225 kV Guinea-Mali Power Interconnection Project

Lot n ° P6: 225/30 kV Beyla and Nzérékoré substations


International Bidding Document / PART 2 - Project Owner s Requirements
Section VII. Specifications

DATA SHEET

20 MVA 225/30/11 kV transformer

Item Designation Units Specified Value Guaranteed value

Average temperature rise of the windings °C 55


measured by temperature probes
Maximum heating of the sheets °C 60
Maximum heating of the hottest point of the °C 65
windings
Maximum heating of the oil at the top °C 50

Terminal characteristics
HT terminals
18 Manufacturer -
Denomination according to catalog -
19 Terminal type (Oil Impregnated Paper, Res- - resin impregnated
in Impregnated Paper, Resin Impregnated paper capacitor
Synthetics, Resin Impregnated Fiberglass)
20 Material of the connection terminal (porcelain, - porcelain
ceramic, etc.)
21 Nominal current in continuous service A
22 Heating of the conductive parts, with respect °C
to the oil from the upper part to the hottest
point, at nominal current and
continued in service
23 Isolation voltage between phase and earth kV 245
24 Length of the creepage line of 25 mm / kV mm > 6125
applied to phase-to-phase voltages or 43.3
USCD corresponding to the pollution level of
-
IEC 60815-2008 standard)
25 Short duration 50 Hz withstand voltage (1 kV 460
min)
26 Surge withstand voltage (BIL) kV 1050
LV terminals:
27 Manufacturer -
28 Denomination according to catalog -
29 Terminal type (Oil Impregnated Paper, Res- - oiled paper
in Impregnated Paper, Resin Impregnated
Synthetics, Resin Impregnated Fiberglass)
30 Terminal material - copper
31 Nominal current in continuous service A 3150
32 Heating of the conductive parts, with respect °C
to the oil from the upper part to the hottest
point, at nominal current and
continued in service
33 Isolation voltage between phase and earth kV 36
34 Total length of the leakage mm > 1116
35 Short duration 50 Hz withstand voltage (1 kV 70
min)