1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C Work done by tightened. Need to check
during TC washing time.
2 Lighting EM 12.11.2018 Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).
3 03 IE EM 01.11.2018 Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.
9 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
10 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
11 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
12 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
13 HFO Storage tank EM 12.03.15 HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
14 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
15 08IE & 09IE MM 29.10.2018 Fuel booster unit after quick closing v/v pressure gauge faulty . B
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Md. Shofiqul Islam.
02.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks
1 Ins. Air Comp #02 MM 02.12.2018 Belt damage , need to change. A Belt & air end replaced .
2 Ins. Air Comp. Dryer # 01 EM 28.11.2018 Refrigeration Cycle continuously running at a temp. below the dew point temperature. D spare not available
3 Feeder unit MM 30.10.2018 Feeder unit flushing occur in every 21 minute intervals, when despatched 100 MW. A Candle changed on 12.11.2018,U/O .
4 03IE MM 02.12.2018 Lube oil Sep# 03: Water leakage from fresh water inlet line. C Elbow Tighened by RTV u/o
5 06IE MM 30.11.2018 Air Leakage from HT pneumatic controller. C spare not available
Pending
Work done by tightened. Need to check
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C during TC washing time.
2 Lighting EM 12.11.2018 Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).
3 03 IE EM 01.11.2018 Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.
9 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
10 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
11 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
12 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
13 HFO Storage tank EM HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
14 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
15 08IE & 09IE MM 29.10.2018 Fuel booster unit after quick closing v/v pressure gauge faulty . B
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Razu Ahmmed
03.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks
1 Ins. Air Comp. Dryer # 01 EM 28.11.2018 Refrigeration Cycle continuously running at a temp. below the dew point temperature. D spare not available
2 Feeder unit MM 30.10.2018 Feeder unit flushing occur in every 21 minute intervals, when despatched 100 MW. A Candle changed on 12.11.2018,U/O .
3 02IE MM 03.12.2018 Air Leakage from HT pneumatic controller. B spare not available
4 03IE MM 03.12.2018 Dirty leak pump not properly pumping . B cleaning done
5 06IE MM 30.11.2018 Air Leakage from HT pneumatic controller. C spare not available
6 07IE MM 03.12.2018 Air Leakage from mixing tank return line pneumatic controller. B
7 08IE MM 03.12.2018 Air Leakage from booster unit heater controller. B capillary tube change.
8 MM 03.12.2018 Air Leakage from mixing tank return line pneumatic controller. B pneumatic line nipple change
10IE
9 MM 03.12.2018 Exhaustleakage from cyl.B7 indicator cork . B Indicator cock lapping
10 11IE MM 03.12.2018 LO Sep # 11- LO inlet temperature not increase. B steam trap open & clean.
11 12 IE MM 03.12.2018 Lube oil leakage from Cyl. B04 crankcase door. D two bolt change
Pending
Work done by tightened. Need to check
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C during TC washing time.
Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01
2 Lighting EM 12.11.2018 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).
3 03 IE EM 01.11.2018 Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.
9 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
10 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
11 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
12 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
13 HFO Storage tank EM 02.07.15 HFO Storage tank #01&02 :- Level senor faulty. C&D
1 Ins. Air Comp. Dryer # 01 EM 28.11.2018 Refrigeration Cycle continuously running at a temp. below the dew point temperature. D spare not available
2 Feeder unit MM 30.10.2018 Feeder unit flushing occur in every 21 minute intervals, when despatched 100 MW. A Candle changed on 12.11.2018,U/O .
3 HFO Sludge pump MM 04.12.2018 HFO Sludge pump ( yellow colour ) is not working A
4 Hydrover no # 02 MM 04.12.2018 Water leakage through delivery valve. A
5 EGB # 01 MM 04.12.2018 Boiler inlet & out let line exh. flange insulation cover O clamp broken. A Tightened by O clamp
6 02IE MM 03.12.2018 Air Leakage from HT pneumatic controller. B spare not available
7 06IE MM 30.11.2018 Air Leakage from HT pneumatic controller. C spare not available
8 09IE EM 04.12.2018 Q7 breaker ( hall # 02 DB pannel ) trip when DG # 09 walk way lighting switch on A Problem was in two light . Now Ok.
Pending
Work done by tightened. Need to check
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C during TC washing time.
Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01
2 Lighting EM 12.11.2018 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).
3 03 IE EM 01.11.2018 Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.
9 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
10 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
11 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
12 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
13 HFO Storage tank EM HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
14 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
15 08IE & 09IE MM 29.10.2018 Fuel booster unit after quick closing v/v pressure gauge faulty . B
33598
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Md. Shofiqul Islam.
05.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks
1 Ins. Air Comp. Dryer # 01 EM 28.11.2018 Refrigeration Cycle continuously running at a temp. below the dew point temperature. D spare not available
2 Feeder unit MM 30.10.2018 Feeder unit flushing occur in every 21 minute intervals, when despatched 100 MW. A Candle changed on 12.11.2018,U/O .
3 HFO Sludge pump MM 04.12.2018 HFO Sludge diaphragm pump- big one ( yellow colour ) is not working A On Going.
4 11 IE EM/MM 05.12.2018 LO Sep # 11- Abnormal sound comes from feed pump. D Check & found ok .
Pending
Work done by tightened. Need to check
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C
during TC washing time.
2 Lighting EM 12.11.2018 Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).
3 03 IE EM 01.11.2018 Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.
10 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
11 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
12 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
13 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
14 HFO Storage tank EM 12.03.15 HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
15 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
16 08IE & 09IE MM 29.10.2018 Fuel booster unit after quick closing v/v pressure gauge faulty . B
33598
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Razu Ahmmed
06.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks
1 Ins. Air Comp. Dryer # 01 EM 28.11.2018 Refrigeration Cycle continuously running at a temp. below the dew point temperature. D spare not available
2 01IE EM 06.12.2018 ESM lube oil pressure shut down status IS 2011 B check found ok
3 Feeder unit MM 30.10.2018 Feeder unit flushing occur in every 21 minute intervals, when despatched 100 MW. A Candle changed on 12.11.2018,U/O .
4 HFO Sludge pump MM 04.12.2018 HFO Sludge diaphragm pump- big one ( yellow colour ) is not working A On Going.
Pending
Work done by tightened. Need to check
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C
during TC washing time.
2 Lighting EM 12.11.2018 Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).
3 03 IE EM 01.11.2018 Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.
10 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
11 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
12 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
13 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
14 HFO Storage tank EM 12.03.15 HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
15 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
16 08IE & 09IE MM 29.10.2018 Fuel booster unit after quick closing v/v pressure gauge faulty . B
33598
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Md. Mofizur Rahman.
07.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks
1 Ins. Air Comp. Dryer # 01 EM 28.11.2018 Refrigeration Cycle continuously running at a temp. below the dew point temperature. D spare not available
2 Feeder unit MM 30.10.2018 Feeder unit flushing occur in every 21 minute intervals, when despatched 100 MW. A Candle changed on 12.11.2018,U/O .
3 05IE MM 08.12.2018 Air leakage from Preheating unit air press. Regulating valve. C Regulator replaced.
4 10IE MM 08.12.2018 L/O Sep# 10: Sludge tank vent filter lube oil leaky. C Tightened.
Pending
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C Work done by tightened. Need to check
during TC washing time.
2 Lighting EM 12.11.2018 Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).
3 03 IE EM Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.
10 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
11 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
12 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
13 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
14 HFO Storage tank EM HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
15 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
16 08IE & 09IE MM 29.10.2018 Fuel booster unit after quick closing v/v pressure gauge faulty . B
33598
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Md. Mofizur Rahman.
08.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks
1 04IE MM 08.12.2018 Air Leakage from Booster unit temp. control air regulator . A Replaced servicing one.
2 06IE MM 08.12.2018 Air Leakage through visco meter pneumatic controller. A Nipple & tube change.
3 Ins. Air Comp. Dryer # 01 EM 28.11.2018 Refrigeration Cycle continuously running at a temp. below the dew point temperature. D Sensor change. Now Ok.
4 08 IE EM 08.12.2018 Earthing cable of engine body disconnected near A01 crankcase door. D Cable connect.
Pending
Work done by tightened. Need to check
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C during TC washing time.
2 Lighting EM 12.11.2018 Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).
3 03 IE EM Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.
10 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
11 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
12 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
13 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
14 HFO Storage tank EM 12.03.15 HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
15 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
16 08IE & 09IE MM 29.10.2018 Fuel booster unit after quick closing v/v pressure gauge faulty . B Gauge change new one.
33598
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Razu Ahmmed
09.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C Work done by tightened. Need to check
during TC washing time.
2 Lighting EM 12.11.2018 Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).
3 03 IE EM Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.
8 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
9 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
10 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
11 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12 HFO Storage tank EM 12.03.15 HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
13 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
33598
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Md. Mofizur Rahman.
10.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks
1 Feeder unit EM 10.12.2018 Air leakage from Feeder unit quick closing solenoid valve. C Interchanged with LFO Quick closing v/v
2 Aux. boiler MM 10.12.2018 Feed water tank man hole cover gasket damage. A Gasket changed.
3 02IE MM 10.12.2019 Cyl.B7, B8 unit hot box cover hinge damaged. A Bolt changed.
4 03IE EM/MM 10.12.2018 LO Sep # 03 : LO comes through V6 valve. A EM checked found OK.
5 MM 10.12.2018 Condensate leakage through Fuel booster unit steam trap. A Gasket changed.
09IE
6 EM 10.12.2018 Pre lube pump motor abnormal sound. A Bearing changed.
Pending
Work done by tightened. Need to check
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C
during TC washing time.
Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01
2 Lighting EM 12.11.2018 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).
3 03 IE EM Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.
8 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
9 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
10 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
11 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12 HFO Storage tank EM 12.03.15 HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
13 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
33598
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
S M Mamunur Rahman
11.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks
1 Fire Hydrant Point # 025 MM 11.12.2018 Fire Hydrant Point # 025( In front of storage tank)- Valve does not provide seal properly. D Rubber seal changed,but not solved.
2 Aux. boiler MM 10.12.2018 Feed water tank man hole cover gasket damage. A Gasket changed .
3 Hydrovar Pump # 01 MM 11.12.2018 Non return valve does not provide seal properly. D v/v changed with new one.
4 MM 11.12.2018 Exhaust leakage from common short bellows. D A1, B6 cyl. Short bellows changed.
01 IE
5 EM 11.12.2018 LT -water temp . CAC inlet (TE 471) sensor fault. D Cable burn. New cable change.
6 03 IE MM 11.12.2018 LO Sep # 03- Heater can not increase the lube oil temperature more than 77 oC. D steam trap clean. Now ok.
8 10 IE EM 11.12.2018 Radiator frequency converter tripped due to temp high alarm at running condition . B Cooling fan ( card) change.
9 11 IE MM/EM 11.12.2018 LO Sep # 11-Clean oil discharge pressure settings . Alarm no- 45. D Discharge valve adjust.
Pending
Work done by tightened. Need to check
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C
during TC washing time.
2 Lighting EM 12.11.2018 Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).
3 03 IE EM Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.
9 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
10 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
11 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
12 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
13 HFO Storage tank EM HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
14 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
33598
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Razu Ahmmed
12.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks
1 Fire Hydrant Point # 025 MM 11.12.2018 Fire Hydrant Point # 025( In front of storage tank)- Valve does not provide seal properly. D Valve seat polishing &clieaning , solved.
2 MM 12.12.2018 Abnormal vibration at lube oil centrifuse filter. D Centrifuse filter cleaned. U/O
01 IE
3 EM 12.12.2018 TC B-bank RPM not showing. Wire torn. C Sensor & cable changed, now ok.
4 03 IE EM/MM 12.12.2018 LO Sep # 03- Separator motor taking more Ampere about 11.2 A. D
5 04 IE MM 12.12.2018 Cyl B6: Crankcase door relief v/v LO leakage. C O - ring changed ,ok .
6 MM 12.12.2018 Cyl. A02 & Cyl. B10- Multiduct water leakage. D Tightened. Ok .
08 IE
7 MM 12.12.2018 TC B-bank after TC exhaust line insulation damage. C
8 11 IE EM 12.12.2018 Main Bearing # 09 temp decreasing gradually (88 degree to 77 degree) C Control cable old changed ,now ok .
9 12 IE MM 12.12.2018 Cyl. A01- Fuel leakage from clean leak short piece of Cyl. Head. D O' ring of short piece changed, ok .
Pending
Work done by tightened. Need to check during TC
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C
washing time.
2 Lighting EM 12.11.2018 Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).
3 03 IE EM Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.
9 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
10 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
11 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
12 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
13 HFO Storage tank EM HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
14 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
http://61.247.183.69:8021/
33598
25
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Md. Mofizur Rahman
13.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks
1 EM/MM 13.12.2018 LO Sep # 03 : Lube oil comes through V6 valve. C Top part & hood sensor port cleaned. U/O
2 03 IE MM 13.12.2018 Dirty leak diaphragm pump is not working . B Tank cleaned & pump servicing done. Now ok.
3 EM/MM 12.12.2018 LO Sep # 03- Separator motor taking more Ampere about 11.2 A. D
4 EM 13.12.2018 Radiator frequency convertar alarm: 32 fan cooling F T1- T16. C Cooling fan 02 pcs bearing changed. Now ok.
5 MM 13.12.2018 Exhaust leakage from common short bellows. B B09 gasket and A09 bellows changed.
08IE
6 EM 13.12.2018 Turning motor abnormal sound . B
7 MM 12.12.2018 TC B-bank after TC exhaust line insulation damage. C
8 12IE MM 13.12.2018 Exhaust leakage from common short bellows. B
Pending
Work done by tightened. Need to check during TC
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C
washing time.
2 Lighting EM 12.11.2018 Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).
3 03 IE EM Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.
9 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
10 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
11 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
12 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
13 HFO Storage tank EM 02.07.15 HFO Storage tank #01&02 :- Level senor faulty. C&D
1 EM/MM 13.12.2018 LO Sep # 03 : Lube oil comes through V6 valve. C Top part & hood sensor port cleaned. U/O
03 IE
2 EM/MM 12.12.2018 LO Sep # 03- Separator motor taking more Ampere about 11.2 A. D Separator motor open. U/M
3 06IE EM 14.12.2018 CFE panel cooling fan always running. B Thermostat change new one.
4 EM/MM 13.12.2018 Turning motor abnormal sound . B 02 pcs bearing of TG motor changed by EM. Now
electrically ok.
08 IE
5 MM 12.12.2018 TC B-bank after TC exhaust line insulation damage. C Done.
6 09IE EM 14.12.2018 BJA panel cooling fan not running. B Spare not available.
7 12IE EM 14.12.2018 CFE panel cooling fan not running. B Spare not available.
Pending
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C Work done by tightened. Need to check during TC
washing time.
2 Lighting EM 12.11.2018 Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).
3 03 IE EM Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.
9 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
10 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
11 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
12 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
13 HFO Storage tank EM 12.03.15 HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
14 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
33598
25
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Md. Shofiqul Islam.
15.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks
1 EM/MM 13.12.2018 LO Sep # 03 : Lube oil comes through V6 valve. C Top part & hood sensor port cleaned. U/O
03 IE
2 EM/MM 12.12.2018 LO Sep # 03- Separator motor taking more Ampere about 11.2 A. D Separator motor open. U/M
3 04IE EM/MM 15.12.2018 Engine Load setting: 8700 KW ,Engine Load fluctuate ( 9052 to 8424 ) KW. C New connector install ,U/O .
4 10IE MM 15.12.2018 Water leakage through LT Controller shaft seal. A Tighteen by treat tape .
5 12IE MM 15.12.2018 Water leakage through LT Controller shaft seal. A Tighteen by treat tape .
Pending
Work done by tightened. Need to check during TC
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C
washing time.
2 Lighting EM 12.11.2018 Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).
3 03 IE EM Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.
11 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
12 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
13 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
14 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
15 HFO Storage tank EM 02.07.15 HFO Storage tank #01&02 :- Level senor faulty. C&D
1 EM/MM 13.12.2018 LO Sep # 03 : Lube oil comes through V6 valve. C Top part & hood sensor port cleaned. U/O
03 IE
2 EM/MM 12.12.2018 LO Sep # 03- Separator motor taking more Ampere about 11.2 A. D Separator motor open. U/M
3 04IE EM/MM 15.12.2018 Engine Load setting: 8700 KW ,Engine Load fluctuate ( 9052 to 8424 ) KW. C New connector install ,U/O .
4 12IE EM 16.12.2018 Pre-lube pump abnormal sound . B check found ok
Pending
Work done by tightened. Need to check during TC
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C washing time.
Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01
2 Lighting EM 12.11.2018 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).
3 03 IE EM Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.
11 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
12 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
13 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
14 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
15 HFO Storage tank EM HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
16 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
33598
25
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
S M Mamunur Rahman.
17.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks
1 02IE MM 17.12.2018 Air leakage through pre- heating unit before air regulator pipe line A Nipple change.
2 EM/MM 13.12.2018 LO Sep # 03 : Lube oil comes through V6 valve. C Top part, hood sensor port cleaned & motor fix up U/O
03 IE
3 EM/MM 12.12.2018 LO Sep # 03- Separator motor taking more Ampere about 11.2 A. D Separator motor open , U/M .
4 04IE EM/MM 15.12.2018 Engine Load setting: 8700 KW ,Engine Load fluctuate ( 9052 to 8424 ) KW. C New connector install ,U/O .
5 HFO Feeder unit MM 17.12.2018 HFO leakage through HFO Feed pump # 1 & 2 Inlet Glove valve A Tightened ,U/O .
Pending
Work done by tightened. Need to check during TC
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C
washing time.
2 Lighting EM 12.11.2018 Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).
3 03 IE EM Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.
11 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
12 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
13 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
14 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
15 HFO Storage tank EM 12.03.15 HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
16 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
33598
25
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Md. Shofiqul Islam.
18.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks
1 11 KV bus EM 18.12.2018 11 kV "B" bus Frequency sensor fault alarm. C Not solved ,U/M .
2 Ins. Air comp # 01 EM 18.12.2018 Drayer cooling fan not running. C Capacitor changed .
3 Roof Top MM 18.12.2018 Water leakage from roof top ventilation fan DG# 02 & DG#04 back side. C Rectifited
4 01 IE EM 18.12.2018 TC-B-bank rpm fluctuates. A
5 EM/MM 13.12.2018 LO Sep # 03 : Lube oil comes through V6 valve. C Top part, hood sensor port cleaned.U/O
03 IE
6 EM/MM 12.12.2018 LO Sep # 03- Separator motor taking more Ampere about 11.2 A. D Separator motor bearing chnaged. U/O
7 04 IE EM/MM 15.12.2018 Engine Load setting: 8700 KW ,Engine Load fluctuate ( 9052 to 8424 ) KW. C New connector install ,U/O .
Pending
Work done by tightened. Need to check during TC
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C
washing time.
Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01
2 Lighting EM 12.11.2018 nos) , 11 IE (02 nos) , 12 IE( 01 nos). D
3 03 IE EM Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.
11 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
12 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
13 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
14 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
15 HFO Storage tank EM 12.03.15 HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
16 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
33598
25
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Razu Ahmmed
19.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks
3 03 IE EM Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.
11 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
12 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
13 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
14 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
15 HFO Storage tank EM HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
16 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
33598
25
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
S M Mamunur Rahman
20.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks
3 03 IE EM Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.
11 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
12 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
13 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
14 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
15 HFO Storage tank EM HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
16 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
33598
25
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Md. Shofiqul Islam.
21.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks
1 11 KV bus EM 18.12.2018 11 kV "B" bus Frequency sensor fault alarm. C Not solved ,U/M .
Aux. Boiler MM 22.22.2018 Aux. boiler steam delivery valve steam leakey . B tightened. Now ok.
2 EM 21.12.2018 LO Sep # 03 : BJN pannel main switch missing A
3 03 IE EM/MM 13.12.2018 LO Sep # 03 : Lube oil comes through V6 valve. C Top part, hood sensor port cleaned.U/O
4 EM/MM 12.12.2018 LO Sep # 03- Separator motor taking more Ampere about 11.2 A. D Separator motor bearing chnaged. U/O
5 04 IE EM/MM 15.12.2018 Engine Load setting: 8700 KW ,Engine Load fluctuate ( 9052 to 8424 ) KW. C New gov. connector & MCM installed. U/O .
6 05 IE EM 21.12.2018 LO Sep # 05 : BJN pannel main switch missing A
7 07 IE EM 21.12.2018 LO Sep # 07 : BJN pannel main switch missing A
Pending
Work done by tightened. Need to check during TC
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C washing time.
2 Lighting EM 12.11.2018 Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).
3 03 IE EM 01.11.2018 Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.
11 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
12 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
13 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
14 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
15 HFO Storage tank EM HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
16 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
33598
25
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Razu Ahmmed
22.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks
1 Engine Hall # 02 MM 22.12.2018 Pocket Door beside DG # 12- Can not be shutoff properly. D Repaired
2 11 KV bus EM 18.12.2018 11 kV "B" bus Frequency sensor fault alarm. C Not solved ,U/M .
3 EM 21.12.2018 LO Sep # 03 : BJN pannel main switch missing A
4 03 IE EM/MM 13.12.2018 LO Sep # 03 : Lube oil comes through V6 valve. C Top part, hood sensor port cleaned.U/O
5 EM/MM 12.12.2018 LO Sep # 03- Separator motor taking more Ampere about 11.2 A. D Separator motor bearing chnaged. U/O
6 04 IE EM/MM 15.12.2018 Engine Load setting: 8700 KW ,Engine Load fluctuate ( 9052 to 8424 ) KW. C New gov. connector & MCM installed. U/O .
7 05 IE EM 21.12.2018 LO Sep # 05 : BJN pannel main switch missing A
8 06IE EM 22.12.2018 Turning gear engaged alarm not showing PLC . B Sensor changed
9 07 IE EM 21.12.2018 LO Sep # 07 : BJN pannel main switch missing A
10 10 IE MM 22.12.2018 One piece bolt broken of B05 unit crankcase door. D
Pending
Work done by tightened. Need to check during TC
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C
washing time.
Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01
2 Lighting EM 12.11.2018 nos) , 11 IE (02 nos) , 12 IE( 01 nos). D
3 03 IE EM 01.11.2018 Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.
11 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
12 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
13 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
14 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
15 HFO Storage tank EM 02.07.15 HFO Storage tank #01&02 :- Level senor faulty. C&D
1 11 KV bus EM 18.12.2018 11 kV "B" bus Frequency sensor fault alarm. C Not solved ,U/M .
2 EM/MM 13.12.2018 LO Sep # 03 : Lube oil comes through V6 valve. C Top part, hood sensor port cleaned .Now ok
03IE
3 EM/MM 12.12.2018 LO Sep # 03- Separator motor taking more Ampere about 11.2 A. D Separator motor bearing changed. Now 10.5 A taking
4 04 IE EM/MM 15.12.2018 Engine Load setting: 8700 KW ,Engine Load fluctuate ( 9052 to 8424 ) KW. C New gov. connector & MCM installed. Now ok.
5 10 IE EM 23.12.2018 Fuel booster unit Mixing tank level low alarm. C Now ok
Pending
Work done by tightened. Need to check during TC
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C washing time.
Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01
2 Lighting EM 12.11.2018 nos) , 11 IE (02 nos) , 12 IE( 01 nos). D
3 03 IE EM 01.11.2018 Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.
13 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
14 04,10 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
15 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
16 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
17 HFO Storage tank EM HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
18 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
33598
25
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Md. Shofiqul Islam.
24.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks
1 11 KV bus EM 18.12.2018 11 kV "B" bus Frequency sensor fault alarm. C Not solved ,U/M .
Pending
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C Work done by tightened. Need to check during TC
washing time.
Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01
2 Lighting EM 12.11.2018 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).
3 03 IE EM 01.11.2018 Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D Re-winding motor install.
14 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
15 04,10 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
16 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
17 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
18 HFO Storage tank EM 12.03.15 HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
19 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Razu Ahmmed
25.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks
1 11 KV bus EM 18.12.2018 11 kV "B" bus Frequency sensor fault alarm. C Not solved ,U/M .
Pump side screw & coupling rubber pad, mechanical
2 02 IE MM 25.12.2018 HFO Leakage from booster pump mechanical seal. C seal replaced.
3 04 IE EM/MM 15.12.2018 Engine Load setting: 8700 KW ,Engine Load fluctuate ( 8873 to 8448 ) KW. C New gov. connector & MCM installed. Not sloved. Load
fluctuation starts after 1.5 hrs of running.
14 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
15 04,10 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
16 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
17 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
18 HFO Storage tank EM HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
19 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Md. Mofizur Rahman.
26.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks
1 Hydrophore unit MM 26.12.2018 Pump #02: Water leakage from delivary pipe line after valve. C Heat tape & clamp added. But not sloved.
Pending
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C Work done by tightened. Need to check during TC
washing time.
2 Lighting EM 12.11.2018 Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 nos) , D
11 IE (02 nos) , 12 IE( 01 nos).
Spare not available
1 11 KV bus EM 18.12.2018 11 kV "B" bus Frequency sensor fault alarm. C
2 LFO Feeder Unit EM 24.12.2018 Air leakage from the solenoid of quick closing valve. D
3 03IE EM 21.12.2018 LO Sep # 03 : BJN pannel main switch missing A
4 05 IE EM 21.12.2018 LO Sep # 05 : BJN pannel main switch missing A
5 07 IE EM 21.12.2018 LO Sep # 07 : BJN pannel main switch missing A
6 09IE EM 14.12.2018 BJA panel cooling fan not running. B
7 12IE EM 14.12.2018 CFE panel cooling fan not running. A
8 HFO Feeder unit EM 22.11.2018 BJL Pannel viscometer B016 selector switch open , need to fix up. A
9 03 IE MM 16.10.2018 Pre - heating pump water leakage . B
10 04 IE EM 18.10.2018 Both bank TC rpm high about 29500. D
11 EM 22.10.2018 TC-B-bank rpm fluctuates. D
10IE
12 EM 04.10.2018 TC A-bank rpm 30000. A
13 04IE,05IE EM 04.04.2018 Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection. D
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working (20.10.2017).
14 All AC related issue EM 09.09.2017 A,B,C,D
15 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
16 04,10 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
17 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
18 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
19 HFO Storage tank EM HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
20 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
S M Mamunur Rahman
27.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks
1 Hydrophore unit MM 26.12.2018 Pump #02: Water leakage from delivary pipe line after valve. C Heat tape & clamp added. But not sloved.
MM 27.12.2018 Fuel flow meter line choked. D Line cleaned .
Pending
Work done by tightened. Need to check during TC
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C
washing time.
Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 nos) ,
2 Lighting EM 12.11.2018 D
11 IE (02 nos) , 12 IE( 01 nos).
Spare not available
1 11 KV bus EM 18.12.2018 11 kV "B" bus Frequency sensor fault alarm. C
2 LFO Feeder Unit EM 24.12.2018 Air leakage from the solenoid of quick closing valve. D
3 03IE EM 21.12.2018 LO Sep # 03 : BJN pannel main switch missing A
4 05 IE EM 21.12.2018 LO Sep # 05 : BJN pannel main switch missing A
5 07 IE EM 21.12.2018 LO Sep # 07 : BJN pannel main switch missing A
6 09IE EM 14.12.2018 BJA panel cooling fan not running. B
7 12IE EM 14.12.2018 CFE panel cooling fan not running. A
8 HFO Feeder unit EM 22.11.2018 BJL Pannel viscometer B016 selector switch open , need to fix up. A
9 03 IE MM 16.10.2018 Pre - heating pump water leakage . B
10 04 IE EM 18.10.2018 Both bank TC rpm high about 29500. D
11 EM 22.10.2018 TC-B-bank rpm fluctuates. D
10IE
12 EM 04.10.2018 TC A-bank rpm 30000. A
13 04IE,05IE EM 04.04.2018 Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection. D
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working (20.10.2017).
14 All AC related issue EM 09.09.2017 A,B,C,D
15 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
16 04,10 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
17 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
18 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
19 HFO Storage tank EM HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
20 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Razu Ahmmed
28.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks
1 01IE EM/MM 27.12.2018 Engine Load fluctuates from 8600 KW to 8300 KW. ( Load Setting -8400 KW) D A new gov. of 04 IE installed & MCM change with DG#
04 but load fluctuates from 8673 KW to 8181 KW.
2 10IE EM 28.12.2018 LO Sep # 10 : Top tubelight does not illuminate . C New tube light installed.
Pending
Work done by tightened. Need to check during TC
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C
washing time.
2 Lighting EM 12.11.2018 Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 nos) , D
11 IE (02 nos) , 12 IE( 01 nos).
Spare not available
1 11 KV bus EM 18.12.2018 11 kV "B" bus Frequency sensor fault alarm. C
2 LFO Feeder Unit EM 24.12.2018 Air leakage from the solenoid of quick closing valve. D O Ring change.
3 03IE EM 21.12.2018 LO Sep # 03 : BJN pannel main switch missing A
4 05 IE EM 21.12.2018 LO Sep # 05 : BJN pannel main switch missing A
5 07 IE EM 21.12.2018 LO Sep # 07 : BJN pannel main switch missing A
6 09IE EM 14.12.2018 BJA panel cooling fan not running. B
7 12IE EM 14.12.2018 CFE panel cooling fan not running. A
8 HFO Feeder unit EM 22.11.2018 BJL Pannel viscometer B016 selector switch open , need to fix up. A
9 03 IE MM 16.10.2018 Pre - heating pump water leakage . B
10 04 IE EM 18.10.2018 Both bank TC rpm high about 29500. D
11 EM 22.10.2018 TC-B-bank rpm fluctuates. D
10IE
12 EM 04.10.2018 TC A-bank rpm 30000. A
13 04IE,05IE EM 04.04.2018 Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection. D
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working (20.10.2017).
14 All AC related issue EM 09.09.2017 A,B,C,D
15 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
16 04,10 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
17 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
18 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
19 HFO Storage tank EM 12.03.15 HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
20 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
S M Mamunur Rahman
29.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks
1 Feeder unit MM 29.12.2018 Feeder unit diaphragm sludge pump not properly pumping . B
2 Transfer pump unit EM 29.12.2018 Control panel BJG 902 alarm comes several times and suddenly transfer pump stopped . B Check, U/O.
3 EM 29.12.2018 Turning gear motor trip during engine turning time. C
01IE A new gov. of 04 IE installed & MCM change with DG#
4 EM/MM 27.12.2018 Engine Load fluctuates from 8600 KW to 8300 KW. ( Load Setting -8400 KW) D
04 but load fluctuates from 8673 KW to 8181 KW.
14 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
15 04,10 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
16 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
17 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
18 HFO Storage tank EM HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
19 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
S M Mamumur Rahman
30.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks
1 Boiler feed pump MM 30.12.2018 Boiler feed pump-1 delivery line press. gauge water leakage . B Tighting & Thread tape used.
2 Feeder unit MM 29.12.2018 Feeder unit diaphragm sludge pump not properly pumping . B Flushing time Change (2:30 To 3:30) Minites.
3 EM 29.12.2018 Turning gear motor trip during engine turning time. C U/M
01IE A new gov. of 04 IE installed & MCM change with DG#
4 EM/MM 27.12.2018 Engine Load fluctuates from 8600 KW to 8300 KW. ( Load Setting -8400 KW) D
04 but load fluctuates from 8673 KW to 8181 KW.
5 02IE EM/MM 30.12.2018 Pre lube pump abnormal sound & vibration. C Bearing change & Housing sim install.
6 03IE EM 29.12.2018 CA temp. engine inlet sensor fault . B Found Normal.
7 10 IE EM 30.12.2018 Module rack fault alarm comes several times. B Tighting.
Pending
Work done by tightened. Need to check during TC
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C
washing time.
Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 nos) ,
2 Lighting EM 12.11.2018 D
11 IE (02 nos) , 12 IE( 01 nos).
Spare not available
1 11 KV bus EM 18.12.2018 11 kV "B" bus Frequency sensor fault alarm. C
2 03IE EM 21.12.2018 LO Sep # 03 : BJN pannel main switch missing A
3 05 IE EM 21.12.2018 LO Sep # 05 : BJN pannel main switch missing A
4 07 IE EM 21.12.2018 LO Sep # 07 : BJN pannel main switch missing A
5 09IE EM 14.12.2018 BJA panel cooling fan not running. B
6 12IE EM 14.12.2018 CFE panel cooling fan not running. A
7 HFO Feeder unit EM 22.11.2018 BJL Pannel viscometer B016 selector switch open , need to fix up. A
8 03 IE MM 16.10.2018 Pre - heating pump water leakage . B
9 04 IE EM 18.10.2018 Both bank TC rpm high about 29500. D
10 EM 22.10.2018 TC-B-bank rpm fluctuates. D
10IE
11 EM 04.10.2018 TC A-bank rpm 30000. A
12 04IE,05IE EM 04.04.2018 Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection. D
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working (20.10.2017).
13 All AC related issue EM 09.09.2017 A,B,C,D
14 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
15 04,10 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
16 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
17 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
18 HFO Storage tank EM HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
19 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
Orion Power Meghnaghat L
Current & Pending Maintenance R
Md. Shofiqul Islam
31.12.2018
SL no. Equip. Name Dept. Request Date
2 02IE EM 29.12.2018
Pending
2 Lighting EM 12.11.2018
Engine Load fluctuates from 8600 KW to 8300 KW. ( Load Setting -8400 KW)
Water leakage through exhaust common bellows last flange during TC washing time.
Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 nos) ,
11 IE (02 nos) , 12 IE( 01 nos).
Spare not available
11 kV "B" bus Frequency sensor fault alarm.
LO Sep # 03 : BJN pannel main switch missing
LO Sep # 05 : BJN pannel main switch missing
LO Sep # 07 : BJN pannel main switch missing
BJA panel cooling fan not running.
CFE panel cooling fan not running.
BJL Pannel viscometer B016 selector switch open , need to fix up.
Pre - heating pump water leakage .
Both bank TC rpm high about 29500.
TC-B-bank rpm fluctuates.
TC A-bank rpm 30000.
Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection.
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working (20.10.2017).
C Motor install.
C
A
A
A
B
A
A
B
D
D
A
D
A,B,C,D
B
C+D
C
C
C&D