Professional Documents
Culture Documents
DXM Digital
Heat Pump Controllers
Application, Operation,
& Maintenance
97B0003N13
Rev.: March 30, 2017
WATER-SOURCE HEAT PUMPS
Random Start S S S
Advanced Features
Intelligent Reset S S S
Dehumidistat Input S S S
CE Approval S S S
DXM-Lon = DXM with LonMark Module DXM-MPC = DXM with MPC Module
* = Check with your Factory Representative for model availability MPC = Multiple ProtoCol (BACNET, N2, Modbus)
† = Compatible with our thermostats. For customer supplied thermostat, check with Controls Engineering Department for approval.
2
THE SMART SOLUTION FOR ENERGY EFFICIENCY
DXM Unit Control
R e v. : M a r c h 3 0 , 2 0 1 7
3
WATER-SOURCE HEAT PUMPS
6LJ
6LJ
&
&
&
3 &RP
5 3 3 )DQ(QDEOH
)DQ(QDEOH
<
&RP &RP 9DF
9DF
<
: 12
2:
&RP
*
5 )DQ6SHHG
9DF
&
$/ 12 1&
$/
5 $ODUP -:
5HOD\ $/'U\ 0LFUR 6WDWXV
16% +3
8 +3
&
7HVW /3
(6' /3
295 )DXOW )3
+
3 )3
)3 )DFWRU\ORZ
$ )3 YROWDJHPROH[
FRQQHFWLRQIRU
59 XQLWKDUQHVV
0LFUR 59 59
5HOD\
8 &2
&2
5
3 )DFWRU\ORZ
12
7HVW-XPSHUV YROWDJHPROH[
1& 9GF FRQQHFWLRQIRU
-:)3/RZ7HPS HOHFWULFKHDW
&20 KDUQHVV
-:)3/RZ7HPS (+
12 -:/31RUP2SHQ (+
1& $FF 3
)DFWRU\ 8VH
µVWDQGRII
5 &&*
3 &RPS
$FF 5HOD\
5HOD\ &&
6 6
8VHPRXQWLQJ
VFUHZVVKHHW
PHWDOVFUHZµORQJ
4
THE SMART SOLUTION FOR ENERGY EFFICIENCY
DXM Unit Control
R e v. : M a r c h 3 0 , 2 0 1 7
DXM Controls
Field Selectable Inputs Alarm Relay Setting - Jumper 4 (JW4-AL2 Dry) provides
Test Mode - Test Mode allows the service personnel to field selection of Alarm Relay terminal AL2 to be
check the operation of the control in a timely manner. By jumpered to 24VAC or to be dry (no connection).
momentarily shorting the test terminals, the DXM Control Not Clipped = AL2 connected to R.
enters a 20 minute Test Mode period in which all time Clipped = AL2 dry contacts (no connection).
delays are sped up 15 times. During Test Mode, the test
LED will turn on. For diagnostic ease at the thermostat, Low Pressure Normally Open - Jumper 1 (JW1-LP Norm
the Alarm Relay will also cycle during Test Mode. The Open) Provides field selection for low pressure input to
Alarm Relay will cycle on and off similar to the fault LED be normally closed or normally open.
to indicate a code representing the last fault, at the Not Clipped = LP normally closed.
thermostat. Clipped = LP normally open.
Note: Code 1 indicates there is no fault in memory;
stated differently, the control has not faulted since DIP Switches
the last power-down to power-up sequence.
Note: In the following field configuration options,
Test Mode can be exited by shorting the test terminals DIP switches should only be moved when power is
for 3 seconds. Test Mode can also be entered and exited removed from the DXM Control to ensure proper
by cycling the G input, 3 times within a 60 second time operation.
period.
DIP Package #1 (S1)
During Test Mode, the control monitors to see if the DIP Package #1 is 8 position and provides the following
LT1 and LT2 thermistors are in the appropriate place. If setup selections.
the control is in Test Mode, the control will lockout, with
Code 9, after 30 seconds if: DIP 1.1: Unit Performance Sentinel Disable - Provides
a) the compressor is On in Cooling Mode and the LT1 field selection to disable the UPS feature.
sensor is colder than the LT2 sensor. or, On = Enabled. Off = Disabled.
b) the compressor is On in Heating Mode and the LT2
sensor is colder than the LT1 sensor. DIP 1.2: Compressor Relay Staging Operation - Provides
selection of Compressor Relay staging operation. The
Retry Mode - If the control is attempting a retry of a Compressor Relay can be selected to turn on with Stage
fault, the status LED will slow flash (slow flash = one flash 1 or Stage 2 call from the thermostat. This is used with
every 2 seconds) to indicate the control is in process of Dual Stage units (2 compressors where 2 DXM Controls
retrying. are being used) or with master/slave applications. In
Note: In the following field configuration options, master/slave applications, each compressor and fan will
jumper wires should be clipped ONLY when power is stage according to its appropriate DIP 1.2. If set to stage
removed from the DXM Control. 2, the compressor will have a 3 second on-delay before
energizing during a Stage 2 demand. Also, if set for stage
Note: Jumpers 2 & 3 must not be clipped prior to 2, the Alarm Relay will NOT cycle during Test Mode.
adding antifreeze to the water loop. Antifreeze On = Stage 1. Off = Stage 2.
protection to 15°F required. Clipping JW2 & JW3
without antifreeze may result in freeze damage and DIP 1.3: Thermostat Type (Heat/Cool) - Provides
will void the unit warranty. selection of thermostat type. Heat Pump or Heat/Cool
thermostats can be selected. When in Heat/Cool Mode,
Water Coil Low Temperature Cut-Out Limit Setting - Y1 is input call for Cooling Stage 1, Y2 is input call for
Jumper 3 (JW3-LT1 Low Temp) provides field selection of Cooling Stage 2, W1 is input call for Heating Stage 1,
temperature limit setting for LT1 to be 30°F or 10°F. and O/W2 is input call for Heating Stage 2. In Heat Pump
Not Clipped = 30°F. Clipped = 10°F. Mode, Y1 is input call for Compressor Stage 1, Y2 is input
call for Compressor Stage 2, W1 is input call for Heating
Air Coil Low Temperature Cut-Out Limit Setting - Stage 3 or Emergency Heat, and O/W2 is the input call
Jumper 2 (JW2-LT2 Low Temp) provides field selection of for RV (heating or cooling dependent upon DIP 1.4).
temperature limit setting for LT2 to be 30°F or 10°F. On = Heat Pump. Off = Heat/Cool.
Not Clipped = 30°F. Clipped = 10°F.
5
WATER-SOURCE HEAT PUMPS
DIP 1.4: Thermostat Type (O/B) - Provides selection On = normal. Off = Boilerless operation.
of thermostat type. Heat pump thermostats with “O” DIP 1.8: Boilerless Changeover Temperature - Provides
output on with Cooling or “B” output on with Heating selection of boilerless changeover temperature setpoint.
can be selected. On = 50°F. Off = 40°F.
On = HP Stat with O output with cooling. Off = HP Stat
with B output with heating. DIP Package #2 (S2)
DIP Package #2 is 8 position and provides the following
DIP 1.5: Dehumidification Mode - Provides selection setup selections.
of normal or Dehumidification Fan Mode. In
Dehumidification Mode, the fan speed relay will remain DIP 2.1: Accessory1 relay personality - Provides selection
off during Cooling Stage 2. In Normal Mode, the fan of Acc1 relay personality. See Table 2.
speed relay will turn on during Cooling Stage 2. DIP 2.2: Accessory1 relay personality - Provides selection
On = Normal Fan Mode. Off = Dehumidification Mode. of Acc1 relay personality. See Table 2.
DIP 2.3: Accessory1 relay personality - Provides selection
DIP 1.6: DDC Output at EH2 - DIP Switch 1.6 provides of Acc1 relay option. See Table 2.
selection for DDC operation. If set to DDC Output at DIP 2.4: Accessory2 relay personality - Provides selection
EH2, the EH2 terminal will continuously output the last of Acc2 relay personality. See Table 3.
fault code of the controller. If set to EH2 normal, then the DIP 2.5: Accessory2 relay personality - Provides selection
EH2 will operate as standard electric heat output. of Acc2 relay personality. See Table 3.
On = EH2 Normal. Off = DDC Output at EH2. DIP 2.6: Accessory2 relay personality - Provides selection
of Acc2 relay option. See Table 3.
DIP 1.7: Boilerless Operation - Provides selection DIP 2.7: Auto Dehumidification Fan Mode or High Fan
of Boilerless Operation. In Boilerless Mode, only the Mode - Provides selection of Auto Dehumidification
compressor is used for Heating Mode when LT1 is above Fan Mode or High Fan Mode. In Auto Dehumidification
the temperature specified by the setting of DIP 1.8. If DIP Mode, the Fan Speed relay will remain off during Cooling
1.8 is set for 50°F, then the compressor is used for heating Stage 2 IF the H input is active. In High Fan Mode, the
as long as LT1 is above 50°F. Below 50°F, the compressor Fan Enable and Fan Speed relays will turn on when the H
is not used and the control goes into Emergency Heat input is active.
Mode, staging on EH1 and EH2 to provide heating.
On = Auto Dehumidification Mode. Off = High Fan Mode.
If a thermal switch is being used in place of the LT1
thermistor, then only the compressor will be used for DIP Switch 2.8: Factory Setting - Normal position is On.
Heating Mode when the LT1 terminals are closed. If the Do not change selection unless instructed to do so by
LT1 terminals are open, then the compressor is not used the Factory.
and the control goes into Emergency Heat Mode.
Table 1: Accessory Relay 1 Configuration Safety Features
The following safety features are provided to protect
DIP 2.1 DIP 2.2 DIP 2.3 ACC1 Relay Option
the compressor, heat exchangers, wiring and other
ON ON ON Cycle with fan
components from damage caused by operation outside
OFF ON ON Digital NSB
of design conditions.
ON OFF ON Water Valve - Slow opening
ON ON OFF OAD
Anti-Short Cycle Protection - The control features a 5
OFF OFF OFF Reheat Option - Humidistat
minute anti-short cycle protection for the compressor.
OFF ON OFF Reheat Option - Dehumidistat
Note: The 5 minute anti-short cycle also occurs at
OFF OFF ON Hydronic Economizer
power up.
All other DIP combinations are invalid
Table 2: Accessory Relay 2 Configuration Random Start - The control features a 5-80 second
DIP 2.4 DIP 2.5 DIP 2.6 ACC2 Relay Option random start upon power up. The random start delay will
ON ON ON Cycle with compressor be present after a control power up and after returning
OFF ON ON Digital NSB from Night Setback or Emergency Shutdown modes.
ON OFF ON Water Valve - Slow Opening Extended Compressor Operation Monitoring - If the
ON ON OFF OAD compressor relay has been on for 4 continuous hours,
All other DIP combinations are invalid then the control will automatically turn off the compressor
6
THE SMART SOLUTION FOR ENERGY EFFICIENCY
DXM Unit Control
R e v. : M a r c h 3 0 , 2 0 1 7
relay and wait the short cycle protection time. All Example: 2 quick flashes, 10-sec pause, 2 quick
appropriate safeties including the LP will be monitored flashes, 10-sec. pause, etc.
during the off time. If all operation is normal, and if the
compressor demand is still present, the control will turn Low Pressure Switch - The Low Pressure Switch must be
the compressor back on. open and remain open for 30 continuous seconds during a
compressor “on” cycle to be recognized as a Low Pressure
Fault Retry - In Fault Retry Mode, the Status LED begins fault. If the low pressure switch is open for 30 seconds
slow flashing to signal that the control is trying to recover prior to compressor power up it will be considered a
from a fault input. The Fault LED will also begin flashing low pressure (loss of charge) fault. The Low Pressure
a code representing the last fault, which occurred. The Switch input is bypassed for the initial 120 seconds of a
DXM Control will stage off the outputs and then “try compressor run cycle. The Fault LED will immediately
again” to satisfy the thermostat call for compressor. begin flashing Code 3 when a Low Pressure Fault occurs.
Once the thermostat input calls are satisfied, the control
will continue on as if no fault occurred. If 3 consecutive Low Pressure Lockout Code = 3
faults occur without satisfying the thermostat call for
compressor, then the control will go to Lockout Mode. Water Coil Low Temperature Cut-Out Limit (LT1) - The
The last fault causing the lockout will be stored in control will recognize an LT1 fault, during a compressor
memory and is displayed by the Fault LED. run cycle if:
Note: LT1 and LT2 faults are factory set for for one a) the thermistor temperature is below the selected low
try, so there will be no “retries” for LT1 and LT2 faults. temperature protection limit setting, AND
The control will only try one time for these faults. b) the thermistor temperature is rising (getting warmer)
at a rate LESS than 2°F per 30 second time period.
Lockout - In Lockout Mode, the Status LED will
begin fast flashing. The Fault LED will be flashing a The LT1 input is bypassed for the initial 120 seconds of
code representing the last fault, which occurred that a compressor run cycle. The Fault LED will immediately
caused the lockout. The compressor relay is turned off begin flashing Code 4 when a LT1 Fault occurs.
immediately. Lockout Mode can be soft reset via the
thermostat by removing the call for compressor, or can LT1 Lockout Code = 4
be hard reset via the disconnect. The last fault causing
the lockout will be stored in memory and is displayed by Air Coil Low Temperature Cut-Out Limit (LT2) - The
the Fault LED. control will recognize an LT2 fault, during a compressor
run cycle if:
Lockout with Emergency Heat - If the DXM is a) the thermistor temperature is below the selected low
configured for Heat Pump thermostat Mode (see DIP 1.3), temperature protection limit setting, AND
the DXM is in Lockout Mode, and the W input becomes b) the thermistor temperature is rising (getting warmer)
active, then Emergency Heat Mode will occur during at a rate LESS than 2°F per 30 second time period.
Lockout.
The LT2 input is bypassed for the initial 120 seconds of
a compressor run cycle. The Fault LED will immediately
CAUTION! begin flashing Code 5 when a LT2 Fault occurs.
CAUTION! Do not restart units without inspection and
remedy of faulting condition. Equipment damage may occur. LT2 Lockout Code = 5
7
WATER-SOURCE HEAT PUMPS
Over/Under Voltage Shutdown - An Over/Under Swapped LT1/LT2 Thermistors - During Test Mode, the
Voltage condition exists when the control voltage is control monitors to see if the LT1 and LT2 thermistors are
outside the range of 18VAC to 31.5VAC. Over/Under in the appropriate place. If the control is in Test Mode,
Voltage Shutdown is self-resetting in that if the voltage the control will lockout, with Code 9, after 30 seconds if:
comes back within range of 18.5VAC to 31VAC for at least a) the compressor is On in Cooling Mode and the LT1
0.5 seconds, then normal operation is restored. This is sensor is colder than the LT2 sensor. Or,
not considered a fault or lockout. If the DXM is in over/ b) the compressor is On in Heating Mode and the LT2
under voltage shutdown for 15 minutes, the Alarm Relay sensor is colder than the LT1 sensor.
will close.
Swapped LT1/LT2 Thermistor Code = 9.
Over/Under Voltage Shutdown Code = 7
ESD - The ESD (Emergency Shut Down) Mode is utilized
Unit Performance Sentinel-UPS (patent pending) - The when the ERV (Energy Recovery Ventilator) option is
UPS feature warns when the heat pump is operating applied to an TRE series rooftop unit to indicate an ERV
inefficiently. A UPS condition exists when: fault. A contact closure at the ERV unit will connect
a) In Heating Mode with compressor energized, if LT2 is common to the ESD terminal, which will shut down the
greater than 125°F for 30 continuous seconds, or rooftop/ERV units. The green status light will flash code
b) In Cooling Mode with compressor energized, if LT1 3 when the unit is in ESD Mode. The ESD Mode can also
is greater than 125°F for 30 continuous seconds, OR be enabled from an external common signal to terminal
LT2 is less than 40°F for 30 continuous seconds. ESD (see “Thermostat Inputs” section for details).
If a UPS condition occurs, the control will immediately go ESD Mode = code 3 (green “status” LED)
to UPS warning. The status LED will remain on as if the
control is in Normal Mode. (see "LED and Alarm Relay Diagnostic Features - The Status LED and Fault LED on
Operation Table"). Outputs of the control, excluding the DXM Control advises service personnel of the current
Fault LED and Alarm Relay, will NOT be affected by UPS. status of the DXM Control. The Status LED will indicate
The UPS condition cannot occur during a compressor off the current mode that the DXM Control is in. The Fault
cycle. During UPS warning, the Alarm Relay will cycle on LED will ALWAYS flash a code representing the LAST fault
and off. The cycle rate will be On for 5 seconds, Off for 25 in memory. If there is no fault on memory, then the Fault
seconds, On for 5 seconds, Off for 25 seconds, etc. LED will flash Code 1. See Table 4 for a complete listing
of codes.
Unit Performance Sentinel Warning Code = 8
8
THE SMART SOLUTION FOR ENERGY EFFICIENCY
DXM Unit Control
R e v. : M a r c h 3 0 , 2 0 1 7
Heating Stage 2 - In Heating Stage 2 Mode, the Fan Night Low Limit (NLL) Staged Heating - In NLL Staged
Enable and Compressor relays remain on. The Fan Speed Heating Mode, the OVR input becomes active and is
relay is turned on immediately. The Fan Speed relay is recognized as a call for Heating (OVR is an alternate means
turned off immediately when the Heating Stage 2 demand of calling for Heating Mode). In NLL Staged Heating
is removed. The control reverts to Heating Stage 1 Mode. Mode, the control will immediately go into Heating Stage
If there is a Master/Slave situation or a Dual Compressor 1 Mode with an additional 30 minutes of NLL demand,
situation, all Compressor relays and related functions will the control will go into Heating Stage 2 Mode. With an
track with their associated DIP1.2. additional 30 minutes of NLL demand, the control will go
into Heating Stage 3 Mode.
Heating Stage 3 - In Heating Stage 3 Mode, the Fan
Enable, Fan Speed and Compressor relays will remain on. Special DXM Application Notes - Generally the following
EH1 output is turned on immediately. With continuing applications are based upon configuring the accessory
Heating Stage 3 demand, EH2 will turn on after 10 minutes. relays.
EH1 and EH2 are turned off immediately when the Heating
Stage 3 demand is removed. The control reverts to Heating Cycle with Fan - If Accessory relay 1 is configured to
Stage 2 Mode. During Heating Stage 3 Mode, EH2 will be “cycle with fan”, Accessory relay 1 will be on any time the
off (or will turn off if already on) if LT1 is greater than 45°F Fan Enable relay is on.
AND LT2 is greater than 110°F (LT2 greater than 110°F
includes the condition that LT2 Cycle with Compressor - If Accessory relay 2 is
is shorted). This condition will have a 30-second recognition configured to “cycle with compressor”, Accessory relay 2
time. During Heating Stage 3 Mode, EH1, EH2, Fan Enable will be on any time the Compressor relay is on.
and Fan Speed will be on if the G input is not active.
9
WATER-SOURCE HEAT PUMPS
Digital Night Setback - If an Accessory relay is Dehumidification Operation with DXM - A heat pump
configured for Digital NSB, the Accessory relay will be on equipped with a dedicated Dehumidification Mode can
any time the NSB input is connected to Ground “C”. operate in three modes, cooling, cooling with reheat, and
Note: If there are no Accessory relays configured heating. The cooling/heating modes are like any of our
for Digital NSB, then the NSB and OVR inputs are other WSHP. The reversing valve (“O” signal) is energized
automatically configured for “mechanical” operation. in cooling, along with the compressor contactor(s) and
See Mechanical NSB operation below. blower relay. In the Heating Mode the reversing valve
is de-energized. Almost any thermostat will activate
Note: Digital Night Setback feature requires a the heat pump in heating or cooling modes. The
compatible thermostat. Contact manufacturer for Reheat Mode requires a either a separate humidistat/
information on compatible thermostats. dehumidistat or a thermostat that has an integrated
dehumidification function for activation. The DXM
Mechanical Night Setback - When the NSB input is board is configured to work with either a humidistat or
connected to Ground “C”, all thermostat inputs (G, Y1, dehumidistat input to terminal “H” (DIP switch settings
Y2, W1, and O/W2) are ignored. A thermostat setback for the DXM board are shown in table 2). Upon receiving
Heating call can then be connected to the OVR input. If an “H” input, the DXM board will activate the Cooling
the OVR input becomes active, then the DXM will enter Mode and engage reheat. Table 5 shows the relationship
NLL Staged Heating Mode. NLL Staged Heating Mode between thermostat input signals and unit operation.
would then provide heating during the NSB period.
Thermostat Inputs - Table 5 shows the resulting demand
Water Valve/Slow Opening - If an Accessory relay is from differing combinations of inputs.
configured for Water Valve/Slow Opening, the Accessory
relay will turn on 60 seconds prior to the Compressor Y1 - Y1 is the input for compressor stage 1 if DIP1.3 =
Relay turning on. on. Y1 is the input for Cooling Stage 1 if DIP1.3 = off.
Y2 - Y2 is the input for compressor stage 2 if DIP1.3 = on.
Outside Air Damper - If an Accessory relay is configured Y2 is the input for Cooling Stage 2 if DIP1.3 = off.
for OAD, the Accessory relay will normally turn on any W1 - If Y1 and Y2 are active and DIP1.3 = on, then W1 is
time the Fan Enable relay is on. But, following a return the input for Heating Stage 3. If Y1 and Y2 are not active
from NSB (NSB input no lrelonger connected to Ground and DIP1.3 = on, then W1 is the input for Emergency Heat.
“C”) to Normal Mode, the Accessory Relay will not turn If DIP1.3 = off, then W1 is the input for Heating Stage 1.
on for 30 minutes even if the Fan Enable Relay is on. After
this 30-minute timer expires, the Accessory Relay will turn O/W2 - O/W2 is the input for Reversing Valve Relay
on if the Fan Enable Relay is on. if DIP1.3 = on and DIP1.4 = on. O/W2 is the input for
Heating Stage 2 if DIP1.3 = off. O/W2 is the input for
Table 4: Thermostat Inputs with Resulting Demands
Thermostat Operating Modes
Input3 Output
Mode
O/W2 G Y1 Y24 W1 H RV Fan 1st stg H/C 2nd stg H/C4 AUX Reheat
No Demand ON/OFF OFF OFF OFF OFF OFF ON/OFF OFF OFF OFF OFF OFF
Fan Only ON/OFF ON OFF OFF OFF OFF ON/OFF ON OFF OFF OFF OFF
Cooling 1st Stage ON ON ON OFF OFF OFF ON ON ON OFF OFF OFF
Cooling 2nd Stage ON ON ON ON OFF OFF ON ON ON ON OFF OFF
1
Cooling & Dehumidistat ON ON ON ON/OFF OFF ON ON ON ON ON/OFF OFF OFF
Dehumidistat Only ON/OFF OFF OFF OFF OFF ON ON ON ON ON OFF ON
Heating 1st Stage OFF ON ON OFF OFF OFF OFF ON ON OFF OFF OFF
Heating 2nd Stage OFF ON ON ON OFF OFF OFF ON ON ON OFF OFF
Heating 3rd Stage OFF ON ON ON ON OFF OFF ON ON ON ON OFF
Heating & Dehumidistat2 OFF ON ON ON/OFF ON/OFF ON OFF ON ON ON/OFF ON/OFF OFF
1
Cooling input takes priority over dehumidify input.
2
DXM is programmed to ignore the H demand when the unit is in heating mode.
3
Above inputs assume DIP 1.3 is in the heat pump position, and DIP 1.4 is in the O position. When 1.3 is in the heat/cool position, Y1 & Y2 are used for cooling inputs;
W1 and O/W2 are used for heating inputs. When 1.4 is in the B position, the O/W2 column would be opposite logic.
4
N/A for single stage units; Full load operation for dual capacity units.
5
ON/OFF = Either ON or OFF; H/C = Either Heating or Cooling.
10
THE SMART SOLUTION FOR ENERGY EFFICIENCY
DXM Unit Control
R e v. : M a r c h 3 0 , 2 0 1 7
“Heat Mode” if DIP1.3 = on and DIP1.4 = off; this means that H - The H input function is determined by the setting of
the thermostat outputs a “B” call when in Heating Mode DIP2.7. If DIP2.7 = on then the H input is defined as Automatic
and does NOT have an “O” output. The DXM Control will Dehumidification Mode and is used as an “automatic”
employ “Smart RV” control. This ensures that the RV will only counterpart to DIP1.5, meaning if H is connected to 24VAC
switch positions if the thermostat has called for a Heating/ then the Fan Speed Relay will not turn on during Cooling
Cooling Mode change. Stage 2. If H is not connected to 24VAC then the Fan Speed
Relay will turn on during Cooling Stage 2.
G - G is the input for Fan Enable Relay.
If DIP2.7 = off then the H input is defined as High Speed Fan
NSB and Override - NSB is the input for Night Setback input and is used as an input to call for High Speed Fan. If
Mode. When Digital NSB is selected via the Accessory Relays the control is in normal operating modes such as Standby,
DIPswitch inputs and the NSB input is connected to Ground Cooling or Heating AND the H input is connected to 24VAC,
“C”, then the appropriately configured Accessory Relay is then the Fan Enable and Fan Speed Relays will be on at
turned on to signal the digital thermostat to go to Night all times (this operation is very similar to the G/Fan Enable
Setback Setpoints. Stated differently, when configured for operation).
Digital NSB Mode, the Accessory Relay directly tracks the
NSB input. Note: Units with Modulating Reheat Option operate
differently from the above descriptions. DIP 1.5 should
Note: Digital Night Setback feature requires a compatible be in the ON position, and 2.7 should be in the OFF
thermostat. Contact manufacturer for information on position. DIP 2.1, 2.2, and 2.3 indicate whether the
compatible thermostats. DXM will operate with or without dehumidification.
Table 2 shows the two available selections for
When Digital NSB is NOT selected via the Accessory Relays dehumidification, humidistat/dehumidistat operation.
DIP switch inputs and the NSB input is connected to Ground With either selection (OFF/OFF/OFF or OFF/ON/
“C”, then Y1, Y2, W1 and O/W2 and G are ignored. During OFF), the DXM microprocessor will operate in Reheat
this time period, if OVR is momentarily connected to 24VAC, Mode when an external input from a humidistat or
then Y1, Y2, W1 and O/W2 and G are once again monitored dehumidistat is applied to terminal H.
for 2 hours. After the 2 hour override period, the DXM reverts
back to ignoring Y1, Y2, W1, and O/W2 and G, assuming the Other Outputs - Table 12 displays input and output
NSB input is still connected to Ground “C”. There will be a signals.
random start timer when coming back from NSB Mode. Electric Heat - Outputs EH1 and EH2 turn on whenever
the DXM Control is in the following modes: Heating Stage
Note: The maximum number of DXM Controls with daisy- 3, Emergency Heat, and Boilerless Operation.
chained "NSB" terminals is 75. Also, the maximum total Status LED - The Status LED is green. The Status LED
wire resistance of the "NSB" wiring is 500 Ohms. indicates what mode the DXM Control is in. See Table 4:
“LED and Alarm Relay Operation”.
ESD - ESD is the input for Emergency Shutdown Mode. Test LED - The Test LED is yellow. The Test LED will be on
When the ESD input is connected to Ground “C”, all inputs any time the control is in Test Mode. See Table 4: “LED
are ignored and all outputs are turned off. There will be a and Alarm Relay Operation”.
random start timer when coming back from ESD.
Fault LED - The Fault LED is red. The Fault LED ALWAYS
OVR - OVR is the input for Night Setback Override or Night flashes the corresponding code for the last fault that has
Low Limit Staged Heating input (NLL). When Digital NSB is occurred. If there is no fault in memory, then the fault LED
NOT selected via the Accessory Relays DIP switch inputs and will flash Code 1. If the Fault type is “Primary” (HP, LP, LT1,
NSB is connected to Ground “C”, then if OVR is momentarily LT2, or CO) then the Fault type will always be retained in
connected to 24VAC (minimum 1 second) then the OVR memory (Primary faults will overwrite Secondary faults).
input is recognized as a Night Setback Override signal and If the Fault type is “Secondary” (Over/Under Voltage,
the DXM Control reverts from Night Setback and begins UPS or Swapped LT1/LT2) then the Fault type will only
monitoring thermostat inputs for heating and cooling calls be retained if there are no “Primary” faults in memory.
for a 2 hour override period. If NSB is connected to ground The Secondary Fault types will not “overwrite” the
"C", then if OVR is continuously connected to 24VAC, then Primary fault memory. See Table 4: “LED and Alarm Relay
the OVR input is recognized as a call for NLL Staged Heating Operation”.
and the control enters NLL Staged Heating.
11
WATER-SOURCE HEAT PUMPS
Communications
There are two communications ports (Com1 and Com2) CO signal. Regarding water valve/pump restart control,
which provide robust communications to external DXM if either the Master or Secondary DXM Control faults or
Control boards via a simple noise resistant low speed goes into Lockout Mode, it will continue to provide water
protocol. Wiring to Com1 and Com2 does NOT require valve/pump restart operation for the other functioning
the use of shielded wiring for operation; standard DXM Control.
thermostat wire can be used.
Table 5: System Inputs With The Resulting Demand.
Com1 - Com1 is used to communicate thermostat and
Table 5 describes demand changes with differing system
external calls to other DXM Master/Slave controls. In this
input (ESD, NSB, OVR) and DIP input settings. Resulting
configuration, up to 3 heat pumps can be controlled by
Demand #1 is derived from Table 4.
one thermostat.
System Inputs Resulting
Resulting Demand
NSB Type Demand #2
Note: Each heat pump could potentially be a Dual #1 (From Table 4) ESD NSB OVR (After ESD, NSB)
Compressor unit thus there could be up to 6 DXM - X - - - ESD
Controls being controlled by one thermostat. Invalid - - - - Invalid
However, only 1 DXM Control in each heat pump will All (Excluding Invalid) - - - - All (Excluding Invalid)
be daisy-chained on Com1.etc
All (Excluding Invalid) - - M - All (Excluding Invalid)
C1, C2 - - X - Invalid
OFF, F, H1, H2, or H3 - - X - NLL Staged Heating
The Master DXM Control is defined as the DXM Control, EH - - X - EH
which is directly connected to the wall-mounted All (Excluding Invalid) - X - Mechanical Standby/OFF
thermostat, time clock, fire alarm, and humidistat. The All (Excluding Invalid) - X M Mechanical
All for 2 hours and then
revert to Standby/OFF
Master DXM communicates to the Slave DXM typical (Excluding Invalid)
signals such as: Y1, Y2, W1, O/W2, G, NSB, ESD, OVR, C1, C2 - X X Mechanical Invalid
and H. The Slave DXM Controls should have no direct OFF, F, H1, H2, or H3 - X X Mechanical NLL Staged Heating
EH - X X Mechanical EH
connections to any exterior devices such as thermostats, All (Excluding Invalid) - X - Digital All (Excluding Invalid)
time clocks, fire alarms, humidistats, etc. All (Excluding Invalid) - X M Digital All (Excluding Invalid)
C1, C2 - X X Digital Invalid
Note: When using the Com1 port on DXM controllers OFF, F, H1, H2. or H3 - X X Digital NLL Staged Heating
to revise the units’ low voltage wiring. Contact “M” is momentary input
manufacturer’s Applications Department for details. “X” is continuous input
Com2 - Com2 is used to communicate thermostat and Table 6: "H" Input With Resulting Demand Modes.
external calls to a second DXM Control being used Table 6 describes demand changes with "H" input and
for Dual Compressor Function. A heat pump with two DIP 2.1-2.3, and 2.7 settings. Resulting Demand #2 is
compressors will have a DXM Control for each compressor. derived from Table 5.
The Master DXM Control will handle all I/O with external Resulting Demand # 3 (After
sources as well as monitor and control operations of the Resulting Demand
#2 (From Table 5)
H
Auto Dehum / F2
DIP 2.7
DIP 2.1-2.3,
Secondary DXM Control. The Master DXM Control is 2.7 Logic)
defined as the DXM Control, which is directly connected Standby/OFF X Auto Dehum Mode
Standby/OFF with Auto
Dehum enabled
to the wall-mounted thermostat, time-clock, fire alarm, Standby/OFF X High Fan Mode F2
and humidistat. The Master DXM communicates to the F1 X Auto Dehum Mode F1 with Auto Dehum enabled
Secondary DXM typical signals such as: Y1, Y2, W1, O/W2, F1 X High Fan Mode F2
G, NSB, ESD, OVR, and H. The Secondary DXM Control C1 X Auto Dehum Mode C1 with fan destage
C1 X High Fan Mode *Cooling with High Fan
should have no connections to any exterior devices such C2 X Auto Dehum Mode C2 with fan destage
as thermostats, time clocks, fire alarms, humidistats, etc. C2 X High Fan Mode *Cooling with High Fan
H1 X Auto Dehum Mode H1
Since the Master and Secondary DXM Controls share CO H1 X High Fan Mode Heating with High Fan
12
THE SMART SOLUTION FOR ENERGY EFFICIENCY
DXM Unit Control
R e v. : M a r c h 3 0 , 2 0 1 7
level. Upon a high condensate level the water will short 32.5 31871 32512 32190
between the air coil and the quick connect producing 31.5 32653 33310 32980
a resistance less than 100,000 Ohms. Since condensate 30.5 33728 34406 34065
is free of impurities, it has no conductivity. Only the 1.5 80624 82244 81430
impurities from the drain pan and coil dust or dirt create 0.5 83327 85002 84160
the conductance. A second ground wire with appropriate
0.0 84564 86264 85410
terminal to the drain pan can be used with the control to
replace the air coil ground path. The Condensate Sensor
can also essentially be any open contact that closes upon
Chart 2: Thermistor Nominal Resistance
a fault condition.
13
WATER-SOURCE HEAT PUMPS
14
THE SMART SOLUTION FOR ENERGY EFFICIENCY
DXM Unit Control
R e v. : M a r c h 3 0 , 2 0 1 7
Troubleshooting Information
General - DXM board troubleshooting in general is Table 10: DXM Input/Output Reference Table
best summarized as simply verifying inputs and outputs. Input or
Connection Description
After this process has been verified, confidence in board Output
15
WATER-SOURCE HEAT PUMPS
Troubleshooting Chart
Use the following troubleshooting flow chart to find appropriate troubleshooting strategies on the following
pages for the DXM Control and most water source heat pump applications.
Start
Did unit No
attempt to Check main power
start? (see power problems)
Yes
Did unit Yes
Check fault LED code No fault
lockout at
on control board shown
start-up?
No
See "Unit Yes See
Unit short See HP See LT1 Replace
short LP/LOC
cycles? Fault Fault DXM
CXM/ DXM
cycles" Fault
No
See "Only Yes See See Over/
Only fan See LT2
fan runs" Condensate Under
runs? Fault Fault Voltage
No
See "Only Yes Only
comp compressor
runs" runs?
No
Did unit lockout Yes
after a period of
operation?
No
See "Does No Does unit
not operate operate in
in clg" cooling?
Yes
Unit is OK!
"See Performance
Troubleshooting" for
further help
16
THE SMART SOLUTION FOR ENERGY EFFICIENCY
DXM Unit Control
R e v. : M a r c h 3 0 , 2 0 1 7
17
WATER-SOURCE HEAT PUMPS
Functional Troubleshooting
18
THE SMART SOLUTION FOR ENERGY EFFICIENCY
DXM Unit Control
R e v. : M a r c h 3 0 , 2 0 1 7
Performance Troubleshooting
Low Discharge Air Temperature X Too high of air flow Check fan motor speed selection and air flow chart.
in Heating X Poor performance See ‘Insufficient Capacity’
X Too high of air flow Check fan motor speed selection and airflow chart.
High humidity
X Unit oversized Recheck loads & sizing. Check sensible clg load and heat pump capacity.
19
WATER-SOURCE HEAT PUMPS
Revision History
06/11/10 Table 7: Replacement Thermistor LT1, LT2 Part Numbers Part Numbers Updated
*97B0003N13*
97B0003N13
We work continually to improve our products. As a result, the design and specifications of each product at the time of order may be changed without
notice and may not be as described herein. Please contact our Customer Service Department at 1-405-745-6000 for specific information on the
current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any
bargain between the parties, but are merely our opinion or commendation of its products.
20