Orion Power Meghnaghat Ltd.

Current & Pending Maintenance Request


S M Mamunur Rahman
01.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks

1 Lighting EM 01.12.2018 Barge light not illuminate. B Light change.


2 Ins. Air Comp. Dryer # 01 EM 28.11.2018 Refrigeration Cycle continuously running at a temp. below the dew point temperature. D spare not available
3 Feeder unit MM 30.10.2018 Feeder unit flushing occur in every 21 minute intervals, when despatched 100 MW. A Candle changed on 12.11.2018,U/O .
4 04IE EM 01.12.2018 Fuel booster unit air regulating valve is not working. A Rectified.
5 MM 30.11.2018 Air Leakage from HT pneumatic controller. C
06IE
6 EM 01.12.2018 Pre -lube pump abnormal sound . B Bearing change.
7 07IE MM 01.12.2018 Air line broken from Gov. surbo booster unit. A Welding.
8 08IE MM 01.121.2018 Air Leakage from pre -heating controller regulator. B Rectified.
Pending

1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C Work done by tightened. Need to check
during TC washing time.

2 Lighting EM 12.11.2018 Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).

3 03 IE EM 01.11.2018 Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.

Spare not available


1 HFO Feeder unit EM 22.11.2018 BJL Pannel viscometer B016 selector switch open , need to fix up. A
2 Transfer pump -1 MM 29.10.2018 Mechanical seal FO leakey . A
3 03 IE MM 16.10.2018 Pre - heating pump water leakage . B
4 04 IE EM 18.10.2018 Both bank TC rpm high about 29500. D
5 EM 22.10.2018 TC-B-bank rpm fluctuates. D
10IE
6 EM 04.10.2018 TC A-bank rpm 30000. A
7 04IE,05IE EM 04.04.2018 Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection. D
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working
8 All AC related issue EM 09.09.2017 (20.10.2017). A,B,C,D

9 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
10 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
11 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
12 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C

13 HFO Storage tank EM 12.03.15 HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
14 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
15 08IE & 09IE MM 29.10.2018 Fuel booster unit after quick closing v/v pressure gauge faulty . B
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Md. Shofiqul Islam.
02.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks

1 Ins. Air Comp #02 MM 02.12.2018 Belt damage , need to change. A Belt & air end replaced .
2 Ins. Air Comp. Dryer # 01 EM 28.11.2018 Refrigeration Cycle continuously running at a temp. below the dew point temperature. D spare not available
3 Feeder unit MM 30.10.2018 Feeder unit flushing occur in every 21 minute intervals, when despatched 100 MW. A Candle changed on 12.11.2018,U/O .
4 03IE MM 02.12.2018 Lube oil Sep# 03: Water leakage from fresh water inlet line. C Elbow Tighened by RTV u/o
5 06IE MM 30.11.2018 Air Leakage from HT pneumatic controller. C spare not available
Pending
Work done by tightened. Need to check
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C during TC washing time.

2 Lighting EM 12.11.2018 Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).

3 03 IE EM 01.11.2018 Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.

Spare not available


1 HFO Feeder unit EM 22.11.2018 BJL Pannel viscometer B016 selector switch open , need to fix up. A
2 Transfer pump -1 MM 29.10.2018 Mechanical seal FO leakey . A Seal change U/O.
3 03 IE MM 16.10.2018 Pre - heating pump water leakage . B
4 04 IE EM 18.10.2018 Both bank TC rpm high about 29500. D
5 EM 22.10.2018 TC-B-bank rpm fluctuates. D
10IE
6 EM 04.10.2018 TC A-bank rpm 30000. A
7 04IE,05IE EM 04.04.2018 Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection. D
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working
8 All AC related issue EM 09.09.2017 (20.10.2017). A,B,C,D

9 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
10 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
11 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
12 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
13 HFO Storage tank EM HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
14 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
15 08IE & 09IE MM 29.10.2018 Fuel booster unit after quick closing v/v pressure gauge faulty . B
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Razu Ahmmed
03.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks

1 Ins. Air Comp. Dryer # 01 EM 28.11.2018 Refrigeration Cycle continuously running at a temp. below the dew point temperature. D spare not available
2 Feeder unit MM 30.10.2018 Feeder unit flushing occur in every 21 minute intervals, when despatched 100 MW. A Candle changed on 12.11.2018,U/O .
3 02IE MM 03.12.2018 Air Leakage from HT pneumatic controller. B spare not available
4 03IE MM 03.12.2018 Dirty leak pump not properly pumping . B cleaning done
5 06IE MM 30.11.2018 Air Leakage from HT pneumatic controller. C spare not available
6 07IE MM 03.12.2018 Air Leakage from mixing tank return line pneumatic controller. B
7 08IE MM 03.12.2018 Air Leakage from booster unit heater controller. B capillary tube change.
8 MM 03.12.2018 Air Leakage from mixing tank return line pneumatic controller. B pneumatic line nipple change
10IE
9 MM 03.12.2018 Exhaustleakage from cyl.B7 indicator cork . B Indicator cock lapping
10 11IE MM 03.12.2018 LO Sep # 11- LO inlet temperature not increase. B steam trap open & clean.
11 12 IE MM 03.12.2018 Lube oil leakage from Cyl. B04 crankcase door. D two bolt change
Pending
Work done by tightened. Need to check
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C during TC washing time.
Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01
2 Lighting EM 12.11.2018 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).

3 03 IE EM 01.11.2018 Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.

Spare not available


1 HFO Feeder unit EM 22.11.2018 BJL Pannel viscometer B016 selector switch open , need to fix up. A
2 Transfer pump -1 MM 29.10.2018 Mechanical seal FO leakey . A Seal change U/O.
3 03 IE MM 16.10.2018 Pre - heating pump water leakage . B
4 04 IE EM 18.10.2018 Both bank TC rpm high about 29500. D
5 EM 22.10.2018 TC-B-bank rpm fluctuates. D
10IE
6 EM 04.10.2018 TC A-bank rpm 30000. A
7 04IE,05IE EM 04.04.2018 Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection. D
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working
8 All AC related issue EM 09.09.2017 (20.10.2017). A,B,C,D

9 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
10 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
11 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
12 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
13 HFO Storage tank EM 02.07.15 HFO Storage tank #01&02 :- Level senor faulty. C&D

14 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C


15 08IE & 09IE MM 29.10.2018 Fuel booster unit after quick closing v/v pressure gauge faulty . B
6173496
33598
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Md.Shofiqul Islam.
04.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks

1 Ins. Air Comp. Dryer # 01 EM 28.11.2018 Refrigeration Cycle continuously running at a temp. below the dew point temperature. D spare not available
2 Feeder unit MM 30.10.2018 Feeder unit flushing occur in every 21 minute intervals, when despatched 100 MW. A Candle changed on 12.11.2018,U/O .
3 HFO Sludge pump MM 04.12.2018 HFO Sludge pump ( yellow colour ) is not working A
4 Hydrover no # 02 MM 04.12.2018 Water leakage through delivery valve. A
5 EGB # 01 MM 04.12.2018 Boiler inlet & out let line exh. flange insulation cover O clamp broken. A Tightened by O clamp
6 02IE MM 03.12.2018 Air Leakage from HT pneumatic controller. B spare not available
7 06IE MM 30.11.2018 Air Leakage from HT pneumatic controller. C spare not available
8 09IE EM 04.12.2018 Q7 breaker ( hall # 02 DB pannel ) trip when DG # 09 walk way lighting switch on A Problem was in two light . Now Ok.
Pending
Work done by tightened. Need to check
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C during TC washing time.
Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01
2 Lighting EM 12.11.2018 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).

3 03 IE EM 01.11.2018 Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.

Spare not available


1 HFO Feeder unit EM 22.11.2018 BJL Pannel viscometer B016 selector switch open , need to fix up. A
2 Transfer pump -1 MM 29.10.2018 Mechanical seal FO leakey . A Seal change U/O.
3 03 IE MM 16.10.2018 Pre - heating pump water leakage . B
4 04 IE EM 18.10.2018 Both bank TC rpm high about 29500. D
5 EM 22.10.2018 TC-B-bank rpm fluctuates. D
10IE
6 EM 04.10.2018 TC A-bank rpm 30000. A
7 04IE,05IE EM 04.04.2018 Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection. D
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working
8 All AC related issue EM 09.09.2017 (20.10.2017). A,B,C,D

9 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
10 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
11 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
12 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
13 HFO Storage tank EM HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
14 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
15 08IE & 09IE MM 29.10.2018 Fuel booster unit after quick closing v/v pressure gauge faulty . B
33598
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Md. Shofiqul Islam.
05.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks

1 Ins. Air Comp. Dryer # 01 EM 28.11.2018 Refrigeration Cycle continuously running at a temp. below the dew point temperature. D spare not available
2 Feeder unit MM 30.10.2018 Feeder unit flushing occur in every 21 minute intervals, when despatched 100 MW. A Candle changed on 12.11.2018,U/O .
3 HFO Sludge pump MM 04.12.2018 HFO Sludge diaphragm pump- big one ( yellow colour ) is not working A On Going.
4 11 IE EM/MM 05.12.2018 LO Sep # 11- Abnormal sound comes from feed pump. D Check & found ok .
Pending
Work done by tightened. Need to check
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C
during TC washing time.

2 Lighting EM 12.11.2018 Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).

3 03 IE EM 01.11.2018 Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.

Spare not available


1 HFO Feeder unit EM 22.11.2018 BJL Pannel viscometer B016 selector switch open , need to fix up. A
2 02IE MM 03.12.2018 Air Leakage from HT pneumatic controller. B
3 03 IE MM 16.10.2018 Pre - heating pump water leakage . B
4 04 IE EM 18.10.2018 Both bank TC rpm high about 29500. D
5 06IE MM 30.11.2018 Air Leakage from HT pneumatic controller. C
6 EM 22.10.2018 TC-B-bank rpm fluctuates. D
10IE
7 EM 04.10.2018 TC A-bank rpm 30000. A
8 04IE,05IE EM 04.04.2018 Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection. D
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working
9 All AC related issue EM 09.09.2017 (20.10.2017). A,B,C,D

10 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
11 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
12 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
13 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C

14 HFO Storage tank EM 12.03.15 HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
15 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
16 08IE & 09IE MM 29.10.2018 Fuel booster unit after quick closing v/v pressure gauge faulty . B
33598
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Razu Ahmmed
06.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks

1 Ins. Air Comp. Dryer # 01 EM 28.11.2018 Refrigeration Cycle continuously running at a temp. below the dew point temperature. D spare not available
2 01IE EM 06.12.2018 ESM lube oil pressure shut down status IS 2011 B check found ok
3 Feeder unit MM 30.10.2018 Feeder unit flushing occur in every 21 minute intervals, when despatched 100 MW. A Candle changed on 12.11.2018,U/O .
4 HFO Sludge pump MM 04.12.2018 HFO Sludge diaphragm pump- big one ( yellow colour ) is not working A On Going.
Pending
Work done by tightened. Need to check
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C
during TC washing time.

2 Lighting EM 12.11.2018 Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).

3 03 IE EM 01.11.2018 Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.

Spare not available


1 HFO Feeder unit EM 22.11.2018 BJL Pannel viscometer B016 selector switch open , need to fix up. A
2 02IE MM 03.12.2018 Air Leakage from HT pneumatic controller. B
3 03 IE MM 16.10.2018 Pre - heating pump water leakage . B
4 04 IE EM 18.10.2018 Both bank TC rpm high about 29500. D
5 06IE MM 30.11.2018 Air Leakage from HT pneumatic controller. C
6 EM 22.10.2018 TC-B-bank rpm fluctuates. D
10IE
7 EM 04.10.2018 TC A-bank rpm 30000. A
8 04IE,05IE EM 04.04.2018 Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection. D
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working
9 All AC related issue EM 09.09.2017 (20.10.2017). A,B,C,D

10 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
11 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
12 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
13 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C

14 HFO Storage tank EM 12.03.15 HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
15 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
16 08IE & 09IE MM 29.10.2018 Fuel booster unit after quick closing v/v pressure gauge faulty . B
33598
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Md. Mofizur Rahman.
07.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks

1 Ins. Air Comp. Dryer # 01 EM 28.11.2018 Refrigeration Cycle continuously running at a temp. below the dew point temperature. D spare not available
2 Feeder unit MM 30.10.2018 Feeder unit flushing occur in every 21 minute intervals, when despatched 100 MW. A Candle changed on 12.11.2018,U/O .
3 05IE MM 08.12.2018 Air leakage from Preheating unit air press. Regulating valve. C Regulator replaced.
4 10IE MM 08.12.2018 L/O Sep# 10: Sludge tank vent filter lube oil leaky. C Tightened.
Pending

1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C Work done by tightened. Need to check
during TC washing time.

2 Lighting EM 12.11.2018 Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).

3 03 IE EM Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.

Spare not available


1 HFO Feeder unit EM 22.11.2018 BJL Pannel viscometer B016 selector switch open , need to fix up. A
2 02IE MM 03.12.2018 Air Leakage from HT pneumatic controller. B
3 03 IE MM 16.10.2018 Pre - heating pump water leakage . B
4 04 IE EM 18.10.2018 Both bank TC rpm high about 29500. D
5 06IE MM 30.11.2018 Air Leakage from HT pneumatic controller. C
6 EM 22.10.2018 TC-B-bank rpm fluctuates. D
10IE
7 EM 04.10.2018 TC A-bank rpm 30000. A
8 04IE,05IE EM 04.04.2018 Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection. D
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working
9 All AC related issue EM 09.09.2017 (20.10.2017). A,B,C,D

10 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
11 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
12 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
13 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
14 HFO Storage tank EM HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
15 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
16 08IE & 09IE MM 29.10.2018 Fuel booster unit after quick closing v/v pressure gauge faulty . B
33598
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Md. Mofizur Rahman.
08.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks

1 04IE MM 08.12.2018 Air Leakage from Booster unit temp. control air regulator . A Replaced servicing one.
2 06IE MM 08.12.2018 Air Leakage through visco meter pneumatic controller. A Nipple & tube change.
3 Ins. Air Comp. Dryer # 01 EM 28.11.2018 Refrigeration Cycle continuously running at a temp. below the dew point temperature. D Sensor change. Now Ok.
4 08 IE EM 08.12.2018 Earthing cable of engine body disconnected near A01 crankcase door. D Cable connect.
Pending
Work done by tightened. Need to check
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C during TC washing time.

2 Lighting EM 12.11.2018 Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).

3 03 IE EM Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.

Spare not available


1 HFO Feeder unit EM 22.11.2018 BJL Pannel viscometer B016 selector switch open , need to fix up. A
2 02IE MM 03.12.2018 Air Leakage from HT pneumatic controller. B Seal & o ring change.
3 03 IE MM 16.10.2018 Pre - heating pump water leakage . B
4 04 IE EM 18.10.2018 Both bank TC rpm high about 29500. D
5 06IE MM 30.11.2018 Air Leakage from HT pneumatic controller. C Seal & o ring change.
6 EM 22.10.2018 TC-B-bank rpm fluctuates. D
10IE
7 EM 04.10.2018 TC A-bank rpm 30000. A
8 04IE,05IE EM 04.04.2018 Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection. D
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working
9 All AC related issue EM 09.09.2017 (20.10.2017). A,B,C,D

10 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
11 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
12 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
13 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C

14 HFO Storage tank EM 12.03.15 HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
15 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
16 08IE & 09IE MM 29.10.2018 Fuel booster unit after quick closing v/v pressure gauge faulty . B Gauge change new one.
33598
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Razu Ahmmed
09.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks

1 03 IE EM 09.12.2018 Pre lube pump selector switch opeartion problematic. C


2 08 IE MM 09.12.2018 HT water outlet line rubber belows cracked. C Bellows changed.
Pending

1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C Work done by tightened. Need to check
during TC washing time.

2 Lighting EM 12.11.2018 Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).

3 03 IE EM Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.

Spare not available


1 HFO Feeder unit EM 22.11.2018 BJL Pannel viscometer B016 selector switch open , need to fix up. A
2 03 IE MM 16.10.2018 Pre - heating pump water leakage . B
3 04 IE EM 18.10.2018 Both bank TC rpm high about 29500. D
4 EM 22.10.2018 TC-B-bank rpm fluctuates. D
10IE
5 EM 04.10.2018 TC A-bank rpm 30000. A
6 04IE,05IE EM 04.04.2018 Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection. D
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working
7 All AC related issue EM 09.09.2017 (20.10.2017). A,B,C,D

8 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
9 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
10 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
11 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C

12 HFO Storage tank EM 12.03.15 HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
13 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
33598
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Md. Mofizur Rahman.
10.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks

1 Feeder unit EM 10.12.2018 Air leakage from Feeder unit quick closing solenoid valve. C Interchanged with LFO Quick closing v/v

2 Aux. boiler MM 10.12.2018 Feed water tank man hole cover gasket damage. A Gasket changed.
3 02IE MM 10.12.2019 Cyl.B7, B8 unit hot box cover hinge damaged. A Bolt changed.
4 03IE EM/MM 10.12.2018 LO Sep # 03 : LO comes through V6 valve. A EM checked found OK.
5 MM 10.12.2018 Condensate leakage through Fuel booster unit steam trap. A Gasket changed.
09IE
6 EM 10.12.2018 Pre lube pump motor abnormal sound. A Bearing changed.
Pending
Work done by tightened. Need to check
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C
during TC washing time.
Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01
2 Lighting EM 12.11.2018 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).

3 03 IE EM Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.

Spare not available


1 HFO Feeder unit EM 22.11.2018 BJL Pannel viscometer B016 selector switch open , need to fix up. A
2 03 IE MM 16.10.2018 Pre - heating pump water leakage . B
3 04 IE EM 18.10.2018 Both bank TC rpm high about 29500. D
4 EM 22.10.2018 TC-B-bank rpm fluctuates. D
10IE
5 EM 04.10.2018 TC A-bank rpm 30000. A
6 04IE,05IE EM 04.04.2018 Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection. D
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working
7 All AC related issue EM 09.09.2017 (20.10.2017). A,B,C,D

8 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
9 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
10 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
11 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C

12 HFO Storage tank EM 12.03.15 HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
13 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
33598
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
S M Mamunur Rahman
11.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks

1 Fire Hydrant Point # 025 MM 11.12.2018 Fire Hydrant Point # 025( In front of storage tank)- Valve does not provide seal properly. D Rubber seal changed,but not solved.
2 Aux. boiler MM 10.12.2018 Feed water tank man hole cover gasket damage. A Gasket changed .
3 Hydrovar Pump # 01 MM 11.12.2018 Non return valve does not provide seal properly. D v/v changed with new one.
4 MM 11.12.2018 Exhaust leakage from common short bellows. D A1, B6 cyl. Short bellows changed.
01 IE
5 EM 11.12.2018 LT -water temp . CAC inlet (TE 471) sensor fault. D Cable burn. New cable change.
6 03 IE MM 11.12.2018 LO Sep # 03- Heater can not increase the lube oil temperature more than 77 oC. D steam trap clean. Now ok.
8 10 IE EM 11.12.2018 Radiator frequency converter tripped due to temp high alarm at running condition . B Cooling fan ( card) change.
9 11 IE MM/EM 11.12.2018 LO Sep # 11-Clean oil discharge pressure settings . Alarm no- 45. D Discharge valve adjust.
Pending
Work done by tightened. Need to check
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C
during TC washing time.

2 Lighting EM 12.11.2018 Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).

3 03 IE EM Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.

Spare not available


1 LFO Feeder Unit EM 11.12.2018 Quick closing valve is in dismantle condition. D
2 HFO Feeder unit EM 22.11.2018 BJL Pannel viscometer B016 selector switch open , need to fix up. A
3 03 IE MM 16.10.2018 Pre - heating pump water leakage . B
4 04 IE EM 18.10.2018 Both bank TC rpm high about 29500. D
5 EM 22.10.2018 TC-B-bank rpm fluctuates. D
10IE
6 EM 04.10.2018 TC A-bank rpm 30000. A
7 04IE,05IE EM 04.04.2018 Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection. D
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working
8 All AC related issue EM 09.09.2017 (20.10.2017). A,B,C,D

9 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
10 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
11 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
12 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
13 HFO Storage tank EM HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
14 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
33598
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Razu Ahmmed
12.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks

1 Fire Hydrant Point # 025 MM 11.12.2018 Fire Hydrant Point # 025( In front of storage tank)- Valve does not provide seal properly. D Valve seat polishing &clieaning , solved.
2 MM 12.12.2018 Abnormal vibration at lube oil centrifuse filter. D Centrifuse filter cleaned. U/O
01 IE
3 EM 12.12.2018 TC B-bank RPM not showing. Wire torn. C Sensor & cable changed, now ok.
4 03 IE EM/MM 12.12.2018 LO Sep # 03- Separator motor taking more Ampere about 11.2 A. D
5 04 IE MM 12.12.2018 Cyl B6: Crankcase door relief v/v LO leakage. C O - ring changed ,ok .
6 MM 12.12.2018 Cyl. A02 & Cyl. B10- Multiduct water leakage. D Tightened. Ok .
08 IE
7 MM 12.12.2018 TC B-bank after TC exhaust line insulation damage. C
8 11 IE EM 12.12.2018 Main Bearing # 09 temp decreasing gradually (88 degree to 77 degree) C Control cable old changed ,now ok .
9 12 IE MM 12.12.2018 Cyl. A01- Fuel leakage from clean leak short piece of Cyl. Head. D O' ring of short piece changed, ok .
Pending
Work done by tightened. Need to check during TC
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C
washing time.

2 Lighting EM 12.11.2018 Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).

3 03 IE EM Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.

Spare not available


1 LFO Feeder Unit EM 11.12.2018 Quick closing valve is in dismantle condition. D
2 HFO Feeder unit EM 22.11.2018 BJL Pannel viscometer B016 selector switch open , need to fix up. A
3 03 IE MM 16.10.2018 Pre - heating pump water leakage . B
4 04 IE EM 18.10.2018 Both bank TC rpm high about 29500. D
5 EM 22.10.2018 TC-B-bank rpm fluctuates. D
10IE
6 EM 04.10.2018 TC A-bank rpm 30000. A
7 04IE,05IE EM 04.04.2018 Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection. D
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working
8 All AC related issue EM 09.09.2017 (20.10.2017). A,B,C,D

9 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
10 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
11 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
12 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
13 HFO Storage tank EM HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
14 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
http://61.247.183.69:8021/
33598
25
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Md. Mofizur Rahman
13.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks

1 EM/MM 13.12.2018 LO Sep # 03 : Lube oil comes through V6 valve. C Top part & hood sensor port cleaned. U/O

2 03 IE MM 13.12.2018 Dirty leak diaphragm pump is not working . B Tank cleaned & pump servicing done. Now ok.

3 EM/MM 12.12.2018 LO Sep # 03- Separator motor taking more Ampere about 11.2 A. D

4 EM 13.12.2018 Radiator frequency convertar alarm: 32 fan cooling F T1- T16. C Cooling fan 02 pcs bearing changed. Now ok.

5 MM 13.12.2018 Exhaust leakage from common short bellows. B B09 gasket and A09 bellows changed.
08IE
6 EM 13.12.2018 Turning motor abnormal sound . B
7 MM 12.12.2018 TC B-bank after TC exhaust line insulation damage. C
8 12IE MM 13.12.2018 Exhaust leakage from common short bellows. B
Pending
Work done by tightened. Need to check during TC
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C
washing time.

2 Lighting EM 12.11.2018 Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).

3 03 IE EM Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.

Spare not available


1 LFO Feeder Unit EM 11.12.2018 Quick closing valve is in dismantle condition. D
2 HFO Feeder unit EM 22.11.2018 BJL Pannel viscometer B016 selector switch open , need to fix up. A
3 03 IE MM 16.10.2018 Pre - heating pump water leakage . B
4 04 IE EM 18.10.2018 Both bank TC rpm high about 29500. D
5 EM 22.10.2018 TC-B-bank rpm fluctuates. D
10IE
6 EM 04.10.2018 TC A-bank rpm 30000. A
7 04IE,05IE EM 04.04.2018 Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection. D
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working
8 All AC related issue EM 09.09.2017 (20.10.2017). A,B,C,D

9 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
10 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
11 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
12 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
13 HFO Storage tank EM 02.07.15 HFO Storage tank #01&02 :- Level senor faulty. C&D

14 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C


33598
25
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
S M Mamunur Rahman
14.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks

1 EM/MM 13.12.2018 LO Sep # 03 : Lube oil comes through V6 valve. C Top part & hood sensor port cleaned. U/O
03 IE
2 EM/MM 12.12.2018 LO Sep # 03- Separator motor taking more Ampere about 11.2 A. D Separator motor open. U/M
3 06IE EM 14.12.2018 CFE panel cooling fan always running. B Thermostat change new one.

4 EM/MM 13.12.2018 Turning motor abnormal sound . B 02 pcs bearing of TG motor changed by EM. Now
electrically ok.
08 IE
5 MM 12.12.2018 TC B-bank after TC exhaust line insulation damage. C Done.

6 09IE EM 14.12.2018 BJA panel cooling fan not running. B Spare not available.

7 12IE EM 14.12.2018 CFE panel cooling fan not running. B Spare not available.
Pending

1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C Work done by tightened. Need to check during TC
washing time.

2 Lighting EM 12.11.2018 Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).

3 03 IE EM Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.

Spare not available


1 LFO Feeder Unit EM 11.12.2018 Quick closing valve is in dismantle condition. D
2 HFO Feeder unit EM 22.11.2018 BJL Pannel viscometer B016 selector switch open , need to fix up. A
3 03 IE MM 16.10.2018 Pre - heating pump water leakage . B
4 04 IE EM 18.10.2018 Both bank TC rpm high about 29500. D
5 EM 22.10.2018 TC-B-bank rpm fluctuates. D
10IE
6 EM 04.10.2018 TC A-bank rpm 30000. A
7 04IE,05IE EM 04.04.2018 Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection. D
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working
8 All AC related issue EM 09.09.2017 (20.10.2017). A,B,C,D

9 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
10 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
11 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
12 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C

13 HFO Storage tank EM 12.03.15 HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
14 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
33598
25
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Md. Shofiqul Islam.
15.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks

1 EM/MM 13.12.2018 LO Sep # 03 : Lube oil comes through V6 valve. C Top part & hood sensor port cleaned. U/O
03 IE
2 EM/MM 12.12.2018 LO Sep # 03- Separator motor taking more Ampere about 11.2 A. D Separator motor open. U/M
3 04IE EM/MM 15.12.2018 Engine Load setting: 8700 KW ,Engine Load fluctuate ( 9052 to 8424 ) KW. C New connector install ,U/O .
4 10IE MM 15.12.2018 Water leakage through LT Controller shaft seal. A Tighteen by treat tape .
5 12IE MM 15.12.2018 Water leakage through LT Controller shaft seal. A Tighteen by treat tape .
Pending
Work done by tightened. Need to check during TC
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C
washing time.

2 Lighting EM 12.11.2018 Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).

3 03 IE EM Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.

Spare not available


1 09IE EM 14.12.2018 BJA panel cooling fan not running. B
2 12IE EM 14.12.2018 CFE panel cooling fan not running.
3 LFO Feeder Unit EM 11.12.2018 Quick closing valve is in dismantle condition. D
4 HFO Feeder unit EM 22.11.2018 BJL Pannel viscometer B016 selector switch open , need to fix up. A
5 03 IE MM 16.10.2018 Pre - heating pump water leakage . B
6 04 IE EM 18.10.2018 Both bank TC rpm high about 29500. D
7 EM 22.10.2018 TC-B-bank rpm fluctuates. D
10IE
8 EM 04.10.2018 TC A-bank rpm 30000. A
9 04IE,05IE EM 04.04.2018 Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection. D
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working
10 All AC related issue EM 09.09.2017 (20.10.2017). A,B,C,D

11 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
12 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
13 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
14 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
15 HFO Storage tank EM 02.07.15 HFO Storage tank #01&02 :- Level senor faulty. C&D

16 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C


33598
25
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Md. Mofizur Rahman
16.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks

1 EM/MM 13.12.2018 LO Sep # 03 : Lube oil comes through V6 valve. C Top part & hood sensor port cleaned. U/O
03 IE
2 EM/MM 12.12.2018 LO Sep # 03- Separator motor taking more Ampere about 11.2 A. D Separator motor open. U/M
3 04IE EM/MM 15.12.2018 Engine Load setting: 8700 KW ,Engine Load fluctuate ( 9052 to 8424 ) KW. C New connector install ,U/O .
4 12IE EM 16.12.2018 Pre-lube pump abnormal sound . B check found ok
Pending
Work done by tightened. Need to check during TC
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C washing time.
Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01
2 Lighting EM 12.11.2018 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).

3 03 IE EM Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.

Spare not available


1 09IE EM 14.12.2018 BJA panel cooling fan not running. B
2 12IE EM 14.12.2018 CFE panel cooling fan not running.
3 LFO Feeder Unit EM 11.12.2018 Quick closing valve is in dismantle condition. D
4 HFO Feeder unit EM 22.11.2018 BJL Pannel viscometer B016 selector switch open , need to fix up. A
5 03 IE MM 16.10.2018 Pre - heating pump water leakage . B
6 04 IE EM 18.10.2018 Both bank TC rpm high about 29500. D
7 EM 22.10.2018 TC-B-bank rpm fluctuates. D
10IE
8 EM 04.10.2018 TC A-bank rpm 30000. A
9 04IE,05IE EM 04.04.2018 Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection. D
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working
10 All AC related issue EM 09.09.2017 (20.10.2017). A,B,C,D

11 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
12 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
13 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
14 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
15 HFO Storage tank EM HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
16 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
33598
25
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
S M Mamunur Rahman.
17.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks

1 02IE MM 17.12.2018 Air leakage through pre- heating unit before air regulator pipe line A Nipple change.

2 EM/MM 13.12.2018 LO Sep # 03 : Lube oil comes through V6 valve. C Top part, hood sensor port cleaned & motor fix up U/O
03 IE
3 EM/MM 12.12.2018 LO Sep # 03- Separator motor taking more Ampere about 11.2 A. D Separator motor open , U/M .
4 04IE EM/MM 15.12.2018 Engine Load setting: 8700 KW ,Engine Load fluctuate ( 9052 to 8424 ) KW. C New connector install ,U/O .
5 HFO Feeder unit MM 17.12.2018 HFO leakage through HFO Feed pump # 1 & 2 Inlet Glove valve A Tightened ,U/O .
Pending
Work done by tightened. Need to check during TC
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C
washing time.

2 Lighting EM 12.11.2018 Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).

3 03 IE EM Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.

Spare not available


1 09IE EM 14.12.2018 BJA panel cooling fan not running. B
2 12IE EM 14.12.2018 CFE panel cooling fan not running.
3 LFO Feeder Unit EM 11.12.2018 Quick closing valve is in dismantle condition. D
4 HFO Feeder unit EM 22.11.2018 BJL Pannel viscometer B016 selector switch open , need to fix up. A
5 03 IE MM 16.10.2018 Pre - heating pump water leakage . B
6 04 IE EM 18.10.2018 Both bank TC rpm high about 29500. D
7 EM 22.10.2018 TC-B-bank rpm fluctuates. D
10IE
8 EM 04.10.2018 TC A-bank rpm 30000. A
9 04IE,05IE EM 04.04.2018 Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection. D
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working
10 All AC related issue EM 09.09.2017 (20.10.2017). A,B,C,D

11 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
12 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
13 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
14 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C

15 HFO Storage tank EM 12.03.15 HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
16 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
33598
25
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Md. Shofiqul Islam.
18.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks

1 11 KV bus EM 18.12.2018 11 kV "B" bus Frequency sensor fault alarm. C Not solved ,U/M .
2 Ins. Air comp # 01 EM 18.12.2018 Drayer cooling fan not running. C Capacitor changed .
3 Roof Top MM 18.12.2018 Water leakage from roof top ventilation fan DG# 02 & DG#04 back side. C Rectifited
4 01 IE EM 18.12.2018 TC-B-bank rpm fluctuates. A
5 EM/MM 13.12.2018 LO Sep # 03 : Lube oil comes through V6 valve. C Top part, hood sensor port cleaned.U/O
03 IE
6 EM/MM 12.12.2018 LO Sep # 03- Separator motor taking more Ampere about 11.2 A. D Separator motor bearing chnaged. U/O
7 04 IE EM/MM 15.12.2018 Engine Load setting: 8700 KW ,Engine Load fluctuate ( 9052 to 8424 ) KW. C New connector install ,U/O .
Pending
Work done by tightened. Need to check during TC
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C
washing time.
Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01
2 Lighting EM 12.11.2018 nos) , 11 IE (02 nos) , 12 IE( 01 nos). D

3 03 IE EM Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.

Spare not available


1 09IE EM 14.12.2018 BJA panel cooling fan not running. B
2 12IE EM 14.12.2018 CFE panel cooling fan not running.
3 LFO Feeder Unit EM 11.12.2018 Quick closing valve is in dismantle condition. D
4 HFO Feeder unit EM 22.11.2018 BJL Pannel viscometer B016 selector switch open , need to fix up. A
5 03 IE MM 16.10.2018 Pre - heating pump water leakage . B
6 04 IE EM 18.10.2018 Both bank TC rpm high about 29500. D
7 EM 22.10.2018 TC-B-bank rpm fluctuates. D
10IE
8 EM 04.10.2018 TC A-bank rpm 30000. A
9 04IE,05IE EM 04.04.2018 Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection. D
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working
10 All AC related issue EM 09.09.2017 (20.10.2017). A,B,C,D

11 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
12 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
13 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
14 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C

15 HFO Storage tank EM 12.03.15 HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
16 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
33598
25
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Razu Ahmmed
19.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks

Supply Ventilation Local Panel


1 EM 19.12.2018 Cooling fan missing. D new fan fix up
DG# 01,02,03,04
Supply Ventilation Local Panel
2 EM 19.12.2018 Abnormal sound from cooling fan. D Check & done
DG# 05& 06
Supply Ventilation Local Panel
3 EM 19.12.2018 Cooling fan is not running. D Check & done
DG# 07& 08
4 11 KV bus EM 18.12.2018 11 kV "B" bus Frequency sensor fault alarm. C Not solved ,U/M .
5 EM 19.12.2018 Turning gear motor several times trip . B
01 IE
6 EM 18.12.2018 TC-B-bank rpm fluctuates. A
7 EM/MM 13.12.2018 LO Sep # 03 : Lube oil comes through V6 valve. C Top part, hood sensor port cleaned.U/O
03 IE
8 EM/MM 12.12.2018 LO Sep # 03- Separator motor taking more Ampere about 11.2 A. D Separator motor bearing chnaged. U/O
9 04 IE EM/MM 15.12.2018 Engine Load setting: 8700 KW ,Engine Load fluctuate ( 9052 to 8424 ) KW. C New connector install ,U/O .
10 05IE MM 19.12.2018 Air leakage from pre -heating controller shaft top side air leakage . B Tightened by taflon tape
11 07IE MM/EM 19.12.2018 TC A-bank lube oil inlet pressure sensinig line pressure fluctuates . B Tube cleaned by MM.
Pending
Work done by tightened. Need to check during TC
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C
washing time.
Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01
2 Lighting EM 12.11.2018 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).

3 03 IE EM Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.

Spare not available


1 09IE EM 14.12.2018 BJA panel cooling fan not running. B
2 12IE EM 14.12.2018 CFE panel cooling fan not running.
3 LFO Feeder Unit EM 11.12.2018 Quick closing valve is in dismantle condition. D
4 HFO Feeder unit EM 22.11.2018 BJL Pannel viscometer B016 selector switch open , need to fix up. A
5 03 IE MM 16.10.2018 Pre - heating pump water leakage . B
6 04 IE EM 18.10.2018 Both bank TC rpm high about 29500. D
7 EM 22.10.2018 TC-B-bank rpm fluctuates. D
10IE
8 EM 04.10.2018 TC A-bank rpm 30000. A
9 04IE,05IE EM 04.04.2018 Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection. D
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working
10 All AC related issue EM 09.09.2017 (20.10.2017). A,B,C,D

11 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
12 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
13 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
14 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
15 HFO Storage tank EM HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
16 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
33598
25
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
S M Mamunur Rahman
20.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks

1 WTP MM 20.12.2018 RO Inlet line Elbow broken A Elbow change u/o


2 11 KV bus EM 18.12.2018 11 kV "B" bus Frequency sensor fault alarm. C Not solved ,U/M .
3 MM 20.12.2018 LO Sep # 03 : Sludge tank full. A Cleaned.
4 MM/EM 20.12.2018 Turning gear motor abnormal sound. A MM & EM checked. Found Ok.
01 IE
5 EM 19.12.2018 Turning gear motor several times trip . B Serviced motor installed.
6 EM 18.12.2018 TC-B-bank rpm fluctuates. A Cable tightened. Now ok.
7 EM 20.21.2018 CA temp. engine inlet TE601 sensor fault . B Cable tightened. Now ok.
8 MM 20.12.2018 Fuel booster duplex filter top part fuel leakage . B O ring changed. Now ok.
03 IE
9 EM/MM 13.12.2018 LO Sep # 03 : Lube oil comes through V6 valve. C Top part, hood sensor port cleaned.U/O
10 EM/MM 12.12.2018 LO Sep # 03- Separator motor taking more Ampere about 11.2 A. D Separator motor bearing chnaged. U/O
11 EM 20.12.2018 SHD,ESM shut down status IB 7324 Alarm activated . A MCM changed by new one. Now ok.
04 IE
12 EM/MM 15.12.2018 Engine Load setting: 8700 KW ,Engine Load fluctuate ( 9052 to 8424 ) KW. C New connector install ,U/O .
13 10IE EM 20.12.2018 Radiator frequency converter tripped due to converter cooling fan alarm(Alarm#32). B Cooling fan installed. Now ok.
14 12IE MM/EM 20.12.2018 Turning gear motor abnormal sound. A Bearing changed.
Pending
Work done by tightened. Need to check during TC
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C
washing time.
Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01
2 Lighting EM 12.11.2018 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).

3 03 IE EM Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.

Spare not available


1 09IE EM 14.12.2018 BJA panel cooling fan not running. B
2 12IE EM 14.12.2018 CFE panel cooling fan not running.
3 LFO Feeder Unit EM 11.12.2018 Quick closing valve is in dismantle condition. D
4 HFO Feeder unit EM 22.11.2018 BJL Pannel viscometer B016 selector switch open , need to fix up. A
5 03 IE MM 16.10.2018 Pre - heating pump water leakage . B
6 04 IE EM 18.10.2018 Both bank TC rpm high about 29500. D
7 EM 22.10.2018 TC-B-bank rpm fluctuates. D
10IE
8 EM 04.10.2018 TC A-bank rpm 30000. A
9 04IE,05IE EM 04.04.2018 Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection. D
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working
10 All AC related issue EM 09.09.2017 (20.10.2017). A,B,C,D

11 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
12 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
13 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
14 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
15 HFO Storage tank EM HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
16 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
33598
25
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Md. Shofiqul Islam.
21.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks

1 11 KV bus EM 18.12.2018 11 kV "B" bus Frequency sensor fault alarm. C Not solved ,U/M .
Aux. Boiler MM 22.22.2018 Aux. boiler steam delivery valve steam leakey . B tightened. Now ok.
2 EM 21.12.2018 LO Sep # 03 : BJN pannel main switch missing A
3 03 IE EM/MM 13.12.2018 LO Sep # 03 : Lube oil comes through V6 valve. C Top part, hood sensor port cleaned.U/O
4 EM/MM 12.12.2018 LO Sep # 03- Separator motor taking more Ampere about 11.2 A. D Separator motor bearing chnaged. U/O
5 04 IE EM/MM 15.12.2018 Engine Load setting: 8700 KW ,Engine Load fluctuate ( 9052 to 8424 ) KW. C New gov. connector & MCM installed. U/O .
6 05 IE EM 21.12.2018 LO Sep # 05 : BJN pannel main switch missing A
7 07 IE EM 21.12.2018 LO Sep # 07 : BJN pannel main switch missing A
Pending
Work done by tightened. Need to check during TC
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C washing time.

2 Lighting EM 12.11.2018 Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).

3 03 IE EM 01.11.2018 Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.

Spare not available


1 09IE EM 14.12.2018 BJA panel cooling fan not running. B
2 12IE EM 14.12.2018 CFE panel cooling fan not running. A
3 LFO Feeder Unit EM 11.12.2018 Quick closing valve is in dismantle condition. D
4 HFO Feeder unit EM 22.11.2018 BJL Pannel viscometer B016 selector switch open , need to fix up. A
5 03 IE MM 16.10.2018 Pre - heating pump water leakage . B
6 04 IE EM 18.10.2018 Both bank TC rpm high about 29500. D
7 EM 22.10.2018 TC-B-bank rpm fluctuates. D
10IE
8 EM 04.10.2018 TC A-bank rpm 30000. A
9 04IE,05IE EM 04.04.2018 Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection. D
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working
10 All AC related issue EM 09.09.2017 (20.10.2017). A,B,C,D

11 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
12 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
13 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
14 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
15 HFO Storage tank EM HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
16 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
33598
25
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Razu Ahmmed
22.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks

1 Engine Hall # 02 MM 22.12.2018 Pocket Door beside DG # 12- Can not be shutoff properly. D Repaired
2 11 KV bus EM 18.12.2018 11 kV "B" bus Frequency sensor fault alarm. C Not solved ,U/M .
3 EM 21.12.2018 LO Sep # 03 : BJN pannel main switch missing A
4 03 IE EM/MM 13.12.2018 LO Sep # 03 : Lube oil comes through V6 valve. C Top part, hood sensor port cleaned.U/O
5 EM/MM 12.12.2018 LO Sep # 03- Separator motor taking more Ampere about 11.2 A. D Separator motor bearing chnaged. U/O
6 04 IE EM/MM 15.12.2018 Engine Load setting: 8700 KW ,Engine Load fluctuate ( 9052 to 8424 ) KW. C New gov. connector & MCM installed. U/O .
7 05 IE EM 21.12.2018 LO Sep # 05 : BJN pannel main switch missing A
8 06IE EM 22.12.2018 Turning gear engaged alarm not showing PLC . B Sensor changed
9 07 IE EM 21.12.2018 LO Sep # 07 : BJN pannel main switch missing A
10 10 IE MM 22.12.2018 One piece bolt broken of B05 unit crankcase door. D
Pending
Work done by tightened. Need to check during TC
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C
washing time.
Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01
2 Lighting EM 12.11.2018 nos) , 11 IE (02 nos) , 12 IE( 01 nos). D

3 03 IE EM 01.11.2018 Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.

Spare not available


1 09IE EM 14.12.2018 BJA panel cooling fan not running. B
2 12IE EM 14.12.2018 CFE panel cooling fan not running. A
3 LFO Feeder Unit EM 11.12.2018 Quick closing valve is in dismantle condition. D O - ring changed
4 HFO Feeder unit EM 22.11.2018 BJL Pannel viscometer B016 selector switch open , need to fix up. A
5 03 IE MM 16.10.2018 Pre - heating pump water leakage . B
6 04 IE EM 18.10.2018 Both bank TC rpm high about 29500. D
7 EM 22.10.2018 TC-B-bank rpm fluctuates. D
10IE
8 EM 04.10.2018 TC A-bank rpm 30000. A
9 04IE,05IE EM 04.04.2018 Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection. D
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working
10 All AC related issue EM 09.09.2017 (20.10.2017). A,B,C,D

11 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
12 04,10IE, 12 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
13 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
14 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
15 HFO Storage tank EM 02.07.15 HFO Storage tank #01&02 :- Level senor faulty. C&D

16 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C


33598
25
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Md. Mofizur Rahman.
23.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks

1 11 KV bus EM 18.12.2018 11 kV "B" bus Frequency sensor fault alarm. C Not solved ,U/M .
2 EM/MM 13.12.2018 LO Sep # 03 : Lube oil comes through V6 valve. C Top part, hood sensor port cleaned .Now ok
03IE
3 EM/MM 12.12.2018 LO Sep # 03- Separator motor taking more Ampere about 11.2 A. D Separator motor bearing changed. Now 10.5 A taking
4 04 IE EM/MM 15.12.2018 Engine Load setting: 8700 KW ,Engine Load fluctuate ( 9052 to 8424 ) KW. C New gov. connector & MCM installed. Now ok.
5 10 IE EM 23.12.2018 Fuel booster unit Mixing tank level low alarm. C Now ok
Pending
Work done by tightened. Need to check during TC
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C washing time.
Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01
2 Lighting EM 12.11.2018 nos) , 11 IE (02 nos) , 12 IE( 01 nos). D

3 03 IE EM 01.11.2018 Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D motor connection open.

Spare not available


1 03IE EM 21.12.2018 LO Sep # 03 : BJN pannel main switch missing A
2 05 IE EM 21.12.2018 LO Sep # 05 : BJN pannel main switch missing A
3 07 IE EM 21.12.2018 LO Sep # 07 : BJN pannel main switch missing A
4 09IE EM 14.12.2018 BJA panel cooling fan not running. B
5 12IE EM 14.12.2018 CFE panel cooling fan not running. A
6 HFO Feeder unit EM 22.11.2018 BJL Pannel viscometer B016 selector switch open , need to fix up. A
7 03 IE MM 16.10.2018 Pre - heating pump water leakage . B
8 04 IE EM 18.10.2018 Both bank TC rpm high about 29500. D
9 EM 22.10.2018 TC-B-bank rpm fluctuates. D
10IE
10 EM 04.10.2018 TC A-bank rpm 30000. A
11 04IE,05IE EM 04.04.2018 Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection. D
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working
12 All AC related issue EM 09.09.2017 (20.10.2017). A,B,C,D

13 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
14 04,10 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
15 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
16 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
17 HFO Storage tank EM HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
18 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
33598
25
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Md. Shofiqul Islam.
24.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks

1 11 KV bus EM 18.12.2018 11 kV "B" bus Frequency sensor fault alarm. C Not solved ,U/M .

New gov. connector & MCM installed. Not sloved. Load


2 04 IE EM/MM 15.12.2018 Engine Load setting: 8700 KW ,Engine Load fluctuate ( 8873 to 8448 ) KW. C fluctuation starts after 1.5 hrs of running.

Pending

1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C Work done by tightened. Need to check during TC
washing time.
Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01
2 Lighting EM 12.11.2018 D
nos) , 11 IE (02 nos) , 12 IE( 01 nos).

3 03 IE EM 01.11.2018 Radiator fan F7 motor's breaker tripped and subsequently radiator frequency converter tripped due to over current. D Re-winding motor install.

Spare not available


1 LFO Feeder Unit EM 24.12.2018 Air leakage from the solenoid of quick closing valve. D
2 03IE EM 21.12.2018 LO Sep # 03 : BJN pannel main switch missing A
3 05 IE EM 21.12.2018 LO Sep # 05 : BJN pannel main switch missing A
4 07 IE EM 21.12.2018 LO Sep # 07 : BJN pannel main switch missing A
5 09IE EM 14.12.2018 BJA panel cooling fan not running. B
6 12IE EM 14.12.2018 CFE panel cooling fan not running. A
7 HFO Feeder unit EM 22.11.2018 BJL Pannel viscometer B016 selector switch open , need to fix up. A
8 03 IE MM 16.10.2018 Pre - heating pump water leakage . B
9 04 IE EM 18.10.2018 Both bank TC rpm high about 29500. D
10 EM 22.10.2018 TC-B-bank rpm fluctuates. D
10IE
11 EM 04.10.2018 TC A-bank rpm 30000. A
12 04IE,05IE EM 04.04.2018 Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection. D
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working
13 All AC related issue EM 09.09.2017 (20.10.2017). A,B,C,D

14 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
15 04,10 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
16 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
17 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C

18 HFO Storage tank EM 12.03.15 HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
19 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Razu Ahmmed
25.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks

1 11 KV bus EM 18.12.2018 11 kV "B" bus Frequency sensor fault alarm. C Not solved ,U/M .
Pump side screw & coupling rubber pad, mechanical
2 02 IE MM 25.12.2018 HFO Leakage from booster pump mechanical seal. C seal replaced.

3 04 IE EM/MM 15.12.2018 Engine Load setting: 8700 KW ,Engine Load fluctuate ( 8873 to 8448 ) KW. C New gov. connector & MCM installed. Not sloved. Load
fluctuation starts after 1.5 hrs of running.

4 06 IE EM/MM 25.12.2018 Turning Gear motor abnormal sound C done


Pending
Work done by tightened. Need to check during TC
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C washing time.
Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01
2 Lighting EM 12.11.2018 nos) , 11 IE (02 nos) , 12 IE( 01 nos). D

Spare not available


1 LFO Feeder Unit EM 24.12.2018 Air leakage from the solenoid of quick closing valve. D
2 03IE EM 21.12.2018 LO Sep # 03 : BJN pannel main switch missing A
3 05 IE EM 21.12.2018 LO Sep # 05 : BJN pannel main switch missing A
4 07 IE EM 21.12.2018 LO Sep # 07 : BJN pannel main switch missing A
5 09IE EM 14.12.2018 BJA panel cooling fan not running. B
6 12IE EM 14.12.2018 CFE panel cooling fan not running. A
7 HFO Feeder unit EM 22.11.2018 BJL Pannel viscometer B016 selector switch open , need to fix up. A
8 03 IE MM 16.10.2018 Pre - heating pump water leakage . B
9 04 IE EM 18.10.2018 Both bank TC rpm high about 29500. D
10 EM 22.10.2018 TC-B-bank rpm fluctuates. D
10IE
11 EM 04.10.2018 TC A-bank rpm 30000. A
12 04IE,05IE EM 04.04.2018 Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection. D
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working
13 All AC related issue EM 09.09.2017 (20.10.2017). A,B,C,D

14 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
15 04,10 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
16 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
17 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
18 HFO Storage tank EM HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
19 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Md. Mofizur Rahman.
26.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks

1 Hydrophore unit MM 26.12.2018 Pump #02: Water leakage from delivary pipe line after valve. C Heat tape & clamp added. But not sloved.

A new gov. of 04 IE installed in test purpose to check


2 01 IE EM/MM 27.12.2018 Engine Load fluctuates from 8600 KW to 8300 KW. ( Load Setting -8400 KW) D load fluctuation. These new gov. gave load fluctuation
of 8873 KW to 8448 KW on 04 IE.

3 04 IE EM/MM 27.12.2018 ESM overspeed shutdown. D

Pending

1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C Work done by tightened. Need to check during TC
washing time.

2 Lighting EM 12.11.2018 Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 nos) , D
11 IE (02 nos) , 12 IE( 01 nos).
Spare not available
1 11 KV bus EM 18.12.2018 11 kV "B" bus Frequency sensor fault alarm. C
2 LFO Feeder Unit EM 24.12.2018 Air leakage from the solenoid of quick closing valve. D
3 03IE EM 21.12.2018 LO Sep # 03 : BJN pannel main switch missing A
4 05 IE EM 21.12.2018 LO Sep # 05 : BJN pannel main switch missing A
5 07 IE EM 21.12.2018 LO Sep # 07 : BJN pannel main switch missing A
6 09IE EM 14.12.2018 BJA panel cooling fan not running. B
7 12IE EM 14.12.2018 CFE panel cooling fan not running. A
8 HFO Feeder unit EM 22.11.2018 BJL Pannel viscometer B016 selector switch open , need to fix up. A
9 03 IE MM 16.10.2018 Pre - heating pump water leakage . B
10 04 IE EM 18.10.2018 Both bank TC rpm high about 29500. D
11 EM 22.10.2018 TC-B-bank rpm fluctuates. D
10IE
12 EM 04.10.2018 TC A-bank rpm 30000. A
13 04IE,05IE EM 04.04.2018 Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection. D
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working (20.10.2017).
14 All AC related issue EM 09.09.2017 A,B,C,D

15 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
16 04,10 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
17 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
18 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
19 HFO Storage tank EM HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
20 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
S M Mamunur Rahman
27.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks

1 Hydrophore unit MM 26.12.2018 Pump #02: Water leakage from delivary pipe line after valve. C Heat tape & clamp added. But not sloved.
MM 27.12.2018 Fuel flow meter line choked. D Line cleaned .

01 IE A new gov. of 04 IE installed in test purpose to check


2 EM/MM 27.12.2018 Engine Load fluctuates from 8600 KW to 8300 KW. ( Load Setting -8400 KW) D load fluctuation. These new gov. gave load fluctuation
of 8873 KW to 8448 KW on 04 IE.

A overhauled gov. of 01 IE installed & MCM interchange


3 04 IE EM/MM 27.12.2018 ESM overspeed shutdown. D with DG# 01, & Engine test run carried out . Now ok.
(U/O)

Pending
Work done by tightened. Need to check during TC
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C
washing time.
Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 nos) ,
2 Lighting EM 12.11.2018 D
11 IE (02 nos) , 12 IE( 01 nos).
Spare not available
1 11 KV bus EM 18.12.2018 11 kV "B" bus Frequency sensor fault alarm. C
2 LFO Feeder Unit EM 24.12.2018 Air leakage from the solenoid of quick closing valve. D
3 03IE EM 21.12.2018 LO Sep # 03 : BJN pannel main switch missing A
4 05 IE EM 21.12.2018 LO Sep # 05 : BJN pannel main switch missing A
5 07 IE EM 21.12.2018 LO Sep # 07 : BJN pannel main switch missing A
6 09IE EM 14.12.2018 BJA panel cooling fan not running. B
7 12IE EM 14.12.2018 CFE panel cooling fan not running. A
8 HFO Feeder unit EM 22.11.2018 BJL Pannel viscometer B016 selector switch open , need to fix up. A
9 03 IE MM 16.10.2018 Pre - heating pump water leakage . B
10 04 IE EM 18.10.2018 Both bank TC rpm high about 29500. D
11 EM 22.10.2018 TC-B-bank rpm fluctuates. D
10IE
12 EM 04.10.2018 TC A-bank rpm 30000. A
13 04IE,05IE EM 04.04.2018 Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection. D
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working (20.10.2017).
14 All AC related issue EM 09.09.2017 A,B,C,D

15 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
16 04,10 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
17 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
18 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
19 HFO Storage tank EM HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
20 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Razu Ahmmed
28.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks

1 01IE EM/MM 27.12.2018 Engine Load fluctuates from 8600 KW to 8300 KW. ( Load Setting -8400 KW) D A new gov. of 04 IE installed & MCM change with DG#
04 but load fluctuates from 8673 KW to 8181 KW.

2 10IE EM 28.12.2018 LO Sep # 10 : Top tubelight does not illuminate . C New tube light installed.
Pending
Work done by tightened. Need to check during TC
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C
washing time.

2 Lighting EM 12.11.2018 Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 nos) , D
11 IE (02 nos) , 12 IE( 01 nos).
Spare not available
1 11 KV bus EM 18.12.2018 11 kV "B" bus Frequency sensor fault alarm. C
2 LFO Feeder Unit EM 24.12.2018 Air leakage from the solenoid of quick closing valve. D O Ring change.
3 03IE EM 21.12.2018 LO Sep # 03 : BJN pannel main switch missing A
4 05 IE EM 21.12.2018 LO Sep # 05 : BJN pannel main switch missing A
5 07 IE EM 21.12.2018 LO Sep # 07 : BJN pannel main switch missing A
6 09IE EM 14.12.2018 BJA panel cooling fan not running. B
7 12IE EM 14.12.2018 CFE panel cooling fan not running. A
8 HFO Feeder unit EM 22.11.2018 BJL Pannel viscometer B016 selector switch open , need to fix up. A
9 03 IE MM 16.10.2018 Pre - heating pump water leakage . B
10 04 IE EM 18.10.2018 Both bank TC rpm high about 29500. D
11 EM 22.10.2018 TC-B-bank rpm fluctuates. D
10IE
12 EM 04.10.2018 TC A-bank rpm 30000. A
13 04IE,05IE EM 04.04.2018 Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection. D
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working (20.10.2017).
14 All AC related issue EM 09.09.2017 A,B,C,D

15 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
16 04,10 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
17 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
18 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C

19 HFO Storage tank EM 12.03.15 HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
20 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
S M Mamunur Rahman
29.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks

1 Feeder unit MM 29.12.2018 Feeder unit diaphragm sludge pump not properly pumping . B
2 Transfer pump unit EM 29.12.2018 Control panel BJG 902 alarm comes several times and suddenly transfer pump stopped . B Check, U/O.
3 EM 29.12.2018 Turning gear motor trip during engine turning time. C
01IE A new gov. of 04 IE installed & MCM change with DG#
4 EM/MM 27.12.2018 Engine Load fluctuates from 8600 KW to 8300 KW. ( Load Setting -8400 KW) D
04 but load fluctuates from 8673 KW to 8181 KW.

5 03IE EM 29.12.2018 CA temp. engine inlet sensor fault . B


6 04IE MM 29.12.2018 Air leakage from steam shut off v/v of booster unit. C Air regulator changed .
7 05 IE MM 29.12.2018 Booster unit fuel heater steam by-pass v/v does not work properly. C Pipe line clean.
Pending
Work done by tightened. Need to check during TC
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C
washing time.
Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 nos) ,
2 Lighting EM 12.11.2018 D
11 IE (02 nos) , 12 IE( 01 nos).
Spare not available
1 11 KV bus EM 18.12.2018 11 kV "B" bus Frequency sensor fault alarm. C
2 03IE EM 21.12.2018 LO Sep # 03 : BJN pannel main switch missing A
3 05 IE EM 21.12.2018 LO Sep # 05 : BJN pannel main switch missing A
4 07 IE EM 21.12.2018 LO Sep # 07 : BJN pannel main switch missing A
5 09IE EM 14.12.2018 BJA panel cooling fan not running. B
6 12IE EM 14.12.2018 CFE panel cooling fan not running. A
7 HFO Feeder unit EM 22.11.2018 BJL Pannel viscometer B016 selector switch open , need to fix up. A
8 03 IE MM 16.10.2018 Pre - heating pump water leakage . B
9 04 IE EM 18.10.2018 Both bank TC rpm high about 29500. D
10 EM 22.10.2018 TC-B-bank rpm fluctuates. D
10IE
11 EM 04.10.2018 TC A-bank rpm 30000. A
12 04IE,05IE EM 04.04.2018 Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection. D
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working (20.10.2017).
13 All AC related issue EM 09.09.2017 A,B,C,D

14 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
15 04,10 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
16 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
17 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
18 HFO Storage tank EM HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
19 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
S M Mamumur Rahman
30.12.2018
SL no. Equip. Name Dept. Request Date Problem list/Maintenance request Group Remarks

1 Boiler feed pump MM 30.12.2018 Boiler feed pump-1 delivery line press. gauge water leakage . B Tighting & Thread tape used.
2 Feeder unit MM 29.12.2018 Feeder unit diaphragm sludge pump not properly pumping . B Flushing time Change (2:30 To 3:30) Minites.
3 EM 29.12.2018 Turning gear motor trip during engine turning time. C U/M
01IE A new gov. of 04 IE installed & MCM change with DG#
4 EM/MM 27.12.2018 Engine Load fluctuates from 8600 KW to 8300 KW. ( Load Setting -8400 KW) D
04 but load fluctuates from 8673 KW to 8181 KW.

5 02IE EM/MM 30.12.2018 Pre lube pump abnormal sound & vibration. C Bearing change & Housing sim install.
6 03IE EM 29.12.2018 CA temp. engine inlet sensor fault . B Found Normal.
7 10 IE EM 30.12.2018 Module rack fault alarm comes several times. B Tighting.
Pending
Work done by tightened. Need to check during TC
1 02IE & 09IE MM 15.09.2018 Water leakage through exhaust common bellows last flange during TC washing time. A+C
washing time.
Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 nos) ,
2 Lighting EM 12.11.2018 D
11 IE (02 nos) , 12 IE( 01 nos).
Spare not available
1 11 KV bus EM 18.12.2018 11 kV "B" bus Frequency sensor fault alarm. C
2 03IE EM 21.12.2018 LO Sep # 03 : BJN pannel main switch missing A
3 05 IE EM 21.12.2018 LO Sep # 05 : BJN pannel main switch missing A
4 07 IE EM 21.12.2018 LO Sep # 07 : BJN pannel main switch missing A
5 09IE EM 14.12.2018 BJA panel cooling fan not running. B
6 12IE EM 14.12.2018 CFE panel cooling fan not running. A
7 HFO Feeder unit EM 22.11.2018 BJL Pannel viscometer B016 selector switch open , need to fix up. A
8 03 IE MM 16.10.2018 Pre - heating pump water leakage . B
9 04 IE EM 18.10.2018 Both bank TC rpm high about 29500. D
10 EM 22.10.2018 TC-B-bank rpm fluctuates. D
10IE
11 EM 04.10.2018 TC A-bank rpm 30000. A
12 04IE,05IE EM 04.04.2018 Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection. D
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working (20.10.2017).
13 All AC related issue EM 09.09.2017 A,B,C,D

14 Engine hall-02 EM 02.11.2017 Common surge arrestor above stack top has been broken. B
15 04,10 IE MM 30.03.2017 Exhaust Emission stack bellows cracked. C+D
16 DG # 06,07 EM 26.07.2016 Main cabinet parameter faulty(Start air pressure ) C
17 DG#01,05, EM 26.07.2016 Main cabinet parameter faulty(Start air pressure & control air pressure ) C
12.03.15
18 HFO Storage tank EM HFO Storage tank #01&02 :- Level senor faulty. C&D
02.07.15
19 HFO Day Tank MM 22.12.2017 Local level indicator scale faulty. C
Orion Power Meghnaghat L
Current & Pending Maintenance R
Md. Shofiqul Islam
31.12.2018
SL no. Equip. Name Dept. Request Date

1 01IE EM/MM 27.12.2018

2 02IE EM 29.12.2018
Pending

1 02IE & 09IE MM 15.09.2018

2 Lighting EM 12.11.2018

Spare not available


1 11 KV bus EM 18.12.2018
2 03IE EM 21.12.2018
3 05 IE EM 21.12.2018
4 07 IE EM 21.12.2018
5 09IE EM 14.12.2018
6 12IE EM 14.12.2018
7 HFO Feeder unit EM 22.11.2018
8 03 IE MM 16.10.2018
9 04 IE EM 18.10.2018
10 EM 22.10.2018
10IE
11 EM 04.10.2018
12 04IE,05IE EM 04.04.2018

13 All AC related issue EM 09.09.2017

14 Engine hall-02 EM 02.11.2017


15 04,10 IE MM 30.03.2017
16 DG # 06,07 EM 26.07.2016
17 DG#01,05, EM 26.07.2016

18 HFO Storage tank EM 12.03.15


02.07.15
19 HFO Day Tank MM 22.12.2017
Orion Power Meghnaghat Ltd.
Current & Pending Maintenance Request
Md. Shofiqul Islam
31.12.2018
Problem list/Maintenance request

Engine Load fluctuates from 8600 KW to 8300 KW. ( Load Setting -8400 KW)

Turning gear motor trip during engine turning time.


Pending

Water leakage through exhaust common bellows last flange during TC washing time.

Engine Hall overhead light does not illuminate of following engine- 01 IE(01 nos), 05 IE( 01 nos), 06 IE (01 nos), 07 IE( 01 nos) ,
11 IE (02 nos) , 12 IE( 01 nos).
Spare not available
11 kV "B" bus Frequency sensor fault alarm.
LO Sep # 03 : BJN pannel main switch missing
LO Sep # 05 : BJN pannel main switch missing
LO Sep # 07 : BJN pannel main switch missing
BJA panel cooling fan not running.
CFE panel cooling fan not running.
BJL Pannel viscometer B016 selector switch open , need to fix up.
Pre - heating pump water leakage .
Both bank TC rpm high about 29500.
TC-B-bank rpm fluctuates.
TC A-bank rpm 30000.
Oil leakage from DE & NDE side of Alternator (Varistor cover side). Need inspection.
Control room A/C #05 not working, Warehouse safety store one AC out of order, Change room AC is not working (20.10.2017).

Common surge arrestor above stack top has been broken.


Exhaust Emission stack bellows cracked.
Main cabinet parameter faulty(Start air pressure )
Main cabinet parameter faulty(Start air pressure & control air pressure )

HFO Storage tank #01&02 :- Level senor faulty.

Local level indicator scale faulty.


Group Remarks

A new gov. of 04 IE installed & MCM change with DG#


D 04 but load fluctuates from 8673 KW to 8181 KW. ( on
31.12.2018 Governor Interchange Between DG# 01 &
DG# 07 ) U/O.

C Motor install.

Work done by tightened. Need to check during TC


A+C washing time.

C
A
A
A
B
A
A
B
D
D
A
D

A,B,C,D

B
C+D
C
C

C&D