2.0 Observations
Figure 4: Front Wall – Very little old scale and very little uniform corrosion
observed. Water level observed to be fluctuated most of the time.
Figure 5: Rear fire wall – Very little old scale and some uniform corrosion observed.
b) TDS: TDS(Total Dissolved Solids) level were below high control limit most of
the time.
c) H. Alkalinity: Hydrate Alkalinity level was within control limit on par with pH.
d) T.Hardness: Total hardness was above high control limit due to hardness breakthrough
but start reduce at the end of time.
e) Chloride: Chloride level was below high control limit most of the time.
f) Total Iron: Total iron was below high control limit all the time.
g) DEHA: DEHA reserves were fluctuated and above low control limit all the time.
h) Phosphate: Ortho-Phosphate reserves were fluctuated and within control limit most of
the time.
4.0 Chemicals
CHEMICAL DESCRIPTION
Hydrate Alkalinity
150 – 400 Add BL 210 to increase.
(ppm CaCO3)
6.0 Conclusion:
1. Some old scale still can observed especially at the bottom part of the fire tubes
and drum.
3. Water level in the boiler has always been fluctuated through the time.
7.0 Recommendation: