Zone Input
Zone 1: Cuarto Eléctrico (1323.212 sq.ft) (Group 1)
Air Handler number: 1 Zone occurrences: 1
Zone length: (feet) 1,323.21 Zone width (feet): 1.00
Lighting Watts: 2,646 Equipment Watts: 11,250
Number of people in zone: 0 People profile number: 5
Lighting profile number: 2 Equipment profile number: 3
Ceiling height (feet): 11.48 Heating safety factor (%): 0
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 245 Latent heat per person (Btuh): 155
Cooling ventilation method: CFM/Pr & Cooling ventilation value: 10.000
CFM/sq.ft 0.120
Cooling infiltration method: CFM/sq.ft Cooling infiltration value: 0.000
Heating ventilation method: CFM/Pr Heating ventilation value: 0.000
Heating infiltration method: CFM/sq.ft Heating infiltration value: 0.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 26 Exposed floor slab perimeter (ft): 0
Cooling loads only are calculated for this zone.
Glass Type S.U-F. Shd C. Height Width Occur. Area Shade Tilt Ref
1 1 1.040 1.000 11.48 3.67 1 42.1 0 90 1
2 1 1.040 1.000 11.48 8.27 1 94.9 0 90 3
Glass Type S.U-F. Shd C. Height Width Occur. Area Shade Tilt Ref
1 1 1.040 1.000 9.84 2.27 1 22.3 0 90 3
2 1 1.040 1.000 9.84 1.84 1 18.1 0 90 4
Check Figures
Total Building Supply Air (based on a 18° TD): 5,142 CFM
Total Building Vent. Air (3.65% of Supply): 188 CFM
Total Conditioned Air Space: 1,557 Sq.ft
Supply Air Per Unit Area: 3.3019 CFM/Sq.ft
Area Per Cooling Capacity: 157.4 Sq.ft/Ton
Cooling Capacity Per Area: 0.0064 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 9.89 Tons
Check Figures
Total Air Handler Supply Air (based on a 18° TD): 5,142 CFM
Total Air Handler Vent. Air (3.65% of Supply): 188 CFM
Total Conditioned Air Space: 1,557 Sq.ft
Supply Air Per Unit Area: 3.3019 CFM/Sq.ft
Area Per Cooling Capacity: 157.4 Sq.ft/Ton
Cooling Capacity Per Area: 0.0064 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 9.89 Tons