.
(v) Any liner or bore hole; which is temporarily located and shows partial collapse that would affect
the load carrying capacity of the pile, shall be rejected or repaired as directed by the Engineer-in-
Charge.
20.1.3.6 A proper record of pile driving and other details such as depth driven, sequence of installation in
a group, cut off level/working level shall b e mentioned in sequence of occurrence worksheet for the
inspection of Engineer-in-charge.
20.1.4 Jetting
(i) D riving of pile may be assisted by preboring holes or by the use of jets or both subject to the
approval of t he E ngineer-in-charge. These may be used essentially to achieve the minimum
penetration shown on the drawings where such penetration is not reached under normal
conditions of d riving. T he diameter of the hol e s hall; not be gr eater t han t he d iagonal di mension
of the pile less 100 mm.
(ii) The m aximum d epth of the p reboring s hall be such t hat t he s pecified s et (or less) i s o btained
when t he t oe of t he pi le is a t f ounding level. P reboring s hall be as approved by t he E ngineer-in-
charge and s hall not ex tend bey ond one m etre abov e t he f ounding l evel a nd t he pi le s hall be
driven t o at l east one metre bel ow the prebored hole. To e nsure t hat the pile i s pr operly
supported l aterally i n t he hol e, a ny space r emaining a round t he pi le at t he gr ound l evel after
driving is finished shall be backfilled with approved granular material.
(iii) W hen t he w ater j etting i s us ed at l east t wo j ets s hall be at tached t o t he pile s ymmetrically. T he
volume and pressure of w ater at t he outlet n ozzles shall b e s ufficient t o f reely e rode m aterial
adjacent to the toe of the pile. The maximum depth of jetting shall be such that the specified set
is obtained when the toe of the pile is at founding level. Jetting shall cease as directed by the
Engineer-in-Charge and shall not proceed beyond one metre above the founding level and the
pile shall be driven at least one metre below the prebored hole.
(iv) To avoid very hard driving and vibration in materials such as sand, jetting of piles by means of
water may be c arried out in such a m anner as not to impair the bearing capacity of piles already
in p lace, t he s tability of the s oil or the s afety of an y adjoining bu ildings. D etails of arra ngement
for jetting shall be got approved from the Engineer-in-Charge in advance.
Vol-2 , 2013
driving which s hall al ways be f inished by ord inary methods. J etting s hall be stopped if there i s
any t endency f or t he p ile t ips to b e d rawn t owards t he p ile a lready d riven ow ing t o the
disturbance to the ground.
20.1.5 Reinforcement
(i) T he des ign of reinforcing c age varies depending upon t he dri ving and i nstallation c onditions, t he
nature of the sub-soil an d the nature of load to be t ransmitted by the shaft, axial or otherwise.
The m inimum ar ea of longitudinal reinforcement of any type or gr ade w ithin the pi le shaft s hall
be 0. 4 per cent of t he sectional ar ea calculated on the bas is of t he out side area of the casings of
the shaft.
(iii) P iles shall al ways be r einforced w ith a minimum amount o f reinforcement as do wels keeping t he
minimum bond l ength i nto t he pi le s haft below i ts cut-off l evel, and w ith adequate projection i nto
the pile cap, irrespective of design requirements.
Note: In s ome c ases t he cage may l ift at bot tom o r a t t he l aps dur ing w ithdrawal o f casing. This
can be m inimized by m aking t he rei nforcement “U ” shaped at t he bot tom and up t o w ell
secured j oints. Also t he l ifting 5 perc ent of t he l ength s hould b e c onsidered not t o af fect
the quality of pile.
(iv) C lear c over t o all m ain r einforcement i n pi le s haft s hall be not l ess t han 5 0 m m and shall b e
maintained by s uitable s pacers. T he l aterals of reinforcing c age m ay be i n the f orm of links or
spirals. The d iameter and s pacing of the s ame is c hosen to im part adequa te rig idity of t he
reinforcing c age dur ing t he handi ng and i nstallation. T he m inimum diameter of l inks o r s pirals
shall be 6 m m and t he spacing of the links or spirals shall be not less than 150 m m. The
minimum c lear di stance b etween two adjacent m ain reinforcement should normally be 100 m m
for full depth of the cage.
(v) T he r einforcing c age should be l eft with adequat e pr otruding l ength abov e t he c ut of f l evel f or
proper e mbedment in t he pi le cap. P rior to t he l owering o f reinforcement cage into t he pi le s haft,
the shaft shall be cleaned of all loose materials.
(vi) R einforcement i n the form o f cage s hall be a ssembled w ith addi tional s upport, s uch as s preader
forks and l acings; n ecessary t o f orm a ri gid c age hoops, l inks, or hel ical rei nforcement has t o f it
closely aro und t he m ain l ongitudinal bars and shall be t ied b y bi nding w ire o f approv ed qu ality.
The ends of t he b inding wire s hall be t urned i nto t he i nterior of t he p ile. Reinforcement shall be
placed and m aintained in c orrect po sition. The reinforcements shall be joined w herever
necessary by welding and the procedure of welding be followed as described in IS 2751.
20.1.6 Concrete
20.1.6.1 Cement : Cement shall be as specified in agreement item or as specified under sub-head 3.0 of
Specifications. However, high alumina cement shall not be used.
20.1.6.2 Water: Water to be used for concreting shall be as specified under sub-head 3.0
Vol-2 , 2013
20.1.6.3 Fine Aggregate: Fine ag gregate t o be us ed f or c oncreting s hall be as s pecified under
subhead 3.0 of Specifications.
20.1.6.4 Coarse Aggregate: For tremie concreting, coarse aggregate having nominal size more than
20 m m s hould not be us ed. N atural rounded s hingle of appropriate s ize m ay al so be us ed as c oarse
aggregate. It helps to give high slump with less water cement ratio.
20.1.6.5 Chemical Admixtures: Admixtures to be used in the concrete shall be as per IS 9103.
(ii) Only concrete Grade M-25 and/or higher grades shall be used for concreting the piles. The exact
grade of concrete to be used shall mainly depend upon the nature of work and the general
design consideration. However, Concrete Grade M-15 and Grade M-20 shall not be used for
concreting piles under any circumstances, even with weigh batching. The minimum cement
content shall be 400 kg/m3 in all conditions.
(iii) When concreting under water or drilling mud 10 per cent additional cement over the minimum
cement content for the particular grade shall be used subject to a minimum cement content of
370 kg/cum.
20.1.6.7 Workability of Concrete: The minimum slump shall be 100 mm when the concrete for the
piles i s being v ibrated and w hen t he c oncrete i s not v ibrated the maximum permitted s lump i s 150 m m.
The degree of workability in both the cases is considered as very high.
(ii) Wherever practicable concrete should be placed in a clean dry hole where concrete is placed in
dry hol e an d when casing i s pr esent, the top 3 m pile shall be compacted using internal
vibrators. T he c oncrete s hould i nvariably b e p oured t hrough a t remie, with a funnel s o that t he
flow i s directed and c oncrete c an be depos ited i n the hol e w ithout s egregation. C are s hall be
taken during concreting t o p revent as f ar as p ossible t he segregation of t he i ngredients. T he
displacement or di stortion of rei nforcement during concreting and al so w hile ex tracting t he t ube
shall be avoided.
(iii) Where the casing is withdrawn from cohesive soils for the formation of cast-in-situ pile, the
concreting s hould be d one with necessary precautions to minimize t he softening of the s oil b y
excess w ater. W here m ud fl ow c onditions e xist, the c asing o f ca st-in-situ pil es s hall no t be
allowed to be withdrawn.
(iv) The concrete shall be self compacting and shall not get mixed with soil, excess water, or other
extraneous matter. Special c are s hall be taken in silt clays and ot her s oils w ith t endency to
squeeze into newly deposited concrete and cause necking. Sufficient head of green concrete
shall be m aintained t o prevent inflow of s oil or wager i nto c oncrete. T he placing of concrete s hall
be continuous process from the toe level to the top of pile to prevent segregation, a tube of
299 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
tremie pi pe as s appr opriate s hall be us ed to pl ace c oncrete i n al l pi les. To en sure compaction by
hydraulic static heads, rate of placing concrete in the pile shaft shall not be less than 6 m (length of
pile) per hour.
(v) The diameter of the finished pile shall not be less than specified and a continuous record shall
be kept by the Engineer as to the volume of concrete placed in relation to the length of pile cast.
After eac h pi le has been cast and any em pty pi le hole r emaining s hall be p rotected and ba ck
filled as soon as possible with approved material.
(vi) The minimum embedment of cast-in-situ concrete piles into pile cap shall be 150 mm. Any
defective concrete at the head of the completed pile shall be cut away and made good with new
concrete. T he clear cover bet ween t he bot tom reinforcement i n pi le cap from top o f pi le s hall not
be less than 30 mm. The reinforcement in the pile shall be exposed for full anchorage length to
permit it t o be adequat ely bonded i nto t he pi le c ap. E xposing s uch l ength s hall be don e carefully
to avoid damaging the rest of t he pile. In cases where the pile cap is t o be lai d on ground a
leveling course with cement concrete of Grade M-15 and of 100 mm thickness shall be provided.
(viii) In case of withdrawal of tremie out of concrete, either accidentally or to removed a choke in the
tremie, t he t remie m ay be re-introduced t o p revent i mpregnation of l aitance s cum l ying on t he
top of the c oncrete already deposited in the bore. T he tremie shall be gently lowered on to the
old c oncrete w ith v ery l ittle penet ration i nitially. A v ermiculite pl ug s hould b e i ntroduced i n t he
tremie. F resh c oncrete of s lump bet ween 150 m m and 175 m m should b e f illed i n t he t remie
which will push t he plug f orward and swill emerges out of t he t remie displacing t he
laitance/scum. The tremie will be pushed further in steps masking fresh concrete sweep away
laitance scum in its way. When the tremie is buried by about 60 to 100 cms, concreting may be
resumed.
(ix) The top of concrete in a pile shall be brought above the cut-off level to permit removal of all
laitance and w eak concrete bef ore c apping and t o ensure g ood concrete at the c ut-off l evel f or
proper embedment into the pile cap.
(x) Where cut-off level is less than 1.5 metres below the working level concrete shall be cast to a
minimum o f 300 mm abov e cut-off level. F or eac h addi tional 0. 3 m increase in cut-off l evel below
the w orking level additional c overage of 50 mm m inimum s hall be al lowed. Higher allowance
may be nec essary depend ing on the length o f the p ile. W hen c oncrete is p laced by t remie
method c oncrete shall be c ast to the pi ling pl atform level t o per mit ov erflow o f concrete for v isual
inspection or to a minimum of one metre above cut off level. In the circumstances where cut-off
level is bel ow ground w ater l evel t he n eed t o m aintain pr essure on t he uns et c oncrete eq ual t o or
greater t han w ater pressure s hould be obs erved an d ac cordingly l ength of ex tra c oncrete ab ove
cut-off level shall be determined.
Vol-2 , 2013
should be maintained at 1. 5 m above t he gr ound w ater l evel. C oncreting und er w ater for cast-in-
situ concrete piles may be done either with the use of tremie method or by the use of approved
method specialty designed to permit under water placement of concrete. General requirements
and precautions for concreting under water are as follows:
(a) The concreting of pile must be completed in one continuous operation. Also for bored holes,
the finishing of the bore, cleaning of the bore, lowering of reinforcement cage and concreting
of pile for full length must be accomplished in one continuous operation without any
stoppage.
(b) T he c oncrete s hould be c oherent, ri ch in c ement w ith high slump & re stricted water c ement
ratio.
(c) The tremie pipe will have to be large enough with due regard to the size of the aggregate.
For 30 mm aggregate the tremie pipe should be of diameter not less than 150 mm and for
larger aggregate, larger diameter of tremie pipe may be necessary.
(d) The f irst c harge o f concrete should be pl aced w ith a sli ding pl ug p ushed d own the t ube
ahead of it to prevent mixing of water and concrete.
(e) T he t remie pipe s hould a lways p enetrate well i nto t he concrete with a n adequate margin of
safety against accidental withdrawal if the pipe is surged to discharge the concrete.
(f) The pi le should be c oncentrated wholly b y t remie and t he method o f d eposition s hould not be
changed part way up the pile to prevent the laitance from being entrapped within the pile.
When concreting i s c arried o ut u nder water a t emporary casing should be i nstalled t o t he f ull
depth of the b ore hole or 2 m i nto non c ollapsible s tratum, s o t hat f ragments of ground c annot
drop from the sides of the hole into the concrete as it is placed. The temporary casing may not be
required except near the top when concreting under drilling mud.
20.1.7.1 The concrete for the piles shall be sampled in accordance with the norms specified in IS 456.
The frequency of sampling is given in Table 20.1.
TABLE 20.1
Notes: (i) At least one sample shall be taken from each shift.
(ii) Where concrete is produced as continuous production unit, such as ready mix concrete
plant. The frequency of sampling may be agreed upon mutually by suppliers and
purchasers.
301 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
20.1.7.2 Test Specimen: Three t est s pecimens s hall be m ade f or each s ample f or t esting at 28 da ys.
Additional samples may be required for various purposes such as to determine the strength of concrete at
7 days or t o d etermine the duration of curing, or check the testing error, additional sample may also b e
required for testing samples cured by accelerated methods as described in IS 9103. The specimen shall
be tested as described in IS 516.
20.1.7.3 Test Results of Samples: The test results of the samples shall be the average of the strength of
three specimens. The individual variation should not be more than ±15% percent of the average
strength. If the variation is more, the test result of the sample is invalid.
20.1.8 Curing
As pe r IS 456 - 2000, e xposed s urfaces of c oncrete s hall be k ept c ontinuously i n a d amp or w et
condition by ponding or by covering w ith a layer o f sacking, c anvas, H essian or s imilar m aterials an d
kept constantly wet for at least 10 days from the date of placing concrete. The period of curing shall not be
less than 14 days for concrete exposed to dry and hot weather conditions.
(ii) Any deviation from the designed location alignment or load capacity of any pile shall be noted
and adequate measures taken well before concreting of the pile cap and plinth beam, if the
deviations are beyond permissible limit.
(iii) D uring chipping o f the pile, top manual c hipping may be per mitted a fter three da ys o f p ile c asting
pneumatic tools for chipping shall not be used before seven days after pile casting.
(iv) After concreting the actual quantity of concrete shall be compared with average obtained from
observations actually made in the case of a few piles initially cast. If the actual quantity is found
to be considerably less, special investigations shall be conducted and appropriate measures
taken.
20.1.11 Measurement
Dimension shall be measured near est to a cm. Me asurement o f length on completion shall be al ong
the axis of pile and s hall be m easured from top of shoe to the bottom of pile cap. No allowance shall be
made f or bul king, s hrinkage, c ut off t olerance, wastage and hiring o f tools and equi pment for e xcavating
driving etc.
20.1.12 Rate
The r ate i ncludes t he c ost of m aterials and l abour i nvolved i n al l t he oper ations des cribed abov e
including pile embedded in pile cap, except soil investigation, reinforcement, pile cap and grade beam.
302 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
20.2 BORED CAST-IN-SITU REINFORCED CONCRETE PILES
20.2.1 General
The piles are formed within the gr ound by excavating or boring a pi le within i t with or without the use
of t emporary c asing a nd subsequently f illing i t w ith pl ain or rei nforced c oncrete. W hen the c asing i s l eft
permanently it is termed as cased pile and when the casing is taken out it is termed as uncased pile.
20.2.2 Equipment
The equipment and accessories used for bored cast-in-situ piles shall depend on subsoil strata,
ground water conditions, type of founding material and penetration etc.
General requirements of boring equipment are as per A ppendix ‘ D’. T he equipment i s appl icable f or
bored piles without the use of bentonite.
20.2.2.1 Boring operation s hall be don e by rotary per cussion type drilling rigs u sing direct m ud
circulation or re verse m ud c irculation methods t o b ail out t he c uttings or as specified. I n soft clays an d
loose s and, b ailer a nd c hisel m ethod s hould be u sed w ith c aution to av oid t he ef fect of s uction. R ope
operated grabbing tool Kelly mounted hydraulically o perated grab are also used. T his method o f
advancing t he h ole avoids s uction. T he size of c utting t ool shall be as per [IS 29 11 (Part I S ection 2)]
and not less than the diameter of pile by more than 75 mm.
20.2.2.2 Use of drilling m ud i s s tabilizing s ides of bore hol e w here s pecified s hall hav e pr operties as
defined in Appendix A.
Permanent casing where specified shall be used to avoid aggressive action of water.
(ii) The ground shall be roughly leveled and position of pile marked. The boring shall be done with
or without the use of temporary casing. The sides of bore hole; shall be s tabilized with the aid of
temporary casing or with the aid of drilling mud of suitable consistency.
(iii) T he e quipment and accessories shall d epend u pon t he t ype of b ored pile chosen f or t he j ob,
consideration o f s ub-soil s trata, gr ound w ater c ondition, t ype o f f ounding m aterial. B oring
operation nor mally ar e do ne b y r otary or per cussion t ype dr illing rigs us ing d irect mud c irculation
on reverse mud tool shall be as detailed in IS 2911 (Part 1/Sec.2).
(iv) I n c ase pe rmanent/temporary c asing i s not us ed t hen bor ed pi le i s s tablised w ith dr illing f luid.
Bentonite s upplied to site s hall conform to IS 12584 . A c ertificate shall be obt ained b y t he
contractor from the manufacturer showing properties of each consignment and should be
submitted t o t he Engineer-in-charge. B entonite s hall be m ixed t horoughly w ith f resh c lean water
to make a suspension which will maintain the stability of the pile excavation for the period
necessary t o place concrete and complete c onstruction. The t emperature of t he water us ed i n
mixing t he be ntonite s uspension and w hen s upplied t o bor e hole s hall not be l ower t han 5 ºC.
Consistency of t he dr illing fluid s uspension and when c ontrolled t hroughout the bor ing as w ell as
in concreting operations in order to keep the hole stabilized as well as to avoid concrete getting
mixed up with thick suspension of mud.
303 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
Frequency and methods of testing drilling fluid shall be as specified and the test results shall be as
specified in IS 2720 (Part V).
(v) Bored cast-in-situ piles in soils which are stable may often be installed with a small casing length
at the top. A minimum of 2.0 m length of top of bore shall; invariably be provided with casing to
ensure against loose soil falling in to drilling mud, or a suitable steel casing. The casing may be left
in place permanently especially in cases where the aggressive action of the ground water is to be
avoided, or in the cases of piles built in water or in cases where significant length of piles could be
exposed due to scour.
(vi) For bored cast-in-situ piles, casing/liner shall be driven open ended with a pile driving hammer
capable of achieving penetration of the liner to the length shown on the drawing or as directed by the
Engineer-in-charge. Materials inside the casing shall be removed progressively by air lift, grap or
percussion equipment or other approved means.
(vii) Where bored cast-in-situ piles are used in soils liable to inflow, the bottom of the casing shall be
kept low enough i n advance of the boring tool; to prevent the entry of soil into the casing, thus
presenting t he f ormation of s ettlements i n t he adj oining gr ound. T he w ater l evel i n t he c asing
should gen erally be m aintained a t the na tural gr ound w ater level for the s ame r easons. T he
joints of t he c asing s hall be m ade as t ight a s pos sible t o m inimize i nflow of water or l eakage of
slurry during concreting.
(viii) Boring shall be carried out using rotary or percussion type equipment. Unless otherwise directed
by t he Engineer-in-charge th e d iameter of t he bore h oles s hall b e n ot more t han th e i nside
diameter of the liner.
(ix) After the boring has reached the required depth, the steel reinforcement shall be lowered in
position maintaining the specified size of cover on all sides. The bore shall then be flushed with
bentonite slurry and concreting shall be taken up exactly as described under clause 20.1.6.8.
20.2.3.4 A proper record of p ile driving and other details such as sequence of installation of piles,
dimension of piles, d epth bor ed, tim e ta ken for concreting et c. s hall be maintained i n se quence of
occurrence at site as per clause 20.1.3.6.
While d rilling m ud is u sed, t he specific g ravity of fresh s upply and c ontaminated mud i n t he hole
before concreting is taken up shall be recorded for first ten piles and subsequently at interval of 10 piles or
as specified.
20.2.4 Reinforcement
As specified under clause 20.1.5.
20.2.5 Concrete
As specified under clause 20.1.6.
20.2.7 Measurement
Dimensions shall be measured nearest to a cm. Measurement of length on completion shall be
along the axis of pile and shall be measured up to the bottom of pile cap. No allowance shall be made
for bul king, shrinkage, c ut of f t olerance, w astage a nd hi ring of tools, equipment f or e xcavating, dri ving
etc.
304 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
20.2.8 Rate
The rate i ncludes t he cost of m aterial and l abour i nvolved i n a ll t he operations described above
including pile embedded in pile cap except reinforcement, pile cap and grade beam.
(ii) T hese p iles f ind application i n widely v arying s ituations i n d ifferent types o f soils w here
foundation ar e r equired t o be t aken dow n t o a c ertain dept h i n v iew of c onsiderations l ike t he
following requirements :
(a) To avoid the undesirable effect of seasonal moisture changes as in expansive soils.
(b) To reach firm strata.
(c) To obtain adequate capacity for downward, upward and lateral loads and moments
(d) To take foundations below scour level.
(iv) When the ground consists of expansive soil e. g. black cotton soil, the bulb of the under r eam pile
provides anchorage against uplift due to swelling pressure apart from the increased bearing
capacity.
(v) I n c ase o f f illed up or otherwise w eak s trata ov erlying t he f irm s trata, enl arged bas e in t he f orm
of u nder-reamed bulb i n firm s trata p rovides l arger bearing area and piles of greater bearing
capacity can be made.
(vi) I n lo ose t o m edium pervious s andy silty str ata, b ored co mpaction pi les ca n be used a s th e
process of compaction increases the loads bearing capacity of the piles.
(iii) I n non-expansive soils, when the cap of the pile group is cast directly on a reasonably firm
stratum it may additionally contribute towards the bearing capacity of the group.
(iv) I n l oad bea ring w alls pi les s hould g enerally b e provided unde r al l w all junctions t o av oid poi nt
loads on bea ms. Position of i ntermediate p iles i s t hen dec ided by k eeping door openi ngs f all i n
between two piles as far as possible.
Vol-2 , 2013
(ii) A typical list of equipment for manual construction is given in Appendix B.
(iii) Bore holes may be may be made by earth augers. In case of manual boring, an auger boring
guide shall be used to keep bores vertical or to desired inclination and in position. After the bore
is made to the req uired depth, en larging of the ba se shall be carried out by means of an under-
reaming tool.
(iv) In ground with higher water table having unstable pile bores, boring and under-reaming may be
carried out using suitable drilling mud. General g uidelines f or ben tonite drilling m ud are gi ven i n
Appendix ‘ A’. In no rmally m et s oil strata, dri lling m ud can be p oured from t op w hile boring an d
under-reaming can be done by normal spiral earth auger and under-reamer.
(v) The level of drilling mud should always be about one meter above water table or the level at
which c aving-in oc curs. I n c ase of very unstable strata w ith ex cessive c aving-in c ontinuous
circulation of dri lling m ud using suitable pu mping equipment and t ripod, et c along with m odified
auger and under-reamer may be used.
(vi) Some times permeable strata overlying a rim clayey stratum may be cased and normal boring
and under-reaming operation may be carried out in clayey stratum.
(vii) To avoid irregular shape and widening of bore hole in very loose strata at top a casing pipe of
suitable length may be used temporarily during boring and concreting.
(viii) For improved control over the inclination of batter/raker piles a tripod hoist with fixed pulley
should be used for lowering in of under-reaming tools.
(ix) For placing concrete in bore holes full of drilling mud or sub-soil water tremie pipe of not less
than 150 mm diameter with flap valve at the bottom should be used.
(x) For batter/raked under-reamed piles the reinforcement cage should be placed guiding it by a
chute or any other suitable method. If concreting is not done by tremie, it should be done by
chute.
(xi) In under-reamed compaction piles, suitable device should be used for guiding the movement of
drop weight and specified core as sembly for its v ertical d riving for oper ating the d rop w eight an d
specified core assembly for its vertical driving for operating the drop weights of adequate
capacity, suitable winch with hoisting attachment should be used.
(ii) In c onstruction with e quipment suggested under Appendix ‘B’ initially boring gu ide is f ixed with
its lower f rame l eveled f or m aking desired angu lar adjustment f or p iles at ba tter/rake. Boring i s
done up to required depth and under-reaming is completed.
(iii) I n order to achieve proper under-reamed bul b, the depth of bore hole should be c hecked before
starting under r eaming. I t s hould al so be c hecked dur ing under -reaming and an y ex tra s oil at the
bottom of bore hole; removed by auger before reinserting the under-reaming tool.
Vol-2 , 2013
(v) I n do uble or m ulti under-reamed piles, boring is fist completed to t he depth t o t he fi rst ( top)
under-ream only and after completing the under-reaming boring is extended further for the
second under-ream and the process is repeated.
(ii) A s a guide for v ertical piles a dev iation o f 1.5 per c ent and for raker p iles a dev iation o f four
percent shall not normally be exceeded. In special cases, a closer tolerance may be necessary.
(iii) P iles s hall not dev iate more t han 75 mm o r one quarter t he s tem di ameter, whichever i s l ess (75
mm o r D/10 whichever is m ore i n c ase of piles having di ameter m ore than 600 m m) f rom the
designed position at the working level.
(iv) In case of single pile under a c olumn the positional deviation should not be more than 50 mm or
one quar ter of t he s tem di ameter w hichever i s l ess ( 100 m m i n c ase of pi les hav ing di ameter
more than 600 mm).
(v) F or pi les w here c ut-off i s at s ubstantial dept hs, t he des ign should prov ide f or w orst c ombination
of the above tolerances in position and inclination.
(vi) I n c ase of piles d eviating b eyond t hese l imits c orrective m easures w here necessary m ay be
taken i n t he form o f i ncreasing pi le s ize, p rovision o f ex tras r einforcement i n t he pi le, redesign o f
pile cap and pile ties. If the resulting eccentricity cannot be taken care of by the above
measures, the piles should be replaced or supplemented by; one more additional piles.
(ii) The minimum area of longitudinal reinforcement (any type or grade) within the pile shaft should
be 0.4 per cent of the sectional area calculated on the basis of outside area of shaft or casing if
used.
(iii) Reinforcement is to be provided in the full length irrespective of any other considerations and is
further subject to condition that a minimum number of three 10 mm dia mild steel or three 8 mm dia
high strength steel bars shall be prov ided. The transverse reinforcement as circular stirrups shall
not be l ess than 6 m m dia. Mild steel bars at a s pacing of not more than the stem diameter or 30
cm, whichever is less.
(iv) For under reamed compaction piles, a minimum number of four 12 mm diameter mild steel or
four 10 mm diameter high strength steel bars shall be provided.
(v) For piles of lengths exceeding 5 m and or 37.5 cm diameter, a minimum number of six 12 mm
diameter HSD bars shall be provided.
(vi) For piles exceeding 40 cm diameter a minimum number of six 12 mm diameter high strength
steel bars shall be provided.
307 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
(vii) The circular stirrups for piles of length exceeding 5 m and diameter exceeding 37.5 cm shall be
bars of 8 mm diameter.
(viii) For pi les subject t o upl ift l oads, adequat e r einforcement s hall be provided to t ake full up lift w hich
shall not be curtailed at any stage.
(ix) F or piles up to 30 c m diameter, if c oncreting is done by t remie, equi valent amount of steel placed
centrally, may be provided at sides.
(x) The minimum clear cover over longitudinal reinforcement shall be 50 mm. In aggressive
environment of sulphates etc. it may be increased to 75 mm.
20.3.6 Concrete
20.3.6.1 Materials : Cement, water, f ine aggregate, c oarse aggregate and chemical admixtures etc. as
described under clause 20.1.6.
(ii) Concreting shall be done as soon as possible after completing the pile bore. The bore hole full of
drilling mud s hould not be l eft un -concreted f or m ore t han 12 t o 24 hours dependi ng upon t he
stability of the bore hole.
(iii) For placing concrete in pile bores, a funnel should be used and method of concreting should be
such the e ntire v olume of the p ile before is filled u p w ithout formation of v oids a nd/or m ixing of
soil and drilling fluid in concrete.
(iv) In empty bore holes for under-reamed piles a small quantity of concrete is poured to give about
100 mm layer of concrete at bottom. Reinforcement is lowered next and positioned correctly.
Then concrete is poured to fill the bore hole. Care should be taken that soil is not scrapped from
side if rodding is done for compaction. Vibrators shall not be used.
(v) If water is confined up to the bucket length portion at the toe & seepage is low, the water should
be bailed out and concreting should be done as prescribed in Para (iv) above.
(vi) In case the pile bore is stabilized with drilling mud or by maintaining water head within the bore
hole, the bo ttom of bore hole shall be carefully cleaned b y flushing it with fresh drilling mud and
pile bore will be checked for its depth immediately before concreting.
(vii) Concreting shall be done by tremie method. The tremie should have a valve at bottom and
lowered w ith valve c losed at the s tart a nd filled up w ith c oncrete. The v alve is then opened s o
permit the flow of concrete which permits upward displacement of drilling mud.
(viii) The pouring should be continuous and tremie is gradually lifted up such that the tremie pipe
opening remains always i n t he c oncrete. A t t he f inal stage t he quan tity of c oncrete i n t remie
should be enough so that on final withdrawal some concrete spills over the ground.
Vol-2 , 2013
Note: (1) The concrete should be coherent, rich in cement (not less than 350 kg/m 3) and slump
not less than 150 mm.
(2) The tremie pipe should always penetrate well into the concrete with an adequate
margin of safety against accidental withdrawal if the pipe is surged to discharge the
concrete.
(ix) In inclined piles, concreting should be done through a chute or by tremie method.
(x) For under-reamed bored compaction piles, the pile bore is first filled up without placing any
reinforcement. Concreting is done as prescribed in paras (iv) depending upon the situation. Soon
after the specified core assembly shall be driven and extra concrete shall be poured in
simultaneously to keep the concrete up to ground level. If hollow driving pipe is used in core
assembly the pipe shall be withdrawn after filling it with fresh concrete which will be left behind.
(ii) F or under -reamed c ompaction pi les the a mount o f concrete us ed is about 1. 2 t imes o f the under -
reamed cast-in-situ piles.
Note: If the estimates of concrete consumption are on the volume of the bore holes and not on
the basis of concrete quantity actually consumed, the concrete used may be found lesser
than estimated and cement consumption may work out to be less.
(ii) The pile caps may be designed by assuming that the load from column or pedestal is dispersed
at 45º from the top of the cap up to the mid depth of the pile cap from the based of the column or
pedestal. The reaction from piles may also to be taken to be distributed at 45º from the edge of
the pile, up to the mid depth of the pile cap on this basis, the maximum bending moment and
shear forces should be worked out at critical sections.
(iii) Full dimension of the cap shall be taken as width to analyse the section for bending and shear in
respective direction. Method of analysis and allowable stresses may be according to IS 456.
(iv) T he clear overhang o f the pile cap be yond the outermost pile in the grou p shall normally be 10 0
to 150 mm depending upon the size of the pile.
309 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
(v) The cap is generally cast over a 75 mm thick leveling course of concrete. The clear cover for the
main reinforcement of cap slab shall be not less than 75 mm.
(vi) The pile should project 50 mm into the cap concrete. The design of grade beams if used shall be
as given in IS 2911 (Part III).
X = Core
Y = Casing Casing & Core bot h
withdrawn and concrete
laid for pile
X
X Concrete
Concrete Pedastal
Y Surface
Y Y
X
Y
Pedastal Pile in
Complete Shape
Concrete
Spacer
Loops
6"
3"
3" B ed of weak 3'-9" S pan
concrete to provide Say 4' -3" to allow f or 15" x 15" Pile
working base possible spread of piles
7' 6"
2'-0" Radius
Butt Weld
Vol-2 , 2013
20.3.8 Grade Beams
(i) The grade beams supporting the walls; shall be designed taking due account of arching effect
due masonry above beam. The beam with masonry due to composite action behaves as a deep
beam.
(ii) The minimum overall depth of grade beams shall be 150 mm. The reinforcement at bottom
should be kept continuous in all the beams and an equal amount may be provided at top to a
distance of quart span both ways from the pile centre.
(iii) The l ongitudinal reinforcement both at bottom an d top should not be less than three bars of 10 m
diameter mild steel (or equivalent deformed steel).
(iv) Stirrups of 6 mm diameter bars should be at 300 mm spacing which should be reduced to 100 m
at the door openings near the wall edge to a distance of three times he depth of beam. No shear
connectors are necessary in wall.
(v) In expansive soil the grade beam shall be kept a minimum of 80 mm clear off the ground. In
other soils, the beams may rest on ground over a leveling concrete course of about 80 mm as
shown. In this case part load may be considered to be borne by ground and it may be accounted
for; in the design of piles. However, the beams should be designed as usual.
(vi) In case of exterior beams over piles in expansive soils a ledge projection of 75 mm thickness an
extending 80 mm into ground as shown shall be provided on outer side beam. Typical sections
of internal and external beams are shown below.
6 mm φ stirrups
at 300 c/c Concrete s lab
150 mm
or back on
mm
150
Outer edge
Side
200 mm
200 m
mm mm
G.L.
80 80
G.L.
20.4.2 Reinforcement
(i) The longitudinal reinforcement of specified grade and size shall be provided in the pre-cast
concrete piles, for the entire length. All the longitudinal bars shall be of same length and should
fit tightly in the pile shoe if the same is provided.
311 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
(ii) Extra bars for supporting the longitudinal steel shall be provided, to resist the local bending
moments but the s ame s hould be de tailed i n the draw ings p rominently s o tha t the s udden
discontinuity c an be av oided. T he non prov ision of t he ex tra bars m ay l ead t o c racks i n t he pi le
during heavy driving.
(iii) As per IS 2911 (Part1/Sec.3) the area of main longitudinal reinforcement shall not be less than
the percentages of cross sectional area of the piles as detailed below:
(a) Piles with a length 30 times the least dimension: 1.25 per cent
(b) Piles with a length 20 to 40 times the least dimension: 1.5 per cent
(c) Piles with a length more than 40 times the least dimension: 2 per cent
(iv) The lateral reinforcements, which are normally in the form of hooks and links of not less than 6
mm diameter TMT bars, has its own particular importance in resisting the driving stresses
induced in the pile. The volume of lateral reinforcement shall not be less than the following:
(a) At b oth e nds of the p ile for a distance o f 3 t imes the least width - not less than 0.6 p er cent
of the gross volume of pile.
(b) At central portions of the pile - not less than 0.2 per cent of the gross volume of pile.
(v) The spacing of the lateral ties in a pile shall be so arranged that the concrete should have free
flow a round t he reinforcements. The gr adual t ransition o f close s pacing o f lateral reinforcements
near the ends to the increased spacing in the central portions of the piles should be
accommodated by gr adually i ncreasing t he s pacing of t he t ies i n a length of 3 t imes t he l east
width of the pile.
(vi) The cover to reinforcement should be provided to longitudinal bars. In normal conditions the
cover thickness to be pr ovided is 50 mm and i n c ase the piles are ex posed to sea water or water
having other corrosive contents the minimum thickness of cover shall be 75 mm.
Note: Where the concrete of pile is liable to attack of sulphates, chlorides present in ground
water a minimum cover thickness of 75 mm shall be provided. In addition, the piles may
be coated with some suitable material.
(vii) Each longitudinal bar shall be in one length as far as possible, also preferably the full length bar
shall be used. However, in unavoidable cases if the bars are to be joined, they shall be done by
butt welding duly staggering the joints.
(viii) The hoops o r l inks that are t o be t ied t o l ongitudinal reinforcement shall be tied w ith t he specified
type of binding wire and the free ends of the wire shall be turned into the interior of the pile.
(ix) P referably the hoop or link reinforcement shall be welded to the longitudinal bars so as to
achieve a tight fitting.
(xi) Before concreting, the reinforcements shall be checked by Engineer-in-charge who shall ensure
that the reinforcements are tied as per approved design and drawing and shall ascertain that the
tying is perfect.
312 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
20.4.3 Equipment and Ancillaries
(i) The selection of equipment mostly depends upon the hardness of the strata. For deriving the
size and weight of the pile to be handled, the most important point is the location of work.
(ii) Generally, the following equipments are necessary for the installation of piles:
(a) Mo vable s teel or timber structure dul y designed t o handl e t he pi tching and driving t he pi les to
the correct position and alignment.
(c) To prevent the head of the pile from being damaged during drilling operation and to distribute
the blow over the cross section of the head of the pile. A temporary steel driving cap,
normally termed as ‘Drive cap’ is placed on the top of the pile.
(d) A pad, block or packing of hard wood or some suitable resilient material normally termed as
“Dolly” is fixed to the upper portion of he cap (helmet) for preventing the shock from hammer
on the head of the pile.
(e) A single acting” or “double acting” hammer is used depending on whether the hammer is
allowed to fall under gravity along or is operated with the source of motive power to derive
the energy.
(f) Sometimes it so happens that he piles are to be driven below the pile frame leaders, with the
result the hammer may not be in a position to reach the pile. Under such circumstances a
removable extension piece known as “follower” or “long dolly” is used to transmit the hammer
blows over the pile head.
(g) W hen a par ticular t ype of soil strata is m et w ith, t he driving conditions m ay r equire
equipments for jetting/pre-boring for installation of piles.
(h) When the piles are to be driven in rock, coarse gravel, clay with cobbles, or other soils, which
may damage the tip of the pile, flat or coaxial shoes made out of steel or cast iron shall be
provided at the tip of the pile.
(i) While driving a pile in a uniform clayey soil or sandy soil no advantage can be derived by
tapering the tip of the pile hence no shoe need be provided for the tip of the pile while driving
piles in such soils.
(j) When jetting is to be undertaken a jet tube may be cast into the pile by connecting the same
to the pile shoe which is normally provided with jet holes. It is not advisable to provide a
central which is likely to be choked.
(k) The best results can be achieved by providing four holes in four directions. However,
providing two holes in opposite direction may also serve the purpose.
(l) A lternatively, two or m ore jet pies may be at tached to the sides of the pile. The pile may g et
off loaded if proper balanced arrangement of jet is not made.
20.4.4 Concrete
20.4.4.1 Materials: Cement, w ater, f ine and c oarse aggregat e, c hemical ad mixtures et c. A s des cribed
under clauses 20.1.6.
Vol-2 , 2013
20.4.4.3 Workability of Concrete: The degree of workability i n this case is “low” a s the c oncrete is
placed w here t he section i s not he avily reinforced, al so t he c oncrete i n t he pi le i s v ibrated w ith b oth
internal as well as external vibrators, and therefore minimum slump should be 25 mm to 50 mm.
20.4.4.4 Form-Work/Mould
(i) Only steel moulds manufactured out of sturdy steel sections and sheets to cast the required size
of the pile are to be used. Timber moulds shall not be permitted, under any circumstances.
(ii) The mould shall sustain the stresses generated due to the use of immersion/plate vibrators and
some time even form vibrator, depending upon the size and strength of the pile to be cast.
(ii) The manufacturing of the mould shall be so simple that the sides could be opened within 16 to
24 hours of casting by simply loosening the bolts without damaging the edges of the pile.
(iv) Fixing supports for the sides of the mould shall be done from outside and no use of through bolts
through the concrete shall be permitted to support the opposite sides of the mould.
(v) Proper mechanism shall be introduced to fix the sides to the top of the casting platform so that
the plate from vibrators can be operated without disturbing the mould.
(vi) In case of square piles provision for forming champhers of the pile for the corners shall be made
in the mould itself.
(vii) The mould should be such that when the pile is demoulded all the surfaces of the pile except the
side from which the concrete is laid should get form finish. No rendering or finishing shall be
permitted on any surface of the concrete after demoulding.
(viii) Piles whose surfaces are plastered or rendered, edges repaired etc. shall be rejected and
removed from site.
(ix) After every casting, when the sides of the mould are opened the same shall be cleaned nicely
and form o il m anufactured by r eputed c ompany s hall be a pplied ov er the s urface b efore the
mould i s adj usted f or f illing t he c oncrete, f or nex t pile. T he normal practice of appl ying grease
mixed with diesel or waste oil instead of the form-oil shall not be permitted.
(ii) T he c asting y ard s hall hav e w ell drained s urface s o t hat t he water us ed f or c uring t he al ready
cast piles do not accumulate on the yard inconveniencing the working on subsequent piles.
(iii) The size of the casting platform shall be large enough to accommodate the minimum number of
piles to be cast for full 11 days depending upon the proposed progress of work per day, as a pile
once cast cannot be lifted from the casting bed till the expiry of ten days, therefore no piles can
be cast on these spaces till the piles more than 10 days old are shifted.
(iv) The casting yard shall be well covered not only from top but also from sides to avoid t he di rect sun-
rays falling on the piles that are under set. The pile should also be protected from rain and wind.
(v) Before taking up actual concreting, the moulds to be concreted for full days work shall be fixed in
position and preferably moulds for concreting on the subsequent day shall also be kept ready in
advance.
Vol-2 , 2013
(vi) If the contractor is permitted to start concrete with lesser number of moulds than that can be cast
within a d ay, th e action will pr ompt the contractor to o pen the s ides of m oulds alr eady c ast
prematurely t o c ontinue c oncreting f or t he full day , w hich is not des irable a s t he qual ity o f t he
concrete will be hampered.
(vii) The inner faces of the mould shall be cleaned; form-oil of approved brand and manufacture shall
be applied.
(viii) The reinforcements shall be lowered carefully in the mould and fixed in position with proper
cover blocks and spacers on all surfaces.
(ix) On getting formal approval of the Engineer-in-charge for the fixing of form-work in position and on
getting t he pr e-measurements o f t he r einforcements recorded, c oncreting w ith s pecified gr ade s hall
be taken up. The slump should be checked frequently and constant w/c ratio shall be maintained.
(x) The piles should be cast from end to end, using immersion, form vibrators, avoiding over vibration.
Proper care should be taken to see that the concrete is packed in the mould and consolidated. When the
mould is full the top surface of concrete shall be neatly toweled and finished smooth.
(xi) Proper precaution shall be taken to ensure that the vibration from the adjoining work does not
affect the previously placed concrete for piles during setting period.
(xii) On completing the concreting for a particular pile the following information shall be engraved (not
painted) on each pile.
(1) Date of casting.
(2) Grade of concrete used.
(3) No. of lot.
The lot No. will help to locate the exact position where the particular pile has to be used.
20.4.8 Curing
(i) Provision for curing as given under clause 20.1.8 shall be followed in addition.
(ii) T he piles shall not be lifted from the casting be d for a minimum per iod of 10 da ys from the date
of casting.
(iii) When the piles are shifted to stacking yard after the expiry of ten days, where the piles will have
to be kept for a period of 28 days from the date of casting, the piles in stacks shall be covered
with sacks so that the piles do not come in contact with sun rays till they attain full strength.
(iv) Las tly, t he m ost i mportant f actors af fecting t he t ime of c uring are t he method of c uring, w eather
during hardening, probable hardness of driving and the method of lifting and pitching.
(v) The Engineer-in-charge may fix up the exact period of curing for a particular project considering
all the factors mentioned in Para (iv) above.
Vol-2 , 2013
(ii) Th e piles shall be stored on a firm ground which will not liable for unequal subsidence or
settlement under the weight of the stack of piles.
(iii) Timber sections of suitable size shall be placed over the level ground to stack the piles on top.
The spacing between the timber sections shall be so adjusted that the piles are not subjected to
undue bending stresses, while in stack.
(iv) Spaces shall be left around the piles in the stack so that they can be lifted without difficulty and
necessary piles can be cured beyond 10 days.
(v) The order of stacking the piles shall be such that the older piles can be withdrawn without
disturbing the newly placed piles. Separate stacks shall be provided for the piles of different
lengths.
(vii) C are shall be taken to see that the piles are not damaged or cracked at the time of lifting,
handling transportation, etc.
(viii) While transporting the piles from the stocking yard to the site, the piles shall be supported at
approximate lifting holes provided for the purpose. In case during transportation if the piles are to
be unloaded temporarily they shall be placed on trestles or blocks located at the lifting points.
(ii) The heads of the pre-cast concrete piles to be driven shall be protected with packing of resilient
material against the possible damage due to the use of heavy hammers. Care shall be taken to
see that pac king is evenly spread and placed securely. O n top of t he pac king a helmet should be
placed and p rovided with a dol ly o f har dwood or any s uitable material not thickens than t he w idth
of the pile.
(iii) The failure in the pile may occur by compression or tension when the blow of the hammer
generates the stress waves which traverses t he length of t he p ile. Failure due t o c ompressive
stresses m ostly occurs at t he heads. Head s tresses a re i ndependent o f ground conditions and
mainly depend upon the weight of the hammer, its drop and the stiffness of the head cushion.
(iv) By using heaviest hammer and softest packing the maximum set for a given stress is obtained.
The drop of the hammer however should; be adjusted to suit the allowable stress in the
concrete.
(v) Optimum driving conditions can be maintained only by regular replacement of packing materials
as prescribed i n P ara (ii) ab ove, s ince t he stiffness i n head p acking m aterials i ncreases w ith
repeated use.
(vi) Only in cases of exceptionally hard driving, where theoretically the compressive stresses of toe
can r each t wice t he h ead s tresses, f ailure i n l ower p ortions of t he pi le c an oc cur. I n pr actice,
however, t his r arely o ccurs as t he c ompressive stresses t o a g reat extent tend t o be uniform
over the considerable length of the pile.
Vol-2 , 2013
(vii) Due to reflection of compressive wave to “free end”, the longitudinal tension is caused in the pile.
This situation arises at a time when the ground resistance is low and/or when the hammer
rebounds due to head conditions mainly because of the use of hard packing and light hammer.
In addition, an unsupported long pile negotiating a hard stratum will be subjected to transverse
or flexural vibrations in the pile in case the blow from the hammer becomes non-axial or if the
pile is not restrained to reduce the effect of a long pile.
(viii) F or driving a p ile; any type o f ha mmer c an be used provided the pile p enetrates to the
prescribed depth or attain the specific resistance without getting damaged.
(ix) The hammer, helmets, dolly and the pile below should be co-axial and should sit perfectly one
over the other. However, the heaviest possible hammer should preferably be used and the
stroke should be so managed so as not to damage the pile.
(x) The choice of hammer mainly depends upon whether the pile is to be driven to a gi ven
resistance or to a given depth.
(xi) Normally, for a single acting or a drop hammer the stroke should be limited to 1.2 m but 1.0 m is
preferable. Shorter stroke may be used in cases where there is a danger of damaging the pile, a
few examples of which are described below:
(a) Hard surface has to be penetrated in the early stages when a long pile has to be driven.
(b) When there is a s oft ground up to a c onsiderable depth, a l arge penetration is achieved at
each blow.
(c) The pile suddenly reaches refusal when it meets with rock or other virtually impenetrable soil.
(xii) If a satisfactory set is achieved for ten consecutive blows with an appropriate hammer and drop
the method of driving should be repeated with caution and long continued driving. However, after
the pile has almost ceased to penetrate the driving should be stopped especially when the
hammer with moderate weight is used.
(xiii) Sometimes it so happens that the rate of penetration suddenly changes without any satisfactory
reasoning or soil conditions. Under such circumstances the pile driving should not be continued
till real problem is investigated and remedy thought over.
(ii) The main purpose of jetting is to minimize or almost eliminate the resistance at the toe and last
the same time the frictional resistance along the surface of the pile shaft also gets reduced.
(iii) Very hard driving and vibrations can be avoided when the toe resistance is eliminated and also
the rate of penetration is increased considerably when compared to the normal driving methods
without jetting.
(iv) Jetting operations shall be carried out only when specifically ordered by the Engineer-in-Charge.
Jetting shall be carried in a manner that the stability of soil and the bearing capacity of piles
already driven is not in any way impaired. Similarly, the safety of the adjoining structures shall be
taken into consideration.
(v) For effective jetting the quantity of water required is directly related to the cross sectional area of
the piles (including external jet pipes). In dense cohesion less soils the quantity of water up to 2
litres per minutes per sq.cm. of pile cross section may be required. Less quantity of water may
be needed in loosely compacted soils.
Vol-2 , 2013
(vi) The water pressure to be maintained is between 5.6 kgf/cm2 to 10.6 kgf/cm2 or more. In case
large qu antities of water are us ed the dr aining arrangement for the w ater that e merges on the
ground s hall have t o be made otherwise t he s tagnant w ater m ay s often the ground endangering
the piling equipment resting above.
(vii) To minimize the risk of blockages, the nozzle should not be positioned at the point of the toe.
The arrangement of jets should be balanced to ascertain the penetration of the pile vertically. It is
advisable to surge down an independent pile or two pipes may be attached to the opposite sides
of the pile for effective jetting operation.
(viii) The pile shall be allowed to enter the ground gradually after operating the water under the weight
of pi le and t he hammer. Acceptable verticality m ay b e a chieved b y use of rigid l eaders, d uly
controlling the rate of penetration with a pile winch.
(ix) On achieving maximum apparent penetration with light driving by the method prescribed above
and w hen t he water jets ar e running t he further pen etration may be at tained i n t he cohesion l ess
soils. The piles shall be driven to the final position or set when the jetting is complete.
(x) Before closing the driving operation, the jetting should be stopped and the driving shall be
continued b y ordinary dr iving methods. I f due to t he gr ound di sturbances, t he pi le tips t end t o be
drawn towards the piles already driven, jetting should be stopped immediately.
(xi) The correct working of jets should be tested before the work on driving the pile is commenced. If
the pile is not provided with as “built in jet arrangement” independent jet pipes down the outside the
pile can be used and to achieve the best result jets working on several faces of the pile can be
practical which will also assist maintaining the verticality.
(ii) The stripping operation or exposing the reinforcement of the pile shall be done very carefully
without damaging the pile proper. In case any portion of the concrete cracks, the defective
portion shall be cut and the portion repaired with new concrete joining properly with old concrete.
(ii) The exposed steel should be cleaned properly and shall be held in firm position, while full
penetration butt welding is done.
(iii) In case the conditions on site are not favorable to attempt butt welding, a minimum length of 40 d
(40 times the diameter of main bar) of the original pile shall be exposed and the new steel should
be overlapped over the exposed steel. The overlap shall be spot welded.
(iv) On completion of welding/overlapping the reinforcement and tying the spirals, for the extended
length of reinforcements the extras portion of the pile can be concreted thus extending the
original pile.
Vol-2 , 2013
20.4.11 Risen Piles
(i) Sometimes due to ground heave there is a possibility that piles already driven to the final depth
may start rising when adjacent piles are being driven; such rising shall be noted at frequent
intervals till driving on adjacent piles is in progress.
(ii) O n c ompletion of driving t he adj acent pi les, the pi les t hat are risen s hall agai n be dr iven bac k
either to their original level or up to a point of resistance.
20.4.14 Measurement
Dimension shall be measured near est to a cm. Me asurement o f length on completion shall be al ong
the axis of pile and s hall be m easured from top of shoe to the bottom of pile cap No allowance shall be
made f or bul king, s hrinkage, c ut of f tolerance, w astage and hi ring of t ools, equi pment f or ex cavating
and driving etc.
20.4.15 Rate
The r ate i ncludes t he c ost of m aterials and l abour i nvolved i n al l t he oper ations des cribed abov e
including pi le em bedded in pile cap, centering, shuttering except reinforcement, pile cap and grade
beam.
20.5.3.2 Preparation of Pile Head: Pile head s hall be c hipped of f t o hori zontal pl ane, proj ecting s teel
shall be c ut or bent and top finished smooth and leveled with plaster of Paris or similar synthetic
material as specified to give a plane surface which is normal to the axis of the pile. A bearing plate with a
hole at the centers shall be placed on the head of pile for the jacks to rest.
Vol-2 , 2013
20.5.3.3 Loading Platform: A prop er l oading pl atform i s installed as s pecified. C ontractor s hall ensure
that when the hy draulic j ack and l oad m easuring devices are m ounted on pile head the whole system
will be s table on the m aximum specified load. For s ingle pile two d ial gauges s hall be f ixed t o t he pi le
and b ear o n s urfaces on r eference f rame. T he di al ga uges s hall b e pl aced i n di ametrically o pposite
positions and b e equ idistant f rom the p ile axis. F our di al gauge s are us ed f or groups , hav ing 0.01 mm
sensitivity. The arrangement shall be approved by the Engineer-in-charge.
20.5.3.4 Application of Load: The t est i s c arried out by appl ying a s eries of dow nward i ncremental
load (20 per c ent of safe loads on pile). In this method application of increment of test load and taking of
measurement or di splacement i n each stage i s maintained till t he rate of di splacement is either 0.1 mm
in first 30 minutes or 0.2 mm in first one hour or 2 hours, whichever occurs first. The test load shall be
maintained for 24 hours. This method is applicable for both initial and routine test. For testing of raker
piles the loading shall be along its axis. Safe load on single pile for initial test is least of following:
(i) Two-thirds of the final l oad at which t he total d isplacement attains a value of 12 m m unl ess o therwise
stated, in such case the safe load should be corresponding to total displacement permissible.
(ii) 50 per cent of the final load at which the total displacement equal 10 per cent of pile diameter
and 7.5 per cent of bulb diameter in case of under-reamed piles.
Routine test shall be carried for a test load of one and half times the working load, maximum
settlement not to exceed 12 mm or as stated.
Safe load on group of piles for initial test shall be least of the two
(i) Final load at which total displacement is 25 mm or as stated.
(ii) Two-thirds of final load at which the total displacement is 40 mm.
Routine test s hall b e c arried for a tes t lo ad equ al to not less than w orking l oad, t he m aximum
settlement not to exceed 25 mm.
20.5.3.5 Maintained Load Method: This i s appl icable f or bot h i nitial and r outine t est. I n t his method
application o f inc rement of te st lo ad a nd t aking o f m easurement o r dis placement in e ach st age of
loading is maintained till rate of displacement of the pile top is either 0.1 mm in first 30 m inutes or 0 .2
mm i n f irst on e h our o r t ill 2 hou rs, w hichever o ccurs f irst. I f t he l imit of per missible di splacement as
given in 20.5.3.4 is not exceeded, testing of pile is not required to be c ontinued further. The test load
shall be maintained for 24 hours.
Pile t est dat a s uch as load, di splacement and t ime s hall be rec orded i n s uitable pre scribed t abular
form. Results can be presented by suitable curves.
Test s hall be c arried out in proper m anner and t o the ent ire satisfaction of t he E ngineer-in-charge.
After the test is completed the test cap shall be dismantled and pile surface shall be resorted to original
shape.
20.5.3.6 Measurement: Each completed test shall be enumerated for initial test, routine test separately.
20.5.3.7 Rate: The rate i ncludes t he c ost of l abour, m aterial a nd al l t he o perations d escribed a bove
such as pr eparatory work i ncluding i nstallation o f l oading pl atform, appl ying l oad, pr eparing pi le hea d for
load test, trimming of pile head etc. complete.
Vol-2 , 2013
20.5.4.2 Preparatory Pile Head: As per clause 20.5.3.2.
20.5.4.4 Application of Load: Relevant prov ision as per c lause 20. 5.3.4 shall be app licable. The t est
may be continued up to 50 per cent over the safe load.
Test shall be carried out in proper manner and to the entire satisfaction of the Engineer-in-charge.
After t he t est i s c ompleted, t he t est c ap shall be dismantled and pi le s urface s hall b e r estored t o
original shape.
20.5.4.6 Measurement: Each completed test shall be enumerated for different load ranges.
20.5.4.7 Rate: The r ate i ncludes t he cost of l abour, m aterials a nd a ll the operations described a bove
such as preparatory work, trimming of pile head etc. complete.
20.5.5.2 Application of Load: Full load imposed by the jack shall be taken as l ateral resistance on each pile
or gr oup. Lo ad s hould b e applied i n increments of about 2 0 per c ent of t he es timated s afe l oad. T he ne xt
increment shall be applied after the rate of displacement is approximately equal to 0.1 mm per 30 minutes.
20.5.5.4 Displacements: Displacement is read by at least two dial gauges of 0.1 mm sensitivity spaced at
30 c m and kept hor izontally one a bove the ot her a nd di splacement i s i nterpolated at c ut of f l evel. O ne dia
gauge p laced diametrically oppos ite t o j ack s hall di rectly m easure di splacement. Where, i t i s n ot pos sible
to locate one of the dial gauges in the line of the jack axes, then two dial gauge may be kept at a distance
of 30 cm at a suitable height and the displacement interpolated at load point from similar triangles.
Note: One of the methods of keeping dial gauge on pile surface is to chip off uneven concrete on the
side of the pile and to fix a piece of glass 20 to 30 mm square. The dial gauge tips shall rest on
the central portion of the glass plate.
20.5.5.5 Measurement: Each completed test shall be enumerated for different load ranges.
20.5.5.6 Rate: The rate includes the costs of labour, materials and all the operations described above.
Vol-2 , 2013
$3 3 (1',;$
A- 1 Properties
A-1.1 The bentonite suspension used in bore holes is basically clay of montmorillonite group having
exchangeable s odium c at i ons. B ecause o f t he pr esence o f s odium c at-ions, bent onite on di spersion w ill
break down i nto s mall pl ate l ike particles having a negative c harge on t he surfaces and positive charge
on t he edge s. W hen t he dispersion i s l eft to s tand undi sturbed, t he part icles bec ome or iented b uilding
up a m echanical s tructure at i ts o wn. T his m echanical s tructure he ld b y el ectrical bond i s obs ervable
as a jelly like mass or jell material. When jelly is agitated, the weak electrical bonds are broken and the
dispersion becomes fluid.
A-2 Functions
A-2.2 In the c ase of g ranular s oil, the b entonite s uspension pe netrates into the sides un der po sitive
pressure and af ter a w hile forms a j elly. The bentonite suspension gets deposited on t he sides of the
hole not pen etrate into the s oil, bu t depos its on ly a this film on the s urface o f the ho le. U nder s uch
condition, stability is derived from the hydrostatic head of the suspensions.
A-3 Specification
A-3.1 The bentonite suspension used for pilling work shall satisfy the following requirements:
(a) The liquid limit of bentonite when tested in accordance with IS 2720 (Part V) 1965 shall be more
than 300 per cent and less than 450 per cent.
(b) The sand content of the bentonite powder shall not be greater than 7 per cent.
Note: The purpose of limiting the sand content i s m ainly t o control a nd reduce the w ear and
tear of the pumping equipment.
(c) B entonite s olution should be m ade b y m ixing i t with f resh w ater u sing pu mp f or circulation. T he
density of the bentonite solution should be bout 1.12.
(d) The mash viscosity when tested by a Marsh cone should be about 37 second.
(e) The swelling index as m easured by the swelled volume after 12 hours in abundant q uantity of
water shall be at least 2 times its dry volume.
(f) The pH value of the bentonite suspension shall be less than 11.5.
Vol-2 , 2013
$3 3 (1',;%
B-1 Equipment
B-1.1.1 For the piles of size larger than 30 cm and for larger depths additional equipment required will be
portable tripod hoist with a manually operated winch.
B-1.1.2 For piles in high ground water table and unstable soil conditions, boring and under-reaming
shall be carried out with bentonite slurry using suitable equipment. Tremie pipe shall be used for
concreting
(a) Drop weight for driving the core assembly, and
Vol-2 , 2013
$3 3 (1',;&
PILE FRAME
Scope
Specification for pile frame shall be i n conformity to the one l aid in IS 6428. Contractor shall use the
proper height of pile frame and which is able to take the weight of hammer safety.
Standard size of pile frame will assist the user in determining the type and size of frame. Damages
pile frame which cannot be used for want of spares shall be replaced with sound one.
Size
The size of pile frame shall be des ignated by its height and the weight of the hammer and the pile it
can take.
The pile frame shall be as per the sizes given in table below:
S.No Size Height of Pile Frame Weight of hammer Weight of pile (Any
Type) max
1 I 7.5 1.5 3
2 II 10.5 3 6
3 III 15 5 10
4 IV 20 6 12
5 V 25 6 12
Extension Panels: All pi le f rames s hall be c apable of bei ng f ixed w ith ex tension panel s of 1. 5, 3
and 4.5 m height without reduction in weight capacity.
Performance: Pile f rames w ith or without ex tension panel s s hall be c apable of pl acing piles at t he
maximum backward rake in 1 in 5 and the maximum forward rake 1 in 10.
Vol-2 , 2013
APPENDIX D
PILE BORING EQUIPMENT- GENERAL REQUIREMENT
(Clause 20.2.2)
Scope
Specification for pile boring equipment shall be as per IS 14362. Constructions of bored piles require
careful s election of boring equ ipment. Choice of appropr iate equ ipment will de pend up on sub soil
conditions, diameter of pile, their depths and ot her specific requirements of any particular work. Details
of equipment and proposed methods of driv ing the pile shall be submitted by the tenderer for scrutiny
and approval by the competent authority
Equipment desc ribed herei n refers t o co nstruction of bored pil es on land and without the user of
bentonite. The standard nominal diameter of piles shall be 450 mm, 500 mm, 600 mm and the like.
Materials
All materials used i n the construction of pile boring equip ment shall conform to the requi rement of
relevant Indian Standard IS 800 ‘Code of Practice’ for general construction in steel.
1. Winch drum
2. Prime mover
7 3. Transmission
4. Clutch operating lever
5. Brake pedal
6. Main shear leg
9 7. Side shear leg
8. Pulley
4.4 m (H) Typical
9. Sludge pump
10 10. Wire Rope
12 11. Winch frame
12. Safety Link
1 3 4 2
11
Fig. D1
Vol-2 , 2013
Winch Drum: This s tandard c apacities (drum rope pull) of the w inch dr um s hall be 5 t. A nd the drum
meter shall not be less than 20 times the diameter of the wire ropes used.
Prime Mover: The p rime m over s hall usually be a di esel e ngine of t he ai r cooled t ype or an electric
motor. A suitable reduction gear shall also be provided.
Clutch System: The clutch s ystem shall c onsist o f a c lutch wheel and friction plate(s) o r a F riction c one
operated by a lever.
Brake System: This shall consist of a brake band connected with the foot brake pedal or brake handle for
hand operation.
Winch Frame: A typical w inch frame s hall be made from s tructural s teel section an d s hall be ei ther
truck-mounted c rawler-mounted or skid-mounted. A pr oper s tabilizer s hall be pr ovided to transmit the
load to the ground smoothly.
Derrick
General: The standard derrick shall consist of the following components:
(a) Main shear leg,
(b) Side shear leg,
(c) Shear leg base,
(d) Pulley, and
(e) Safety link.
The h oisting c apacity o f t he de rrick s hall be a t least eq ual to the m aximum dr um r ope pu ll land
preferably more by 25%.
Main Shear Leg: The main s hear l eg s hall be a box s ection fabricated ac cording t o I S 80 0-1984 ei ther
from tw o mild steel angle s ections or tw o channel sections. T he box s ection s hall hav e minimum
dimensions of 125 mm2 and the minimum length of the leg shall be 5.6 m.
Side Shear Legs: The two sides shear legs shall have a minimum box section of 100 mm2. One of the two
side legs shall be provided with suitable mild steel rings spaced 0.3 m apart up t o the top. These legs
shall be placed part at as distance of minimum of 3 m.
Shear Leg Base: These shall consist of as steel plate welded to the base of the leg. Additional plates shall
be welded on all four sides of the leg for up to 15 mm above the bottom of the leg.
Pulley: The pulley shall be usually provided at the top of the main shear-leg and it shall have a diameter at
least 20 t imes the di ameter o f the wire-rope us ed. T he pul ley s hall hav e a suitable guar d and s hall b e
properly lubricated.
Safety Link: An inte rconnected steel-chain shall be provided near the top of the derrick so as to
preclude any accidental increase in the distances between the legs.
Boring/Chiseling Tools
The various tools shall be as follows:
(a) Sludge pump,
(b) Bailers,
Vol-2 , 2013
(c) Chisels,
(d) Casings,
(e) Casing extractor plate,
(f) Casing extractor bar,
(g) Casing drive bar, and
(h) Tiller
Sludge Pump: Boring shall be u sually ad vanced b y us ing a sludge pu mp (also called shell) a s shown i n
Fig. D-2. Weight of the sludge ump shall vary with the diameter but normally minimum weight shall be
7.5 k N. Sludge p ump is a h ollow cylindrical steel bo dy with a c utting s hoe at the bottom and a l ifting
hook at its top. It has hinged trap door immediately abov e the bottom c utting edged and it has an
opening (window) near the top for muck removal. Above this window, lead or steel or concrete may be
added to increase the weight of the sludge pump for effective boring.
Bailer: The bailer (see Fig. D-3) is used for removal of water or slush from the bore hole. It is made up
of a hollow steel cylinder with a lifting hook at the top and a truncated base plate with perforation at the
bottom. There is a pl unger passing through a c entral hole of the b ase plate which acts a s a pl ug valve.
This plu nger is ab out 20 cm long an d has about 15 c m diameter steel pla tes welded at its to p an d
bottom. This c loses t he central hol e in t he base plate of t he plunger and thus ret ains t he s lush m aterial
for removal.
Trap Door
Chisels: Hard strata during boring shall be broken by chisels. The chisels shall be made of solid round bar
with hard faced edged at the bottom. The chisel shall weigh at least 7.5 KN for 450 mm 12.5 KN for 500
and 600 mm piles.
Casing: These s hall b e made f rom 16 m m t hick plates a nd t he standard l ength shall be 1.5 m . The
casings shall be threaded on both sides and suitable collar shall be used to protect the threads.
Vol-2 , 2013
Casing Extractor Plate: A s teel pl ate of s uitable size shall be us ed f or t he extraction c asing af ter t he
boring operation is complete.
Casing Extractor Bar: his s hall be a round of ab out 75 m m di ameter. I t s hall be pas sed t hrough t he
holes only sides of the casing and through the extractor plate, to enable extractor of casing.
Casing Drive Bar: This s hall hav e a c ross-section of at l east 75 m m2 and shall be us ed t o dr ive t he
casing.
Tiller: This gadget shall be used to rotate the casing manually, whenever necessary.
Temporary Casing
This shall consist of the following.
The casing collar shall be attached at the casing top to take the blows during casing driving. The
main casing shall be made from 16 mm thick steel and shall be threaded at one end. The casing
shall be provided with as cutting edge at the bottom to facilitate driving.
Tremie Arrangements
The tremie arrangements shall include the Following:
(a) Concrete hopper
(b) Hopper plug
(c) Tremie pipe
(d) Holding clamp and
(e) Hoisting plug.
Accessories
Accessories shall include the following:
(a) Concrete placer
(b) Wheel barrow
(c) Measuring chain
(d) Bailers
(e) Crowbars
(f) Dog-clamps with pins
(g) Steel measuring tape; and
(h) Mucking shovel.
Vol-2 , 2013
$3 3 (1',;(
CYCLIC LOAD TEST METHOD
(Clause 20.5.4.5)
E-1 Method
E-1.1 Alternate l oading an d unl oading shall be carried out at eac h s tage as i n 20. 5.3.5 and eac h l oading
stage s hall b e m aintained as i n 2 0.5.5.2 a nd e ach unloading s tage shall b e maintained f or a t l east 1 5
minutes and the subsequent elastic rebound in the pile should be measured accurately by dial gauges as
in 20.5.5.5. The test may be continued up to 50 per cent over the sage load.
E-2.1.1 Assuming that there is no compression in the pile, plot a gr aph r elating total el astic recovery an d
load at the pile top.
E-2.1.3 Draw a straight l ine par allel t o t he s traight por tion of curve I to di vide t he load i nto t wo par ts and
thereby obtained approximate values of point resistance and skin friction.
E-2.1.4 From t he a pproximate v alue o f s kin f riction, an d k nowing t he l oads of t op o f pi le, c ompute t he
elastic compression of the pile corresponding to these loads, by the following formula:
Δ = (T-F/2)L
AE
Where
Δ = Elastic compression of pile in cm,
T = Load on pile top in kgf,
F = Frictional resistance in kgf,
L = Length of the pile in cm,
A = Cross-sectional area of the pile in cm2, and
E = Modulus of elasticity of the pile material in kgf/cm3
(The v alue s hould no rmally be m easured f rom an ex posed por tion o f pi le s tem by m eans o f
compress meter during the load test itself.)
E-2.1.5 Obtain values of the elastic compression of the sub grade by subtracting the elastic
compression of t he pile from t he t otal elastic r ecovery of pile, a nd plot t he gra ph re lating t hese new
values the negative value shall be ignored until the value is positive.
E-2.1.6 Repeat the procedures given in E-2.1.3 to obtain new values of skin friction.
E-2.1.7 The process of f urther approximations c overed i n E -2.1.6 may be r epeated f urther t o any
desired e xtent, b ut usually the t hird c urve w ould gi ve s ufficiently ac curate v alues for skin friction for
practical purposes.
Vol-2 , 2013
E-2.2 Analytical Method
Analysis of Cyclic Load Test Data for Separation of Skin Frication and Point Resistance.
0 20 40 60 80 100
0.5
1.0
Elastic Compression of Sub-Grade in mm
1.5 Skin Friction
2.0
Parallel
2.5
Point II
3.0 Resistance III and Final
3.5 Parallel
4.0
4.5
E-2.2.1 From straight l ine portion of c urve c alculate t he v alue of c onstant f rom t he equa tion.
m = Δ s - (ΔT/AE)L
ΔT
Where
m = A constant;
ΔS = Change in total elastic settlement of pile
ΔT = Change in applied load = (Tb- Ta) in kgf
L = length of pile in cm;
A = cross-sectional area of pile in cm2
E = elastic modulus of the material of pile in kgf/cm2
T = Load on pile top in kgf.
E-2.2.3 Knowing v alue of m and S c ompute s kin friction and po int bear ing by s olving s imultaneous
equation (3) and (4).
T =P+F
S = mP + (T-F/2)L
AE
Where
P = point bearing in kgf, and
F = skin friction in kgf.
Vol-2 , 2013
AP P ENDIX F
PILE DRIVING HAMMER
(Clause 20.1.2)
Scope
Specifications for driving hammer shall be in conformity to the one laid in IS 6426. Driving hammer of
standard weight and strokes of different types be used.
The ob ject should be to keep weights o f ha mmers to a l imited r ange and s tandardize weight interval
and stroke to facilitate their use with pilling rig & pilling attachments of different plants.
Piles m ay be dr iven w ith any t ype of ham mer, provided t hey pe netrate t o t he prescribed dept h o r
attain to ensure a final penetration of not more than 5 mm per blow.
Classification
It is preferable to em ploy the heaviest hammer practicable and to limit the stroke, s o as not to
damage the pile. Pile hammers shall be classified as given in the Table below:
Sizes
The r ecommended s izes ( weight of r am o r s triking pa rt) an d s troke of di fferent t ypes s hall b e as
given in Table below:
TABLE
Sizes (Weight of Ram or the Striking Part) and Stroke of Different Types of Hammers
S. Type of Light (up to 500 Kg) Medium (over 500 up to Heavy (over
No. Hammers 2500 kg) 2500 kg)
(1) (2) (3) (4) (5)
1 Drop Hammer 250 to 500 kg at multiples of 750 to 2500 kg at multiples 2750 to 4500 kg
125 of 250 at multiples of
250
2 Single acting (a) 25 to 100 kg at multiples 750 to 2500 kg at multiples 3000 to 7500 kg
capable of of 25 kg at maximum of 250, at maximum stroke at multiples of
working on stroke of 20 cm of 90 cm. 500 kg at
steam or air at (b) 100 to 500 kg at multiples maximum stroke
5.5 kg/cm2 at of 100 kg at maximum at 120 cm.
the hammer stroke of 40 cm.
3 Double acting (a) 25 to 100 kg at multiples 750 to 2500 kg at multiples
capable of of 25 kg at maximum of 500, at maximum stroke
working on stroke of 20 cm of 45 cm.
steam or air at (b) 100 to 500 kg at multiples
5.5 kg/cm2 at of 100 kg at maximum
the hammer stroke of 25 cm.
4 Diesel 500 kg at maximum stroke of Over 500 up to 2500 kg at
Hammer 250 cm multiples of 500 kg at
maximum stroke of 250 cm.
Vol-2 , 2013
21.0 : ALUMINIUM WORK
Vol-2 , 2013
CONTENTS
Sl. No. Brief Description Page No.
List of Bureau of Indian Standards (BIS) Codes 334
Vol-2 , 2013
LIST OF BUREAU OF INDIAN STANDARD (BIS) CODES
Vol-2 , 2013
21.0 ALUMINIUM WORK
21.0 TERMINOLOGY
Bar
Any solid section, other than round, with at least one dimension of 10 mm or more.
Rod
Any round solid section with a diameter of 10 mm or greater.
Hollow Section
An ex truded s hape ot her than round t ube, t he cross s ection of w hich c ompletely enc loses a v oid or
voids and which is not subject to cold drawing.
Anodized Aluminium
Aluminium w ith an a nodic c oating, pr oduced b y an e lectrolytic ox idation pr ocess, i n w hich t he s urface
of the aluminium is covered with a coating, generally an oxide, to give protective and decorative properties.
Shoe
The device fixed to the bottom of the door leaf in order to hoist it to the floor spring.
Vol-2 , 2013
Centre - Hung Ventilator
A v entilator horizontally pivoted at t he centre on both s ides. Top half opens inwards and bottom half
opens outwards.
21.1 ALUMINIUM
The per missible di mensional t olerances of t he ex truded s ections s hall be as pe r I S 6477 an d s hall be
such as not to impair the proper and smooth functioning/operation and appearance of door and
windows.
Aluminium glazed doors, windows etc. shall be of sizes, s ections and details as s hown in the
drawings. The details shown in the drawings may be varied slightly to suit the standards adopted by the
manufacturers of t he al uminium w ork, w ith t he ap proval of E ngineer-in-Charge. B efore proc eeding w ith
any f abrication work, th e co ntractor sh all pr epare an d submit, complete f abrication and i nstallation
drawings for ea ch type of glazing do ors, w indows, ventilators an d p artition e tc. for the ap proval of t he
Engineer-in-Charge. If the sections are varied, the contractor shall obtain prior approval of Engineer-in-
Charge and nothing extra shall be paid on this account.
21.1.2 Anodising
Standard al uminium ex trusion s ections a re m anufactured i n v arious s izes an d s hapes i n w ide ra nge
of s olid a nd hollow p rofiles with d ifferent f unctional shapes f or ar chitectural, s tructural glazing, c urtain
walls, d oors, w indow & ven tilators an d va rious o ther purposes. T he an odizing of th ese pr oducts is
required to be done before the fabrication work by anodizing/electro coating plants which ensures
uniform c oating i n uni form c olour and shades. T he extrusions are ano dized u p t o 30 m icron in di fferent
colours. The anod ized extrusions are t ested regularly under s trict quality c ontrol a dhering t o I ndian
Standard.
21.1.3.2 Pre-treatment: Each a luminium al loy ex trusion o r pe rformed s ection s hall b e tho roughly
cleaned by al kaline or acidic s olutions under t he c onditions specified by c hemical c onversion c oating
supplier and t hen r insed. A c hemical c onversion c oating s hall be appl ied by t reatment w ith a s olution
containing essentially chromate ions or chromate and phosphate ions as the active components as
applicable. T he am ount o f t he c onversion coating d eposited d epends on t he t ype u sed b y t he
conversion c oating c hemical s upplier. The c onversion c oating s hall be thoroughly ri nsed either w ith t he
solution specified by the conversion coating chemical supplier or with de-mineralized water and then
dried at the temperature for the time specified by the conversion coating chemical supplier. The
contractor s hall s ubmit t he det ail s pecifications an d ap plication proc edure f or appl ication of c onversion
coating for appr oval of E ngineer-in-Charge. T he m etal s urface after the c onversion c oating pretreatment
and prior to the application of the coating shall be free from dust or powdery deposits.
Vol-2 , 2013
21.1.3.3 Process: The pol yester po wder shall be ap plied b y el ectrostatic po wder s pray m ethod. B efore
start o f po wder coating t he contractor shall submit det ail s pecification for app lication o f pol yester po wder
from manufacturer of the polyester powder for approval of Engineer-in-Charge. The powder coating shall be
applied as per the specification approved by Engineer-in-Charge.
21.1.3.4 Thickness: The thickness of the finished polyester powder coating measured by micron meter
shall not be less than 50 micron nor more than 120 micron at any point.
(ii) Adhesion: When a coated test piece is tested using a spacing of 2 mm between each of the six
parallel cuts (the cut is made through the full depth of powder coating so that metal surface is
visible) and a piece of adhesive tape, approximately 25 mm x 150 mm approved by the
Engineer-in-Charge i s ap plied f irmly t o t he c ut area and t hen rem oved rapi dly by pul ling at ri ght
angles to the test area, no pieces of the finish other than debris from the cutting operation shall be
removed from the surface of the finish.
21.1.3.7 Measurement: All the aluminium sections in cluding s nap beading fix ed in place s hall be
measured i n runni ng m eter al ong t he out er peri phery of c omposite s ection correct t o a m illimeter. T he
weight calculated on the basis of actual average (average of five samples) weight of composite section in
kilogram correct to the second place of decimal shall be taken for payment. (Weight shall be taken after
anodizing). T he w eight of c leat s hall be added f or payment. N either any de duction nor any thing extra
shall be paid for skew cuts.
21.1.3.8 Rate: The rate shall include the cost of all the materials, labours involved in all the operations as
described in nomenclature of item and particular specification.
Vol-2 , 2013
TABLE 21.1
Physical and Mechanical Properties
(Para 21.2.1)
Sl. Properties Flat Pressed Three Layer,
No. Multilayer and Graded
Grade-I Grade-II
(i) Density variation (Max.) Percent + 10 + 10
(ii) Water absorption (Max )
(a) 2 hours 7.0 15.0
(b) 24 hours 15.0 30.0
(iii) Thickness swelling (Max.), percent, 2 hours 5.0 8.0
(iv) Modulus of rupture (Min) N/mm2
(a) Up to 20 mm thickness 15.0 11.0
(b) Above 20 mm thickness 12.5 11.0
(v) Tensile strength perpendicular to surface (Min.)
N/m2
(a) Up to 20 mm thickness 0.45 0.3
(b) Above 20 mm thickness 0.4 0.3
(vi) Tensile strength perpendicular to surface (Min.)
N/mm2
(a) After cyclic test* 0.2 -
(b) After accelerated water resistance test** 0.15 -
(vii) Screw withdrawal strength (Min.), N:
(a) Face 1250 1250
(b) Edge 850 750
(viii) Abrasion resistance (Min.) in number of revolutions
(a) Type I 450 450
(b) Type II 250 250
(c) Type III 80 80
* Cyclic Test at : Specimen are immersed in water at 27±2o C for a period of 72 hours, followed by
drying in air at 27 ± 2o C for 24 hours and then heating in dry air at 70o C for 72 hours. Three such
cycles are to be followed and t hen s pecimens are t ested f or t ensile s trength per pendicular to t he
surface. These tests are to be conducted at manufacturer place.
** Accelerated Water Resistance Test: Specimens are immersed in water at 27±2o C and water is
brought to boiling and kept at boiling temperature for two hours. Specimens are then cooled in
water to 27±2o C and tested at manufacturer place for tensile strength perpendicular to the surface.
21.2.1.1 Particle Board: Synthetic resin bonded f lat pr essed t hree l ayers, multilayer and gr aded par ticle
board def ined i n I S 3087 having superfine s urface shall b e us ed f or produ ction of prel aminated part icle
board. F or E CO M arks t he part icle board s hall al so c onform t o t he requirements of E CO M ark s pecified
in IS 3087.
21.2.1.2 Impregnated Base Paper: Printed or plain coloured absorbent base paper having a weight of 60-
140 g /m 2 impregnated i n a suitable s ynthetic resin a nd dr ied t o a v olatile content o f 4 -8 per c ent s hall be
used for pre-lamination on both surfaces of particle board.
21.2.1.3 Impregnated Overlay: An absorbent tissue, paper having a weight of 18-40 g/m2 impregnated in
a s uitable s ynthetic r esin an d dr ied t o a v olatile c ontent of 4 -8 pe r c ent s hall be us ed f or t he
manufacture of pre-laminated particle board.
338 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
21.2.1.4 Manufacture: Particle boards h aving s uperfine and c losed s urface with hi gh f ace s trength a nd
steep density gradient across t he t hickness is used f or m aking prelaminated particle boards.
Impregnated base papers rich in a s ynthetic resin are placed on ei ther side of the particle board and t he
assembly is taken inside a short cycle single opening lamination press or a multi day light press. Under
heat and pressure the resin flows and forms a permanent bond with particle board.
The top surface of impregnated paper comes in contact with special surface chromium plates or
steel caul plates and takes the impression of surface finish of these cauls. Hot boards are extracted out of
the short cycle press and cooled in air, whereas cooling of boards is done inside the dress in multiday light
type. Care should be taken to keep cycle times low in the press to avoid heat penetration to the centre
of the boar edge.
The i mpregnated ov erlay paper may be u sed b y pl acing it ov er the impregnated bas e paper ( IBP) on
one s urface while us ing a n ormal IBP on the o ther s urface and pr essure. The impregnated ov erlay
becomes transparent after pressing. Such boards are used for high surface abrasion application.
In case of finished foil par ticle boards, the finished foil is pa sted on bo th surfaces of particle board after
spreading suitable s ynthetic gl ue on board’s surface and pas sing the assembly i n a roller press or a f lat
press under the influence of pressure and/or heat depending on the type of binder used.
21.2.1.5 Finish: The finish o f the pap er ov erlaid boar d depe nds on the s urface o f c aul p lates us ed.
Common s urface f inishes i n us e are gl ossy, m att t extured ( soft, S wede, w ood por e and l eather), et c.
The surface finish of the foil finished boards depends on the original finish of the foil used.
21.2.1.6 Dimensions and Tolerances: Dimensions and tolerances shall conform to IS 12049.
21.2.1.7 Testing: One sample for every 100 sqm. or part thereof shall be taken and testing done as per IS
12823. F or quantity less than 100 sqm, the test certificate from manufacturer shall be relied upon. The
Engineer-in-charge may ask for testing even if the quantity is less than 100 sqm.
21.2.2.2 Fixing: The req uired s ize of panel , k eeping s ufficient m argin t o be i nserted i nside t he s ection,
shall be c ut to correct size and f ixed firmly in the frame with CP brass or al uminium or stainless steel
screws o f star head ed, counter sunk and matching size gr oove. Joints s ealed with epox y r esin o r s ilicon
sealant to make the unit water proof.
21.2.3.2 Thickness : The t hickness of f loat gl ass s hall depend on t he s ize of panel . T he t olerance i n
thickness shall be as under:
TABLE 21.2
Nominal Thickness (in mm ) Tolerance (in mm )
4.0 ± 0.3
5.0 ± 0.3
6.0 ± 0.3
8.0 ± 0.6
339 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
21.2.3.3 Allowable Defects: The allowable defects shall be as per Table 21.3 below:
TABLE 21.3
21.2.3.4 Allowable Cluster of Defects: The allowable cluster of defects mentioned under Sl. No. 1, 2 &
3 of Table 21.3 shall be as per IS 14900.
21.2.4 Tests
21.2.4.1 Thickness: The thickness of float glass shall be measured with micrometers or a c aliper which is
graduated to 0.01 mm or with a measuring instrument having an equivalent capacity.
21.2.4.2 Scratches, Rubs and Crush : Place the sample of float glass in a vertical position
approximately 50 c m from the v iewer’s position and look through it using either day light w ithout direct
sunlight or a background light suitable for observing each type of defect.
21.2.4.3 Bow : Depending on the side on w hich bo w i s pr esent, stand t he sample v ertically on a wooden
plank. Stretch a thread edge to edge. Measure the longest perpendicular. Distance from the thread to
the surface of float glass facing the thread and express it as percentage of the length of float glass from
edge along the thread.
21.2.4.4 Reams, Strings and Lines : Focus a light projector with a 500 W lamp and an objective lens with
an approximate 5 cm aperture and about 30 cm focal length on a flat white projection screen placed about
760 cm from the light source in a dark room. Place the float glass in a vertical position parallel to the
screen be tween t he l ight and t he s creen. M ove the gl ass s lowly t owards t he s creen with a v ertical
oscillating motion. The s hadowgraph read out i s t he distance at w hich the di stortion just bl ends w ith t he
general shadow of the glass on the screen.
TABLE 21.4
Vol-2 , 2013
21.2.4.5 Perspective Distortion: When tested a s per t est pr ocedure d escribed be low it s hall n ot gi ve
distorted vision of straight stripe pattern.
The EPDM gasket shall meet the requirements as given in Table 21.5 below:
TABLE 21.5
21.4 SEALANT
21.4.1 The sealants of approved grade and colour shall only be used. The silicone for perimeter joints
(between A luminium s ection an d R CC/Stone m asonry) shall be of m ake approved by the E ngineer in
Charge.
21.4.3 Masking
Areas a djacent t o j oints shall b e m asked t o ensure neat s ealant l ines. M asking t ape s hall not be
allowed t o t ouch clean surfaces t o which the silicone sealant i s to adhere. Tooling shall be c ompleted i n
one continuous stroke immediately after sealant application and before a skin forms and masking shall be
removed immediately after tooling.
21.4.4 Application
Install bac ker r od of appr opriate s ize and appl y s ilicone s ealant i n a c ontinuous oper ation us ing a
positive pressure ad equate to properly fill and seal the joint. T he silicone sealant shall be t ooled with
light pressure to spread the sealant against backing material and the joint surfaces before a skin forms. A
tool with convex profile shall be used to keep the sealant within the joint. Soap or water shall not be used
as a tooling aid. Remove masking tape as soon as silicone joint is tooled.
Tolerance: A tolerance of + 3 mm shall be allowed in the width of silicone joints. The depth of the joints at
throat shall not be less than 6 mm.
Vol-2 , 2013
21.5 REFLECTIVE GLASS
21.5.1 Definitions
(i) Shading Coefficient: The shading coefficient is the ratio of total solar transmittance to the
transmittance through 3.2 mm (1/8”) clear glass. Windows with low shading coefficient values
improve comfort for building, lower the total cooling load of the building and help smooth out of
the difference in cooling loads between perimeter & core zones.
(ii) Luminous Efficacy Constant (Ke) indicates a windows relative performance in rejecting solar
heat-while transmitting day light. It is the ratio of the visible transmittance to the shading coefficient;
clear glass which lets in roughly equal amounts of visible light and solar near-infrared energy has a
Ke close to 1.0. The solar radiation contains about 50% invisible near-infrared & ultra violet light.
Therefore, a perfectly selective glazing, which would all allow visible light pass through while
blocking all of the invisible near-infrared & ultraviolet light, would have Ke of about 2.0.
(iii) Resistance to Heat Conduction (R-valve): It is a measure of resistance to heat flow that occurs
because of temperature difference between the two sides of the windows. The inverse of R-value
is termed as U-value.
21.5.2.1 Types of Coatings: There ar e t wo t ypes of reflective gl ass, P yroltic ( Hard) coated and v acuum
(soft) coated.
(i) Pyroltic : It is a c oating applied during glass m anufacture. The coating is fused into the g lass a t
1200°C.
(ii) Vacuum Coated Glass: It involves the deposition of metal particles on the glass surface by a
chain reaction in a vacuum vessel. It is often called a soft coat; because the coating is more
susceptible to damage than hard coat glass. Where toughening of product is required, the
product must be toughened first & then vacuum coated. Vacuum coated products have better
shading coefficient values than pyroltic products.
Vol-2 , 2013
21.5.2.3 Testing: The reflective glass shall be tested for the followings:
(i) Physical/Field Test: In a t rue re flective glass, when a pointed p encil is placed, then tip of pencil
(physical) & image should coincide.
(ii) Lab. Test: In the lab, the reflective glass shall be tested for the parameter specified in 21.5.2.2
above.
Actual measurement of openi ngs left at site for different type of door /window etc. shall be taken. The
fabrication of t he i ndividual door /windows/ventilators et c. s hall be done as per t he ac tual s izes of t he
opening left at site. The frames shall be truly rectangular and flat with regular shape corners fabricated to
true right angles. The frames shall be fabricated out of section which have been cut to length, mitered and
jointed m echanically us ing appropriate m achines. M itered j oints s hall be c orner crimped or f ixed with
self t apping stainless s teel s crews u sing ex truded al uminium c leats of req uired l ength and prof ile. All
aluminium w ork shall provide for replacing da maged/broken gl ass panes w ithout hav ing to remove or
damage any member of exterior finishing material.
In t he case of composite windows a nd doors, t he diff erent units are t o b e ass embled first. The
assembled composite units shall be checked for line, level and plumb before final fixing is done.
Engineer-in-Charge i n hi s s ole di scretion may al low t he uni ts t o be as sembled in their final l ocation i f the
situation so warrants. S nap beadings a nd EPDM gasket shall be f ixed as per the detail shown in the
shop drawings.
Where al uminium c omes i nto c ontact w ith s tone m asonry, b rick w ork, c oncrete, pl aster or di ssimilar
metal, it shall be c oated with an appr oved insulation lacquer, paint or plastic tape to ensure that
electrochemical c orrosion i s av oided. Insulation material s hall be trimmed off t o a clean f lush l ine o n
completion.
The contractor shall be responsible for the doors, windows etc. being set straight, plumb, level and for
their satisfactory operation after fixing is complete.
21.6.3 Measurements
All t he aluminium s ections i ncluding s nap b eadings f ixed in pl ace s hall b e m easured in r unning m eter
along the outer periphery of c omposite section c orrect to a millimeter. T he weight calculated on the basis
of ac tual a verage ( average of f ive s amples) w eight of c omposite s ection i n k ilogram c orrect t o t he s econd
place of decimal shall be taken for payment (weight shall be taken after anodizing). The weight of cleat
shall be added for payment. Neither any deduction nor anything extra shall be paid for skew cuts.
343 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
21.6.4 Rate
The rate shall include the cost of all the materials, labour involved in all the operations as described in
nomenclature of item and particular specification.
21.7.1 Terminology
The components of doors, windows and ventilators shall be defined as in Figure 21.1 below.
Head of Frame
Lintel Level
Ventilator
Transome
Sill Level
Lugs Mullion Sill
Kick Plate Bottom Rail
Floor Level
SECTION XX
Vol-2 , 2013
21.7.2 Standard Sizes, Tolerances and Designations
The t ypes a nd t he o verall s izes of al uminium doors, w indows and ventilators s hall be as gi ven i n
Figure 21 .2. T heir siz es are de rived aft er allowing 1.25 m m clearances on all the four sid es for th e
purpose of fitting the doors, windows and ventilators into modular openings .
57.5 97.5 117.5 147.5 177.5
6 HF 6 10 HF 6 12 HF 6 15 HF 6 18 HF 6
6 HT 6 10 HT 6 12 HT 6 15 HT 6 18 HT 6
6 HC 6 10 HC 6 12 HC 6 15 HC 6 18 HC 6
6 HF 9 10 HF 9 12 HF 9 15 HF 9 18 HF 9 57.5
6 HS 9 10 HS 9 12 HS 9 15 HS 9 18 HS 9 6 HT 9
6 HF 12 10 HF 12 12 HF 12 15 HF 12 18 HF 12
6 HS 12 10 HS 12 12 HS 12 15 HS 12 18 HS 12
6 HF 15 10 HF 15 12 HF 15 15 HF 15 18 HF 15
6 HS 15 10 HS 15 12 HS 15 15 HS 15 18 HS 15
77.5
8 HF 6 8 HT 6 8 HC 6
6 HF 21 8 HS 21 12 HS 21
No te : 1 .Windows without horizontal glazing bars shall be designated by 'N' in place of 'H' in the range shown.
No te : 2. Doors and side lights shall only be coupled with 12 module (117.5 cm) high windows.
Vol-2 , 2013
21.7.3 Tolerances
The sizes for doors, windows and ventilators frames shall not vary by more than ±1.5 mm.
21.7.4 Material
Aluminium alloy extruded sections used in the manufacture of extruded window sections shall
conform t o IS 7 33. H ollow al uminium alloy s ections u sed sh all c onform t o IS 12 85. D imension and
weight per metre run of the extruded sections shall be as given in Figure 21.3.
46.0 20.6
2
3.2 3.2 3.2 120°
3.2
4.8
19.0
19.0
25.4
25.4
19.0
19.0
3.2
4.8 12.7
GLAZING BAR AI-T6 GLAZING BAR AI-T7 GLAZING BAR AI-T8 MULLION BAR AI-F4B OPENING FRAME AI -CF6
0.306 kg/m 0.334 kg/m 0.363 kg/m 0.837 kg/m 0.614 kg/m
15.9 3.2 9.5 15.9 3.2 9.5 19.0 3.2 28.6 3.2
R R
2 3.2 3.2
22.2
2 2 29.0
29.0
29.0
29.0
22.2
2 8.4 8.4
3.2
R R 3.2 3.2
INSIDE FRAME AI -HFX5 INSIDE FRAME AI -HFX6 INSIDE FRAME BAR AI-FX5 INSIDE FRAME BAR AI-FX6
0.73 kg/m 0.73 kg/m 1.033 kg/m 1.033 kg/m
13.5
8 R 3.2 R
19.8
4.8 R 3.2
29.0
3.2
32.5
33.3
3.2
R 3.2
55.6
R R
55.6
120° 3.2
15.9
3.2
2
3.2
VENTILATOR BAR AI -F5 OUTSIDE FRAME AI-FX8 OUTER BAR FOR COUPLING AI-HK11B COUPLING WITH WEATHER
0.614 kg/m 0.805 kg/m VENTILATOR AI-F8 1.15 kg/m BAR AI-HK12B
0.63 kg/m 1.61 kg/m
Note 1 : All radii R = 1.6 mm
Note 2 : The weights of sections per metre length as indicated are nominal.
All dimensions in millimeters
Fig. 21.3 : Extruded Aluminium Sections for Doors, Windows and Ventilators
21.7.6 Screws
Screws threads of machine screws used in the fabrication of aluminium doors, windows and
ventilators shall conform to IS 1362.
Vol-2 , 2013
TABLE 21.6
Glass Sizes (Clearance Allowed)
(Clause 21.7.5)
Designation Quantity Glass size Width X Designation Quantity Glass size Width X
Height cm Height cm
No Glazing Bar Fixed Type No Glazing Bar Centre-Hung Type
6NF6 1 53.0 x 53.0 6NC6 1 46.0 x 46.0
10NF6 2 45.0 x 53.0 10NC6 2 42.5 x 46.0
12NF6 2 55.0 x 53.0
12NC6 2 52.5 x 46.0
15NF6 {2 45.0 x 53.0
{1 47.5 x 53.0 15NC6 {2 45.0 x 53.0
18NF6 {2 55.0 x 53.0 {1 43.5 x 46.0
{1 57.5 x 53.0 18NC6 {2 55.0 x 53.0
6NF9 1 53.0 x 83.0 {1 53.5 x 46.0
10NF9 2 45.0 x 83.0 8NC6 1 66.0 x 46.0
12NF9 2 55.0 x 83.0 No Glazing Bar Side-Hung Type
15NF9 {2 45.0 x 83.0 6NS9 1 50.0 x 80.0
{1 47.5 x 83.0 10NS9 2 43.5 x 80.0
18NF9 {2 55.0 x 83.0
{1 57.5 x 83.0 12NS9 2 52.5 x 80.0
6NF12 1 53.0 x113.0 15NS9 {2 43.5 x 80.0
10NF12 2 45.0 x 113.0 {1 47.5 x 83.0
12NF12 2 55.0 x 113.0 18NS9 {2 52.5 x 80.0
15NF12 {2 45.0 x 113.0 {1 57.5 x 83.0
{1 47.5 x 113.0 6NS12 1 50.0 x 110.0
18NF12 {2 55.0 x 113.0 10NS12 2 43.5 x 110.0
{1 57.5 x 113.0 12NS12 2 52.5 x 110.0
6NF15 {1 53.0 x 27.0 15NS12 {2 43.5 x 110.0
{1 53.0 x 113.0
{1 47.5 x 113.0
10NF15 {2 {45.0 x 27.0
{2 {45.0 x 113.0 18NS12 {2 53.0 x 27.0
12NF15 {2 55.0 x 27.0 {1 50.0 x 110.0
{2 55.0 x 113.0 6NS15 {1 53.0 x 27.0
15NF15 {2 45.0 x 27.0 {1 50.0 x 110.0
{1 47.5 x 27.0 10NS15 {2 45.0 x 27.0
{2 45.0 x 113.0 {2 43.5 x 110.0
{1 47.5 x 113.0 12NS15 {2 55.0 x 27.0
18NF15 {2 55.0 x 27.0 {2 52.5 x 110.0
{1 57.5 x 27.0
{2 55.0 x 113.0 15NS15 {2 45.0 x 27.0
{1 57.5 x 113.0 {1 47.5 x 27.0
8NF6 1 73.0 x 53.0 {2 43.5 x 110.0
6NF21 {1 53.0 x 84.5 {1 47.5 x 113.0
{1 53.0 x 27.5 18NS15 {2 55.0 x 27.0
{1 53.0 x 56.0 {1 57.5 x 27.0
No Glazing Bar Top-Hung Type {2 52.5 x 110.0
6NT6 1 50.0 x 50.0 {1 57.5 x 113.0
10NT6 2 44.5 x 50.0 8NS21 {1 66.0 x 81.0
12NT6 2 54.5 x 50.0 {1 56.0 x 27.5
15NT6 {2 45.0 x 53.0 {1 66.0 x 56.0
{1 45.5 x 50.0
18NT6 {2 55.0 x 53.0 12NS21 {2 50.5 x 81.0
{1 54.5 x 50.0 {2 50.5 x 56.0
8NT6 1 70.0 x 50.0 {1 50.5 x 27.5
6NT9 {1 50.0 x 51.5 {1 40.5 x 27.5
{1 53.0 x 27.5
Vol-2 , 2013
Designation Quantity Glass size Width X Designation Quantity Glass size Width X
Height cm Height cm
Horizontal Glazing Bar Fixed Type Horizontal Glazing Bar Centre-Hung Type
6HF6 2 53.0 x 26.0 6HC6 2 46.0 x 22.5
10HF6 4 45.0 x 26.0 10HC6 4 42.5 x 22.5
12HF6 4 55.0 x 26.0 12HC6 4 52.5 x 22.5
15HF6 {4 45.0 x 26.0 15HC6 {4 45.0 x 26.0
{2 47.5 x 26.0 {2 43.5 x 22.5
18HF6 {4 55.0 x 26.0 18HC6 {4 55.0 x 26.0
{2 57.5 x 26.0 {2 53.5 x 22.5
6HF9 {2 53.0 x 27.5 8HC6 2 66.0 x 22.5
{1 53.0 x 26.0 Horizontal Glazing Bar Side-Hung Type
10HF9 {4 45.0 x 27.5 6HS9 3 50.0 x 26.0
{2 45.0 x 26.0 10HS9 6 43.5 x 26.0
12HF9 {4 55.0 x 27.5 12HS9 6 52.5 x 26.0
{2 55.0 x 26.0 15HS9 {6 43.5 x 26.0
15HF9 {4 45.0 x 27.5 {2 47.5 x 27.5
{2 45.0 x 26.0 {1 47.5 x 26.0
{2 47.5 x 27.5
{1 47.5 x 26.0 18HS9 {6 52.5 x 26.0
{2 57.5 x 27.5
18HF9 {4 55.0 x 27.5
{2 55.0 x 26.0 {1 57.5 x 26.0
{2 57.5 x 27.5 6HS12 {2 50.0 x 26.0
{1 57.5 x 26.0 {2 50.0 x 27.5
6HF12 4 53.0 x 27.5 10HS12 {4 43.5 x 26.0
10HF12 8 45.0 x 27.5 {4 43.5 x 27.5
12HF12 8 55.0 x 27.5 12HS12 {4 52.5 x 26.0
15HF12 {8 45.0 x 27.5 {4 52.5 x 27.5
{4 47.5 x 27.5 15HS12 {4 43.5 x 26.0
18HF12 {8 55.0 x 27.5 {4 43.5 x 27.5
{4 57.5 x 27.5 {4 47.5 x 27.5
6HF15 {1 53.0 x 27.0 18HS12 {4 52.5 x 26.0
{4 53.0 x 27.5 {4 52.5 x 27.5
10HF15 {2 45.0 x 27.0 {4 57.5 x 27.5
{8 45.0 x 27.5 6HS15 {1 53.0 x 27.0
12HF15 {2 55.0 x 27.0 {2 50.0 x 26.0
{8 55.0 x 27.5 {2 50.0 x 27.5
15HF15 {2 45.0 x 27.0 10HS15 {2 45.0 x 27.0
{1 47.5 x 27.0 {4 43.5 x 26.0
{8 45.0 x 27.5 {4 43.5 x 27.5
{4 47.5 x 27.5 12HS15 {2 55.0 x 27.0
18HF15 {2 55.0 x 27.0 {4 52.5 x 26.0
{1 57.5 x 27.0 {4 52.5 x 27.5
{8 55.0 x 27.5 15HS15 {2 45.0 x 27.0
{4 57.5 x 27.5 {1 47.5 x 27.0
8HF6 2 73.0 x 26.0 {4 43.5 x 26.0
6HF21 6 53.0 x 27.5 {4 43.5 x 27.5
Horizontal Glazing Bar Top-Hung Type {4 47.5 x 27.5
6HT6 2 50.0 x 24.5 18HS15 {2 55.0 x 27.0
10HT6 4 44.5 x 24.5 {1 57.5 x 27.0
12HT6 4 54.5 x 24.5 {4 52.5 x 26.0
15HT6 {4 45.0 x 26.0 {4 52.5 x 27.5
{2 44.5 x 24.5 {4 57.5 x 27.5
18HT6 {4 55.0 x 26.0 8HS21 {1 66.0 x 24.0
{2 54.5 x 24.5 {4 66.0 x 27.5
6HT9 {1 50.0 x 26.0 {1 56.0 x 27.5
{1 50.0 x 24.5 12HS21 {2 50.5 x 24.0
{1 53.0 x 27.5 {9 50.5 x 27.5
8HT6 2 70.0 x 24.5 {1 40.5 x 27.5
Vol-2 , 2013
21.7.7 Fabrication
Frames: Frames shall be square and flat, the corners of the frame being fabricated to a true right angle.
Both the fixed and ope ning frames s hall be cons tructed of sec tions which have been c ut t o lengt h,
mitered and we lded at the corners. Where hollow sections are used with we lded joints, argon-arc
welding or flash butt w elding sha ll be emplo yed (gas welding or bra zing not to be done). S ubdividing
bars of units shall be tenoned and riveted into the frame.
The location of the parts and det ails of construc tion of the doors, windows and v entilators are
indicated in Fig. 21.4 to 21.11.
Vol-2 , 2013
Fig 21.5 : Mullion with Fixed Glass on one Side and Side Hung on Other Side
Putty Mastic
Fig 21.7 : Coupling Section Extruded for Coupling Windows Side by Side
Putty
Extruded Coupling
Section
25 mm
Mastic Cement
Fig 21.8 : Detail Through Bottom of Fig 21.9 : Coupling Section Extruded having Weather
Top-Hung Ventilator Bar Fitted with Ventilators on top of Windows
Vol-2 , 2013
50 mm
0.90 mm
Al-CE6
Fig 21.10 : Weather Bar over Extruded Opening Shutter with Fixed Light Above
Ventlator
Mastic
Glass Pane
Door
Inside
Horizontal Section of Door
Vol-2 , 2013
21.7.8 Side-hung Shutters
For fixing aluminium alloy hinges, slots s hall be cut in the fix ed frame and the hinges inserted inside and
may be riv eted to the f rame. The hinges shall normally be of the p rojecting type 67 m m wide (Fi g. 21.12).
The aluminium alloy for cast hinges shall conform to IS Designation A-5-M of IS 617. S pecification for
Aluminium and Aluminiu m Alloy Ingots a nd Castings f or Ge neral Engineering Pu rpose and for ex truded
section of h inges to IS Designat ion HE10-WP or HE30-WP of I S 733. The pins for h inges sh all be of
stainless steel of non-magnetic type or aluminium alloy HR30. Irrespective of hinges being anodized or not,
the aluminium alloy pins shall be anodized to a minimum film thickness of 0.025 mm shall be sealed with oil,
wax or lanolin. Non- projecting types of hinges may also be used where ever required. (Fig. 21.13).
Frictions hinges may be provided for side-hung shutter windo ws, in which case peg st ay may not be
required. The working principle of the friction hinges is illustrated in Fig. 21.14.
The handle for side-hung shutters shall be of cast aluminium conforming to IS Designation A-5-M of
IS 617 and mounted on a handle plate welded or riveted to the opening frame in such a way that it could
be fixed before the shut ter is glazed. The handle should have anodized finish with minimum anodic film
thickness of 0.015 mm. The handle shall have a two points nose which shall engage with an aluminium
striking plate on the fixed frame in a slightly open position as well as in a fast position (Fig. 21.15). The
height of th e handles in eac h t ype of side-hung sh utters shall be fixed in approximate po sition a s
indicated in Fig. 21.16.
22 mm
67 mm Welded
Welded or Welded
Riveted
Vol-2 , 2013
Fixing Screw
33 mm
Shake Proof
Washer
3 mm
Wedge Shape
Striking Plate
11 mm Round
or Square Hole
4 mm
10.3 mm
117.5 cm
Fig. 21.16: Position of Handle Plates in Relation to Heights of ‘HS’ Type Windows
73 mm 80 mm to Web
30 mm
22 mm
20 mm
8 mm PIN
Locking Bracket
18 mm
75 mm 65 mm 65 mm 75 mm
300 mm
Fig. 21.17 : A Typical Peg-Stay for Side-Hung Shutters and Top-Hung Ventilators
Vol-2 , 2013
The peg stay shall be either of cas t aluminium conforming to IS 617 or folded from IS Desi gnation
NS4 a luminium a lloy sh eet c onforming to I S:737 s pecification for wrou ght al uminium and a luminium
alloys, Sheet and s trip. I t s hall be 3 00 mm long , c omplete wi th peg an d locking brackets (Fi g. 21.17).
The stay shall have holes for keeping the shutt er open in three different positions. The peg and locking
bracket shall be riveted or welded to the fixed frame.
Alternatively, and i f specifically required by the purchaser, side-hung shutters may be fitted with a n
internal removable fly screen of 0.375 mm wire and equivalent to IS Sieve 100 in a 0.900 mm aluminium
alloy sheet conforming to IS Designation NS3-1/2H of IS 737 applied to the outer frame of the shutter
by case or extruded alumin ium a lloy turn-buckle at the jambs (F ig. 2 1.18) and by aluminium or p lated
bronze shoes at the sill to allow of the screen being readily removed, and with a rotor operator at the sill
to permit the operation of the shutter through an angle of 90º (Fig. 21.19). On fly-screened shutters the
peg stay is omitted and the normal handle shall be replaced by a locking handle to hold the shutter in the
fast position.
Fig. 21.18 : Detail Through Jamb Fig. 21.19 : Typical Rotor Operator for Side-Hung
Showing Turnbuckle Shutters Fitted with Fly Screens
The pegs stay sha ll be 300 mm lon g as in side-hung shutter (Fig. 21.1 7). The l ocking bracket shall
be fixed to the fixed frame.
Cast aluminium conforming to IS Designation A-5-M of IS 617 or bronze which shall be either chromium-
plated or cadmium-plated spring cat ch shall be fitted in th e centre of t he top b ar of the v entilators fo r th e
operation o f the v entilator. This s pring catch shall be secured to the frame a nd sh all c lose into aluminium
catch plate riveted or welded to the outside of the outer ventilator frame bar (Fig. 21.21).
Vol-2 , 2013
Below Pivot Above Pivot
5 mm
Aluminium or cadmium plated brass cord pulley-wheel in an alumin ium bracket shall be fitted at the
sill of the ventilator with aluminium or galvanized or cadmium plated steel screw or, alternatively, welded
together with an aluminium cord eye riveted or welded to the bottom inner frame bar of the ventilator in a
position corresponding to that of pulley (Fig. 21.22).
Cord Eye
10 mm
Drill for Rivets
Pulley
6 mm
8 mm
15 mm 15 mm Drill and
Tap MS
Fig. 21.22 : Cord Eye and Pulley Arrangement for Centre-Hung Ventilator
21.7.11 Doors
The outer fixed frame shall be of section A1-FX8. The shutter frame shall be of either hollow sections
A1-HFX5 and A1-HFX6 (Fig. 21.3 and Fig. 21.11).
Vol-2 , 2013
The kick panels shall be of 1.25 mm aluminium alloy sheet conforming to IS De signation NS3-1/2H
of IS 737 s pecification for Wrought Aluminium and Al uminium A lloys, S heet and strip and shall be
screwed to the frame and the glazing bar.
Hinges –Cast of extruded aluminium alloy hinges for doors shall be of the same type as in the windows
but of larger size. The hinges shall normally be of the 50 mm projecting type (Fig. 21.23). Non-projecting
type of hinges may also be used (Fig. 21.24).
The handle for doors may be of the design indicated in Fig. 21.25.
A suitable lock for the door operable either from inside or outside shall be provided.
Note: From the point of view of security, the lock wh ich is operable from only one side is better and in
the case of such locks, a bolt shall be provided to make them inoperable from the other side.
Projecting Hinges
50 mm (Welded or Riveted)
to allow Door to Fold
Back against the wall
Plain Hinge
Vol-2 , 2013
Outside View Inside View
In double shutter doors the first closing shutter shall ha ve a c oncealed al uminium alloy bo lt at top
and bottom (Fig. 21.26). It shall be so constructed as not to work loose or drop by its own weight.
Single and double shutter doors may be provided with a three-way bolting device (Fig. 21.27). Where
this is provided in the case of double shutter door, concealed aluminium bolts may not be provided.
90 mm
87 mm
24 mm
Bolt
Vol-2 , 2013
Upper Locking Strip ‘A’ Riveted to
Plate
Strip Locking Strip
Tee Bars
A
Washer
Lever
Stopper
70 mm
Door Section
Guide Pin Riveted
to the Section
at the Bank
Lock
25 mm Long
Slot in the
Locking Strip
100 mm
Lower Locking
Strip Tee B ars
Mastic
Putty
Fig. 21.28 : Coupling Section Extruded for Coupling Door to Window or Side Light
358 | HO Civil Specifications Volume - 2
Vol-2 , 2013
21.7.13 Weather Bar
Where a coupling member is fitt ed o ver an external opening shutter, t he coupling membe r s hould
incorporate an integrally extruded weather bar (Fig. 21.9).
19.1
57.5
19.1
19.1
87.5
19.1
19.1
49.4
117.5
30
19.1
49.4
147.5
59.9
19.1
57.5
19.1
19.1
49.4
30
207.5
64.0
45.0
19.1 19.1 19.1
Fig. 21.29 : Chart Showing Approximate Position of Fixing Holes and Number of Fixing Lugs
Vol-2 , 2013
The fixing screws and lugs shall be as given in Table 21.7
TABLE 21.7
21.7.15 Finish
Alumiumum doors, windows and ventilators may be supplied in either matt, scratch-brush or polished
finish. The y may, additionally, a lso be anodized, if so re quired by t he Engi neer-in-charge. If co lour
anodizing is to be done then only approved light-fast shades should be used.
A thick la yer of clear transparent lac quer based on meth acrylates or ce llulose b utyrate, shall be
applied on aluminium d oors, windo ws and ventilators b y t he supplier to protec t t he surface f rom wet
cement during installation. This lacquer coating shall be removed after installation is completed.
21.7.16 Glazing
Glazing shall be provided on the outside of the frames
If required, glazing clips may be provided a s extra fittings. Four glazing c lips may be provi ded per
glass pane, except for door type 8HS21 where t he glazing clips shall be six per glass pane. In cas e of
doors, wi ndows and ve ntilators without horizontal glazing bars the glazing clips sha ll be spaced
according to the slots in the vertical members, otherwise the spacing shall be 30 cm.
Note: Glazing clips are not usually pro vided for normal size glass panes. Where large size glass panes
are required to be used or where the door or the window is located in heavily exposed situation,
holes for g lazing clips have to be dri lled prior to fabricat ion and cannot be done at any late r
stage. Use of glazing clips, where necessary, shall be specified while placing the order.
21.7.17 Packing
All doors, windows and ventilators shall be dispatched with the opening parts su itably secured to
preserve alignment when fixing and glazing.
Fixing lugs, coupling fittings and all hardware shall be dispatched separately.
21.7.18 Marking
All doors, windows and ventilators shall be suitably marked on the frames with a mark identifying the
manufacturer and the type.
The units may also be marked with the BIS Certification Mark.
360 | HO Civil Specifications Volume - 2
Vol-2 , 2013
21.8 FITTINGS
21.8.5 Measurement
Refer Para 21.6.3.
21.8.6 Rate
Refer Para 21.6.4.
21.9 LOUVERS
Aluminium extruded sections (anodized or power coated) are used for providing Louvers in
aluminium door, window & partition for ventilation.
21.9.1 Fabrication
Refer Para 21.6.1.
21.9.2 Measurements
Refer Para 21.6.3.
21.9.3 Rate
Refer Para 21.6.4.
(b) Desiccant
The desiccant shall be Neftomol 3 A Chemetall or equivalent.
Vol-2 , 2013
The desiccant filled in the al uminium s pacer b ar s hall be s ynthesized crystalline compounds of
Aluminium H ydroxide, Caustic Soda and S odium Silicate which a bsorbs w ater m olecules. T he
desiccant shall be of 3 A size ( A means Angstrom). T he qua ntity of de siccant used shall not be
less t han 35 gm/m l ength of s pacer b ar. F illed spacer b ar f rame s hall n ot be s tored f or m ore
than 6 hours before a ssembly a nd sealing of t he unit t o ensure proper f unctioning of the
desiccant. The contractor shall submit documentary proof of using the above material in the
work.
Measurement
The hei ght an d w idth of do uble gl azed/single glazed unit (the area of gl ass uni t out side the s nap
beading s hall onl y b e measured) as fixed i n pl ace s hall be measured c orrect to one c entimeter and ar ea
calculated in sqm. correct to second place of decimal shall be taken for payment.
Rate
The rate shall include the cost of all the materials, labours involved in all the operations as described in
nomenclature of item and particular specification.
Vol-2 , 2013
22.0 : WATER
PROOFING TREATMENT
Vol-2 , 2013
CONTENTS
Clause No. Brief Description Page No.
List of Bureau of Indian Standards (BIS) Codes 366
22.2 Integral Cement based Water Proofing Treatment on the Vertical Surface 367
of Under-Ground Structures - DELETED
22.5 Water Proofing Treatment in Sunken Portion of WCs, Bathrooms etc. 370
22.7 Integral Cement based Water Proofing Treatment with Brick Bat Coba 371
22.11 Water Proofing Treatment with APP (Atactic Polypropylene Polymeric) 380
Membrane - DELETED
22.12 Five Layered Water Proofing treatment with Atactic Polypropylene 380
Polymer Modified Prefabricated Membrane
Fig. 22.2 Water Proofing Horizontal Surfaces from Inside of a U.G. structure 388
Fig. 22.4 Position of Horizontal and Vertical Waterproofing Treatment in Sunken 389
Portion of W.C./Kitchen and the like
Vol-2 , 2013
Fig. 22.6 Integral Cement based Waterproofing Treatment with Brick-bat Coba 390
Over a RCC Slab
Fig. 22.11 Five Course Water Proofing Treatment with APP Modified Polymeric 393
Membrane
Fig. 22.12 Five Layer Water-Proofing Treatment with APP Modified Prefabricated 393
Membrane
Vol-2 , 2013
LIST OF BUREAU OF INDIAN STANDARDS (BIS) CODES
Vol-2 , 2013
22.0 WATER PROOFING TREATMENT
22.0 TERMINOLOGY
Water Bars
Water bars are preformed strips of impermeable materials which are embedded in the concrete
during construction.
Expansion Joints
Joints provided in the structure to allow for thermal expansion/construction.
Blended Cement
Cement mixed with water proofing compound in liquid or powder form.
The vertical s urfaces of t he d epressed / sunken p ortion should be hacked with a h acking t ool j ust
after the shuttering is removed.
In c ase of ol d w ork, the w ater pr oofing t reatment on s uch s urfaces s hall b e permitted af ter m aking
proper spatter dash key.
Fixing the ‘P’ trap in po sition and all o ther pipes work including the water escape pipe shall b e fixed
properly and the holes should be plugged carefully before taking up the water proofing work.
The c onsistency o f the s lurry s hould be s uch that 4.4 k g. o f b lended c ement w ith w ater pr oofing
compound is used per sq. m etre area of s urface to b e t reated. T he slurry should be started f rom the
vertical faces towards the bottom of the floor as shown in Fig. 22.4. Particular care should be taken to
see that the slurry is applied to corners without leaving any gap.
Vol-2 , 2013
22.3.4 2nd Course
Immediately on ap plying the b lended c ement s lurry on t he s urface to be treated c ement pl aster 20
mm thick in CM 1:3 (1 blended cement: 3 coarse sand) shall be applied both on vertical and horizontal
surfaces t aking pa rticular care t o c omplete t he ent ire depres sed/ s unken port ion of W C within a day s o
that the plaster can be done without any joint. Junctions shall be properly rounded. The surfaces of the
plaster shall be left rough but finished in one plain and cured for a week.
On c ompletion of t he c uring period bot h ho rizontal and v ertical s urfaces s hall be c leaned p roperly
and gently and allowed to dry.
The projections of pipes and ‘P’ trap outlet etc. inside the depressed/sunken portion of WC shall also be
cladded with water proofing treatment layer upto a height of 150 mm, using a coat of bitumen with PVC
sheet complete.
The s urfaces of d epressed/sunken portion of WC s hall not be l eft w ithout covering w ith specified
filling m aterial and bas e concrete, ot herwise the PVC sheet layer m ay be t ampered by th e labour
working in the vicinity.
Fixing up of WC pan, filling specified material and the top base concrete should be done as early as
possible and the top horizontal layer of water proofing may be taken up later i.e. just before laying the
floor tiles.
22.3.7 Measurement
Length and breadth shall be m easured al ong t he f inished surface correct to a c m. and area shall be
worked out to nearest 0.01 sqm. No payment however shall be m ade for the 100 m m overlap of PVC
Sheet over the roof slab.
22.3.8 Rate
The rate shall include the cost of labour and materials involved in all the operations described above.
22.4.1 Water stops conforming to IS 12200 for construction/expansion joints should be fabrication from a
plastic c ompound, the b asic r esin of w hich s hall be pol yvinyl c hloride. T he c ompound s hall c ontain
additional re sin/ plasticizer i nhibitors or other m aterials such t hat when t he m aterials i s c ompounded i t
shall meet the requirement given in IS 15058.
Vol-2 , 2013
22.4.2 Type of Joints for which Water Bars are Provided
The water bars are provided only for the movement of joints in a water retaining structure.
Complete Contraction Joint: This i s a m ovement j oint w ith del iberate di scontinuity b oth i n c oncrete a s
well as the reinforcement but no initial gap is maintained between the c oncrete on either s ide of the joint.
This joint is intended to accommodate the contraction of the concrete.
Partial Contraction Joint: This i s a m ovement j oint w ith d eliberate discontinuity i n c oncrete b ut n o
water bar i s prov ided and no di scontinuity i s prov ided i n s teel. N o i nitial gap i s m aintained bet ween t he
concrete on either side of joint.
Expansion Joint: This i s al so a m ovement j oint w ith c omplete di scontinuity i n bot h rei nforcement an d
concrete. It is intended to accommodate either expansion or contraction of the structure.
In ge neral s uch joint requ ires the prov ision of an initial gap betw een the adjoining pa rts o f the
structure which accommodates expansion or contraction of the structure.
Water bars of c opper, sheet l ead, n atural or s ynthetic r ubber a nd plastic such as p olyvinyl c hloride
(PVC) ar e al so used. T hese bar s c omprise of c entral l ongitudinal hol low t ube w ith t hin w alls and s tiff
wings of about 150 mm width.
Out of the m etals available c opper is m ost s uitable as r egards ductility, r esistance t o c orrosion i n air,
water a nd concrete. H owever, i t m ay be at tacked by s ome w astes. I f s heet l ead i s u sed i t s hould b e
insulated f rom c oncrete b y a good c oat of bituminous or suitable c omposition. N atural s ynthetic rubbe r
and plastics have very considerable advantage in handling, splicing and in making intersections.
Galvanized iron s heets m ay also b e used w ith the s pecific permission of the Engineer-in-charge
provided the liquid stored or the atmosphere around the liquid retaining structure is not excessively
corrosive i.e. sewage.
The strip water bars described as above, while placing in position has to be passed through the end
shutter of the first placed c oncrete with t he result the shuttering at t his point s hould be perfectly water
tight ot herwise c ement s lurry m ay e scape f rom t he c oncrete bei ng l aid and w ill ultimately w eaken t he
structure. Therefore to avoid the above problem one can prefer moulded type of water bar.
The des ign of the m oulded w ater bar w ith s everal pr ojections need t o be p assed t hrough t he end
shutter w hile pl acing the same in pos ition. A nother m ain adv antage o f this w ater bar is that s ince it
occupies bigger proportion of t he t hickness o f t he joint i t would l engthen t he s hortest al ternative water
path through the concrete.
22.4.4 It is important to ensure proper compaction of concrete around the water bar. Proper cover to all the
reinforcement shall be maintained. Sometimes to increase the bond the holes are provided in the
copper w ater bars but in the long run it proves to be disadvantageous as it shortens the path of water
through concrete. Water bars should be pl aced at the centre of the wall or if it is to be pr ovided away
from the centre its distance from either face o f the wall shall not be less than h alf o f the width o f water
bar or as specified/directed by the Engineer-in-charge.
Vol-2 , 2013
22.4.5 Covers Plates for Joint
Sometimes joint cover plates have to be used for expansion joints mainly to avoid the risk of a fault
in the water bar which is embedded. T he plates to be us ed should be ei ther copper or sheet lead. In
case the copper plates are to be us ed, it should b e clamped to the concrete face on eac h side of the
joint. T o ens ure w ater t ightness s uitable gas ket s hall be us ed. J oint c over pl ates of s heet l ead are al so
used and fixed on the joints. In this case the edges may return into grooves formed in the concrete and
can be m ade completely water tight by lead caulking. Faces of the concrete to which sheet lead is to be
fixed s hould be pa inted w ith b ituminous or o ther s uitable c omposition and the lead s heet s hould be
similarly coated before fixing.
In concrete walls, the vertical movement joints should normally be placed at a maximum spacing of
0.75 m i n reinforced w alls. The maximum l ength des irable bet ween v ertical movement joints will depe nd
upon the tensile strength of the walls and may be increased by suitable reinforcements.
Amongst t he m ovement j oints i n f loors a nd walls as m entioned above, e xpansion j oint s hould be
normally be pr ovided at spacing o f not more than 30 m be tween s uccessive ex pansion joints or bet ween
the end of the structure and the next expansion joint, all other joints being of the contraction type.
In case of e xpansion joints the filling of these with bitumen filler, bitumen felt or any such m aterial
etc. s hall b e pa id f or separately i n r unning m etre. The m easurement shall b e t aken upto t wo p laces of
decimal stating the depth and width of joint.
In case joint cover plates either of copper or sheet lead with ancillaries are provided, these shall be
measured and paid for separately.
22.4.7 Measurement
Length shall be m easured c orrect t o a c m and net quant ities s hall be c alculated upt o t wo p laces of
decimal.
Each c ategory of w ater s tops/bar s uch a s P VC, c opper s pecifying w idth, t hickness s hall be
measured and paid for separately.
22.4.8 Rate
The rate shall include all labour and materials in all the operations described above.
Vol-2 , 2013
On d eciding t he correct quantity o f w ater re quired pe r sq m. area th e re quired q uantity of slurry
should be prepared which can be applied over the desired surface within half an hour of mixing with
0.488 kg. of grey c ement + 0.253 k g. water proof ing c ompound as per m anufacturer specifications + x
litres of w ater per s qm. area a nd t he required qu antity of s lurry thus prepared s hould on ly be us ed for
first application.
The first l ayer shall b e applied with painting brushes over t he specified and dampened area
carefully including the corners, holes on the s urfaces and joints o f p ipes in concrete etc. and the
application s hould continue a t least upto 150 m m he ight o f fixtures o f pipes from the s urface. T he
surface on application shall be air cured for 4 hours.
The application of 2nd layer of slurry is same as for first layer as detailed in clause 22.5.3.
The applied surface shall be allowed to air cure for 4 hours and thereafter water curing shall be done for
full 48 hours.
In c ase no f urther w ork a s des cribed abov e i s t o b e t aken up i mmediately on c ompletion of w ater
proofing tr eatment du e t o an y re ason it i s re commended t o pr otect t he t reated portion w ith c ement
plaster 1:4 as a protective layer for which separate payment shall be made to the contractor.
22.5.5 Measurement
Length and breadth shall be m easured al ong the f inished surface correct to a c m and area shall be
worked out to nearest 0.01 sqm.
22.5.6 Rate
The r ate shall i nclude t he c ost of all l abour a nd materials i nvolved i n al l t he operations described
above. The cost of plastering shall be measured and paid for separately.
22.7 INTEGRAL CEMENT BASED WATER PROOFING TREATMENT WITH BRICK BAT COBA (Fig. 22.6)
22.7.1 Before taking up the work the preliminaries to be attended shall be exactly same as described in
clause 22.6.1.
Depending upon t he ar ea o f surface t hat has t o be c overed, t he required q uantity of slurry s hould be
prepared using 2.75 kg. blended cement + water per sqm. area to be covered, taking particular care to
see that onl y that m uch quantity of slurry shall b e prepared w hich c an be used within half a n h our of
preparation i.e. before the initial setting time of cement.
Vol-2 , 2013
The prepared slurry shall be applied over the dampened surface with brushes very carefully,
including t he j oints b etween t he f loor s lab a nd t he parapet wall, h oles on t he s urfaces, j oints of p ipes,
masonry/concrete etc.
The application of the slurry should continue upto a height of 300 mm on the parapet wall and also the
groove as s hown i n F ig. 22.6. T he s lurry s hould a lso be appl ied upt o a hei ght of 150 m m ov er pi pe
projections etc.
Brick bat s shall be l aid t o required slope/gradient ov er the bas e coat o f mortar leaving 15 -25 m m gap
between two bats. Cement mortar 1:5 (1 bl ended cement: 5 c oarse sand) shall be poured ov er the brick
bats and joints filled properly. Under no circumstances dry brick bats should be laid over the base coat.
The haunc hes/gola at t he j unction of parapet w all and t he roof s hall be f ormed onl y w ith brick bat
coba as shown in Fig. 22.6.
In case the brick bat coba is laid on the base coat immediately on initial set there will be no necessity of
applying cement slurry over the base coat before laying the brick bat coba. However, if the brick bat coba
is to be laid on the subsequent day, cement slurry prepared as described in clause 22.7.3 shall be applied
over the top surface of the base coat, then only the brick bat coba shall be laid.
The surface of the finishing layer (protective coat) shall be neatly finished with cement slurry
prepared as per clause 22.7.3. The finished surface shall be allowed to dry for a while and then pattern of
300 mm x 300 mm groove, 8 mm deep shall be made over the entire surface.
Vol-2 , 2013
22.7.9 Measurement
The m easurement s hall b e t aken a long t he finished s urface o f t reatment i ncluding t he rounde d and
tapered po rtion at j unction of p arapet w all. Length an d br eadth s hall be m easured c orrect to a c m an d
area shall be worked out to nearest 0.01 sqm. No deduction i n measurement shall be made for openings
or recesses or chimney stacks, roof lights or khurras of area upto 0.40 sqm., nor anything extra shall be
paid for making s uch openi ngs, recesses e tc. F or ar eas ex ceeding 0. 40 sqm., deduc tion w ill be made i n
the measurements for the full openings and nothing extra shall be paid for making such openings.
22.7.10 Rate
The r ate s hall i nclude t he c ost of all l abour a nd materials i nvolved i n al l t he operations d escribed
above.
Six c ourse w ater proofing tr eatment with s elf fi nished felt i s a heavy d uty tre atment su itable f or
important structures.
22.8.1 Materials
22.8.1.1 Self finished felt (Appendix A and B) shall conform to the type and grade given in the
description of the item. This shall be one of the following types:
(i) Type 3 grade 1 hessian base felt conforming in all respects to IS 1322.
(ii) Type 2 grade 1 fibre base bitumen felt conforming to IS 1322.
(iii) Type 2 grade 2 glass fibre base felt conforming in all respects to IS 7193.
22.8.1.2 Bonding Materials: This shall consist o f b lown type pet roleum bi tumen c onforming t o IS 702 or
residual petroleum bitumen conforming to IS 73. The bonding material shall be so s elected as t o
withstand t he local c ondition o f temperature and gr adient satisfactorily. The penet ration o f bi tumen us ed
shall not exceed 40 i n any c ase. S uitable residual type petroleum bi tumen o f penetration 30/40 (IS g rade
S-35), r esidual t ype p etroleum bi tumen w ith higher penetration a nd l ow softening point an d s uitable
blown type petroleum bitumen of IS grade 85/25 or 90/15 of approved quality shall be used.
Where p roprietary brands of bonding m aterials are p roposed t o be used t hey s hall c onform i n all
respects to the specifications in the preceding paras.
22.8.1.3 Stone Grit and Pea-sized Gravel: Stone grit s hall b e 6 m m and d own s ize. Where pea -sized
gravel is used it shall be hard, round and f ree from dust, dirt etc. The stone grit or pe a-sized gravel shall
not b e s pread ov er v ertical and s loping faces o f f lashings a nd a t d rain m ouths. A t these p laces t he
surface shall be painted with two coats of bituminous solution.
Vol-2 , 2013
The quantity of stone grit or pea -sized grav el required for the final c ourse of four or s ix c ourse
treatment with hessian base self finished bitumen felt type 3 grade 1 shall be 6 cubic decimeter/ sqm.
22.8.2.1 The surface to be treated shall have a m inimum slope of 1 i n 120. This grading shall be c arried
out with cement concrete or cement plaster with coarse sand, as per direction of Engineer-in-charge, to the
average thickness required and finished smooth. Such grading shall be paid for separately.
22.8.2.2 Junctions bet ween t he roof and v ertical faces o f par apet walls, chimneys et c. s hall be cased b y
running triangular f illets 7 .5 x 7. 5 c m s ize, i n c ement c oncrete. A t t he dr ain m ouths, t he f illets s hall b e
suitably cut b ack a nd ro unded o ff f or easy application of w ater proofing treatment an d ea sy flo w o f
water. Cement co ncrete w here used sh all be 1:2:4 m ix (1 cement: 2 co arse sa nd : 4 gr aded st one
aggregate 20 m m nom inal size). The provision of fillets shall be deem ed to be c overed by the item of
water proofing and shall not be measured or paid for separately.
22.8.2.3 In existing roof where gola and drip course are provided at the junction of roof and vertical face of
parapet w all, chi mney stacks etc ., these sh all b e dressed suitably an d fini shed sm ooth so as to
ensure an easy and gradual turning of the flashing. Any dismantlement or forming and finishing smooth the
junction f or f orming t he base of t he f lashing s hall not be measured o r pai d f or separately an d s hall be
deemed to form part of the preparation of the surface in the water proofing treatment.
22.8.2.4 While the grading of roof surface is being done, it shall be ens ured that the outlet drain pipe
have been fixed and mouth at the entrance have been eased and rounded off properly for easy flow of
water.
22.8.2.5 When any pipe passes through the roof to be treated, angular fillet of shape shown in Fig. 22.7
shall be bu ilt ar ound it for the w ater p roofing treatment to b e taken ov er it. These fillets s hall no t be
measured or paid for separately.
22.8.2.6 For c arrying ov er and t ucking i n t he w ater proof ing f elts i nto t he parapet w alls, c himney s tacks
etc. a ho rizontal groove 6.5 cm deep, 7.5 cm wide section with its lower edge at not less than 15 cm
above the graded roof surface shall be left on the inner face of the same during construction if possible.
When such gr oove has not been left, the same s hall be c ut out neatly and t he base at rear of the gr oove
shall be finished smooth with cement plaster 1:4 (1 cement: 4 coarse sand). Such cutting of the groove
and its finishing smooth shall be deemed to be part of the water proofing item and shall not be measured or
paid for separately. No deduction shall be made either for not making the groove or when the later has
already been left in the masonry by the construction agency.
22.8.2.7 Tucking in the water proofing felt will be required where the parapet wall exceeds 45 cm in the
height from the graded surface. Where the h eight is 45 cm or l ess, n o g roove will b e required a s the
water proofing treatment will be carried over the top of the parapet wall to its full thickness. In the case of
low dividing walls of height 30 c m or less, outlets therein shall be c ut open for full height and the bottom
and sides shall be r endered smooth and c orners rounded and such treatment shall not be measured an d
paid for separately.
22.8.2.8 Where expansion j oints ar e l eft i n t he slab, t he provision of d warf w alls a nd/or RCC slabs f or
covering them and finishing the surface smooth shall be the responsibility of the construction agency,
which had laid the roof slab and will not be included the operation of water proofing.
22.8.2.9 The graded surface of the roof and concrete fillets and the faces of walls shall be thoroughly
cleaned with wire brushes and all loose scales etc. removed. The surface shall then be dusted off. Any
crack in the roof shall be cut to ‘V’ section, cleaned and filled up flush with cement mortar slurry 1:4
(1 cement: 4 coarse sand) or blown type petroleum bitumen of IS grade 85/25, or approved quality
conforming to IS 702. Such cleaning of the surface or treating the cracks shall not be paid for separately.
Vol-2 , 2013
22.8.3 Priming Coat
Where s o s pecified, or r equired by t he E ngineer-in-Charge f or ex ample u nder s lightly dam p
conditions a pri ming c oat consisting of a b itumen p rimer c onforming t o I S 33 84 s hould be appl ied with
brush on the roof and wall surface at 0.24 litres per sqm to assist adhesion of the bonding material (i.e.
bitumen).
Such app lication o f pr imer s hall b e paid for s eparately, un less s pecifically included in the w ater
proofing item.
22.8.4 Underlay
Where a f loating t reatment of water proofing w ith s elf f inished bi tumen f elt i s required i .e. where
water pro ofing t reatment i s requi red t o be i solated f rom t he ro of s tructure, a l ayer of bitumen s aturated
felt ( underlay) s hall be s pread ov er t he r oof s urface and t ucked i nto the flashing gr oove. N o bondi ng
material s hall be us ed below t he under lay i n order t o k eep t he under lay f ree of t he s tructure.
Theadjoining strips of t he underlay shall ov erlap t o a minimum of 7.5 cm at sides and 10 c m at ends.
The
overlaps s hall b e s ealed with t he s ame b onding material a s u sed f or t he self f inished f elt t reatment.
Unless specifically included in the water proofing item, the underlay treatment shall be paid for
separately.
The underlay shall be of type 1 saturated felt conforming to IS 1322 i n all respects and having a total
minimum weight of t he f inished bi tumen f elt i n dry condition w ith m ica dus ting pow der @ 6. 8 k g per 10
sqm. The roll shall not be damaged or crack on being unrolled on a fairly smooth and flat surface.
22.8.5 Treatment
22.8.5.1 The water proofing shall consist of a f our or s ix course treatment, as given in the description of
the item, ea ch layer o f bond ing m aterials, s elf finished b itumen felt or s tone grit or p ea s ized gr avel
being counted as a course.
22.8.5.2 The choice of a four or six course treatment will depend on the climatic condition, the
importance of the building, the durability required, cost and other relevant considerations.
22.8.5.4 In a six course treatment, the first, second and third layer shall be of the same as in the four
course treatment. The fourth and fifth layer shall consist of self finished felt and bonding material
respectively. The sixth layer shall consist of stone grit or pea sized gravel.
22.8.5.5 The p rimer or underlay w here required t o be pr ovided s hall not c ount agai nst t he num ber of
courses specified.
22.8.6 Laying
22.8.6.1 Bitumen bonding material of required grade shall be heated to the working temperature
specified f or t he part icular grade by t he bi tumen m anufacturers and conveyed t o t he roof in bu ckets or
pouring canes in weighed quantities.
Vol-2 , 2013
Suitable working temperature for different grades of bitumen are as under:
(i) Blown type petroleum bitumen of IS grade 85/25 or 90/15 - 180 degree C.
(ii) Residual type petroleum bitumen of penetration 30/40 - 180 degree to 190 degree C (IS grade S-35).
22.8.6.2 Drain outlets s hall be given a four or six c ourse treatment as specified for the roof in the
description o f the i tem i n the manner specified for t he flat r oof s urface. Water pr oofing treatment s hall b e
carried i nto t he drain pipe o r o utlets b y at l east 10 c m. The w ater p roofing t reatment l aid on t he roof
surface shall overlap the upper edge of the water proofing treatment in the drain outlets by at least 10 cm.
22.8.6.3 The self finished felt shall be cut to the required length, brushed clean of dusting material and
laid out f lat on t he roof t o el iminate c urls and s ubsequent s tretching. T he f elt s hall normally be l aid i n
length at right angl es t o the direction of the slope an d laying s hall be commenced at the lowest level an d
worked upto crest. T he f elt shall not be l aid i n single piece of very long l engths as t hey are likely to
shrink; 6 t o 8 m are suitable lengths. The roof surface shall be c leaned and dr ied before the felt
treatment i s be gun. E ach l ength of f elt s hall b e l aid i n po sition and r olled u p f or a distance of h alf i ts
length. The hot bonding material shall be poured on the roof across the full width of the rolled felt as the
latter is steadily rolled out and pressed down. The pouring shall be so regulated that the correct weight of
bonding material per uni t ar ea i s spread uni formly ov er the surface. E xcess bondi ng material t hat ge ts
squeezed o ut at the ends shall be levelled up as laying proceeds. When the first half of the strip of felt
has be en bo nded to the roof , the other half sh all be rolled up an d then un rolled on the ho t bonding
material i n t he same way. S ubsequent s trips shall al so b e l aid i n t he same m anner. Each s trip shall
overlap th e pre ceeding o ne by a t lea st 7. 5 cm a t the lo ngitudinal e dges a nd 1 0 cm at t he e nds. All
overlaps s hall be f irmly b onded w ith hot bi tumen. Streaks and t railings of b itumen near edges of l aps
shall be levelled by heating the overlap with a blow lamp and levelling down unevenness.
The t hird la yer o f b onding m aterial i n t he fo ur course tr eatment s hall b e carried o ut in a similar
manner after the flashing has been completed.
22.8.6.4 In a six course t reatment the third and f ourth layers of bon ding m aterial and s elf finished felt
shall be laid in the manner already described, taking care that laps in the felt are staggered from those in
the s econd l ayer. T he f ifth l ayer of bo nding material s hall be c arried out af ter t he f lashing i s done ( See
Fig. 22.7).
22.8.6.5 High Parapet Walls, Chimney Stacks etc.: Felts shall be laid as flashings wherever junctions of
vertical and horizontal surfaces occur. Longitudinal laps shall be 10 cm. The lower layer of flashing felt in a
six course treatment shall overlap the roof water proofing by not less than 20 cm while the upper layer
shall ov erlap the r oofing felt by 10 cm. T he minimum overlap of t he f lashing f elt i n f our course
specification over the roofing felt shall be 10 cm.
The flashing shall consist of the same four or six course treatment as for the roof except that the final
course of s tone g rit o r p ea-sized g ravel s hall be replaced b y an application of bi tuminous solution of
approved quality in two coats on the vertical and sloping faces only, of the flashing. The overlap along
the length of flashing shall stagger with those in the second layer of flashing felt (in a s ix course
treatment and with the joints in the roof felt).
The upper edge of t he f lashing f elt shall b e well t ucked i nto t he f lashing gr ooves i n t he pa rapet,
chimney s tacks et c. t o a depth of not l ess t han 6. 5 c m. C orresponding appl ications of bond ing m aterial
shall also be made. The flashing treatment shall be firmly held in place in the grooves with wood edges at
intervals an d the gro oves shall be f illed up w ith ce ment m ortar 1: 4 (1 ce ment: 4 coarse sa nd) or
cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 6 mm nominal size) and
surface finished smooth with the rest of the wall. The cement work shall be cured for 7 days. When dry, the
exposed plaster joints of grooves shall be painted with bitumen and two coats of bituminous solution shall
be applied on the vertical and sloping surface of flashing (see Fig. 22.7).
Vol-2 , 2013
After th e to p fl ashing f elt l ayer h as been f ixed, t he pe nultimate l ayer of bonding m aterial s hall b e
applied ov er the roofing felt and t he hor izontal ov erlaps and v ertical and sloping surfaces o f the flashings
at the specified rate. Stone grit or pea sized gravel shall then be spread uniformly over the hot bonding
material o n the horizontal roof s urface at the s pecified qu antity p er un it ar ea and pr essed into it w ith a
wooden roller.
22.8.6.6 Low Parapet Walls: Where pa rapet walls are of height 45 c m or less, bitumen felt flashings
shall be provided in the same manner as for flashings in the case of high parapet walls except that the
upper edge shall be carried upto the full height of the wall and taken right a cross the top of the parap et
and down on the external vertical faces to a minimum distance of 5 cm (see Fig. 22.7).
22.8.6.7 Low Dividing Walls: Where l ow dividing walls or i nverted b eams a re m et w ith, t he s ame s hall
be covered with a four or six layer treatment as for the main roof, the l atter bearing c arried dow n both
sides of the wall and overlapping the roofing treatment as in the case of flashing of high parapet walls
(see Fig. 22.7).
Drain outlets where formed in the low dividing walls, shall be given water proofing treatment of the
same number of courses as specified for the flat roof surface. The bottom and sides shall be so treated
that all overlaps are in the direction of flow of drainage.
22.8.6.8 Expansion Joints: Where the expansion joints are provided in the slabs, the joints and their
cover s labs s hall be s uitably t reated w ith w ater proof ing. A t ypical s ketch of an ex pansion j oint w ith t he
RCC slabs on either side of the joint turned vertically up and covered with precast RCC cover slabs as
given in Fig. 22.7. The cover slabs shall cover the vertical turned up dwarf walls by not less than 7.5 cm
and ar e pr ovided w ith t hroatings on their un derside along t heir l ength. T he water proofing t reatment s hall
be t aken up t he s loping j unction f illets and t he vertical f aces of t he walls t o t he u nderside of the c over
slabs. The c over s labs ar e gi ven t he w ater pr oofing treatment like the roof s labs, after the cr oss j oints
between adjacent cover slabs are first sealed with 15 cm width of roofing felt struck to them with
bitumen. T he w ater p roofing t reatment s hall be c arried down t he s ides of t he cover slabs t o t heir f ull
thickness. C are shall be t aken to see that overlaps if any in the r oofing over the cover s labs s tagger with
the joints between cover slabs.
The f ormation of the ex pansion j oints an d provision of cover s labs s hall b e t he responsibility of the
construction agenc y. The formation o f t he junction fillets and the water proofing treatment of the joint and
cover s labs s hall be carried o ut by t he w ater p roofing a gency. N o e xtra s hall be p aid f or t he j unction
fillers or for the sealing of the cross joints in the cover slab with 15 cm width of bitumen strips.
22.8.6.9 Pipes: Where vertical pi pe outlets are met with 7.5 x 7.5 cm fillets of lime or cement concrete of
the t ype a nd section shown i n F ig. 22.7 shall b e p rovided a nd f lashing o f f our or six c ourse t reatment,
same as for the roofing treatment shall be laid.
The u pper edge o f t he f lashing shall be l aid sloping d own f orward and butted a gainst t he pipe and
annular depression so formed shall be filled with hot bitumen. A circular metal collar in the shape of an
inverted truncated c one shall be fixed on t he pi pe to throw off the rain water clear of the flashing and this
shall be paid for separately.
22.8.6.10 Terrace: Where r oof s urfaces ar e ex pected t o be us ed pr ecast c ement c oncrete t iles or 40 mm
thick c ement c oncrete s hall b e l aid o n t he water p roofing t reatment. I n s uch c ases, t he f inal course o f
stone gr it or pea sized gr avel s hall not be l aid i n the water pr oofing treatment. S uitable ad justment i n t he
rates will be effected for not providing the s tone gr it or p ea s ized gr avel layer. C ement c oncrete in situ
flooring s hall be l aid i n p anel not e xceeding 0. 4 s quare m etres e ach. P recast t iles o r i n s itu c oncrete
flooring where laid shall be paid for separately unless included in the description of the water proofing item.
Vol-2 , 2013
22.8.7 Measurements
22.8.7.1 Length and breadth shall be m easured correct to a c m. The area s hall be calculated in square
metres correct to two places of decimal.
22.8.7.2 Measurements shall be taken over the entire exposed area of roofing and flashing treatment
including flashing over low parapet walls, low dividing walls and expansion joints and at pipe projections
etc. Overlaps and tucking into flashing grooves shall not be measured.
22.8.7.3 Vertical and sloping surfaces of water proofing treatment shall also be measured under the four or
six course treatment as the case may be, irrespective of the fact that the final course of grit or pea sized
gravel is replaced by bitumen primer.
22.8.7.4 Primer or saturated felt underlay, where provided, shall also be measured in the same manner as
the w ater pro ofing t reatment and pai d f or s eparately. N o de duction i n m easurements s hall be made for
either openings or recesses f or c himney s tacks, roof l ights and t he l ike, for areas up to 40 square
decimetre (0.4 sqm) nor anything shall be paid for forming such openings.
For s imilar ar eas ex ceeding 40 s q. dec imetre d eductions w ill be m ade in measurements for full
opening and nothing extra shall be paid for forming such openings.
22.8.8 Rate
The r ate shall i nclude t he c ost of all l abour a nd m aterials i nvolved i n al l t he operations described
above and the particular specifications given un der the di fferent i tems, w ith the c orrections noted in t he
relevant sub-paras.
22.9.1 Materials
Cement, coarse s and and graded stone aggregate 20 mm nominal size, shall be used as s pecified in
the i tem. The s pecifications f or t he m aterials an d m ethod of preparat ion of c oncrete s hall c onform i n
general to the specification described in sub-head 4.0 of Specifications.
22.9.1.1 Laying: Before laying cement concrete for grading, the level markings to the required
slope/gradient s hall be made o nly with c ement concrete on t he s urface of t he slab at suitable s pacing
with the h elp of string a nd steel tape (Measuring t ape) so that the m ason can lay the concrete to the
required thickness, slope / gradient easily in between the two level markings.
On g etting t he l evel m arking ap proved b y t he S ite E ngineer t he s urface should b e s prinkled w ith
thick cement slurry and the concrete should be laid carefully, without throwing from height, in
predetermined strips.
The concrete should be consolidated by specially made wooden tamping. After the tamping is done the
surface s hould be f inished t o req uired s lope/gradient with w ooden t rowels w ithout l eaving any s pots of
loose aggregates etc.
The m ixed cement concrete m ust be l aid in position, within half an hour of its m ixing. In case any
quantity of c oncrete remains unus ed fo r m ore than hal f an h our the s ame s hould be rejected and
removed from the site.
22.9.1.2 Finishing: The slope of finished terrace shall not be more than 1 in 120 unless a steeper slope is
desired by the Engineer-in-Charge.
Vol-2 , 2013
The m inimum thickness of t he c oncrete at i ts j unction w ith K hurra or par apets s hall be 5 c m. T he
concrete s hall be r ounded a t t he j unction o f r oof s lab a nd pa rapet. I t i s des irable t o pr ovide a
haunch/gola/filler at the junction of the parapet wall and the roof slab as shown in Fig. 22.8.
The finished concrete surface shall present a smooth surface with correct slopes and uniform
rounding. The concrete should be free from cracks. Excess trowelling shall be avoided.
22.9.1.3 Thickness: Average thickness shall be as per clause 22.9.1.2 as shown in Fig. 22.8.
22.9.1.4 Curing: Curing s hall be don e ei ther by s preading s traw/Hessian c loth ov er t he g raded s urface,
keeping the same wet for full 10 days or flooding the graded area with water by making kiaries with weak
cement mortar, for 10 da ys. Occasional curing by simply s praying water n ow and t hen s hall not be
permitted under any circumstances.
22.9.1.5 Measurement: Length and b readth shall be measured correct to a cm. Area shall be worked out to
nearest 0.01 sqm. and the cubical contents shall be worked out to nearest 0.001 cum.
No de duction sh all be m ade for either op ening or recesses for chi mney sta cks, roof lig hts etc.,
Khurra for area upto 0.1 sqm. Nothing extra shall be paid either for any extra material or labour involved in
forming s uch open ing or re cess or in round ing the concrete func tion of r oof with parape t walls,
chimney stack, khurra etc.
22.9.1.6 Rate: The rate shall include the cost of all the materials and labour involved in all the operations
described above.
22.10.1 Materials
Cement and coarse sand shall be a s specified i n t he i tem o f w ork o r as des cribed i n sub-head 3. 0 o f
Specifications.
22.10.1.1 Cement Mortar : Cement m ortar 1:3 (1 cement: 3 coarse sand) /1:4(1 cement: 4 coarse sand)
specified i n t he i tem of w ork s hall conform t o t he s pecification des cribed i n s ub-head 3 .0 of
Specifications.
22.10.1.2 Preparation of the Surface: The surface shall be cleaned properly with brooms bruch, cloth to
remove all dirts, dust, mortar droppings.
22.10.1.3 Laying: Same as des cribed i n c lause 22. 9.1.1, ex cept t hat c ement m ortar s hall be t amped
with wooden and steel trowels and surface finished with steel trowel.
22.10.1.4 Finishing
(i) T he slope of finished surface shall not be m ore than 1 i n 120 unl ess a s teeper slope is specified
in the item of work.
(ii) The finished surface of the grading shall present a smooth surface with correct slopes and
uniform roundings wherever they are provided. The mortar surface shall be free of cracks.
Excess trowelling shall be avoided.
22.10.1.5 Thickness: The minimum thickness of cement mortar grading at the junction with khurra or
parapet w all s hall be 20 m m. T he cement m ortar s hall be rounded at the junction of roof slab and
parapet. It is desirable to provide a haun ch/gola/filler at the junction of parapet wall and t he roof slab.
The maximum thickness t hat shall be adopted for grading with cement mortar shall be 50 mm. It is not at
all desirable to lay the cement mortar grading for greater thickness and in that case it is advised to go in
for grading with Cement Concrete. The average thickness shall be as shown in Fig. 22.9 and 22.10.
Vol-2 , 2013
22.10.1.6 Curing:
Curing for the grading with cement mortar shall be done exactly as described in clause 22.9.1.4.
22.10.1.7 Measurement:
22.10.1.8 Rate:
The rate shall include the cost of all the labour and material involved in all the operations described
above.
22.12 FIVE LAYERED WATER PROOFING TREATMENT WITH ATACTIC POLYPROPYLENE POLYMER
MODIFIED PREFABRICATED MEMBRANE
22.12.1 Atactic Polypropylene Polymer modified prefabricated five layer water proofing membrane shall be
of thickness as specified. In selecting thickness of membrane due consideration shall be given to the type
and construction of building, climate and atmospheric condition and permanence required. Five layered
treatment 2.00 mm thick with glass fibre is with a normal duly treatment suitable for pitched roofs. Five
layered 3.00 mm thick with glass fibre matt treatment is suitable for moderate condition of rainfall (50 to
150 mm) and five layered 3.00 mm thick with non-woven polyester matt treatment is suitable for heavy
condition of rainfall.
22.12.1.1 Materials
Bitumen pr imer for bi tumen membrane shall hav e d ensity at 25°C i n t he range o f 0. 87 - 0.89 k g./litre
and viscosity of 70-160 CPS primer shall be applied @ of 0.40 litre/sqm.
It is a polymeric water proofing membrane. This shall be one of the following types:
(i) 2 mm thick with glass fibre matt.
(ii) 3 mm thick glass fibre matt.
(iii) 3 mm thick with non-woven polyester matt.
It is prefabricated five layered black finish water proofing membrane comprising of centre core of
50 gsm. Glass fibre matt/170 gsm nonwoven polyester matt sandwiched on both sides by APP
polymer m odified bi tumen w hich i s pr otected on bot h s ides by 20 m icron thermofusible pol yethylene
sheet. Composite thickness of t he membrane including a ll five layers s hall be 2/3 mm with glass
fibre matt and 3 mm with non woven polyester matt. It is available in 1 m width and variable lengths.
Physical and chemical parameters of the membrane shall be as given in Table 22.2.
Vol-2 , 2013
TABLE 22.2
SI. No. of Layers Thickness Elongation at Joint Tear strength Softening Cold
No. 23° C in strength in in longitudinal Point flexibility
longitudinal longitudinal Transverse
transverse and direction
direction Transverse
direction
1 2 3 4 5 6 7 8
1 Five Layered 2 mm 3 N/5 cm. 350/300 60/80 N 150° -2°C
reinforced with N/5 cm.
fibre glass
2 Five layered 3 mm 3.3 N/5 cm. 350/3000 60/80 N 150° -3°C
reinforced with N/5 cm.
fibre glass
3 Five layered 3 mm 40/50 N/5 650 N/450 300/250 N 150° -2°C
reinforced with cm. N/5 cm.
non-woven
polyester matt.
When tested Atactic polypropylene modified black finished is proposed to be used shall conform in all
respects t o the s pecification i n t he pr eceding par as. The w ork should be got done t hrough aut horized
applicator/specification agency.
22.12.1.3 Surface: The surface to be treated shall have a minimum slope of 1 in 120 or as sp ecified,
provision s pecified i n c lause 2 2.12.1.4 shall ap ply f or preparation of s urface e xcept f or pitched r oof
where s urface s hall be c leaned of f an y l oose m aterial dust et c. To ensure g ood a dhesion be tween t he
surface and water proofing treatment suitable method to dry the s urface s hall be adopt ed. A ll hai r l ine
cracks in the surface should be filled with approved sealant.
22.12.1.4 Preparation of Surface: The s urface t o be t reated s hall h ave a minimum slope of 1 t o 12 0.
This grad ing s hall be c arried out with c ement c oncrete or c ement p laster with c oarse s and, as desired,
to the average thickness required and finished smooth. Such grading shall be paid for separately.
Junctions bet ween t he r oof and v ertical f aces of par apet w alls, c himneys et c. s hall be c hased by
running t riangular f illets 7. 5 x 7. 5 c m. s ize, c ement c oncrete. A t t he d rain mouths, t he f illets s hall b e
suitably cut back and rounded off for easy application of water proofing treatment and easy flow of
water. Cement concrete where shall be 1:2:4 mix (1 Cement: 2 Coarse sand: 4 Graded stone aggregate
20 mm. Nominal size). The provision of fillets shall be deemed to be covered by the item of water
proofing and shall not be measured or paid for separately.
In existing roof where gola and drip course are provided at the junction of roof and vertical face of
parapet wall, chimney stacks, etc. These shall be dressed suitably and finished smooth so as to ensure an
easy and gr adual t urning of t he f lashing. A ny di smantlement or f orming and f inishing s mooth t he
junction for forming the base of the flashing shall not be measured or paid for separately and shall be
deemed to form part of the preparation of the surface.
While the grading of roof surface is b eing done, it shall be ens ured that the outlet drain pipe have
been fixed and mouth at the entrance have been eased and rounded off properly for easy flow of water.
When any pipe passes through the roof to be treated, angul ar fillet of shape shown in Fig. 22. 11 shall be
built around it for the water proofing treatment to be taken over it. These fillets shall not be m easured or
paid for separately. For carrying over and tucking in the water proofing felts into the parapet walls,
Vol-2 , 2013
chimneys stacks etc. a horizontal groove 6.5 cm. deep, 7.5 cm. wide section with its lower edge at not
less than 15 cm. abov e the graded roof s urface s hall be left on the inner face of the s ame; during
construction if possible. When such groove has not been left, the same shall be cut out neatly and the
base at rear of the groove shall be finished smooth with cement plaster 1:4 (1 cement: 4 coarse sand).
Such cutting of the groove and its finishing smooth shall be part of the water proofing or paid for
separately. N o deduction shall be m ade ei ther f or not m aking t he groove or w hen t he l atter has al ready
been left in the masonry by the construction agency. Tucking in the water proofing felt will be required
where the parapet wall exceeds 45 c m. in the height from the graded surface. Where the height is 45
cm. or less, no groove will be r equired as the water proofing treatment will be carried over the top of the
parapet wall to its full thickness. In the case of low dividing walls of height 30 cm. or less, outlets therein
shall be cut open for full height and the bottom and sides shall be rendered smooth and corners rounded
and s uch treatment shall not be m easured and paid for separately. Where expansion joints are l eft in the
slab the provision of dwarf walls and/or RCC slabs for covering them and finishing the surface smooth
shall be the responsibility of the construction agency, which had laid the roof slab and will not be
included i n the operation of w ater proofing. T he gr aded s urface of the ro of an d c oncrete f illets an d t he
faces of w alls shall be t horoughly cleaned w ith w ire b rushed and a ll l oose s cales etc. removed. T he
surface shall then be dusted off. Any crack in the roof shall be cut to V section, cleaned and filled up
flush w ith c ement m ortar s lurry 1: 4 (1 c ement : 4 c oarse s and) or b lown t ype pe troleum bi tumen of IS
grade 85 /25, o r app roved qua lity c onforming to IS 702 . S uch c leaning o f t he s urface or treating the
cracks shall not be paid for separately.
22.12.1.4 Treatment: The water proofing shall consist of prefabricated five layered 2 mm / 3 mm
membrane as shown in Fig. 22.12. The choice of 2 mm or 3 mm membrane will depend on the type of
roof i.e. pitched or flat and importance of building, durability, cost and rainfall etc.
22.12.1.5 Laying: Bitumen primer @ 0. 40 l ts/sqm s hall be appl ied t o t he prepared roof, dr ain and all
other surfaces where polymer modified membrane is to be laid. The five layered water proofing
membrane s hall be l aid us ing B utane t orch and s ealing al l j oints and pr eparing the s urface c omplete.
Drain outlets shall be given same treatment as specified for the roof in the description of the item in the
manner s pecified f or t he f lat r oof s urface. Water proofing treatment s hall be carried into t he drain pipe or
outlets b y a t l east 10 cm. T he w ater proo fing t reatment l aid on t he roof surface s hall ov erlap t he upper
edge of the water proofing treatment in the drain outsets by at least 10 cm.
The APP polymer modified pre fabricated w ater proofing m embrane sh all be cut to th e required
length. Water proofing membrane shall normally be laid in length in the direction of the slope and laying
shall be c ommenced a t t he l owest l evel a nd w orked upt o c rest. A PP w ater pr oofing membrane s hall be
laid in 6 t o 8 m lengths. The roof s urface shall be cleaned a nd bitumen primer shall be a pplied in the
correct quantity, ov er t his s pecified w ater p roofing m embrane s hall be laid w ith bu tane to rch a fter
allowing 24 hours for primer to dry. Each strip shall overlap the preceding o ne by at least 10 cm. at the
longitudinal ed ges and 15 c m. at t he ends . A ll ov erlaps s hall be f irmly bo nded w ith bi tumen pri mer an d
levelled by heating the overlap with butane torch.
If the roof is accessible the treatment is protected by brick tiles laid over 12 mm thick cement mortar
of specified grade bedding and joints sealed with cement mortar of which shall be measured and pai d for
separately.
APP water proof ing m embrane s hall be l aid as flashing w herever junction of v ertical and hori zontal
surfaces oc cur. Longi tudinal l aps s hall be 10 c m. The upper edge of f lashing m embrane s hall be well
tucked into the flashing grooves in the parapets, chimney stack etc. to a depth of not less than 6.5 cm;
corresponding applications o f primer coat s hall also be m ade. T he f lashing t reatment s hall be f irmly held
in the grooves and it shall be sealed with the approved sealant after terminating the membrane.
Vol-2 , 2013
Where p arapet walls a re of h eight 45 c m o r l ess AP water proofing m embrane f lashing shall b e
provided in the same manner as for splashing in the core of high parapet walls except that upper edge
shall be c arried out the full height of the wall and t aken right across the top of the parapet and d own on
the external vertical faces to a minimum distance of 5 cm.
Where l ow di viding w alls or i nverted b eams are m et w ith, t he s ame t reatment s hall b e prov ided a s
for the m ain roof, the lateral bea ring c arried dow n both s ides o f the w all and ov erlapping the roof
treatment.
Drain outlets where formed in the low dividing walls, shall be given water proofing treatment same as
for the main roof.
Where the expansion joints are provided in the slabs, the joints and their cover slabs shall be
suitably treated w ith water proofing t reatment. A t ypical s ketch of an ex pansion j oint w ith the R CC s labs
on ei ther s ide of t he j oint t urned v ertically u p a nd covered w ith precise RCC co ver sl abs a s g iven i n
Fig. 22.7. The cover slabs shall cover the vertical turned up dwarf walls by not less than 7.5 cm and are
provided with t hroatings on t heir underside al ong their l ength. T he water p roofing t reatment s hall be
taken u p t he s lopping j unction f illets a nd t he v ertical f aces of t he walls t o the u nderside of t he c over
slabs are gi ven t he w ater proof ing treatment l ike t he roof s labs, after t he c ross j oints b etween ad jacent
cover s labs ar e first s ealed w ith 15 c m. w idth of r oofing felt s truck to them w ith bi tumen. T he w ater
proofing t reatment s hall be c arried do wn t he s ides o f the cover slabs to their f ull thickness. C are s hall be
taken to see that ov erlaps if any i n t he roofing ov er the cover slabs stagger with the joints between c over
slabs.
Measurement shall be taken ov er the ent ire ex posed ar ea o f roofing and flashing treatment i ncluding
flashing over l ow p arapet walls, l ow di viding w alls a nd ex pansion j oints at pi pe proj ections et c. ov erlaps
and tucking into flashing grooves shall not be measured.
No ded uction in m easurements s hall be m ade f or either ope nings or rec esses for c himney s tacks,
roof l ights a nd the l ike, for are as u pto 4 0 square decimeter (0. 4. sqm.) n or any t hing s hall be p aid f or
forming such openings. For areas exceeding 0.40 sqm. deductions will be made in measurements for full
opening and nothing extra shall be paid for forming such openings.
22.12.1.7 Rate: The rates shall include the cost of all labour and materials involved in all the operations
described above.
22.13.1 If the water proofing treatment of flat roof has been done with APP modified five layered
membrane and t he roof i s ac cessible, a s eparation layer on t op of membrane s hould be l aid before any
protected treatment i s done. B rick t iles i n c ement mortar or 25 m m t hick cement concrete 1:2:4 shall be
laid as final layer as shown in Fig. 22.12.
Geotextile 120 gm. Non woven 100% polyester of thickness 1.0 to 1.25 mm manufactured by a
company of repute shall be used.
Vol-2 , 2013
Geotextile of the specified thickness is bonded to the water proofing membrane with intermittent
touch by heating the membrane by Butane torch as per manufacturing recommendations.
22.13.2 Measurements: Length and breadth shall be measured correct to two places of decimal,
measurement shall be taken over the entire exposed area of roofing.
22.13.3 Rate: The rate shall include the cost of all labour and material involved in al l the operation
described above. Final layer of brick tiles or 25 mm thick cement concrete shall be measured and paid for
separately.
Vol-2 , 2013
APPENDIX A
A-1 Weights
The weights of the ingredients used in the manufacture of bitumen felts per 10 sqm shall be not less
than those specified in Table A-I
TABLE A-I
Minimum Weights of Bitumen Felts
Notes:
1. The weight of the untreated base shall be taken as in the dry condition.
2. Includes allowance for 1.2 kg minimum mica dusting powder in dry condition.
A-2 Testing
The samples, when tested as per IS1322 shall conform to the requirements given in Table A-II.
Vol-2 , 2013
TABLE A-II
Vol-2 , 2013
APPENDIX B
B-1 Weight
The weight of the ingredients used in the manufacture of glass fibre felts for 10 square metre shall be
not less than those specified in Table B-I.
TABLE B-I
Minimum Weight of Bitumen Glass Fibre Base Felt
B-2 Tests
The sample, when tested as per IS 7193 shall conform to the requirements given in Table B-II
TABLE B-II
Requirements of Glass Fibre Felts
Vol-2 , 2013
Sub Head : Water Proofing Treatment
Clause : 22.1
22 to 25 mm Thick Rough
Kota Stone
10-12 mm Stone Aggregate
Embedded in C.M. 1:3
25 mm Thick Top
Course of C.M. 1:3
25 mm Thick C.M. 1:3
R.C.C. Floor Slab
Fig. 22.2 : Water Proofing Horizontal Surfaces from Inside of a U.G. Structure
Vol-2 , 2013
Sub Head : Water Proofing Treatment
Clause : 22.2
22 to 25 mm Thick Rough
Kota Stone Slabs
Top
Flooring Filling Material (Lime Conc./Khangar)
W.C.
Pan
Vol-2 , 2013
Sub Head : Water Proofing Treatment
Clause : 22.4
300 mm
15 45 mm 45 mm 45 mm
φ 25
25
6
3 6 φ 12.5
Brick-bat
Jointless Cement Plaster Coba with Tucking in
Haunch in B.B. parapet wall
with C.M. 1:4, 20 mm thick 120mm A Coat of coba for
Average slurry with rounding at
thickness Cement @ junctions
2.75 kg/sqm
Parapet Wall
175
300 mm
65
Fig. 22.6 : Integral Cement based Waterproofing Treatment with Brick-bat Coba
Over a RCC Slab
Vol-2 , 2013
Sub Head : Water Proofing Treatment
Clause : 22.8
C
C
C
C
A D A
α B
A C
B B
A A
Groove Parapet Wall
C. Roof with Projecting Pipe Four Course Treatment D. Raised Type Expansion Joint Six Course
Treatment
Haunch/Fillet
Parapet Wall
8000 mm
Roof Slab
16000 mm
Vol-2 , 2013
Sub Head : Water Proofing Treatment
Clause : 22.10
Grading
with
Haunch/ Cement
Parapet Wall Fillet Mortar
1:3/1:4
Minimum
Thickness
25mm
50 mm
Roof Slab
Haunch/
Fillet
Grading
with
Cement
Mortar
1:3/1:4
35 mm 25 mm Minimum
RCC Chajja
Vol-2 , 2013
Sub Head : Water Proofing Treatment
Clause : 22.11
RCC Slab
Haunch/Fillet out
of grading Layer
T hir d La yer of
APP modi fied First Layer Bitumen Primer
polymeric mem-
Grading w ith brane of specified
Cement Concrete/C.M thickness, weight Second Layer with Bonding Materials
Fourth Lay er w ith Bonding
Material
Fig. 22.11 : Five Course Water Proofing Treatment with APP Modified Polymeric Membrane
Haunch/Fillet
APP Modified Five with Grading
First Layer Layered Prefabricated Grading with
Bitumen Primer Waterproofing Membrane Cement Concrete
Fig. 22.12 : Five Layers Water-Proofing Treatment with APP Modified Prefabricated Membrane
Vol-2 , 2013
23.0 : HORTICULTURE
AND LANDSCAPE
Vol-2 , 2013
CONTENTS
Clause No. Brief Description Page No.
23.0 Horticulture Work 396
23.13 Uprooting Rank Vegetation and Weeds and Preparing the Ground 400
for Planting ‘Select Grass No. 1’
23.14 Excavation and Trenching for preparation of Beds for Hedge and 400
Shrubbery
23.21 Flooding the Ground with Water and Making Kiaries 403
Vol-2 , 2013
23.0 HORTICULTURE AND LAND SCAPING
23.0 HORTICULTURE WORK
Horticultural operations shall be started on ground previously levelled and dressed to required
formation levels and slopes.
In case where unsuitable soil is met with, it shall be either removed or, replaced or it shall be covered over
to a thickness decided by the Engineer-in-charge with good earth.
In t he c ourse of ex cavation or t renching during ho rticultural op erations, a ny walls, fo undations, e tc.
met with shall not be dismantled w ithout pr e-measurement an d p rior t o t he w ritten pe rmission o f t he
Engineer-in-charge.
23.1.0 Trenching is done in order to loosen the soil, turn over the top layer containing weeds etc. and to
bring u p t he l ower l ayer of g ood earth t o f orm a proper medium f or g rassing, r egrassing, h edging a nd
shrubbery.
Trenching shall be done to the depth ordered by the Engineer-in-charge. The depth is generally 30 cm
for grassing and 60 cm for regrassing in good soil.
23.1.1 The trenched ground shall, after rough dress, be f looded with water by m aking small kiaries to
enable t he soil t o s ettle d own. Any l ocal dep ression une venness e tc. s hall be made good by dressing
and/or filling with good soil.
23.1.2 Weeds or ot her v egetation w hich a ppear on t he g round a re t hen uprooted a nd r emoved a nd
disposed off and paid.
23.1.3 Trenching
Trenching shall consist of the following operations:
1. The whole plot shall be divided into narrow rectangular strips of about 1.5 m width or as directed
by the Engineer-in-Charge.
2. T hese s trips s hall be sub-divided l engthwise i nto about 1 m l ong sections. S uch s ections s hall
be excavated serially and excavated soil deposited in the adjacent section preceding it.
3. In excavating and depositing care shall be taken that the top soil with all previous plant growth
including roots, get buried in the bottom layer of trenched area, the dead plants so buried
incidentally being formed into humus.
4. The excavated soil shall be straight away dumped into the adjoining sections so that double
handling otherwise involved in dumping the excavated stuff outside and in back filling in the
trenches with leads is practically eliminated.
23.1.4 Measurements
Length an d b readth of t he pl ot s hall b e t aken c orrect t o 0. 1 m a nd de pths c orrect t o c m. C ubical
contents shall b e calculated i n cubic m eters, correct t o t wo places of decimal. N o d eduction s hall be
made nor ex tra pai d for removing s tones, br ick bats and o ther f oreign m atter m et with during excavation
upto initial lead of 50 m and stacking the same.
23.1.5 Rate
The rate s hall i nclude t he c ost of al l labour and material i nvolved i n the operations described above,
including c ost of al l precautionary measures t o be t aken f or pro tections a nd supporting al l s ervices etc.
met with during trenching. It does not include the cost of mixing of earth, sludge/manure.
23.2.2 Measurements: Length, br eadth and hei ght of s tacks s hall be m easured c orrect t o a c m. T he
volume of the stacks shall be reduced by 20% for voids before payment, unless otherwise described.
Vol-2 , 2013
23.2.3 Rate: The rate s hall include the c ost of excavating the earth from a reas lying at distance not
exceeding one km. from the site, transporting the same at site breaking of clods and stacking at places
indicated. The rate shall also include royalty if payable.
23.3.2 Measurements
The a rrangement f or w eighing s hall be m ade at s ite of w ork by t he d epartment. T he gunny b ags
shall be the property of the government.
23.3.3 Rate: The rate shall include the cost of labour and material involved in all operations described
above, including carriage up to site of work with all lead and lifts, weighing etc.
23.4.2 Measurements
Length, br eadth and depth of s tacks s hall b e m easured c orrect t o a c m. T he v olume of t he s tack
shall be reduced by 8% for looseness in stacking and to arrive at the net quantity for payment.
23.4.3 Rate
The rate s hall i nclude t he c ost of l abour a nd m aterial i nvolved i n al l operations d escribed above,
including carriage up to one km. The rate shall also include royalty if payable.
23.6.1 The trenched ground s hall be levelled and rough dressed and if there are any hollows and
depressions resulting from subsidence which cannot be so levelled, these shall be filled properly with
earth brought from outside to bring the depressed s urface to the level of the adjoining land and to
remove d iscontinuity o f s lope a nd t hen ro ugh dressed again. T he s upply and s preading of soil i n such
depressions is payable separately. In rough dressing, the soil at the surface and f or 75 m m depth below
shall be broken down to particle size not more than 10 mm in any direction.
23.6.2 Measurements
Length, breadth of superficial area shall be measured correct to 0.1 metre. The area shall b e
calculated in sqm. correct to two places of decimal.
23.6.3 Rate
The rate shall include the cost of all the labour and material involved in all the operations described
above.
Vol-2 , 2013
23.7 UPROOTING WEEDS FROM TRENCHED AREAS
23.7.1 After 10 da ys and within 15 day s of f looding t he rough dres sed t renched ground w ith w ater, t he
weeds appearing on the ground shall be rooted out carefully and the rubbish disposed off as directed by the
Engineer-in-charge.
23.7.2 Measurements
Length, breadt h of superficial area shall be m easured c orrect t o 0. 1 m eters. Superficial area of the
weeded ground shall be measured for purpose of payments.
23.7.3 Rate
The rate shall include the cost of all the labour and material involved in all the operations described
above.
23.8.2 Measurements
Length, breadth and depth of stacks shall be measured correct to a cm. The area shall be calculated in
sqm. correct to two places of decimal.
23.8.3 Rate
The rate shall include the cost of all the labour and material involved in all the operations described
above.
23.9.2 Measurements: The quantity of good eart h spread s hall be determined by the d ifference in t he
volume of go od earth i n stacks bef ore a nd after s preading d uly reduced f or l ooseness i n s tacking by
20% of good earth.
23.9.3 Rate: The rate shall include of all the labour and material involved in all the operations described
above, but does not include the cost of the good earth which shall be p aid for separately unless
specifically described in the item.
23.9.A.2 Measurements
The quantity of good earth and sludge or manure mixed shall be determined by the difference in the
volume of g ood e arth an d s ludge or m anure i n s tack, bef ore an d af ter s preading dul y ac counted for
voids and looseness in stack.
23.9.A.3 Rate
The r ate s hall i nclude of all t he labour a nd material i nvolved i n all t he operations described above,
but does not include t he cost of good earth s ludge or manure which shall be paid for separately, unless
otherwise described in the item.
Vol-2 , 2013
23.10 MIXING OF GOOD EARTH AND SLUDGE/MANURE
23.10.1 The stacked earth shall, before mixing be broken down top particle of sizes not exceeding 6 mm in
any di rection. G ood e arth s hall b e t horoughly mixed w ith s ludge or manure i n s pecified p roportion a s
described in the item or as directed by the Engineer-in-charge.
23.10.2 Measurements
The quantity of good earth and sludge or manure mixed shall be determined by the difference in the
volume of good earth, s ludge or manure in s tack, be fore a nd after s preading duly accounted f or v oids
and looseness in stack.
23.10.3 Rate
The r ate s hall i nclude t he c ost of all l abour a nd materials i nvolved i n al l t he operations described
above, but does not include the cost of good earth sludge or manure which shall be paid for separately,
unless otherwise described in the item.
23.11.1 The soil shall be suitably moistened and then the operation of planting grass shall be
commenced. The grass shall be dibbled at 10 cm, 7.5 cm, 5 cm apart in any direction or other spacing
as described i n the i tem. Dead gr ass and weeded shall not be pl anted. The contractor shall be
responsible for watering and m aintenance of levels a nd the lawn for 30 days or till the grass forms a
thick lawn free from weeded and fit for moving whichever is later. Generally planting in other direction at
15 cm, 10 cm, spacing is done in the case of large open spaces, at 7.5 cm spacing in residential lawn
and at 5cm spacing f or T ennis Court and sports ground l awn. Rates a re including c ost of labour a nd
material (grass shall be paid separately.)
23.11.2 During the maintenance period, any irregularities arising in ground levels due to watering or due to
trampling by labour, or due to cattle straying thereon, shall be constantly made up to the proper levels with
earth as available or brought from outside as necessary, Constant watch shall be maintained to ensure
that dead patches are replanted and weeds are removed.
23.11.3 Measurements
Length, br eadth of t he l awn gr assed s hall be measured c orrect t o 0. 1 m eter an d t he a rea s hall b e
calculated in sqm. correct to two places of decimal.
23.11.4 Rate
The r ate s hall i nclude of all t he labour a nd material i nvolved i n all t he operations described above,
excluding s upply of the requisite quant ity o f good e arth and gr ass so needed for pr operly maintaining t he
levels of the lawns. (payment of grass to be paid separately).
Specified quantity of s ludge or m anure s hall t han be s pread uniformly w ith wooden s traight edge
(phatti) as directed by the Engineer-in-charge. The area shall then be slightly sprinkled with water so as to
facilitate proper integration of the manure or sludge with the soil and later flooded. The contractor shall
be responsible for watering, proper m aintenance and tending of the lawn for 30 days or till the grass
forms a lawn fit for mowing, whichever is later.
During t he ab ove operations, al l und esirable growths s hall be c onstantly w eeded out and al l rubbish
removed and disposed off as directed by the Engineer-in-Charge.
399 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
23.12.2 Measurements
Length, breadth of t he l awn renovated s hall be m easured c orrect to 0. 1 meter and t he area shall be
calculated in sqm. correct to two places of decimal.
23.12.3 Rate
The r ate shall include of al l the labour an d T& P ( excluding RH pipe/grass) involved in al l t he
operations des cribed abov e, e xcluding the s upply of the requisite quant ity o f good ear th i f so need ed for
proper maintenance of the levels of the lawns. The cost of the sludge or m anure shall be m easured and
paid for separately, unless its supply is specifically included in the description of the item.
23.13 UPROOTING RANK VEGETATION AND WEEDS AND PREPARING THE GROUND FOR PLANTING
‘SELECT GRASS NO. 1’
23.13.1 Initially the area shall be dug up to a depth of 30 cm. and weeds and rank vegetarian with roots
removed thereon by repeated forking. The whole area then shall be retrenched to a depth of 60 cm in
the same manner as described in 23.1. Clods of excavated earth shall then be broken upto the size not
more than 75 m m in an y direction. T he a rea s hall then be flooded with w ater and after 10 day s an d
within 15 days of flooding, weeds shall be uprooted carefully. The rubbish arising from the above
operations shall be r emoved and di sposed of f i n a m anner di rected b y t he E ngineer-in-charge, aw ay
from the site. The earth shall then be rough dressed and fine dressed as described in 23.6 & 23.8.
23.13.2 Measurements
Length, breadth of upr ooted are a shall be m easured c orrect to 0 .1 meter and th e ar ea s hall b e
calculated in sqm. correct to two places of decimal.
23.13.3 Rate
The rate shall include the cost of all the labour and material involved in all the operations described
above.
23.14 EXCAVATION AND TRENCHING FOR PREPARATION OF BEDS FOR HEDGE AND
SHRUBBERY
23.14.1 Beds for hedges and shrubbery are generally prepared to width of 60 cm. to 125 c m. and 2 t o 4
meters respectively.
23.14.2 Beds f or hedge s and s hrubbery s hall be pr epared i n t he f ollowing m anner. T he bed s s hall f irst
be excavated to a depth of 60 cm. and the excavated soil shall be stacked on the sides of the beds. The
surface o f the excavated bed shall then be trenched to a further d epth of 30 cm, in or der to loosen the
soil, in the manner de scribed in 23.1. No flooding will be done at this stage but the top surface shall be
rough dressed and l evelled. The excavated soil from the top 60 cm depth of the bed s tacked at the site
shall then be thoroughly m ixed with s ludge ov er manner i n the p roportion 8: 1 b y r atio or o ther pr oportion
described in the item. T he m ixed ear th a nd m anure s hall be r efilled ov er the trenched bed, levelled
neatly a nd p rofusely f looded s o t hat t he w ater r eaches ev en t he b ottom most l ayers of t he t renched
depth of t he bed. T he surface after f ull s ubsidence s hall a gain b e refilled with t he earth a nd m anure
mixture, w atered and al lowed to s ettle and finally f ine dressed to the level of 50 m m t o 75 mm below the
adjoining gr ound or as di rected b y t he E ngineer-in-Charge. S urplus ear th i f an y, s hall be di sposed o ff as
directed by the Engineer-in-charge. Any surplus earth if removed beyond initially lead shall be paid
separately. S tones, bri cks bat s and ot her f oreign m atter i f m et w ith duri ng e xcavation or t renching s hall
be removed and stacked w ithin i nitially l ead & l ift, s uch m aterial as i s declared u nserviceable b y t he
Engineer-in-charge shall be disposed by spreading and levelling at places ordered by him. If disposed
outside the initial lead & lift, then the transport for the extra leads will be paid for separately. If a large
proportion o f m aterial unsuitable f or the h edging a nd shrubbery operations is met with and earth f rom
outsides is required to be brought in for mixing with manure and filling, the supply and stacking of such
earth will be paid for separately.
23.14.3 Measurements
Length, b readth and dept h of t he pi t ex cavated and t renched shall be m easured correct to a cm. T he
cubical contents shall be calculated in cubic meter correct to two places of decimal.
Vol-2 , 2013
23.14.4 Rate
The rate shall include the cost of all the labour and material involved in all the operations described
above. The rate shall not include the cost of supply & stacking of the manure unless the same is
specifically included in the description of the item.
23.15.1.1 Holes of circular shape in or dinary soil shall b e excavated to the dimensions described in the
items and excavate soil broken to clods of size not exceeding 75 mm in any direction, shall be stacked
outside t he ho le, s tones, brick ba ts, un suitable e arth and ot her rubbi sh, al l root s and ot her un desirable
growth m et w ith d uring ex cavation s hall be separated o ut a nd unserviceable m aterial re moved f rom the
size a s directed. Useful material, if any, shall be s tacked properly and separately. Good earth i n
quantities as required to replace such discarded stuff shall be brought and stacked at site by the
contractor which shall be paid for separately.
The tree holes s hall be manured w ith powdered N eam/castor oi l cake at t he s pecified rate al ong w ith
farm y ard m anure o ver s ludge s hall be uni formly mixed w ith t he ex cavated s oil af ter t he m anure ha s
been broken down to powder, (size of particle not be exceeded 6 mm in any direction) in the specified
proportion, the mixture shall be filled in t o t he hol e up to the level o f adj oining gr ound and t hen pr ofusely
watered an d ena ble the s oil to s ubside the r efilled s oil s hall then be dr essed ev enly w ith its s urface
about 50 to 75 mm below the adjoining ground level or as directed by the Engineer-in-charge.
23.15.1.3 Rate: The rate shall include the cost of all the labour a nd material involved in all the
operations described above, e xcluding the c ost of s upply and s tacking the r equisite qua ntity of
manure/sludge and oil cake.
23.15.2.2 The stack measurement of ordinary rock and hard rock shall be reduced by 50% and of soil by
20% to arrive at the excavated volume. This excavation shall be paid for as extra over the rate for holes
dug in ordinary soil above, at rate appropriate to particular soil concerned.
23.15.2.3 Sufficient quantity of good s oil to replace the solid volume of stones, brick bats, unsuitable
earth and othe r rubbish, all roo ts and o ther undes irable grow th, ord inary and ha rd s tacks s hall be
brought and stacked at site but the supply and stacking of such shall be paid for separately.
23.15.2.4 The useless excavated stuff shall be di sposed off by spreading at places as ordered by the
Engineer-in-charge. If s uch pl aces are outside i nitially l eads, c arriage f or t he extra l ead s hall be paid for
separately.
23.15.2.5 The ordinary s oil excavated from the hole and the earth brought f rom outside shall then be
mixed w ith m anure screened t hrough s ieve of I S designation 1 6 m m in t he pro portion s pecified in t he
description of the item and filled with the pit and the same watered and finally dressed.
23.15.2.6 Measurements: The pit s hall be enumerated. T he volume of excavation i n s oil a nd other
than a or dinary soil s hall be det ermined b y r educing t he stack volume o f t he r elevant s oil w ith respective
percentage for voids specified in 23.14.2.2.
23.15.2.7 Rate: The rate shall include the cost o f all the labour an d material involved in all the
operations described above, including mixing refilling, watering, dressing etc. but shall not include
401 | P a g e H O C i v i l S p e c i f i c a t i o n s Volume -2....
Vol-2 , 2013
(a) cost of manure over sludge (b) cost of supplying and stacking of good earth for replacement and (c) the
cost of carriage beyond i nitial l ead for di sposing of f useless materials. The excavation other t han that of
ordinary soil shall be paid extra over and above the rate if excavation in ordinary soil.
23.16.1.1 The tree guard shall be 600 mm in diameter and 2 meter high above ground level and 25 cm in
below ground level.
23.16.1.2 The tree guard shall be f ramed of 4 n os. 25 x 6 m M.S. flat 2 meter long excluding displayed
outward at lower and upto an extent 10 cm and 8 nos. 25 x 3 mm vertical M.S. Flat Rivetted to 3 Nos.
25 x 6 mm Flat iron rings in two halves, bolted together 8 mm dia and 30 mm long M.S. bolts and nuts.
The ent ire tree guar d s hall be given t wo c oats of synthetic enamel paint of approved br and a nd
manufacturer of re quired shade ov er a priming c oat of rea dy m ixed s teel primer o f app roved br and a nd
manufacturer. The design of tree guards shall be shown in the drawing.
23.16.1.4 Rate: The rate shall include the cost o f all the labour an d material involved in all the
operations described above.
23.16.2.2 The tree guard shall be f ramed of 4 n os. 25 x 6 mm MS. Flat 2 metres long excluding
displayed outward at lower and upto an extent 10 cm and 8 Nos. 25 x 3 mm vertical M.S. Flat Riveted to
3 nos. 25 x 6 mm flat iron rings in two halves, bolted together 8 mm dia and 30 mm long M.S. Bolts &
nuts. T he ent ire t ree guard s hall be gi ven t wo c oats of s ynthetic enam el pai nt of approved brand and
manufacturer of required shade brand and m anufacturer of required s hade over a pri ming c oat of ready
mixed steel primer of approved brand and manufacturer. The design of tree guards shall be shown i n the
drawing.
23.16.2.4 Rate: The rate shall include the cost of all the labour and material involved in all the
operations described above.
23.17.1 Measurements
Measurement s hall be m ade in (Length, breadth and h eight o f stacks) c ubic m eter. The c ubical
contents shall be worked out to the nearest two places of decimal in cubic meter.
23.17.2 Rate
The rate shall include the cost of all the labour and material involved in all the operations described
above, but do not include the good earth, sludge or manure which will be paid separately.
Vol-2 , 2013
leads and lifts. Such material as is declared unserviceable by the Engineer-in-Charge be disposed within 50
m. The excavated surface shall be neatly dressed and levelled.
23.18.2 Measurements
Measurement shall be made in (Length, breadth and height of stacks) cu bic m eter. The cu bical
contents shall be worked out to the nearest two places of decimal in cubic meter.
23.18.3 Rate
The ra te shall i nclude t he c ost of all the l abour and m aterial i nvolve i n a ll t he operations d escribed
above.
23.19.2 Measurements
Same as 23.18.2.
23.19.3 Rate
Same as 23.18.3.
23.20.2 Measurements
Measurement s hall be m ade in (Length, breadth and h eight o f stacks) c ubic m eter. The c ubical
contents shall be worked out to the nearest two places of decimal in cubic meter.
23.20.3 Rate
The rate shall include the cost of all the labour and material involved in all the operations described
above.
23.21.2 Measurements
Measurement shall be made in sqm. of area.
23.21.3 Rate
The rate shall be for 100 sqm of area and include the cost of all the labour and material involved in all
the operations described above.