You are on page 1of 1

ALL AND LEVELS ARE TO BE VERIFIED ON SITE BY THE

CONTRACTOR BEFORE COMMENCING ANY WORK.


REINFORCING NOTES: GENERAL CONCRETE NOTES
1. MIN. CONCRETE COVER TO REINFORCEMENT:
1. GENERALLY ALL CONCRETE WORK IS TO BE IN ACCORDANCE WITH THE
- FOUNDATIONS = 50mm
FOLLOWING - CONTRACT SPECIFICATION, SANS 1200, SANS 10100 AND
- SLABS = 30mm
SANS 10161
1 2 3 4 5 6 7 - BEAMS/COLUMNS = 30mm
2. READ THIS DRAWING IN CONJUNCTION WITH THE RELEVANT
2. REINFORCEMENT TO BE SECURELY WIRED AT ALL INTERSECTIONS
13580 13580
SPECIFICATIONS; ARCHITECTS DRAWINGS;AND SERVICES DRAWINGS
3. REINFORCEMENT MUST BE FORMED AROUND, AND AS CLOSE AS
4527 4527 4527 4527 4527 4527 3. DIMENSIONS MUST NOT BE SCALED OR ASSUMED
ALLOWED TO HOLES, AND MUST NOT BE CUT. (SEE NOTE 1)
4. CONCRETE MIXES: MASS CONCRETE
4. BARS INDICATED THUS Y10, Y12 ETC. ARE HIGH TENSILE STEEL
MASS CONCRETE (USED AS BACKFILL TO OVERBREAK) 10/19
FOUNDATIONS(LOAD BEARING WALLS) 25/19
5. ALL LAPS TO BE STAGGERED
EAVE CUT FROM SLABS 25/19
305 x 102 x 25 I-SECTION BEAMS/COLUMNS 25/19
6. MILD STEEL TO COMPLY WITH SABS 920 TYPE A - GRADE 3
SURFACE BEDS 25MPa
7. HIGH TENSILE STEEL TO COMPLY SABS 920 TYPE C - GRADE 1
5. ALL REINFORCEMENT FIXING AND PLACING MUST BE INSPECTED AND
APPROVED BY THE ENGINEER PRIOR TO POURING CONCRETE
150 x 75 x 20 x 2,0 C-CHANNEL 150 x 75 x 20 x 2,0 C-CHANNEL 8. BENDING DIMENSIONS IN ACCORDANCE WITH SABS 82 GENERAL NOTES
PURLINS PURLINS 6. COVER TO REINFORCING:
9. STIRRUP DIMENSIONS GIVEN AS OVERALL
1578 1578 FOUNDATIONS = 50 (EARTHFACE = 40mm) 1.0 SETTING OUT AND GENERAL
305 x 102 x 25 I-SECTION 3157 305 x 102 x 25 I-SECTION BEAMS/COLUMNS = 30 (EARTHFACE = 40mm)
2600

RAFTER RAFTER 10. DIMENSION D MUST ALLWAYS BE GREATER THAN 2 x BAR DIAMETER 1.1 ALL WORK TO BE DONE IN ACCORDANCE WITH
7. CONCRETE FINISHES: TOP OF SLABS TO BE POWER FLOATED
NATIONAL BUILDING REGULATIONS AND
11. RADII OF ALL BENDS ARE STANDARD UNLESS r IS GIVEN IN THE MUNICIPAL BYLAWS.
SCHEDULE 1.1 ALL DIMENSIONS TO BE CHECKED ON SITE PRIOR
8. COLD/WET WEATHER CONCRETING AS PER SPECIFICATION
TO CONSTRUCTION.
12. DIMENSIONS ARE ALL OUTSIDE DIMENSIONS
9. ALL LOADBEARING BRICKWORK TO BE OF BRICKS WITH A CHARACTERISTIC 1.2 ALL MATERIAL TO MANUFACTURER'S
COMPRESSIVE STRENGTH OF 14 MPA & LAID IN CLASS II MORTAR SPECIFICATIONS
13. MINIMUM LAP LENGTH - 50 x DIAMETER
EXTERNAL WALLS = 220MM WIDE &
2640
2640 10. BRICKFORCE IN EVERY FOURTH COURSE TO LOADBEARING BRICKWORK
14. MINIMUM ANCHORAGE - 50 x DIAMETER INTERNAL WALLS = 110MM WIDE UNLESS
1400

11. STRIPPING OF FORMWORK AS PER SPECIFICATION.(WITH ENGINEERS OTHERWISE STATED.


15. REINFORCEMENT MUST BE STORED ON SITE IN CLEAN DRY AREA TO 1.3 THE DEVELOPER RESERVES THE RIGHT TO
APPROVAL)
AVOID RUST FORMING.
ADAPT ALL LEVELS AND VARY POSITIONING OF
12. DPC FORMED BRICKWORK OF 2 LAYERS OF 3 PLY MALTOID LAID ON UNITS TO SUIT SITE CONDITIONS.
HAUNCH CUT FROM HAUNCH CUT FROM SMOOTH MORTAR BED ON TOP OF BRICKWORK. VERTICAL SURFACES OF 1.4 ALL CONSTRUCTION WORK SHOULD COMPLY
305 x 102 x 25 I-SECTION 305 x 102 x 25 I-SECTION CONCRETE TO BE SEPARATED FROM BRICKWORK BY 10 MM WITH STANDARD SPECIFICATION.
POLYETHELENE FILLER BOARD
1.5 PLAN TO BE CHECKED BY DEVELOPER PRIOR TO
9924

13. NO HOLES OR CHASES SHALL BE CUT OR FORMED IN CONCRETE UNLESS


COUNCIL SUBMISSION AND CONSTRUCTION.
SHOWN ON DRAWINGS, DETAILED IN SPECIFICATION OR APPROVED BY 1.6 STRENGTH & STABILITY OF WALLS ACC. SABS
ENGINEER

14. LOADING DURING CONSTRUCTION - MAXIMUM LOAD ON FLOOR DURING


7324

C001 C002 C003 C004 C003 C002 C001 CONSTRUCTION TO BE 500 kg/m²

15. ANY DISCREPANCIES MUST BE BROUGHT TO THE ATTENTION OF THE


ENGINEER AS SOON AS POSSIBLE. IF THERE IS ANY DISCREPANCY
5924

BETWEEN THE DRAWINGS AND THE SPECIFICATION, THE ENGINEER MUST


BE INFORMED

STRUCTURAL STEELWORK:
S1) MATERIAL SPECIFICATION:
a. HOT ROLLED SECTIONS SABS 1431 GRADE 350W
b. COLD FORMED SECTIONS SABS 1431 GRADE 350W
c. PLATES, FLATS AND ROUNDS SABS 1431 GRADE 350W
d. BOLTS AND NUTS (BEARING) SABS 1700 GRADE 8.8
e. HSFG BOLTS SABS 1700 GRADE 8.8S
S2) MINIMUM STANDARD WELD SIZE TO BE 6mm. ALL WELDED PARTS TO BE
SEAL WELDED.
1300

S3) ALL WELDING TO BE DONE BY QUALIFIED WELDERS.


S4) FLOOR BRACES SHALL BE CONNECTED TO ALL FLOOR BEAMS AT POINTS
OF CONTACT.
S5) WHERE NO FORCES OR MOMENTS ARE INDICATED ON THE DRAWING,
THE FABRICATOR WILL BE REQUIRED TO DETAIL THE CONNECTION TO
FT001 FT001 FT001 FT001 FT001 FT001 FT001 RESIST:
a. TRUSSES AND BRACING - 40% OF THE LARGER MEMBERS TENSILE
STRENGTH
b. ROOF AND FLOOR BEAMS - 50% OF THE LARGER MEMBERS SHEAR
STRENGTH
S6) A MINIMUM OF TWO BOLTS SHALL BE USED IN ALL BOLTED CONNECTIONS.
SECTION A-A CROSS BRACES SHALL BE CONNECTED AT THE INTERSECTION WITH A
MINIMUM OF ONE M20 BOLT.
(STRUCTURAL STEEL ONLY) FOOTING LEGEND S7) HSFG BOLTS SHALL BE INSTALLED IN ACCORDANCE WITH SABS 094 USING
THE TURN OF NUT METHOD.
SCALE 1:50
NUMBER BASE SIZE STUB COLUMN SIZE No. OFF S8) BOLTS, NUTS AND WASHERS SHALL BE CADMIUM OR ZINC PLATED.
S9) MILD STEEL GRATING SHALL BE OPEN GRID, NON-SLIP TYPE, WITH 100 X 40
FT001 1500 x 1500 x 400 Dp 440 x 440 x 900 Dp 34 OPENINGS AND 30 X 4.5 BEARER BARS. (<--->) INDICATES DIRECTION OF
SPAN. THE GRATING SHALL BE HOT DIP GALVANISED TO SABS 763.
S10) ALL MOMENT CONNECTIONS SHALL BE FULL STRENGTH.
COLUMN LEGEND S11) VASTRAP PLATE SHALL BE SECURED TO SUPPORTING BEAMS WITH
COUNTERSUNK BOLTS.
NUMBER COLUMN SIZE HEIGHT (mm) No. OFF S12) STAIR TREADS SHALL BE OPEN GRID TYPE 750mm SPAN, WITH NON-SLIP
203 x 133 x 30 UC NOSING.
C001 7280 18
S13) HANDRAILING STANDARDS TO BE 1000mm ABOVE FINISH FLOOR LEVEL.
C002 203 x 133 x 30 UC 7835 4 S14) KICK FLATS TO BE 6mm THICK EXTENDING 130mm ABOVE FINISH FLOOR
C003 203 x 133 x 30 UC 8710 4 LEVEL.
C004 203 x 133 x 30 UC 9254 2 S15) HANDRAIL TO BE FIXED TO FLOOR SUPPORTING STEELWORK AND NOT TO
KICK FLAT.
C005 203 x 133 x 30 UC 2635 6 S16) THE FABRICATOR SHALL SUPPLY ALL BOLTS, NUTS AND WASHERS
NECESSARY FOR ASSEMBLY AND ERECTION.
S17) ITEM NUMBER, DRAWING NUMBER, ORDER NUMBER AND RING NUMBER TO
ROOF LEGEND BE CLEARLY HARD MARKED AND PAINTED ON ALL ITEMS AND PARTS
THEREOF.
1 2 3 4 5 6 7 NUMBER SIZE LENGTH (mm) No.OFF S18) SHOP PREPARATION AND PAINTING TO BE IN ACCORDANCE WITH THE
PROJECT SPECIFICATION.
RT001 305 x 102 x 25 UB 13700 18
S19) THE FABRICATOR SHALL SUPPLY ALL BOLTS FOR CONNECTING
13580 13580 HAUNCH 305 x 102 x 25 UB (CUT) MECHANICAL ITEMS TO STRUCTURAL STEEL AS INDICATED ON THE
BC001 60 x 60 x 8 L DRAWINGS.
4527 4527 4527 4527 4527 4527 S20) BOLTS THAT ARE CADMIUN PLATED SHALL BE DEBRITTLED IN
ACCORDANCE WITH BS 1706 CLASS A. CERTIFICATION OF COMPLIANCE IS
REQUIRED.
S21) CONTACT SURFACES AT FRICTION GRIP CONNECTIONS SHALL BE
SANDBLASTED AND PRIMED.
S22) ALL FLAME-CUT EDGES, BURRS AND SHARP EDGES TO BE GROUND
SMOOTH.

150 x 75 x 20 x 2,0 C-CHANNEL 150 x 75 x 20 x 2,0 C-CHANNEL


PURLINS PURLINS
2600

ISSUED FOR
0 - PM PM
CONSTRUCTION

No Date Details Chd Appd


Revisions

Client

METHODIST CHURCH
1400

Engineer
9880

2949
7280

C001 C002 C003 C004 C003 C002 C001


5880

5924
255
ADDRESS

2720
CONTACTS

Project

PROPOSED NEW CHURCH


340
1344

FT001 FT001 FT001 FT001 FT001 FT001 FT001 Description

PLAN:
SECTIONS AND DETAILS
SECTION A-A (SHEET 03)
(INCLUDING SLAB & BRICKWORK)
SCALE 1:50
Scale Date
AS SHOWN JUL 2020
Project No Drg. No Rev

PF005/19 WSG028-ENG 03

You might also like