PTAP El Portico Proyecto III

HVAC Load Analysis


for

Prepared By:

HMV Ingenieros

Friday, November 12, 2021


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
HMV Ingenieros LTDA PTAP El Portico Proyecto III
Itagui Capricentro, Page 2

Zone Input
Zone 1: Cuarto Eléctrico (1323.212 sq.ft) (Group 1)
Air Handler number: 1 Zone occurrences: 1
Zone length: (feet) 1,323.21 Zone width (feet): 1.00
Lighting Watts: 2,646 Equipment Watts: 11,250
Number of people in zone: 0 People profile number: 5
Lighting profile number: 2 Equipment profile number: 3
Ceiling height (feet): 11.48 Heating safety factor (%): 0
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 245 Latent heat per person (Btuh): 155
Cooling ventilation method: CFM/Pr & Cooling ventilation value: 10.000
CFM/sq.ft 0.120
Cooling infiltration method: CFM/sq.ft Cooling infiltration value: 0.000
Heating ventilation method: CFM/Pr Heating ventilation value: 0.000
Heating infiltration method: CFM/sq.ft Heating infiltration value: 0.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 26 Exposed floor slab perimeter (ft): 0
Cooling loads only are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 9 1 0.002 No 1,323.21 1.00 1,323.2 No

Part Type U-Factor Cool TD Heat TD Height Width Area


2 9 0.323 0.000 0.000 11.48 27.16 311.8
4 12 0.105 0.000 0.000 11.48 27.16 311.8

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 12 G 0.002 M 11.48 48.72 559.3 315
3 9 G 0.090 L 11.48 48.72 559.3 135
5(D) 1 G 0.065 L 11.48 8.69 99.8 315

Glass Type S.U-F. Shd C. Height Width Occur. Area Shade Tilt Ref
1 1 1.040 1.000 11.48 3.67 1 42.1 0 90 1
2 1 1.040 1.000 11.48 8.27 1 94.9 0 90 3

Zone 2: Cuarto Control (234.0656 sq.ft) (Group 3)


Air Handler number: 1 Zone occurrences: 1
Zone length: (feet) 234.07 Zone width (feet): 1.00
Lighting Watts: 468 Equipment Watts: 1,212
Number of people in zone: 3 People profile number: 1
Lighting profile number: 2 Equipment profile number: 3
Ceiling height (feet): 9.84 Heating safety factor (%): 0
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 245 Latent heat per person (Btuh): 155
Cooling ventilation method: CFM/Pr & Cooling ventilation value: 5.000
CFM/sq.ft 0.060
Cooling infiltration method: CFM/sq.ft Cooling infiltration value: 0.000
Heating ventilation method: CFM/Pr Heating ventilation value: 0.000
Heating infiltration method: CFM/sq.ft Heating infiltration value: 0.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 6 Exposed floor slab perimeter (ft): 0
Cooling loads only are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 10 1 0.290 No 234.07 1.00 234.1 No

Part Type U-Factor Cool TD Heat TD Height Width Area


1 11 0.26 0.000 0.000 23.42 13.91 325.8
2 11 0.26 0.000 0.000 9.84 16.83 165.6

C:\Users\lpalomino\Documents\HVAC\Cúcuta PIII Verson 2021_3.CHV Friday, November 12, 2021, 10:32 PM


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
HMV Ingenieros LTDA PTAP El Portico Proyecto III
Itagui Capricentro, Page 3

Zone Input (cont'd)


Zone 2: Cuarto Control (234.0656 sq.ft) (Group 3)

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


3 13 G 0.260 M 9.84 13.91 136.9 135
4 13 G 0.260 M 9.84 16.83 165.6 225
5(D) 1 G 0.065 L 8.20 8.53 69.9 225

Glass Type S.U-F. Shd C. Height Width Occur. Area Shade Tilt Ref
1 1 1.040 1.000 9.84 2.27 1 22.3 0 90 3
2 1 1.040 1.000 9.84 1.84 1 18.1 0 90 4

C:\Users\lpalomino\Documents\HVAC\Cúcuta PIII Verson 2021_3.CHV Friday, November 12, 2021, 10:32 PM


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
HMV Ingenieros LTDA PTAP El Portico Proyecto III
Itagui Capricentro, Page 4

Building Summary Loads


Building peaks in January at 11am.
Bldg Load Area Sen %Tot Lat Sen Net %Net
Descriptions Quan Loss Loss Gain Gain Gain Gain
Roof 1,557 0 0.00 0 2,753 2,753 2.32
Wall 1,244 0 0.00 0 4,308 4,308 3.63
Glass 178 0 0.00 0 27,560 27,560 23.21
Floor Slab 0 0 0.00 0 0 0 0.00
Skin Loads 0 0.00 0 34,622 34,622 29.16
Lighting 3,115 0 0.00 0 11,690 11,690 9.85
Equipment 12,462 0 0.00 0 46,774 46,774 39.40
People 3 0 0.00 512 809 1,320 1.11
Partition 1,115 0 0.00 0 0 0 0.00
Cool. Pret. 0 0 0.00 0 0 0 0.00
Heat. Pret. 0 0 0.00 0 0 0 0.00
Cool. Vent. 188 0 0.00 16,038 2,878 18,916 15.93
Heat. Vent. 0 0 0.00 0 0 0 0.00
Cool. Infil. 0 0 0.00 0 0 0 0.00
Heat. Infil. 0 0 0.00 0 0 0 0.00
Draw-Thru Fan 0 0 0.00 0 0 0 0.00
Blow-Thru Fan 0 0 0.00 0 0 0 0.00
Reserve Cap. 0 0 0.00 0 0 0 0.00
Reheat Cap. 0 0 0.00 0 0 0 0.00
Supply Duct 0 0 0.00 0 5,396 5,396 4.55
Return Duct 0 0 0.00 0 0 0 0.00
Misc. Supply 0 0 0.00 0 0 0 0.00
Misc. Return 0 0 0.00 0 0 0 0.00
Building Totals 0 0.00 16,549 102,169 118,718 100.00

Building Sen %Tot Lat Sen Net %Net


Summary Loss Loss Gain Gain Gain Gain
Ventilation 0 0.00 16,038 2,878 18,916 15.93
Infiltration 0 0.00 0 0 0 0.00
Pretreated Air 0 0.00 0 0 0 0.00
Zone Loads 0 0.00 512 93,895 94,406 79.52
Plenum Loads 0 0.00 0 0 0 0.00
Fan/Duct/Misc Loads 0 0.00 0 5,396 5,396 4.55
Building Totals 0 0.00 16,549 102,169 118,718 100.00

Check Figures
Total Building Supply Air (based on a 18° TD): 5,142 CFM
Total Building Vent. Air (3.65% of Supply): 188 CFM
Total Conditioned Air Space: 1,557 Sq.ft
Supply Air Per Unit Area: 3.3019 CFM/Sq.ft
Area Per Cooling Capacity: 157.4 Sq.ft/Ton
Cooling Capacity Per Area: 0.0064 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 9.89 Tons

C:\Users\lpalomino\Documents\HVAC\Cúcuta PIII Verson 2021_3.CHV Friday, November 12, 2021, 10:32 PM


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
HMV Ingenieros LTDA PTAP El Portico Proyecto III
Itagui Capricentro, Page 5

Air Handler #1 - Handler 1 General Confort - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
1 Cuarto Eléctrico 1,323 0 75,090 0 None 10/P, 0.12/ft²
11am January 0 0 4,112 0 0 159
15,190 0.00 3.11 0 0 150

2 Cuarto Control 234 0 19,990 512 None 5/P, 0.06/ft²


3pm January 3 0 1,095 0 0 29
2,303 0.00 4.68 0 0 40
Zone Peak Totals: 1,557 0 95,080 512
Total Zones: 2 3 0 5,207 0 0 188
Unique Zones: 2 17,494 0.00 3.34 0 0 190

C:\Users\lpalomino\Documents\HVAC\Cúcuta PIII Verson 2021_3.CHV Friday, November 12, 2021, 10:32 PM


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
HMV Ingenieros LTDA PTAP El Portico Proyecto III
Itagui Capricentro, Page 6

Air Handler #1 - Handler 1 General Confort - Total Load Summary


Air Handler Description: Handler 1 General Confort Variable Air Volume
Sensible Heat Ratio: 0.99 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 11am in January.
Outdoor Conditions: Clg: 89° DB, 86° WB, 196.76 grains
Indoor Conditions: Clg: 73° DB, 50% RH
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.954 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 93,895 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 5,396 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 99,291 Btuh
Cooling Supply Air: 99,291 / (.954 X 1.1 X 18) = 5,142 CFM
Summer Vent Outside Air (3.7% of supply) = 188 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 2,878 Btuh 188 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 2,878 Btuh
Total sensible gain on air handling system: 102,169 Btuh
Zone space latent gain: 512 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 16,038 Btuh
Total latent gain on air handling system: 16,549 Btuh
Total system sensible and latent gain: 118,718 Btuh

Check Figures
Total Air Handler Supply Air (based on a 18° TD): 5,142 CFM
Total Air Handler Vent. Air (3.65% of Supply): 188 CFM
Total Conditioned Air Space: 1,557 Sq.ft
Supply Air Per Unit Area: 3.3019 CFM/Sq.ft
Area Per Cooling Capacity: 157.4 Sq.ft/Ton
Cooling Capacity Per Area: 0.0064 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 9.89 Tons

C:\Users\lpalomino\Documents\HVAC\Cúcuta PIII Verson 2021_3.CHV Friday, November 12, 2021, 10:32 PM


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
HMV Ingenieros LTDA PTAP El Portico Proyecto III
Itagui Capricentro, Page 7

Zone Detailed Loads (At Zone Peak Times)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Zone 1-Cuarto Eléctrico peaks (sensible) in January at 11am, Air Handler 1 (Handler 1 General
Confort), Group 1, 1,323.2 x 1.0, Construction Type: 22 (Medium)
Roof-1-1-No.Clg-L 1,323 0.50 35.5 0.002 94 0.000 0
Wall-1-315-G-M 417 0.83 14.5 0.002 12 0.000 0
Wall-3-135-G-L 464 0.65 41.8 0.090 1,748 0.000 0
Door-5-315-G-L 100 0.65 12.8 0.065 83 0.000 0
Partition-2-9 311.7968 0/0 0.323 0 0.000 0
Partition-4-12 311.7968 0/0 0.105 0 0.000 0
Gls-315°-1-90-Tran 42.1 1.000 14 1.040 605 0.000 0
0%S-0-UNS-Solar 42.1 1.000 79 0.170 566
Gls-135°-1-90-Tran 94.9 1.000 14 1.040 1,363 0.000 0
0%S-0-UNS-Solar 94.9 1.000 250 0.690 16,377
Lights-Prof=2 2,646 1.000 9,030
Equipment-Prof=3 11,250 1.000 38,387 0
Sub-total 68,264 0 0
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 75,090 0 0

C:\Users\lpalomino\Documents\HVAC\Cúcuta PIII Verson 2021_3.CHV Friday, November 12, 2021, 10:32 PM


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
HMV Ingenieros LTDA PTAP El Portico Proyecto III
Itagui Capricentro, Page 8

Zone Detailed Loads (At Zone Peak Times) (cont'd)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Zone 2-Cuarto Control peaks (sensible) in January at 3pm, Air Handler 1 (Handler 1 General Confort),
Group 3, 234.1 x 1.0, Construction Type: 19 (Light)
Roof-1-1-No.Clg-L 234 0.50 43.5 0.290 2,952 0.000 0
Wall-3-135-G-M 115 0.83 35.7 0.260 1,065 0.000 0
Wall-4-225-G-M 78 0.83 58.2 0.260 1,173 0.000 0
Door-5-225-G-L 70 0.65 47.0 0.065 214 0.000 0
Partition-1-11 325.7722 0/0 0.260 0 0.000 0
Partition-2-11 165.6072 0/0 0.260 0 0.000 0
Gls-135°-1-90-Tran 22.3 1.000 21 1.040 483 0.000 0
0%S-0-UNS-Solar 22.3 1.000 250 0.210 1,173
Gls-225°-1-90-Tran 18.1 1.000 21 1.040 392 0.000 0
0%S-0-UNS-Solar 18.1 1.000 250 0.940 4,255
Lights-Prof=2 468 1.000 1,597
Equipment-Prof=3 1,212 1.000 4,136 0
People-Prof=1 3.0 1.000 735 465
Sub-total 18,173 465 0
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 19,990 512 0

C:\Users\lpalomino\Documents\HVAC\Cúcuta PIII Verson 2021_3.CHV Friday, November 12, 2021, 10:32 PM