You are on page 1of 28

Reinforced Concrete Design©

Using the Ultimate Limit Design Method

Ver. 6.2

Please send your comments & suggestions to improve this tool on


melkateb@hotmail.com

by
Eng. Mahmoud M. El-Kateb

Structural Engineering Dept.


Faculty of Engineering - Ain Shams University

* Calculation of coefficients
* Design of slabs
* Design of flat slabs
* Design of beams
* Design of sections under M,N
* Check shear in beams
* Design for torsion
* Design of rectangular columns
* Design of circular columns
* Design of isolated footings
* Design of isolated footings under moment
* Design of combined footings
* Design of strap footings
* Design of retaining walls
* Deflection of cantilevers
* Deflection of simples
Concrete design according to the Egyptian code 1995.

* Calculation of Coeffecients

* Project :

Hollow Slabs:

Web breadth Spacing Thick Slab th F.C L.L One way Two way
Area ts (cm) Wu (t/m`) Wu (t/m2)
b (cm) e (cm) t (cm) (kg/m )2
(kg/m )2

1 12 40 32 7 150 200 1.237 1.385


2 12 40 27 7 150 200 1.129 1.250
3 12 40 30 5 150 200 1.169 1.318
4 12 40 32 7 150 200 1.237 1.385
5 12 40 32 7 150 200 1.237 1.385

Slabs:

Long span Short span Code of practice Marcus Grashoff


Area
Span (m) contin. Span (m) contin. a b a b a b
1 5.15 1 4.65 1 0.404 0.285 0.481 0.319 0.601 0.399
2 5 1 4 1 0.475 0.224 0.568 0.232 0.709 0.291
3 5 1 4 1 0.475 0.224 0.568 0.232 0.709 0.291
4 5 1 4 1 0.475 0.224 0.568 0.232 0.709 0.291
5 5 1 4 1 0.475 0.224 0.568 0.232 0.709 0.291
6 5 1 4 1 0.475 0.224 0.568 0.232 0.709 0.291
7 5 1 4 1 0.475 0.224 0.568 0.232 0.709 0.291
8 5 1 4 1 0.475 0.224 0.568 0.232 0.709 0.291
9 5 1 4 1 0.475 0.224 0.568 0.232 0.709 0.291
10 5 1 4 1 0.475 0.224 0.568 0.232 0.709 0.291

Beams:

Load on Long Short Load coeff. Load distribution for


Area
slab (t/m2) span (m) span (m) shear moment shear (t/m`) moment (t/m`)
1 1.44 5.05 4 0.604 0.791 1.739 2.278
2 0.85 5 4 0.600 0.787 1.020 1.337
3 0.85 5 4 0.600 0.787 1.020 1.337
4 0.85 5 4 0.600 0.787 1.020 1.337
5 0.85 5 4 0.600 0.787 1.020 1.337
6 0.85 5 4 0.600 0.787 1.020 1.337
7 0.85 5 4 0.600 0.787 1.020 1.337
8 0.85 5 4 0.600 0.787 1.020 1.337
9 0.85 5 4 0.600 0.787 1.020 1.337
10 0.85 5 4 0.600 0.787 1.020 1.337

By: Eng. Mahmoud El-Kateb


Concrete design using the ultimate limit design method.

* Design of Slabs

* Project :

Concrete Fcu = 300 kg/cm2


Steel Fy = 3600 kg/cm2

Ult. Moment Breadth Depth As Asmin Used


Sec. C1 J Rft. /m Notes
Mu (m.t) b (cm) d (cm) (cm2) (cm2) As
1 1.4 100 10 4.629 0.822 4.73 1.50 4.73 7 f 10 safe
2 2 100 12 4.648 0.822 5.63 1.80 5.63 5 f 12 safe
3 2 100 12 4.648 0.822 5.63 1.80 5.63 5 f 12 safe
4 2 100 12 4.648 0.822 5.63 1.80 5.63 5 f 12 safe
5 2 100 12 4.648 0.822 5.63 1.80 5.63 5 f 12 safe
6 2 100 12 4.648 0.822 5.63 1.80 5.63 5 f 12 safe
7 2 100 12 4.648 0.822 5.63 1.80 5.63 5 f 12 safe
8 2 100 12 4.648 0.822 5.63 1.80 5.63 5 f 12 safe
9 2 100 12 4.648 0.822 5.63 1.80 5.63 5 f 12 safe
10 2 100 12 4.648 0.822 5.63 1.80 5.63 5 f 12 safe
11 2 100 12 4.648 0.822 5.63 1.80 5.63 5 f 12 safe
12 2 100 12 4.648 0.822 5.63 1.80 5.63 5 f 12 safe
13 2 100 12 4.648 0.822 5.63 1.80 5.63 5 f 12 safe
14 2 100 12 4.648 0.822 5.63 1.80 5.63 5 f 12 safe
15 2 100 12 4.648 0.822 5.63 1.80 5.63 5 f 12 safe
16 2 100 12 4.648 0.822 5.63 1.80 5.63 5 f 12 safe
17 2 100 12 4.648 0.822 5.63 1.80 5.63 5 f 12 safe
18 2 100 12 4.648 0.822 5.63 1.80 5.63 5 f 12 safe
19 2 100 12 4.648 0.822 5.63 1.80 5.63 5 f 12 safe
20 2 100 12 4.648 0.822 5.63 1.80 5.63 5 f 12 safe
21 2 100 12 4.648 0.822 5.63 1.80 5.63 5 f 12 safe
22 2 100 12 4.648 0.822 5.63 1.80 5.63 5 f 12 safe
23 2 100 12 4.648 0.822 5.63 1.80 5.63 5 f 12 safe
24 2 100 12 4.648 0.822 5.63 1.80 5.63 5 f 12 safe
25 2 100 12 4.648 0.822 5.63 1.80 5.63 5 f 12 safe
26 2 100 12 4.648 0.822 5.63 1.80 5.63 5 f 12 safe
27 2 100 12 4.648 0.822 5.63 1.80 5.63 5 f 12 safe
28 2 100 12 4.648 0.822 5.63 1.80 5.63 5 f 12 safe
29 2 100 12 4.648 0.822 5.63 1.80 5.63 5 f 12 safe
30 2 100 12 4.648 0.822 5.63 1.80 5.63 5 f 12 safe
31 2 100 12 4.648 0.822 5.63 1.80 5.63 5 f 12 safe
32 2 100 12 4.648 0.822 5.63 1.80 5.63 5 f 12 safe

By: Eng. Mahmoud El-Kateb


Concrete design using the ultimate limit design method.

* Design of Slabs

* Project :

Concrete Fcu = 300 kg/cm2


Steel Fy = 3600 kg/cm2

Ult. Moment Breadth Depth As Asmin Used


Sec. C1 J Rft. /m Notes
Mu (m.t) b (cm) d (cm) (cm2) (cm2) As
33 2 100 12 4.648 0.822 5.63 1.80 5.63 5 f 12 safe
34 2 100 12 4.648 0.822 5.63 1.80 5.63 5 f 12 safe

By: Eng. Mahmoud El-Kateb


Concrete design using the ultimate limit design method.

* Design of Flat Slab

* Project :

Concrete Fcu = 225 kg/cm2


Steel Fy = 3600 kg/cm2

Module: Long direction 6 m Short direc. 4.5 m


Marginal beams: 1)Yes 2)No 1
Column dim.: Long direction 55 cm Short direc. 55 cm
Slab thickness: 20 cm
Live load: 300 kg/m2 Walls load: 200 kg/m2
Slab load Wsu = 1.67 t/m2

Long direction 1 8.94 3 13.41


Column strip 8.94 2 7.453 4

Long direction 5 5.96 7 4.47


Field strip 5.96 6 4.472 8

Short direction 9 6.42 11 9.63


Column strip 6.42 10 5.35 12

Short direction 13 4.28 15 3.21


Field strip 4.28 14 3.21 16

Ult. Moment Breadth Depth As Asmin Used


Sec. C1 J Rft. /m Notes
Mu (m.t) b (cm) d (cm) (cm2) (cm2) As
1 8.94 225 18 4.283 0.813 7.54 2.70 7.54 4 f 16 safe
2 8.94 225 18 4.283 0.813 7.54 2.70 7.54 4 f 16 safe
3 7.45 225 18 4.691 0.823 6.21 2.70 6.21 4 f 16 safe
4 13.41 225 18 3.497 0.781 11.77 2.70 11.77 6 f 16 safe
5 5.96 225 18 5.245 0.826 4.95 2.70 4.95 5 f 12 safe
6 5.96 225 18 5.245 0.826 4.95 2.70 4.95 5 f 12 safe
7 4.47 225 18 6.057 0.826 3.71 2.70 3.71 4 f 12 safe
8 4.47 225 18 6.057 0.826 3.71 2.70 3.71 4 f 12 safe
9 6.42 300 18 5.837 0.826 4.00 2.70 4.00 4 f 12 safe
10 6.42 300 18 5.837 0.826 4.00 2.70 4.00 4 f 12 safe
11 5.35 300 18 6.394 0.826 3.33 2.70 3.33 3 f 12 safe
12 9.63 300 18 4.766 0.825 6.01 2.70 6.01 6 f 12 safe
13 4.28 300 18 7.149 0.826 2.67 2.70 2.70 3 f 12 safe
14 4.28 300 18 7.149 0.826 2.67 2.70 2.70 3 f 12 safe

By: Eng. Mahmoud El-Kateb


Concrete design using the ultimate limit design method.

15 3.21 300 18 8.254 0.826 2.00 2.70 2.70 2 f 12 safe


16 3.21 300 18 8.254 0.826 2.00 2.70 2.70 2 f 12 safe

By: Eng. Mahmoud El-Kateb


Concrete design using the ultimate limit design method.

* Design of Beams

* Project : graduation project

Concrete Fcu = 250 kg/cm2


Steel Fy = 3600 kg/cm2

Ult. Moment Breadth Comp.fl. Depth Asmin Used


Sec. C1 J Rft. Notes
Mu (m.t) b (cm) B (cm) d (cm) (cm )2
As
1‫ك‬ 3.8 12 12 58 5.153 0.826 2.13 2.20 2 f 12 safe
2‫ك‬ 6.7 12 12 58 3.881 0.800 2.13 4.01 2 f 16 safe
3‫ك‬ 7.4 12 12 58 3.693 0.792 2.13 4.48 4 f 12 safe
3‫ك‬ 7.7 25 25 58 5.225 0.826 4.43 4.46 4 f 12 safe
4‫ك‬ 13.4 25 25 58 3.961 0.803 4.43 7.99 4 f 16 safe
5‫ك‬ 16.4 25 25 58 3.581 0.786 4.43 9.99 5 f 16 safe
6‫ك‬ 24.6 25 25 58 2.923 0.735 4.43 16.02 8 f 16 safe
8 15 25 25 65 4.196 0.811 4.97 7.91 4 f 16 safe
9 15 25 25 65 4.196 0.811 4.97 7.91 4 f 16 safe
10 15 25 25 65 4.196 0.811 4.97 7.91 4 f 16 safe
11 15 25 25 65 4.196 0.811 4.97 7.91 4 f 16 safe
12 15 25 25 65 4.196 0.811 4.97 7.91 4 f 16 safe
13 15 25 25 65 4.196 0.811 4.97 7.91 4 f 16 safe
14 15 25 25 65 4.196 0.811 4.97 7.91 4 f 16 safe
15 15 25 25 65 4.196 0.811 4.97 7.91 4 f 16 safe
16 15 25 25 65 4.196 0.811 4.97 7.91 4 f 16 safe
17 15 25 25 65 4.196 0.811 4.97 7.91 4 f 16 safe
18 15 25 25 65 4.196 0.811 4.97 7.91 4 f 16 safe
19 15 25 25 65 4.196 0.811 4.97 7.91 4 f 16 safe
20 15 25 25 65 4.196 0.811 4.97 7.91 4 f 16 safe
21 15 25 25 65 4.196 0.811 4.97 7.91 4 f 16 safe
22 15 25 25 65 4.196 0.811 4.97 7.91 4 f 16 safe
23 15 25 25 65 4.196 0.811 4.97 7.91 4 f 16 safe
24 15 25 25 65 4.196 0.811 4.97 7.91 4 f 16 safe
25 15 25 25 65 4.196 0.811 4.97 7.91 4 f 16 safe
26 15 25 25 65 4.196 0.811 4.97 7.91 4 f 16 safe
27 15 25 25 65 4.196 0.811 4.97 7.91 4 f 16 safe
28 15 25 25 65 4.196 0.811 4.97 7.91 4 f 16 safe
29 15 25 25 65 4.196 0.811 4.97 7.91 4 f 16 safe
30 15 25 25 65 4.196 0.811 4.97 7.91 4 f 16 safe
31 15 25 25 65 4.196 0.811 4.97 7.91 4 f 16 safe
32 15 25 25 65 4.196 0.811 4.97 7.91 4 f 16 safe

By: Eng. Mahmoud El-Kateb


Concrete design using the ultimate limit design method.

* Design of Beams

* Project : graduation project

Concrete Fcu = 250 kg/cm2


Steel Fy = 3600 kg/cm2

Ult. Moment Breadth Comp.fl. Depth Asmin Used


Sec. C1 J Rft. Notes
Mu (m.t) b (cm) B (cm) d (cm) (cm )2
As
33 15 25 25 65 4.196 0.811 4.97 7.91 4 f 16 safe
34 15 25 25 65 4.196 0.811 4.97 7.91 4 f 16 safe

By: Eng. Mahmoud El-Kateb


Concrete design using the ultimate limit design method.

* Design of Sec. under M,N

* Project : CHEMICAL BUILDING-FRAME 1

Concrete Fcu = 400 kg/cm2


Steel Fy = 4000 kg/cm2

Ult. Moment Normal Breadth Depth Thick Asmin Used


Sec. ecc. C1 J Rft.
Mu (m.t) Nu (t) b (cm) d (cm) t (cm) (cm2) As
1 28 -7 40 80 90 Big 5.799 0.826 8.80 9.51 5 f 16
2 17 -7 40 80 90 Big 7.256 0.826 7.11 7.11 4 f 16
3 17 -22.5 40 55 60 Big 4.625 0.822 6.05 6.05 4 f 16
4 15 -22.5 40 55 60 Big 4.844 0.826 6.05 6.05 4 f 16
5 26 -4 40 80 90 Big 6.113 0.826 8.80 9.22 5 f 16
6 11 -47 40 55 60 Small 4.612 0.822 3.30 3.30 2 f 16
7 30 -47 40 55 60 Big 3.405 0.776 6.05 10.95 6 f 16
8 27 -4 40 80 90 Big 6.005 0.826 8.80 9.59 5 f 16
9 19 -4 40 80 90 Big 7.085 0.826 8.74 8.74 5 f 16
10 13 -22 40 55 60 Big 5.115 0.826 5.13 5.13 3 f 16
11 14 -22 40 55 60 Big 4.982 0.826 5.86 5.86 3 f 16
12 14 -7 40 80 90 Big 7.890 0.826 5.60 5.60 3 f 16
13 11 -45 40 55 60 Small 4.664 0.823 3.30 3.30 2 f 16
14 30 -45 40 55 60 Big 3.425 0.777 6.05 11.19 6 f 16
15 15 -20 25 65 70 Big 4.485 0.819 4.47 4.47 3 f 16
16 15 -20 25 65 70 Big 4.485 0.819 4.47 4.47 3 f 16
17 15 -20 25 65 70 Big 4.485 0.819 4.47 4.47 3 f 16
18 15 -20 25 65 70 Big 4.485 0.819 4.47 4.47 3 f 16
19 15 -20 25 65 70 Big 4.485 0.819 4.47 4.47 3 f 16
20 15 -20 25 65 70 Big 4.485 0.819 4.47 4.47 3 f 16
21 15 -20 25 65 70 Big 4.485 0.819 4.47 4.47 3 f 16
22 15 -20 25 65 70 Big 4.485 0.819 4.47 4.47 3 f 16
23 15 -20 25 65 70 Big 4.485 0.819 4.47 4.47 3 f 16
24 15 -20 25 65 70 Big 4.485 0.819 4.47 4.47 3 f 16
25 15 -20 25 65 70 Big 4.485 0.819 4.47 4.47 3 f 16
26 15 -20 25 65 70 Big 4.485 0.819 4.47 4.47 3 f 16
27 15 -20 25 65 70 Big 4.485 0.819 4.47 4.47 3 f 16
28 15 -20 25 65 70 Big 4.485 0.819 4.47 4.47 3 f 16
29 15 -20 25 65 70 Big 4.485 0.819 4.47 4.47 3 f 16
30 15 -20 25 65 70 Big 4.485 0.819 4.47 4.47 3 f 16
31 15 -20 25 65 70 Big 4.485 0.819 4.47 4.47 3 f 16
32 15 -20 25 65 70 Big 4.485 0.819 4.47 4.47 3 f 16

By: Eng. Mahmoud El-Kateb


Concrete design using the ultimate limit design method.

* Design of Sec. under M,N

* Project : CHEMICAL BUILDING-FRAME 1

Concrete Fcu = 400 kg/cm2


Steel Fy = 4000 kg/cm2

Ult. Moment Normal Breadth Depth Thick Asmin Used


Sec. ecc. C1 J Rft.
Mu (m.t) Nu (t) b (cm) d (cm) t (cm) (cm2) As
33 15 -20 25 65 70 Big 4.485 0.819 4.47 4.47 3 f 16
34 15 -20 25 65 70 Big 4.485 0.819 4.47 4.47 3 f 16

By: Eng. Mahmoud El-Kateb


Concrete design using the ultimate limit design method.

* Check shear in beams

* Project :

Concrete Fcu = 400 kg/cm2


Concrete qall = 12.247 kg/cm2
Stirrups Fy = 2400 kg/cm2

Ult. Shear Breadth Depth qu As no. of


Sec. Stirrups Notes
Qu (ton) b (cm) d (cm) (kg/cm2) S bran.
1 20 40 80 6.25 0.002 2 1 f 8 safe
2 15 25 65 9.23 0.037 2 4 f 8 safe
3 15 25 65 9.23 0.037 2 4 f 8 safe
4 15 25 65 9.23 0.037 2 4 f 8 safe
5 15 25 65 9.23 0.037 2 4 f 8 safe
6 15 25 65 9.23 0.037 2 4 f 8 safe
7 15 25 65 9.23 0.037 2 4 f 8 safe
8 15 25 65 9.23 0.037 2 4 f 8 safe
9 15 25 65 9.23 0.037 2 4 f 8 safe
10 15 25 65 9.23 0.037 2 4 f 8 safe
11 15 25 65 9.23 0.037 2 4 f 8 safe
12 15 25 65 9.23 0.037 2 4 f 8 safe
13 15 25 65 9.23 0.037 2 4 f 8 safe
14 15 25 65 9.23 0.037 2 4 f 8 safe
15 15 25 65 9.23 0.037 2 4 f 8 safe
16 15 25 65 9.23 0.037 2 4 f 8 safe
17 15 25 65 9.23 0.037 2 4 f 8 safe
18 15 25 65 9.23 0.037 2 4 f 8 safe
19 15 25 65 9.23 0.037 2 4 f 8 safe
20 15 25 65 9.23 0.037 2 4 f 8 safe
21 15 25 65 9.23 0.037 2 4 f 8 safe
22 15 25 65 9.23 0.037 2 4 f 8 safe
23 15 25 65 9.23 0.037 2 4 f 8 safe
24 15 25 65 9.23 0.037 2 4 f 8 safe
25 15 25 65 9.23 0.037 2 4 f 8 safe
26 15 25 65 9.23 0.037 2 4 f 8 safe
27 15 25 65 9.23 0.037 2 4 f 8 safe
28 15 25 65 9.23 0.037 2 4 f 8 safe
29 15 25 65 9.23 0.037 2 4 f 8 safe
30 15 25 65 9.23 0.037 2 4 f 8 safe
31 15 25 65 9.23 0.037 2 4 f 8 safe

By: Eng. Mahmoud El-Kateb


Concrete design using the ultimate limit design method.

* Check shear in beams

* Project :

Concrete Fcu = 400 kg/cm2


Concrete qall = 12.247 kg/cm2
Stirrups Fy = 2400 kg/cm2

Ult. Shear Breadth Depth qu As no. of


Sec. Stirrups Notes
Qu (ton) b (cm) d (cm) (kg/cm2) S bran.
32 15 25 65 9.23 0.037 2 4 f 8 safe
33 15 25 65 9.23 0.037 2 4 f 8 safe

By: Eng. Mahmoud El-Kateb


Concrete Design using the ultimate limit design method.

* Design for Torsion

* Project : Ring Beam

Concrete Fcu = 300 kg/cm2


Concrete qall = 10.607 kg/cm2
Stirrups Fy = 2400 kg/cm2
Horizontal bars Fy = 3600 kg/cm2

Ult. torsional moment Sec. dim. Ult. shear force


Sec. Mu (m.t) b (cm) t (cm) Qu (ton)
1 3 30 80 15

Due to shear qsu Notes


6.67 kg/cm 2
safe

Due to torsion qtu Notes


12.50 kg/cm2 safe

Calculation of stirrups:

Due to shear no. f Notes


6.0 8

Due to torsion no. f Notes


4.1 10

Horizontal Rft. no. f


2 18

By: Eng. Mahmoud El-Kateb


Concrete design using the ultimate limit design method.

* Design of Rectangular Columns

* Project :

Concrete Fcu = 300 kg/cm2


Steel Fy = 3600 kg/cm2

Ult. Load desired dim of column As


Col. Reinforcement
Nu (ton) m% b (cm) t (cm) (cm2)
1 25 30 7.50 4 f 16
1 80 1.3 40 20 10.40 10 f 12
1.6 25 25 10.00 4 f 18
1 25 70 17.50 9 f 16
2 200 1.3 25 65 21.13 11 f 16
1.6 25 65 26.00 11 f 18
1 25 45 11.25 6 f 16
3 120 1.3 25 40 13.00 7 f 16
1.6 25 40 16.00 7 f 18
1 25 55 13.75 7 f 16
4 150 1.3 25 50 16.25 9 f 16
1.6 25 50 20.00 8 f 18
1 30 55 16.50 9 f 16
5 180 1.3 30 50 19.50 10 f 16
1.6 30 50 24.00 10 f 18
1 30 60 18.00 9 f 16
6 210 1.3 30 60 23.40 12 f 16
1.6 30 55 26.40 11 f 18
1 30 70 21.00 11 f 16
7 240 1.3 30 65 25.35 13 f 16
1.6 30 65 31.20 13 f 18
1 30 80 24.00 12 f 16
8 270 1.3 30 75 29.25 15 f 16
1.6 30 70 33.60 14 f 18
1 30 90 27.00 14 f 16
9 300 1.3 30 80 31.20 16 f 16
1.6 30 80 38.40 16 f 18
1 30 95 28.50 15 f 16
10 330 1.3 30 90 35.10 18 f 16
1.6 30 85 40.80 17 f 18
1 30 105 31.50 16 f 16
11 360 1.3 30 100 39.00 20 f 16

By: Eng. Mahmoud El-Kateb


Concrete design using the ultimate limit design method.

* Design of Rectangular Columns

* Project :

Concrete Fcu = 300 kg/cm2


Steel Fy = 3600 kg/cm2

Ult. Load desired dim of column As


Col. Reinforcement
Nu (ton) m% b (cm) t (cm) (cm2)
1.6 30 95 45.60 18 f 18

By: Eng. Mahmoud El-Kateb


Concrete design using the ultimate limit design method.

* Design of Circular Columns

* Project :

Concrete Fcu = 225 kg/cm2


Steel Fy = 3600 kg/cm2

Ult. Load desired Diamter As


Col. Reinforcement
Nu (ton) m% D (cm) (cm2)
1 40 12.56 7 f 16
1 100 1.3 35 12.50 7 f 16
1.6 35 15.39 7 f 18
1 40 12.56 7 f 16
2 120 1.3 40 16.33 9 f 16
1.6 40 20.10 8 f 18
1 45 15.90 8 f 16
3 150 1.3 45 20.67 11 f 16
1.6 45 25.43 11 f 18
1 50 19.63 10 f 16
4 180 1.3 50 25.51 13 f 16
1.6 50 31.40 13 f 18
1 55 23.75 12 f 16
5 210 1.3 55 30.87 16 f 16
1.6 50 31.40 13 f 18
1 60 28.26 15 f 16
6 240 1.3 55 30.87 16 f 16
1.6 55 37.99 15 f 18
1 60 28.26 15 f 16
7 270 1.3 60 36.74 19 f 16
1.6 60 45.22 18 f 18
1 65 33.17 17 f 16
8 300 1.3 65 43.12 22 f 16
1.6 60 45.22 18 f 18
1 70 38.47 20 f 16
9 330 1.3 65 43.12 22 f 16
1.6 65 53.07 21 f 18
1 70 38.47 20 f 16
10 360 1.3 70 50.00 25 f 16
1.6 65 53.07 21 f 18
1 75 44.16 22 f 16
11 390 1.3 70 50.00 25 f 16

By: Eng. Mahmoud El-Kateb


Concrete design using the ultimate limit design method.

* Design of Circular Columns

* Project :

Concrete Fcu = 225 kg/cm2


Steel Fy = 3600 kg/cm2

Ult. Load desired Diamter As


Col. Reinforcement
Nu (ton) m% D (cm) (cm2)
1.6 70 61.54 25 f 18

By: Eng. Mahmoud El-Kateb


Concrete design using the ultimate limit design method.

* Design of Isolated footings

* Project :

Concrete Fcu = 400 kg/cm2


Steel Fy = 3600 kg/cm2
Bearing capacity qall = 1.50 kg/cm2

Column working load column dim. extension


foot Nw (ton) b (cm) t (cm) of P.C (cm)
F1 50 40 60 10

Dims. of P.C : B (cm) L (cm) t (cm)


185 205 10 ###
###
Dims. of R.C : B (cm) L (cm) t (cm)
165 185 50

Actual soil stress (kg/cm2) Notes


1.44 safe ###

Shear stress (kg/cm2) Notes


2.239 safe ###

Punching stress (kg/cm2) Notes


3.134 safe ###

###
Calculation of Rft. : As /m Asmin ###
3.59 6.75 cm2
###
Long Rft. : no. f total no.
4 16 /m 8 ###

Short Rft. : no. f total no.


4 16 /m 9 ###

By: Eng. Mahmoud El-Kateb


Concrete design using the ultimate limit design method

* Design of Isolated footings under moment

* Project :

Concrete Fcu = 300 kg/cm2


Steel Fy = 3600 kg/cm2
Bearing capacity qall = 2.20 kg/cm2

Column working load Moment column dim. extension


foot Nw (ton) Mw (m.t) b (cm) t (cm) of P.C (cm)
F1 226 87 70 200 30
###

Dims. of P.C : B (cm) L (cm) Lmin (cm)


265 395 231
Choose dim of P.C 300 425 ###
###
Dims. of R.C : B (cm) L (cm) t (cm)
240 365 60

Max. Stree (kg/cm2) = 2.74 Safe case (2) ###


Min. Stress (kg/cm2) = 0.81 No tension ###

Shear stress (kg/cm2) Notes


6.051 safe ###
###
Punching stress (kg/cm2) Notes ###
5.206 safe ###

###
Calculation of Rft. : As /m Asmin ###
12.00 8.25 cm2 ###
###
Long Rft. : no. f total no.
6 16 /m 16 ###

Short Rft. : no. f total no.


5 16 /m 20 ###

By: Eng. Mahmoud El-Kateb


Concrete design using the ultimate limit design method.

* Design of Combined footings

* Project :

Concrete Fcu = 300 kg/cm2

Steel Fy = 3600 kg/cm2


Bearing capacity qall = 1.50 kg/cm2

Column working load column dim. (cm) extension


Col Nw (ton) trans. long. of P.C (cm)
exter. 70 40 40 30
inter. 130 40 40 30

Distance from c.g to c.g: 2 m ###


###
Resultant of 2 loads is at: 1.30 m from external column
###

Dims. of P.C : B (cm) L (cm)


minimum 370 365
chosen 300 450

Dims. of R.C : B (cm) L (cm) t (cm) ###


240 390 60 ###
###
###
###
###
Longitudinal direction: ###
###
Top Rft. : no. f total no. ###
5 16 /m 14 ###

Bottom Rft. : no. f total no. ###


6 16 /m 16 ###
###
Transverse direction: ###
###
Top Rft. : no. f total no. ###
5 12 /m 21 ###
###
Bottom Rft. : no. f total no. ###
7 16 /m 29 ###
###
###

By: Eng. Mahmoud El-Kateb


Concrete design using the ultimate limit design method.

* Design of Strap footings

* Project :

Concrete Fcu = 225 kg/cm2

Steel Fy = 3600 kg/cm2

Stirrups Fy = 2400 kg/cm2


Bearing capacity qall = 1.50 kg/cm2

Column working load column dim. (cm) extension


Col Nw (ton) trans. long. of P.C (cm)
exter. 71 50 25 0
inter. 124 80 25 40

Distance from c.g to c.g: 4.14 m

Take eccentricity = 1.2 m

Dims. of P.C : B (cm) L (cm)


external footing 255 265
internal footing 255 250

Dims. of R.C : B (cm) L (cm) t (cm)


external footing 175 225 60
internal footing 175 170 60

Longitudinal direction:

Dim. Of strap beam : b (cm) t (cm)


50 90

Rft. Of strap beam : no. f


Top Rft. 7 22
Bottom Rft. 5 16

Stirrups : no. f
5 10 4 branches

Transverse direction:

Bottom Rft. : no. f total no.


external footing 5 16 /m 13

By: Eng. Mahmoud El-Kateb


Concrete design using the ultimate limit design method.

internal footing 5 16 /m 10

By: Eng. Mahmoud El-Kateb


Concrete design using the ultimate limit design method.

* Pile Caps

* Project :

Concrete fcu = 250 kg/cm2


Steel Fy = 3600 kg/cm2

Pile Diameter = 0.45 m

Pile Capacity = 100 ton

Cap: PC1

Column Load = 400 ton

Estimated No. of piles = 5 piles

Choose pile spacing from 1.35 to 2.7 m = 1.35 m in long direction

Choose pile spacing from 1.35 to 2.7 m = 1.35 m in short direction

Choose arrangement of piles = 3 x 2 Piles used = 6

Dim of R.C Cap = 4.05 x 2.7 x 0.9 m

Dim of P.C Cap = 4.25 x 2.9 x 0.1 m

Actual Pile Load = 71.2 ton Ok

Moment on Short direction = 150 mt C1 = 5.5007 J= 0.826


As (min) = 33.21 cm2
As (used) = 61.52 cm2 17 f 22

Moment on Long direction = 250 mt C1 = 5.2184 J= 0.826


As (min) = 49.82 cm2
As (used) = 102.53 cm2 27 f 22

By: Eng. Mahmoud El-Kateb


Concrete design using the ultimate limit design method.

* Design of Retaining Walls

* Project :

Concrete Fcu = 300 kg/cm2

Steel Fy = 3600 kg/cm2

Bearing capacity qall = 2.40 kg/cm2 0.50

Soil density g = 1.80 ton/m3 0.2 t/m'

Cohesion of soil C = 0.00 kg/cm2

Angle of friction d = 22 degree

7.80

7.20
Coeff. of earth pressure Ka = 0.3
1.00

0.85 2.15

0.60 R.C
P.C
0.30
3.50
4.10

Factor of safety against sliding = 1.42

Factor of safety against overturning = 2.13

Max. stress on soil = 2.45 kg/cm2 Unsafe stress No tension on soil


Min. stress on soil = 0.12 kg/cm2 Safe stress No tension on soil

Calculation of Rft. :

Mu (m.t) C1 J As (cm2) As min


For wall 52.72 3.55 0.784 39.74 7.05 9 f 25
For Base 13.47 8.21 0.826 8.23 8.25 4 f 18

By: Eng. Mahmoud El-Kateb


Concrete design using the ultimate limit design method.

By: Eng. Mahmoud El-Kateb


Concrete design according to the Egyptian code1995.

* Deflection of Cantilevers

* Project :

Concrete Fcu = 225 kg/cm2


Steel Fy = 3600 kg/cm2

PDL+ PLL
WDL+ WLL

Span

Breadth Depth Thickness Span


Sec. Properties of sec: b (cm) d (cm) t (cm) L (m)
1 25 65 70 2.4

Top Rft.: no. f area


5 18 12.72 cm2

Bottom Rft.: no. f area


5 18 12.72 cm2

Working loads: PDL (t) PLL (t) WDL (t/m) WLL (t/m)
2.50 1.50

Initial deflection: 0.20 cm

After long term: 0.30 cm

Allowable value: 0.53 cm

Notes: Safe

By: Eng. Mahmoud El-Kateb


Concrete design according to the Egyptian code 1995.

* Deflection of Simples

* Project :

Concrete Fcu = 225 kg/cm2


Steel Fy = 3600 kg/cm2

PDL+ PLL
WDL+ WLL

Span/2 Span/2

Breadth Depth Thickness Span


Sec. Properties of sec: b (cm) d (cm) t (cm) L (m)
1 25 65 70 6

Top Rft.: no. f area


4 12 4.52 cm2

Bottom Rft.: no. f area


5 16 10.05 cm2

Working loads: PDL (t) PLL (t) WDL (t/m) WLL (t/m)
1.50 1.00 2.00 1.50

Initial deflection: 1.16 cm

After long term: 2.14 cm

Allowable value: 2.40 cm

Notes: Safe

By: Eng. Mahmoud El-Kateb