Attemperator 1.1 Temp High
Attemperator 1.1 Temp High
Over firing in the evaporator section Warn SOR of possible unit trip and announce an emergency With permission, return lost unit
due to firing disturbances namely: over the PA system. to service, using procedure
- Mill start-up Switch NNC and frequency correction off. U/U/OPER-009.
- Mill shutdown. Reduce firing and increase feed flow according to rate of C&I to rectify faulty control.
- Mill running empty. temperature rise. Tripped plant to be returned to
- Mill losses. If temperature rate not too fast, the feedwater master, boiler service with great care.
- Draught start-ups. demand, master fuel and enthalpy controls are to be left on With load loss in force, it should
- Too high excess air values. auto with close observation. be kept as short as possible.
Feed flow less than steam flow for Manual intervention to be kept to a minimum. UC/USS to use
extended period during: their own discretion.
- Loss of EFP’s. Enthalpy control to be selected to manual above 412°C. See
- Feed control manual. OPS/UNT-035.
- Faulty enthalpy control. Ensure following valves are correct according to existing load:
- Main steam pressure.
- Total fuel flow.
- Feed water flow.
- Steam flow.
- Total air flow. (O2 values).
Note:
- Over reaction should be avoided.
- Wait at least 10 minutes for unit to stablise.
- Boiler load signal (black needle) and capability signal (red
needle) to be balanced before trip plant is re-started.
PTO
CP 8/12/2014
PUBLIC DOMAIN