Document Title: DATA SHEET FOR HAZARDOUS AREA DISTRIBUTION BOARD (TYPICAL)
Document File Name: HBR-01-GEN-ELE-DTS-0005 Data sheet for Hazardous area DB.xls
GENERAL NOTES
1 Data sheets to be read in conjuction with following docs.
2 Gland plates (2mm min) on distribution boards to be removable, unpainted, galvanised, supplied undrilled but suitable for drilling. Knockouts not acceptable
3 Purchaser to finalise "As Purchased" sizes and characteristics which may vary between 10 - 32 amps during detail design but prior to agreed freeze date with the Supplier
4 Max height of Lighting & Small Power, MOV, Emergency Lighting & Small Power & Trace Heating Distribution Boards is 2000mm including plinth.
5 Max height of socket / emergency socket supplies DB's is 2300mm including plinth.
6 MCB's require to have been type tested for short-circuit co-ordination (no damage) with the upstream protective device.
7 Swing door to be earthed by supplier
8 Spare
9 MCB and RCD alarm contacts shall only operate if the device trips and shall not change state if the device opens.
10 Refer to Specification for Painting, HBR-01-GEN-MEC-SPE-0004
11 EPC - Contractor to provide during detailed design
12 Distribution boards that supply lighting in a hazardous area, which is not certified for use in a hazardous area, i.e. road lighting, have contactors which isolate the supply to the
distribution board, via an ESD signal, in case of a major gas cloud release.