INCIDENT REPORT
tR NO. LMR-2021-05-0078

t. Residential Unit Concem:


Building: NORTH TOWER Building: Level : BASEMENT 1
lncident Title: TRIPPING OF MAIN Unit No: Location:
CIRCUIT BREAKER Unit Owner: CCW/ELEVATOR/COMMON
lncident Date: May 27,2021 AREA LIGHTINGS
Reported By: Mark Agliam

Aromd 1850H of May 27 ,2021 when our security reported that there is a power interruption at North Tower.
Our maintenance on duty immediately checked the concern and found out that the main circuit breaker located at
basement 1 right wing of North Tower was tripped off again. The circuit breaker has a rated capacity of 800,{
and holds the Elevator, CCTV and common area lightings of the North tower building. It was monitored that the
tripping happened between 1730H to 1900H. When the main circuit breaker trip offl all the CCTV monitors and
lights at common areas were off. Al1 Elevators were stucked up and the lights inside were offltoo. There was an
incident also that the multimedia monitor of elevator 2 of north was damaee during the
lll. lmmediateAction(s): hitiated by:
FO,Security
-Conduct tracing on the main panel and fuund out Date lmplemented:
that the main ckcuit breaker was trip off. May 27,2021

lV. lnterimlTemporary Solution(s):

-Energized the tripped off circuit breaker on


basement 1.
V. Root Cause(s) of the Problem:
- Possible there is an enor on the trip settings of main breaker. We suggest further investigation with contractor to

Vl. Corrective Action(s): lnitiated By:

- Coordinate to Engr.Jerome Pinpin of Date lmplemented:


Construction Group so they will raise this To be done
concem to the service contractor.

Verified and Glosed-Out By:

lX. Lessons Learned / Preventive Action(s):

Date and Time: Recommending Approved By: Date and Time:


e
f

-'i,

This Main Circuit breaker was


tripped off. Location is in the
basement I right wing of north
tower. Trip settings are shown
above. Ground fault detection
settings is .l second

These are the circuits


tied up to the concemed
main breaker

l{PGll trP