Internal Minutes of Meeting

Project: Vietnam, Phong Phu 42MWp

No. Phase Topic / Item Description


1 Operation SCADA-PPC Comms error in PPC

SCB monitors- Comms lost during early morning and


2 Operation
comms error late afternoon

3 Operation UPS 7 UPS 7 battery damaged,

4 Operation Panels damage-0517 Around 376 panels- damaged

Cooperation with SLC, Hard & soft


5 Operation PM schedule
copy

Toolist ready?, Plan? experienced


6 Operation Annual PM
technicians?

7 Operation Tx 6 & 7 relay

8 Operation Animal control Method to prevent animal/ insects

9 Operation UPS 5 UPS 5 battery damaged,

The master & slave


10 Operation The screen was on the blink
screens at SCADA

11 Operation HMI screen of CCTV The screen didn’t display anything

12 Operation CCTV 6 Lost signal on HMI

13 Operation TX 6, 7 T-Plug cable has damaged

Earthing cable
14 Operation Rusty bolts
terminal

15 Operation Panels at MVPS 7 Shading panel


16 Operation Transformers

17 Operation Transformers Tx 8 tripped 3 times on 11-Nov

18 Operation Transformers Tx 7 tripped 4 times on 27-Nov


Date: 2020-12-07
Time: 13:30pm - 16:00pm
Location: Zoom meeting
Target of the Meeting:
Participants: Ella, Hieu, Lam, SLC
Note by 2020-12-07
Start Date
Comment Action / To Do
Identify signal error from SCADA/ ENIC to grid Record issue in document.

Waiting Longmax to send Monitor-


_Comms lost during early morning and late afternoon 18-May
spare part

Check with SCADA for warranty claim or battery


Already quoted price 2-Apr
replacement

SCB- surge arrestor status, fuse, lightning a lot on the Moved back to warehouse
17-May
17/05? Any physical damage?

Team structure, document recording. Process monitoring 1-Jun

Study manual first. Most cleaning job, dust removal.


Performed Annual PM at MVPS 6 1-Jun
Some night shift

Sent mail to SMA Waiting SMA to replace relay

Already sealed cables entry


Poison, catch, cat, electrical device Used mothballs to put in LV room at all 12-Jun
MVPSs.
UPS still showed "fault" led after replacing batteries Ask to supplier 13-Jun

The screens have damaged Replaced 15-Jun

The screen has damaged 27-Jun

Replaced
POE has damaged 27-Jun

T-Plug cable has damaged Replaced 27-Aug

SLC will schedule plan to replace bolts


Rusty bolts 28-Aug
and terminal connectors

SLC removed shading panel then fill


Shading panel 28-Aug
empty strings at MVPS 5
_TX 6 didn't meet the operational
_First priority: Repair TX6 or replace by new one? requirements after conducting TX
Work date of start - scheduled for 15th Nov. testing.
_ Progress of checking, testing, repairing, _ SMA will take a responsibility for lost
confirmation for re-energizing of TX6. production of SLC.
_ Is there any way that SMA could do to make Tx6 re- _12 Nov,2020 SMA will replace the
13-Oct
energize ASAP? Lost production. new TX at MVPS 6.
_ Repair Tx7 and Tx1 _12-Nov: Received the new TX.
_Tx2,3,4,5,8: need to conduct the transformer testing _13-Nov: Replaced the new TX
because total dissolved combustible (TDC) of all TXs _14-Nov: Energized the TX with no
are increased load about 4 hours.

_ 11,12-Nov: Done vacumm following


SMA's instruction then re-energized
Tx, Waiting for SMA to perform oil 11-Nov
treatment
_17-Nov: DNH performed oil treatment

_ 27,28-Nov: Done vacumm following


SMA's instruction then re-energized
Tx, Waiting for SMA to perform oil 27-Nov
treatment
_29-Nov: DNH performed oil treatment
Technic
Procurement
Finance
Legal

Supporting
End Date Responsible Remark
Department
SCADA

ETIC & NANZI Trina, NANZI, Lam

9-Oct SLC & Trina Lam

APAC sales Gordon

1-Jun SLC Lam

30-Jun SLC Lam

IFC & SMA Lam

12-Jun ETIC & SLC Lam

ETIC & Trina Ella

Changed VGA cable of another screen 1.mp4

7-Oct ETIC & Trina Hieu Changed VGAcableofanotherscre n.mp4 Changed VGA cableofanotherscre n.mp4 Changed VGAcableof anotherscre n.mp4
Changed VGA cable of another screen 1.mp4

Changed VGA cable of another screen 1.mp4 Changed VGA cable of another screen 1.mp4

Changed VGA cableofanotherscre n.mp4


ETIC & Trina Lam

12-Sep
ETIC & Trina Ella

ETIC, SMA,
1-Oct Hieu
DNH, IFC

SLC SLC

22-Oct SLC SLC


14-Nov SLC SLC

17-Nov SMA, DNH, IFC SMA, DNH, IFC

29-Nov SMA, DNH, IFC SMA, DNH, IFC


Done
Open

Open

Close

Open

Close

Open

Open

Close

Open

Changed VGA cable of another screen 1.mp4

Close
Changed VGA cable of another screen 1.mp4

Close

Close

Close

Open

Close
Close

Close

Close
Note: TX No. are default as x.1
One Work Order will have multiple tasks, this table is

Work order Category No Start Date End Date


1 Tx 2.1 4-Jul-19 1-Feb-20
2 INV 7.2 27-Jan-20 30-Jan-20
3 SCB 6.2 9-Feb-20 9-Feb-20
4 Tx 12-Feb-20 12-Feb-20
5 PPC 15-Feb-20

6 PPC 17-Feb-20
7 INV 8.2 11-Feb-20 17-Feb-20
8 SCB 1 24-Feb-20
9 SCB 2.2 24-Feb-20
10 INV 8.2 26-Feb-20 10-Mar-20
11 INV 7.1 9-Mar-20 9-Mar-20
12 SCB 4.2 27-Mar-20

13 Tx 2.1 4-Jul-19 30-Mar-20

14 Tx 6.1 28-Feb-20 19-Apr-20


15 Tx 7.1 27-Jan-20 20-Apr-20

16 MVPS 1 29-Sep-20 7-Dec-20

17 PPC 5-Mar-20

18 PPC 21-Feb-20 21-Feb-20

19 Tx 6.1 3-Apr-20 8-May-20


20 SCADA
21 SCADA
22 SCADA
23 PPC
24 SCB 7.1 28-Apr-20 28-Apr-20
25 SCB 6.2 28-Apr-20 28-Apr-20
26 SCB 4.2 28-Apr-20 28-Apr-20
27 SCB 2.1 28-Apr-20 28-Apr-20
28 SCB 1 28-Apr-20 28-Apr-20
30 Tx 7.1 6-May-20 6-May-20

33 INV 6.1 4-May-20 2-Jul-20

34 SCADA 7-May-20 7-May-20

35 Tx 7.1 8-May-20 8-May-20

36 INV 6.1 20-May-20 20-May-20

37 Tx 6.1 3-Apr-20 24-May-20


38 Tx ALL 28-May-20 28-May-20
4.1
39 SCADA 4.2 19-May-20 14-Aug-20
5.2

40 UPS 5.1 13-Jun-20

41 CCTV 6.1 17-May-20 31-May-20


42 CCTV 7.1 17-May-20 31-May-20
43 CCTV 6.1 27-Jun-20

44 CCTV 3.1 27-Jun-20 11-Jul-20

45 SCADA 15-Jun-20 12-Sep-20


10-Jul-20 10-Jul-20
46 Panel
6-Aug-20 6-Aug-20

47 Tx 7.1 2-Aug-20 27-Aug-20


48 INV 8.1 3-Aug-20 4-Aug-20
48 SCADA 13-Aug-20 13-Aug-20
49 UPS 7.1 3-Apr-20 9-Oct-20
50 CCTV
51 SCB 3.1 26-Aug-20 26-Aug-20

52 Tx 1 28-Aug-20 29-Aug-20

53 Panel 1 3-Sep-20 4-Sep-20


54 Tx 1 13-Sep-20 13-Sep-20
55 CCTV 6.1 27-Jun-20 18-Sep-20
56 Tx 6.1 17-Sep-20 1-Oct-20

57 Tx 6.1 12-Oct-20 13-Oct-20

58 Tx 1 13-Oct-20 13-Oct-20

59 Panel 6.1 16-Oct-20 16-Oct-20

60 Tx 6.1 21-Oct-20 21-Oct-20


61 Panel 7.2 22-Oct-20 22-Oct-20

62 SCB 7.2 24-Oct-20 30-Oct-20


63 Tx 8.1 10-Nov-20
64 INV 7.1 11-Nov-20 11-Nov-20
65 INV 4.1 2-Dec-20 2-Dec-20

66 INV 2.2 24-Dec-20 24-Dec-20


TX No. are default as x.1.
ultiple tasks, this table is summary when WO close.

Phong
Issue Description
Temperature value of Transformer is under Zero
P and Q changed continuously
Ground fault at INV 6.2

Coil was damaged


The communication is lost
The communication is lost
Coil was damaged
P and Q changed continuously
The communication is lost

Displayed “Fan fault MV TRF” error on screen monitor and made "noise" from
fans.

Tripped
Tripped

Oil leakage from MV Transformer

Actual value exceeds setpoint value

The communication between PPC and ION meter is interrupted.

MVSG
Slow response
The status signals on SCADA
Symbol of schematic on SCADA
The communication is lost (pink column)
The communication is lost
The communication is lost
The communication is lost
The communication is lost
The communication is lost
MV transformer tripped

HMI screen didn't display anything

Slave freeze

Could not switch on MVSG after swapped 2 terminal blocks and 2 Relays
(STSD cabinet) between MVPS 6 and MVPS 7).

INV was down

MV transformer tripped
Take oil sample of all Tx

SCBs of MVPS 4, 5 have been lost communication.

UPS at MVPS 5 has been damaged

Lost signal on HMI


Lost signal on HMI
Lost signal on HMI

Lost signal on HMI

2 HMI screens Master & Slave were on the blink


A2.1-J08-M8, A5.1-J04-M12
A4.1-J14-M23

Tx tripped bcz low oil level


INV was down
HMI SCADA didn't display value of INVs
UPS at MVPS 7 has been damaged
Invalid password or username
SPD has damaged

Oil leakage from MV Transformer

A2.1-J05-M12: damaged MC4


Tx tripped bcz low oil level
Lost signal on HMI
T-plug has been damaged

MVPS was down bcz low oil level at TX but TX is not tripped

MVPS was down bcz low oil level at TX


SCB7.2-J05: Wrong value on SCADA
Tx tripped
INV was down
Warning low grounding resistance.

INV was down


Phong Phu Solar Farm Work Order Register
Root Cause Analysis
Faulty cable

Damaged cable

Damaged coil
Damaged monitor
Damaged monitor
Damaged coil

Damaged monitor

Damaged cable

Oil issue
Oil issue

Loose cable
Wrong procedure to switch off

Reboot and update infor

Ground fault

Port 1, 2, 5, 7 (MVPS4) and port 8 (MVPS5) of communication


switch have been damaged

UPS 5 showed "fault" led after replacing batteries

POE have been damaged


POE have been damaged
POE have been damaged
Ethernet cable (from Media converter to Switch) has been
damaged
Maybe screens have been damaged

MC4 has been burnt

Low oil level


Batteries have been damaged

Low oil level


POE have been damaged

Low oil level

Low oil level

Avoid lost production from Tx6


Avoid shading location

AC side interference
Low oil level
MC4 burnt at A7.2-J05-M22
Empty strings was not disconnected

ground fault at SCB


ter
Action Performed Follow up
Replaced the new cable
Upgraded firmware
Taped the damaged cable
DGA test for all TXs
Adjust the actual value response parameter according
to A0 request
Adjust the frequency response parameter according to
A0 request
Replaced 1 UV coil
Replaced monitor
Replaced monitor
Replaced 3 coils
Upgraded firmware
Replaced monitor
Joined 2 pink wire (Fan failure detectionn 44) and red
wire (Fan failure detection 45) together at W811.1 and
reconnected
Oil treatment and replaced DMCR
Oil treatment and replaced DMCR

O&M team checked and cleaned MV Transformer'


chamber.
Keep observing
O&M team have tightened the bolt inside the chmaber
of MV transformer according to the SMA instructions.

SMA changed "gradient set-point decrease"


Keep observing
parameter to 15 MW/min

Checked Ethernet gateway and reconnected the cable

_Replaced 4 new cables temporarily from DMCR to


STSD cabinet.
SMA will replace 4
_Connected SC30RIO from INV-slave 6 to INV-slave
new cables in the
7.
future
_Swapped 2 terminal blocks and 2 Relays (STSD
cabinet) between MVPS 6 and MVPS 7).
Replaced 1 monitor
Replaced 1 monitor
Replaced 1 monitor
Replaced 2 monitors
Replaced 1 monitor
Restart the Trafomonitor IKI-30 at MVSG Cabinet.

Replaced HMI screen

Disconnected 1 cable No 1.16 at Relay Q2 (STSD


cabinet)

Found leakage spot and reconnected the wire by MC4

Disconnected 1 cable No 1.16 at Relay Q1 (STSD


cabinet)
Take oil sample of all Tx

Checked SCADA switch via NANZI's software


NANZI engineers fixed remotely.

Connected SCADA power wire directly to STSD box


(bypass UPS).
Replaced 2 batteries, disconnected the fan, Fault led
was on.
Replaced 1 POE (from spare part)
Replaced 1 POE (from MVPS 5)

Crimped RJ45 Ethernet cable

Replaced 2 monitors

Replaced MC4 connection

Performed the oil treatment


_Reconnected all cables at SC30ACC card and
checked Contactor 400VAC 3 poles
Reboot PSX 643U at substation
Replaced 2 batteries
Supplier give instructions remotely
Replaced new SPD
_Cleaned inside the chamber and the floor
_Used torque wrench to tighten bolts inside the
chamber with 35 Nm
_Sealed the edge of busway from MV TRF side with
silicon gel
Replace MC4 connection
Do the vacumm then start
Replaced 1 POE
Rerplace T-Plug

Performed the oil treatment


_13-Oct: After energize Tx6, there're some cracks on
Tx6, oil spilled and Tx was tripped. SMA filled the
cracks with soap, took the oil out of tx then welded the
cracks.
_14-Oct: SMA filled oil to Tx6, performed the oil
purification and did the test for Tx6.
_ 21-Oct: QT(SMA) performed Tx6 test.
_23-Oct: SMA exported IKI 30 Relay data from MVPS
6.
_13-Nov: Replaced the new TX
_14-Nov: Energized the TX with no load about 4
hours.

Performed the oil treatment

Re-install string from MVPS 6 to another MVPS


+ 6.2-J13-M21 ===> 7.2-J05-M17: 30 panels
+ 6.2-J13-M22 ===> 7.2-J05-M20: 30 panels
+ 6.2-J14-M06 ===> 7.2-J05-M21: 30 panels
+ 6.2-J14-M01 ===> 7.2-J05-M23: 30 panels
+ 6.2-J14-M02 ===> 7.2-J05-M24: 30 panels
+ 6.1-J01-M04 ===> 4.1-J07-M01: 30 panels
+ 6.1-J04-M03 ===> 4.1-J07-M02: 30 panels
+ 6.1-J04-M11 ===> 4.1-J07-M03: 30 panels
+ 6.1-J04-M07 ===> 4.1-J07-M04: 30 panels
+ 6.1-J04-M08 ===> 4.1-J07-M06: 30 panels
+ 6.1-J04-M12 ===> 5.1-J11-M19: 30 panels

SMA performed Tx6 test.


Re-install string from MVPS 7 to MVPS 5
+ 7.2-J07-M1 ===> 5.1-J09-M13: 15 panels
+ 7.2-J07-M2 ===> 5.1-J09-M13: 15 panels
+ 7.2-J07-M5 ===> 5.1-J09-M14: 15 panels
+ 7.2-J07-M6 ===> 5.1-J09-M14: 15 panels
30-Oct: Insert 120 ohm resistance into the serial port,
keep on observation
Released gases from DMCR 8

Disconnected DC 15A fuse of A4.1-J07-M3,A4.1-J07-


M4
Cable has been damaged
Replaced new cable from A2.2-J10-M11 to SCB
Responsible Person Status Referred Photo/Doc Name
SMA, IFC Close
SMA Close Video-INV 7.1-0903-INV 7.2-2701
Lam, SLC Close INV 6.2-0902
QUATEST 2 Close DGA-1202
SMA Close

SMA Close
IFC Close INV 8.2-Coil
Lam Close
Lam Close
IFC Close INV 8.2-Coil
SMA Close Video-INV 7.1-0903-INV 7.2-2701
Lam Close

IFC Close Tx2-3003

SMA, Westrafo, NLP, IFC Close


TX6,7-Oil treatment-18&1904
SMA, Westrafo, NLP, IFC Close

SMA, Etic, Solarcom Close MVPS1-Oil leakage

SMA Close

SMA, Lam Close Video-Ethernet gateway

_TX6-DMCR-2304
SMA, IFC Close _TX6-2 Terminal block and 2 Relays
(STSD)-0805
Trina Open SCADA Low response
Trina Open
Trina Open
SMA, Trina Open
Lam Close
Lam Close
Lam Close
Lam Close
Lam Close
SMA, IFC Close
_20200702-Daily Pre-Start
SMA, IFC Close
_INV 6.1-Screen-0405
Refer to "SCADA" sheet in Monthly
Trina, Lam Close
report_2005

SMA, IFC Open

Hieu Close

SMA Open
Dong Nam Hung Close

Trina, Lam Close

Trina, Lam Open

Close
Close
Trina, Lam Close

Trina, Lam Close

Trina, Lam Close


Close
Hieu
Close

_20200826-Daily Pre-Start
SMA Close
_20200827 - TX7 - Oil treatment
SMA, IFC Close 20200804-INV 8.1-Contactor
Trina, Lam Close
Trina, Lam Close
Trina, Hieu Close
Trina, Hieu Close

SMA, IFC Open

Trina, Lam Close


Trina, Hieu Close
Trina, Hieu Close
DNH Close

DNH Open

DNH Close

SLC Close

QT Close
SLC Close

Trina, Lam, Hieu Close


SLC, SMA, Trina Open
SLC, Trina Close
SLC, Trina Close

SLC, Trina Close


Work order Component Start time End Time
15-Dec-19
9-Jan-20
11-Jan-20

15-Feb-20
1 PPC 17-Feb-20
21-Feb-20 21-Feb-20
5-Mar-20

7-May-20 7-May-20
2 SCADA
19-May-20

15-Jun-20 7-Oct-20
13-Aug-20 13-Aug-20
Issue Description
_ Actual Power doubles as Setpoint
_ Atumatically change into Local, twice in 1 minute

_Actual P exceeded Setpoint

Adjust the actual value response parameter according to A0 request


Adjust the frequency response parameter according to A0 request
The communication between PPC and ION meter is interrupted
Adjust the actual value response parameter to observe the actual value

_Commution between SCADA and PPC was lost at "local" or "remote" mode (The pink
column) every day

Sometimes SCADA responded the status of INV slowly (for example: after replacing IGBT,….,
INV already operated, the SCADA still didn’t show the power of INV on screen or when INV
already turned off, the SCADA still showed the power of INV on screen)
The screen of Sac2 (Slave) is frozen
SCBs of MVPS 4, 5 have been lost communication.
Root cause: port 1, 2, 5, 7 (MVPS4) and port 8 (MVPS5) of communication switch has been
damaged
2 HMI screens Master & Slave were on the blink
HMI SCADA didn't display value of INVs
Solution Recovery
_ 15-Dec: Emailed SMA, no response
9-Jan: SMA analyzed data
11-Jan: sent Service Information of INV to SMA
SMA changed Wgra to 1000 pu/s so INV will respond fastly to PPC
Nikhil changed "gradient set-point increase and gradient set-point decrease"
parameter to 10 MW/min
Avinash changed threshold of frequency to 50.5 Hz
Checked Ethernet gateway and reconnected the cable
Nikhil changed "gradient set-point decrease" parameter to 15 MW/min

Refer to "SCADA" sheet in May-2020

NANZI Engineer fixed remotely

Replaced new monitors


Reboot PSX 643U at substation
Status Image
Close

Close

Close
Close
Close
Close

Open

Open

Close

Close

Close
Close
Start End
Component
Date Time Date Time
11-Feb-20 11-Feb-20
INV 1

INV 2.1

29-Sep-20 22:42 30-Sep-20 8:43

INV 2.2
24-Dec-20 6:25 24-Dec-20 6:40

INV 3.1

INV 3.2

2-Dec-20 2-Dec-20
INV 4.1

INV 4.2

10-Feb-20 10-Feb-20
10-Feb-20 18:04 11-Feb-20 7:25
11-Feb-20 18:07 12-Feb-20 6:57
INV 5.1

INV 5.2

4-May-20 9:20
8-May-20 20:00 8-May-20 21:00

2-Jul-20 20:00

INV 6.1

20-May-20 6:15 20-May-20 15:30

10:00 10:01
4-Oct-20 4-Oct-20
9:58 10:00

9:16 9:25
5-Oct-20 5-Oct-20
5-Oct-20 5-Oct-20
9:39 9:46

9-Feb-20 6:38 9-Feb-20 10:49


INV 6.2

11-Jul-20 5:40 11-Jul-20 6:19

After
9-Mar-20 9-Mar-20
generation

11-Nov-20 7:02 11-Nov-20 7:47


INV 7.1

11-Nov-20 8:01 11-Nov-20 12:20

11-Nov-20 12:30 11-Nov-20 13:46

After
27-Jan-20 30-Jan-20
INV 7.2 generation

24-Feb-20 17:25 25-Feb-20 7:00


INV 8.1
INV 8.1

3-Aug-20 17:59 4-Aug-20 22:00

10-Feb-20 10-Feb-20

11-Feb-20 17:58 17-Feb-20 19:40


INV 8.2

26-Feb-20 18:00 10-Mar-20 11:15


Issue Description

SMA requested to replace new 3 IGBT

Warning Ground fault

INV was down

INV was down because of ground fault at SCB

Warning low grounding resistance.

SMA requested to replace new 3 IGBT

Warning Ground fault


HMI screen didn't display anything

INV was down

INV was down


INV was down

Ground fault

INV was down

The active power and reactive power of INV 7.1 change continuously
(We can see this issue on SCADA and INV web page)

INV was down

The active power and reactive power of INV 7.2 change continuously
(We can see this issue on SCADA and INV web page)

The INV didn’t operate


INV was down

SMA requested to replace new 3 IGBT


Error code

#7601: IPC communication error (0)

#3501: Error:The insulation monitoring device has


measured a too low grounding resistance.

#3501: Error:The insulation monitoring device has


measured a too low grounding resistance.

#9023: Fast stop tripped by DC overcurrent


3501: Insulation failure

#6458: Transformer prot. Triggered


#6458: Transformer prot. Triggered

#3501: Error: The insulation monitoring device has


measured a too low grounding resistance
#3601: Warning: Leakage current to ground
has occurred in the PV array or the
threshold defined in the PvGnd.RisIsoWarnLim
parameter has been
reached

#3501: Error: The insulation monitoring device has


measured a too low grounding resistance

#3501: Error: The insulation monitoring device has


measured a too low grounding resistance

#6423: Error: temperature of MV transformer is too


high. Disconnection
limit exceeded. Inverter stops feeding operation
#7700:An error at the internal switches
has occurred

#7704: An error has occurred at the DC


switchgear
Root cause Loss production

ground fault at SCB

Empty strings was not disconnected


Leakage current at A6.2-J14-M16
Leakage currrent at A6.2-J10-M6

MC4 burnt at A7.2-J05-M22


Actual performed for Solution recovery Follow up

Replaced 3 IGBT

Will check PV array


when it happens
again

SMA restart INV via teamviewer

Cable has been damaged


Replaced new cable from A2.2-J10-M11 to SCB

Disconnected DC 15A fuse of A4.1-J07-M3,A4.1-J07-M4

Replaced 3 IGBT

Set the parameter ErrClr to Ackn

Will check PV array


when it happens
again

N/A
Swapped the SC30COM between INV 6.1 and 6.2 to
check and then swapped back.

Replaced HMI screen


Old S/N: 5619
New S/N: 5340

Reconnected the cable by MC4

Set the parameter ErrClr to Ackn


Set the parameter ErrClr to Ackn

Taped the damaged cable

Set the parameter ErrClr to Ackn

9-Mar-2020, Nikhil upgraded INV 7.1

Replaced the MC4

30-Jan-2020, Vishal upgraded INV 7.2

Set the parameter ErrClr to Ackn


_Reconnected all cables at SC30ACC card and checked
Contactor 400VAC 3 poles

Replaced 3 IGBT

_Turn off Aux about 5 mins and on again and then errclr
(Follow Vishal SMA) every evening until INV 8.2 is
replaced coil
_17-Feb-20, IFC technician replaced 1 UV coil of DC
Switch at INV 8.2
Old S/N: 8340322072305000
New S/N: 8490669072305000

_Turn off the key, off Aux about 5 mins and on again
(Follow Vishal SMA) every evening until INV 8.2 is
replaced coil
_10-Mar-2020, IFC tecnicains replaced 3 coils of DC
Switch at INV 8.2
Status Image

Close

Close

Close

Close

Close

Close
Close

Close

Close
Close

Close

Close

Close

951715385861827879.mp4 1535565327644442342.mp4

Close

Close

Close
Close

Close

Open
Doc Reference

_20200210 and 20200211-Daily Pre-Start


_20200211 - INV 1.1 - Replaced 3 IGBTs

20200210 - INV 8.2 5.1 - Replaced all IGBTs


20200702 - INV 6.1 - Replaced HMI screen
email on the 9/2/2020 from Lam

_20200131-INV7.2-Kvar
_20200804 -Daily Pre-Start
_2020804-INV 8.1 - Check Contactor

_20200210 and 20200211-Daily Pre-Start


_20200210 - INV 8.2 5.1 - Replaced all IGBTs

_20200217-Daily Pre-Start
_20200217-INV 8.2-Replaced UV Coil

_20200310 - INV 8.2 - Replace 3 DC Coils


Start End
Location
Date Time Date Time

3-Jul-19 4-Jul-19

29-Sep-19 12-Dec-19

28-Aug-20 29-Aug-20

9-Jul-19 9:50 9-Jul-19 10:40

13-Sep-20 12:38 13-Sep-20 14:29

TRF 1
17-Sep-20 7:07 17-Sep-20 12:35

19-Sep-20 10:11 19-Sep-20 18:25


25-Sep-20 6:12 25-Sep-20 13:17

27-Sep-20 23:14 28-Sep-20 8:45

1-Oct-20 9:36 1-Oct-20 10:19

5-Oct-20 6:16 5-Oct-20 7:56

6-Oct-20 22:14 7-Oct-20 7:41

9-Oct-20 16:11 9-Oct-20 21:09

11-Oct-20 6:32 11-Oct-20 7:33

13-Oct-20 4:30 13-Oct-20 10:00

4-Jul-19 1-Feb-20

TRF 2

4-Jul-19

30-Mar-20
TRF 3
TRF 4
TRF 5

May 29-Aug-19

28-Feb-20 13:40 28-Feb-20 18:18

2-Apr-20 6:53 2- Apr-20 18:00

3-Apr-20 0:16

6-Apr-20

18-Apr-20 16:30 19-Apr-20 5:30

20-Apr-20 4:30

12:00
21-Apr-20
16:00
22-Apr-20 12:32

23-Apr-20 20:30

26-Apr-20 20:00

4-May-20 5:45 4-May-20 9:20

8-May-20 16:45 8-May-20 21:00

TRF 6

24-May-20 5:48 24-May-20 10:36

19-Sep-20 6:19 20-Sep-20 6:41

2-Oct-20 7:33 2-Oct-20 11:59

3-Oct-20 3:29 3-Oct-20 9:27


4-Oct-20 2:49 4-Oct-20 9:23

3:51 7:58

5-Oct-20 5-Oct-20

12:06 12:48

5-Oct-20 20:03 6-Oct-20 9:58

6-Oct-20 14:41 7-Oct-20 8:07

8-Oct-20 5:29 8-Oct-20 7:42

9-Oct-20 4:29 9-Oct-20 8:01

9-Oct-20 18:10 10-Oct-20 8:09

5:36 11-Oct-20 7:33

11-Oct-20

18:10 12-Oct-20 7:18

12-Oct-20 20:30 13-Oct-20 2:30

13-Oct-20 16:05 14-Oct-20 15:30

1-Oct-20
13-Nov-20 9:30 13-Nov-20 12:30

14-Nov-20 10:30

April 29-Aug-19

27-Jan-20 8:12 27-Jan-20 15:45

19-Apr-20 18:00 20-Apr-20 6:00

20-Apr-20 18:40
21-Apr-20 12:00

TRF 7
6-May-20 6:00 6-May-20 12:30
8-May-20 16:45 8-May-20 21:00

2-Aug-20 13:03 27-Aug-20 17:50

1-Oct-20
27-Nov-20 4:38 27-Nov-20 7:32
27-Nov-20 8:43 27-Nov-20 10:22
27-Nov-20 11:31 27-Nov-20 14:36
27-Nov-20 16:02 27-Nov-20 16:35
27-Nov-20 19:46 28-Nov-20 8:14
28-Nov-20 10:06 28-Nov-20 10:35
28-Nov-20 21:24 29-Nov-20 13:49
10-Nov-20 7:40 10-Nov-20 15:24
10-Nov-20 16:26 11-Nov-20 9:35
TRF 8 11-Nov-20 12:10 11-Nov-20 12:58
11-Nov-20 15:17 11-Nov-20 17:34
12-Nov-20 0:47 12-Nov-20 7:47
Issue Description Error code

Oil leakage from MV Transformer

MV TRF tripped. This issue related to transformer oil


MV TRF tripped. This issue related to transformer oil

Oil treatment

#7004: Cable
break or short
circuit at
Temperature value of Transformer is under Zero
inverter
temperature
sensor

#7505: Fans of
the MV
Fan Fault of Transformer transformers
are
defective
#6485:
Hermetic
MV TRF tripped daily (about 2 times/day), affect protection (gas
production.  This issue is related with all the transformer fill level) of MV
oil issue. transformer is
no longer
assured

MV TRF tripped. This issue related to transformer oil

MV TRF tripped. This issue related to transformer oil

Oil treatment

Could not switch on TRF after the oil treatment


MV TRF tripped.

MV TRF tripped
MVPS was down bcz low oil level at TX

Oil treatment

There are some cracks on tx6


#6485:
Hermetic
MV TRF tripped daily (about 2 times/day), affect protection (gas
production.  This issue is related with all the transformer fill level) of MV
oil issue. transformer is
no longer
assured

MV TRF tripped. This issue related to transformer oil

Oil treatment

MV Transformer tripped, this issue may be related to turn


off switchgear at 110kv station
MV Transformer was tripped

MV Transformer was tripped

MV Transformer was tripped


Root cause Loss production
Cable
damaged
Q1 and Q2
relay are
failed
Low oil level

Low oil level

Low oil level


Actual performed for Solution recovery

1.Inspection of the transformer done and observed


that oil leakage from the the busduct and
transformer body.
2.Check the torque and did the torque for the all
the nuts and bolts for the busduct and suspected
leakage point.
3.cleaning for the oil done and kept transformer
under observation

30-Sep, SMA has tightened the bolt on the outside of the chamber
Check the torque and did the torque for the all the nuts and bolts for the busduct at suspected
point.
30-Nov, O&M team checked and cleaned inside MV Transformer' chamber
2-Dec, O&M team have tightened the bolts inside the chmaber of MV transformer with torque
according to the SMA instructions
7-Dec, after visual inspection, did not detect oil leak again

_29-Aug, IFC cleaned inside MV Transformer' chamber and the foor


_IFC tightened the bolts inside the chamber of MV transformer with torque 35 Nm according to
instructions
_IFC sealed the edge of busway from MV TRF side with silicon gel

Release gases by loosen and tighten nuts at DMCR protection Relay

Tripped because of oil level


Released gases from DMCR by vacuum pump.

IFC technician filled more oil


Released gases from DMCR by vacuum pump
Tripped because of oil level
Released gases from DMCR by vacuum pump.

1-Feb-20, Vishal SMA checked directly at site and found the faulty cable and fixed.

5-Feb-20, Vishal checked directly at site


Switch key to Stop and Errlcr INV 2.2 but the warning still happened.
9-Feb-20, Vishal checked directly at site
Switch key to Stop and Errlcr INV 2.2
10-Feb-20, Vishal and 2 technicians cleaned the fan and swapped fan number 7 to numb

IFC technician joined 2 pink and red wires (W811.1) of F44 and F45 together and reconne
purify oil

_28-Feb-20, Nikhil and 2 IFC technicians came to site to release gases and disconnected bro
temporarily at DMCR protection relay

IFC technicians came to site to release gases from DMCR

Nikhil gave remote instructions to fix MVPS 6 but could not


Brief: _SLC & Lam Released gases from DMCR, then turned off all CBs at sub-distribution cab
switched on TRF, then turned on one by one CB but TRF tripped after turned on MCB
_Tried interchanging IKI 30 relay (at MV switchgear) between MVPS 6 and MVPS 7 and did t
above steps but TRF is still tripped-- IKI 30 relays from MVPS 7 was currently used in MVPS
been swapped.

Nikhil gave remote instructions to fix MVPS 6 but could not


Brief: _IFC Released gases from DMCR, then turned off all CBs at sub-distribution cabinet
switched on TRF, then turned on one by one CB but TRF tripped after turned on MCB
_Tried interchanging 2 relays (at sub-station cabinet) between MVPS 6 and MVPS 7 and did t
above steps but TRF is still tripped-- 2 relays from MVPS 7 was currently used in MVPS 6. It h
swapped.

Perform the oil treatment and replace DMCR

Disconnected 2 cables No.11 and No.12 at IKI30 Relay


Disconnected 2 cables (T14) at 2 Relays (STSD cabinet)
Turned off MVPS as per SMA's request

Disconnected 1 cable No 1.16 at Relay Q2 (STSD cabinet)


Tried replace 4 new signal cables from DMCR to STSD cabinet
Reconnected 2 cables No.11 and No.12 at IKI30 Relay and 2 cables T14 at 2 Relays (STSD

Reconnected 1 cable No 1.16 at Relay Q2 (STSD cabinet)


Connected SC30RIO from INV-slave 7 to INV-slave 6.
Connected SC30RIO from INV-slave 6 to INV-slave 4.
Connected SC30RIO from INV-slave 4 to INV-slave 7.

Disconnected one cable No. 1.16 at Q2 relay (STSD cabinet) and measured the voltages (cor
for all connected cable at Q1, Q2 relay.

Swapped the 2 terminal blocks and 2 Relays (STSD cabinet) between MVPS 6 and MVPS 7. T
MVPS 7 were currently used at MVPS 6.
MVPS 6 has operated normally.

Disconnected 1 cable No. 1.16 at Relay Q1 (STSD cabinet)

Tripped because of oil level


Released gases from DMCR by vacuum pump.
_On 19-Sep, IFC technician filled more oil.
_23-Sep: Do vacuum
Turned off MVSG first and then released gases from DMCR by vacuum pump.
_ 12-Oct: SMA performed the oil treatment at Tx6

_13-Oct: After energize Tx6, there're some cracks on Tx6, oil spilled and Tx was tripped. SMA
cracks with soap, took the oil out of tx then welded the cracks.
_14-Oct: SMA filled oil to Tx6, performed the oil purification and did the test for Tx6.
_ 21-Oct: QT(SMA) performed Tx6 test.
_23-Oct: SMA exported IKI 30 Relay data from MVPS 6.

Replaced T-Plug
Replaced the new TX

Energized TX with no load about 4 hours

purify oil

_27-Jan-20, Vishal and 2 IFC technicians came to site to swap the wiring connection at DMCR
relay
_4-Feb-20, Vishal and 1 IFC technician came to site to release gases by vacuum pump at D
protection relay MVPS 7 but can not
_5-Feb-20, Vishal and 1 IFC technician came to site to release gases by vacuum pump at D
protection relay MVPS 7 but can not
Brief: Vishal site service: swapped cable in order to avoid tripping alarm even oil level is low b
operating and tried to release gases but failed

Perform the oil treatment and replace DMCR

Using a suitable Multimeter to confirm continuity resistance of cable from D.M.C.R to X790 (t
block).
Restart the Trafomonitor IKI-30 at MVSG Cabinet.
Swapped the 2 terminal blocks and 2 Relays (STSD cabinet) between MVPS 6 and MVPS 7. T
MVPS 6 were currently used at MVPS 7.
SMA tried switching on MVSG 7 but could not.
Disconnected 1 cable No 1.16 at Relay Q2 (STSD cabinet)

_Released gases from DMCR by vacuum pump everyday.


_Performed the oil treatment on Aug 27, 2020

Replaced T-Plug

_Released gases and do vacumm from DMCR by vacuum pump.


_ 29-Nov: Oiltreatment

_Released gases from DMCR by vacuum pump


_ 17-Nov: Oil treatment
Follow up Status

Close

Close
Still had oil leakage.
Open
Waiting SMA to perform the repair work

Close

Close
After disconnecting the wire, MVPS is operating
Waiting SMA to check DGA test result

Close
SMA escalated this issue to Germany

Close

MVPS 6 operated with setpoint 1 MW for each INV

MVPS 6 operated with setpoint 2 MW for each INV


MVPS 6 operated with setpoint 3 MW for each INV
MVPS 6 operate with 3 MW for each INV

Close

SMA will replace new cable from DMCR to STSD cabinet

Instruction of SMA through remote communication

Instruction of SMA through remote communication. Open

Close
Open

Close
Close

Close

Close
After swap the wire, MVPS is operating
Waiting SMA to check DGA test result

MVPS 7 operated with setpoint 1 MW for each INV


MVPS 7 operated with setpoint 3 MW for each INV

Instruction of SMA through remote communication Close


Open

Close

Close

Close

Close
Image
Doc Reference
20200201-Daily Pre-Start
_20200201-Temperature sensor
TRF

_20200330 - TX2 - Fan Fault


_20200402 - TX6 - Released
gases DMCR

_20200418-Daily Pre-Start
_20200418 - TX6 - Oil treatment
& replace DMCR &
troubleshooting issue MV SG

_20200426 - MVSG 6 -
Troubleshoot issue MVSG
_20200426 - MVSG 6 -
Troubleshoot issue MVSG

_20200508 - MVPS 6 -
Troubleshoot issue MVSG
_20200419-Daily Pre-Start
_20200419 - TX7 - Oil treatment
& replace DMCR

_20200506 - MVPS 7 - Tripped


due to wrong procedure about
switching off
_20200508 - MVPS 6 -
Troubleshoot issue MVSG

_20200826-Daily Pre-Start
_20200827 - TX7 - Oil treatment
Component Location S/N Old S/N New

Monitor SCB 3.2-J10


SCB 2.1-J05 18130130946
SCB 2.2-J12 18130130852
SCB 5.1-J3 18130130906
SCB 4.1-J9 18130130835 18130130851
SCB 3.2-J6 18130130802
SCB 6.2-J12 018130130931 019060141647
SCB 2.1-J08 018130130919 019060142987
SCB1.1-J07 018130130811 019070143241
SCB5.1-J08 018130130970 019070142798
SCB 1.1-J12 18130130935 19220140454
SCB 2.2-J08 18130130954 19170141701
SCB 4.2-J06 18130130839 19220140449
SCB 6.1-J12 18130130889 19170141700
SCB 7.1-J01 18130130808 19310140670
SCB 6.2-J01 18130130899 19310140675
SCB 4.2-J12 18130130928 19310140665
SCB 2.1-J05 18130130865 19310140677
SCB 2.1-J03 18130130962 19310140674
SCB 1.1-J04 18130130951 19310140676
SCB 6.2-J09 18130130804 19310140681
SCB 6.2-J10 18130130877 19310140673
SCB 3.1-J09 18130130849 19310140679
SCB 5.2-J06 18130130828 19310140718
Monitor
SCB 4.2-J06 19310140680 19220140449
SCB 7.1-J07 18130130830 20110141144
SCB 7.1-J08 18130130829 20110141693
SCB 7.2-J02 18130130977 19330140363
SCB 7.2-J08 18130130984 20110141701
SCB 1.1-J10
SCB 2.2-J09
SCB 3.2-J02
SCB 5.1-J14
SCB 7.2-J07
SCB 6.2-J02
SCB 3.1-J06
SCB 4.1-J03
SCB 5.2-J10
SCB 3.1-J10
SCB 3.1-J11
SCB 6.2-J13
SCB 6.1-J09
SCB 6.1-J13
SCB 7.2-J11
SCB 2.2-J05 18130130855 20110141698
SCB 4.2-J05 18130130834 20110141684
SCB 1.1-J13 18130130871 20110141688

SCB 7.2-J05

SCB 4.2-J03
SCB 4.2-J04
SCB 4.2-J05
SCB 4.2-J06
SCB 4.2-J07
SCB 4.2-J08
SCB 4.2-J09
SCADA switch SCB 4.2-J10
PSX 643S
SCB 4.2-J11
SCB 4.2-J12
SCB 4.2-J13
SCB 4.2-J14
SCB 5.1-J12
SCB 5.1-J13
SCB 5.1-J14
SCB 5.2-J01
SCB 2.1-J06
SPD SCB 3.1-J08 RD1909273500 RD1812077154
SCB 5.2-J07 RD1812077042 RD1909273502
SCB 4.1-J6 18160125247
SCB 5.2-J10 18160127612
Current SCB 3.2-J07 18160127932 18160125208
transformer SCB A7.1-J10-M24 018160127910 018040321460
A2.2-J01-M24 18160127652 18160125373
A2.2-J05-M12 18160125453 18160125374
Start Date End Date Issue Description

lost data on SCADA/ lower value..


13-May-19 15-May-19
13-May-19 15-May-19
25-Jul-19 25-Jul-19
31-Aug-19 31-Aug-19
4-Sep-19 5-Sep-19
28-Oct-19 28-Oct-19
Lost the communication status
14-Nov-19 14-Nov-19
15-Nov-19 15-Nov-19
4-Dec-19 4-Dec-19
24-Feb-20 24-Feb-20
24-Feb-20 24-Feb-20
27-Mar-20 27-Mar-20
25-Apr-20 25-Apr-20
28-Apr-20 28-Apr-20
28-Apr-20 28-Apr-20
28-Apr-20 28-Apr-20
28-Apr-20 28-Apr-20 Lost the communication status
28-Apr-20 28-Apr-20 early in the morning and in the
28-Apr-20 28-Apr-20 afternoon.
13-May-20 13-May-20
13-May-20 13-May-20
13-May-20 13-May-20
13-May-20 13-May-20
14-Aug-20 15-Aug-20 Lost the communication status
31-Aug-20 31-Aug-20
31-Aug-20 31-Aug-20
31-Aug-20 31-Aug-20
31-Aug-20 31-Aug-20

Lost the communication status


early in the morning and in the
afternoon.
Lost the communication status
early in the morning and in the
afternoon.

5-Sep-20
14-Aug-20 5-Sep-20
5-Sep-20
The SCADA value didn’t match
29-Oct-20
with site

19-May-20 14-Aug-20 Lost the communication status

20-May-19 21-May-19
26-Aug-20 26-Aug-20 SPD has damaged
9-Oct-20 10-Oct-20
11-Jul-19 11-Jul-19
13-Sep-19 5-Oct-19
24-Oct-19 24-Oct-19
Wrong current
12-Dec-19 12-Dec-19
19-Nov-20 19-Nov-20
19-Nov-20 19-Nov-20
Root cause Actual performed for Solution recovery

lose cable/damaged cable tighten cable/replaced new monitor

Replaced the monitor


Inserted inserted 120 Ohm to serial port at
INV

Port 1,2,5,7 (MVPS 4)


have been damaged

Port 8 (MVPS 5) have


been damaged

Replaced new SPD


Replaced new SPD
Replaced new SPD
Replaced Current transformer
Replaced Current transformer
Replaced Current transformer
Replaced Current transformer
Replaced Current transformer
Replaced Current transformer
Follow up Status Image Service report

order spare parts Open/Close


Close
Close
Close
Close
Close
Close
Close
Close
Close
Close
Close
Close
Close
Close
Close
Close
Close
Close
Close
Close
Close
Close
Close
Close
Close
Close
Close
Close
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Close
Close
Close

Keep observing Open

Close

Close

Close
Close
Close
Close
Close
Close
Close
Close
Close
Note:Update in 2020
Damaged Component Location Error Start Replaced Date
SCB 2.1-J05 13-May-19 15-May-19
SCB 2.2-J12 13-May-19 15-May-19
SCB 5.1-J3 25-Jul-19 25-Jul-19
SCB 4.1-J9 31-Aug-19 31-Aug-19
SCB 3.2-J6 4-Sep-19 5-Sep-19
SCB 6.2-J12 28-Oct-19 28-Oct-19
SCB 2.1-J08 14-Nov-19 14-Nov-19
SCB1.1-J07 15-Nov-19 15-Nov-19
SCB5.1-J08 4-Dec-19 4-Dec-19
SCB 2.2-J08 24-Feb-20
SCB 4.2-J06 27-Mar-20
SCB 6.1-J12 25-Apr-20
SCB 7.1-J01 28-Apr-20
SCB 6.2-J01 28-Apr-20
SCB 4.2-J12 28-Apr-20
Monitor
SCB 2.1-J05 28-Apr-20
SCB 2.1-J03 28-Apr-20
SCB 1.1-J04 28-Apr-20
SCB 6.2-J09 13-May-20
SCB 6.2-J10 13-May-20
SCB 3.1-J09 13-May-20
SCB 5.2-J06 13-May-20
SCB 4.2-J06 14-Aug-20 15-Aug-20
SCB 7.1-J07 31-Aug-20
SCB 7.1-J08 31-Aug-20
SCB 7.2-J02 31-Aug-20
SCB 7.2-J08 31-Aug-20
SCB 2.2-J05 5-Sep-20
SCB 4.2-J05 5-Sep-20
SCB 1.1-J13 5-Sep-20
SCB 2.1-J06 20-May-19 21-May-19
SPD SCB 3.1-J08 26-Aug-20 26-Aug-20
SCB 5.2-J07 9-Oct-20 10-Oct-20
SCB 4.1-J6 11-Jul-19 11-Jul-19
SCB 5.2-J10 13-Sep-19 5-Oct-19
Current Transformer
Current Transformer SCB 3.2-J07 24-Oct-19 24-Oct-19
SCB 7.1-J10-
12-Dec-19 12-Dec-19
M24
Component Location S/N Old

MC4/Panel/clamp A3.2-J10-M2
Panel A7.1-J07-M24 G01181100106331
Panel A7.1-J05-M1 D02181133500443
Earthing cable A7.1-J1-M1,2
Panel A6.2-J11-M8
Panel A6.2-J14-M22
Earthing cable A6.2-J03-M11,12

Panel A6.1-J13-M3,4
Panel A6.1-J12-M10
Panel A7.1-J13-M21-30 G01181000208052
Panel A7.1-J13-M22-30 G01181000208445
Panel A5.1-J04-M17 G01181002702126
G01181000303338
Panel A5.1-J09-M8
G01181000303601
Panel A5.1-J09-M24 G01181000206998
Panel A5.1-J03-M6 G01181002600303
Panel A5.1-J03-M18 A07181100501503
Panel A5.2-J08-M18 G01181000200436
Panel A5.2-J08-M24 G01181000200416
Panel A5.2-J04-M8 G01181002503532
Panel A4.2-J02-M16 D02181131905760
Panel A4.2-J02-M17 G01181100206888
Panel A4.2-J02-M18 G01181100205202
G01181101905046
Panel A4.2-J02-M19
G01181101904646
Panel A4.2-J02-M24 G01181100305550
Panel A4.2-J08-M10 A07181100604084
Panel A4.2-J09-M10 D02181133702509
Panel A4.2-J09-M12 D02181133504042
Panel A4.1-J09-M23 G01181101903769
A2.2-J09-M1
A2.2-J09-M17
Clamp
A2.2-J09-M21
A2.2-J10-M1
Panel A2.2-J03-M4 G01181101906473

A2.1-J08-M8

MC4 A5.1-J04-M12

A4.1-J14-M23
A2.1-J05-M12
A4.1-J03-M21
A7.2-J05-M22
A7.2-J05-M22
Fuse
A5.2-J05-M2
A1.1-J02-M3 G0118101705006
A1.1-J02-M22 G0118101703993
A1.1-J02-M23 G0118101905139
A1.1-J06-M10 G01181000208738
A1.1-J06-M10 D02181131803341
A1.1-J05-M18 D02181131802257
A7.2-J01R-M1 S87190400202922
A1.1-J08-M21 A0718100503912
A1.1-J11-M1 D02181133607633
A2.2-J10-M15 D021811318018949
A2.1-J11-M17 A07181100600875
Panel
D02181133600571
A2.2-J02-M24
D02181133600272
A2.2-J02-M20 A07181100605000
A3.1-J09-M16 D02181131701773
A3.1-J03-M16 A7181100104255
A3.1-J03-M3 G01181000201283
A3.2-J13-M5 D02181131900967
A3.2-J13-M17 A07181100601409
A3.2-J07-M5 G01181100203185
A4.1-J06-M12 D02181131906076
A4.1-J01-M12 G01181100205810
S/N New Start Date End Date Issue Description

Broken glass/damaged MC4/ loose


clamp
5-May-20 Interface of panel damaged
6-May-20 Interface of panel damaged
Earthing cable terminal is not
6-May-20 6-May-20
tightened
12-May-20 Interface of panel damaged
12-May-20 Interface of panel damaged
Earthing cable terminal is not
14-May-20 15-May-20
tightened
A panel has covered a few cells of
15-May-20 15-May-20
nearby panel
15-May-20 Interface of panel damaged
D02181133703932 29-May-20 Damaged cell
D02181133703847 29-May-20 Damaged cell
1-Jun-20 Interface of panel damaged

1-Jun-20 Interface of panel damaged

1-Jun-20 Interface of panel damaged


2-Jun-20 Interface of panel damaged
2-Jun-20 Interface of panel damaged
3-Jun-20 Interface of panel damaged
3-Jun-20 Interface of panel damaged
3-Jun-20 23-Jul-20 Interface of panel damaged
4-Jun-20 Interface of panel damaged
4-Jun-20 Interface of panel damaged
4-Jun-20 Interface of panel damaged
4-Jun-20 Interface of panel damaged
4-Jun-20 Interface of panel damaged
5-Jun-20 Interface of panel damaged
5-Jun-20 Interface of panel damaged
5-Jun-20 Interface of panel damaged
17-Jun-20 Interface of panel damaged

1-Jul-20 2-Jul-20 Loose clamp


9-Jul-20 Interface of panel damaged

10-Jul-20 10-Jul-20

Damaged MC4

6-Aug-20 6-Aug-20
3-Sep-20 4-Sep-20
5-Nov-20 5-Nov-20
11-Nov-20 11-Nov-20
11-Nov-20 11-Nov-20
17-Nov-20 17-Nov-20
Interface of panel damaged
Interface of panel damaged
Interface of panel damaged
29-Oct-20
Interface of panel damaged
Interface of panel damaged
Interface of panel damaged
Interface of panel damaged
Interface of panel damaged
30-Oct-20
Interface of panel damaged
Interface of panel damaged
31-Nov-20 Interface of panel damaged
Interface of panel damaged
Interface of panel damaged
Interface of panel damaged
1-Nov-20
Interface of panel damaged
Interface of panel damaged
Interface of panel damaged
Interface of panel damaged
Interface of panel damaged
2-Nov-20 Interface of panel damaged
Interface of panel damaged
Interface of panel damaged
Root cause

Contructions

Contructions

Contructions
Actual performed for Solution recovery Follow up

Replaced panel/ changed new MC4/ Tightened bolts order spare parts

Tightened bolts

Tightened bolts

Moved the panel to a suitable position.

Replaced panel
Replaced panel

Replaced panel

Tightened bolts
Replaced MC4

Replaced 1 fuse
Replaced 1 fuse
Status Image Service report

Open/Close
Open
Open
Close
Open
Open
Close

Close
Open
Close
Close
Open

Open

Open
Open
Open
Open
Open
Close
Open
Open
Open
Open
Open
Open
Open
Open
Open

Close
Open

Close

Close
Close
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open

You might also like