FIELD CONCRETE TEST REPORT

RECEIVE : SUMITOMO & MJVC


SITE NAME : Boiler-2 (Section-01)
STANDARD : 20-25-150 TEST DATE 12-Apr-21
:
STRENGTH : C25 TESTED BY M
: D.Masud Rana.
Sample Name Freshly Concrete Sampling Date 12-Apr-21

Sampling Location Site Hajoo 18

□ TEST ITEM
TEST ITEM STANDARD RESULT TEST METHOD JUDGEMENT

Slump
150 ± 25 ㎜ 170 ASTM C 143 Pass
(㎜)
Air Content
2.0 ± 2.0 % 1.9 ASTM C231 & C173 Pass
(%)

Chrolide Content
Less than 0.3 ㎏/㎥ 0.031 ASTM C1218 Pass
(㎏/㎥)

Temperature
Less than 35 ℃ 23.6 ASTM C1064 Pass
(℃)

TESTING PHOTOGRAPH

Attachment

QC Engineer (POSCO E&C) QC Manager(POSCO E&C) Sumitomo MJVC