ALARM RESPONSE PROCEDURE

ARP RESPONSE PROCEDURE

1.0 BOILER MFT

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 PAF stopped  Detection Level 1 Alarm. (Trip Indication)
 SAF stopped  Check DCS page 10 DVOP #2 Furnace Purge for Trip First out
 IDF stopped signal.
 Boiler Emergency Trip on CRT  Verification the Cause of tripping through SER at Rack room
 Boiler Emergency Trip on OPC  Inform Supv, Supt and OM for the tripping incident.
 Total Air flow <25% MCR  Checking, Assessment and Evaluation of Trip Alarm:
 Furnace Press. High-high DCS - process (flow, pressure and temp.)
 Drum level Low-Low; <-254mm Local - Condition of Equipment, Transmitters, and valves
 Loss of all Fuel  Restart the Unit as Possible (depending on the Evaluation Result)
 Instrument Air Pressure Low-Low; <3.5 ksc  Check coal feeder A, B and C running status
 Furnace Temp. inadequate for Coal Firing;
>700 ◦c
 Furnace Press. Low-low
 All FA Blower Stop
 Drum level High-High ; >254 mm
 Cyclone Outlet Gas temp. High-high; >568
◦c
 Reheater Outlet Temp. High-High; >535 ◦c
 Turbine Trip

2.0 BOILER MFT MANUAL

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 Activated Emergency trip Button Push  Inform Supv, Supt and OM for the tripping incident.
 Checking, Assessment and Evaluation of Trip Alarm:
DCS - process (flow, pressure, and temp.)
Local - Condition of Equipment, Transmitters, and valves
 Restart the Unit as Possible (depending on the Evaluation Result)
 Check coal feeder A, B and C running status
ARP RESPONSE PROCEDURE

3.0 MAIN STEAM PRESSURE HI / HI-HI

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 Boiler main steam pressure  Boiler Pressure Control Set at High Value  Check if the Blow off valve is Open. Then, manually control opening
 PI-MS1002 & PI-MS2002  Sudden Decrease of Load (Droop) of Blow off valve.
 Mains steam Press. HI ≥  Closing of Main Steam Control Valves  Adjust the Boiler Pressure Control to Low set value
130ksc  Change of coal From Low to High Calorific  Open soot blower line to help release excess pressure.
 Mains steam Press. HI-HI ≥  Attemperator Problems (Stuck up)  For Change Coal, Set CCS to manual, Go to Page 11 Coal Feeding
134ksc System, adjust coal calorie correction.
 Increase MV to set coal calorie correction near HHV of new Coal.
 For Attemperator problems, Check the actual status of the valve at
local and troubleshoot (communicate with CRO). if still exist, File
SR for maintenance rectification

4.0 MAIN STEAM PRESSURE LO / LO-LO

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 Boiler main steam pressure  Coal feeder Belt slippage  Check coal feeder status at local and make adjustments with close
 PI-MS1002 & PI-MS2002  No coal on belt coordination with CRO
 Mains steam Press. LO ≤  Change of coal From Low to High Calorific  Set CCS to manual, Go to Page 11 Coal Feeding System, adjust
100 ksc  Hunting of valves (Blow-off, Main Steam coal calorie correction.
 Mains steam Press. LO-LO ≤ Valves, Desuperheater Valves)  Inform Supv, SUPT and Dispatch for load adjustment decrease the
72.9ksc  Boiler Tube Leak load to compensate the drop in pressure.
 For Hunting of control valves, Check the actual status of the valve
at local and troubleshoot (communicate with CRO). For sudden
closing of control valve, Coordinate with AO to Open bypass line
with close coordination with CRO to monitor flow and opening. File
SR for maintenance rectification
 For Boiler Tube leak, Follow SOP for Boiler Tube Leak

5.0 MAIN STEAM TEMPERATURE HI / HI-HI

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 TI-MS1004 (1/2) & TI-  Load Variation (Load-up)  Adjust 2nd stage desuperheater settings between 535 ◦c to 525 ◦c
MS2004 (1/2)  Change of coal From Low to High Calorific  Manually adjust Boiler Pressure Control by decreasing set value to
 Main Steam Temp H ≥  Desuperheater Abnormal (clogging or adjust coal flow at CCS mode or Set Boiler Master manual and
548◦C sudden Closing) adjust coal flow for faster reaction.
ARP RESPONSE PROCEDURE

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 Main steam Temp HH  Monitor Furnace Temp. and Temp. Gradient and stabilize MS
≥550◦C Temp.
 Set CCS to manual, Go to Page 11 Coal Feeding System, adjust
coal calorie correction.
 Inform Dispatch to Decrease load generation if necessary.
 For Desuperheater Abnormal Control Valves, Check the actual
status of the valve locally and troubleshoot (communicate with
CRO). If still exist, Coordinate with AO to Open bypass line with
close coordination with CRO to monitor flow and opening. File SR
for maintenance rectification

6.0 MAIN STEAM TEMPERATURE LO / LO-LO

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 TI-MS1004 (1/2) & TI-  No Coal on belt/ Belt slippage  Adjust Set pressure on Boiler Pressure Control to increase coal
MS2004 (1/2)  Desuperheater Abnormal (sudden opening) feed rate.
 Main Steam Temp L ≤ 525◦C  Boiler Pressure control set low <125 ksc  If belt slippage occurs, heck coal feeder status at local and make
 Main steam Temp LL ≤  Finishing Superheater Panel Inefficient heat adjustments with close coordination with CRO
510◦C exchange  Conduct Sootblowing at least Twice Daily
 For Desuperheater Abnormal Control Valves, Check the actual
status of the valve locally and troubleshoot (communicate with
CRO). File SR for maintenance rectification

7.0 BED TEMPERATURE HI / HI-HI

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 Furnace Lower Temp. Ave.  Not Enough Secondary air flow going to  Detection Secondary Air pressure drop < 1250mmH2o,
 TIFG 1090L ≥ 980◦C staging. Check/adjust staging air damper opening suitable for the Load
 TIFG 1090L ≥ 950◦C  PAF bias to low Generated. Check/ adjust SUB damper for increase opening.
 High Coal Heating value  Increased PAF bias, Observe Furnace temp. for reaction.
 Too Low Material Circulating at Furnace  If too low material in the furnace, Maintain Overall DP to
 Bed Material Coarse or Heavy Required/align to Generator load and Conduct Bottom ash
withdrawal.
 Compensate by L/s injection, Increase gradually Air flow SAF and
PAF
 Increased DP by Sand feeding
ARP RESPONSE PROCEDURE

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 Verify by Conducting Windbox and Bottom Ash withdrawal.
8.0 BED TEMPERATURE LO

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 Furnace Lower Temp.  No Coal on belt/ Belt slippage  Check coal feeder status at local and adjust with close coordination
Average  PAF bias to High with CRO.
 TIFG 1090L < 820◦C  Too Much Bed Material  Decrease PAF Bias
 Conduct Bottom Ash withdrawal.

9.0 FAB-A/B STOPPED

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 F-1055A/B and F-2005A/B  Fan and Motor Bearing Temp. >120 ◦c  Check if the standby FAB will Auto Cut-in and adjust the inlet
 Motor winding Temp. (U, V, W) >155 ◦c damper to desired outlet air flow at 29T/H
 Fan and Motor Bearing Temp. >7mm/s  Verify the cause of tripping.
 FAB Local Stop  Notify Maintenance Department to check the Equipment.
 FAB Electric Trouble

10.0 FAB-A/B BEARING TEMP HI/HI-HI

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 TIFA-1055A1/A2 and TIFA-  Insufficient Lubrication to Bearings  For Bearing Temperature HI-HI, Check if the standby FAB will Auto
2055A1/A2  Blower Shaft imbalance Cut-in and adjust the inlet damper to desired outlet air flow at
 Temp. HI > 110 ◦C  Temperature transmitter abnormal reading 29T/H
 Temp. HI-HI > 120 ◦C  Check Oil reservoir of Blower, Top-up oil, if found low
 Verification at local by AO through Equipment Noise
 Notify I&C team to conduct checking of transmitter.
 For Bearing Temperature HI, Conduct Change Over of FA Blower

11.0 FAB-A/B PRESSURE LO/LO-LO

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 PIFA-1055A/B and PIFA-  Conduct Change Over of FA Blower
ARP RESPONSE PROCEDURE

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


2055 A/B  Seal pot Windbox clogged up  Seal pot windbox draining.
 Pressure LO < 3500 mmH20  Inlet suction filter clogged up  Replaced suction filters
 Pressure LO-LO < 3000  Faulty transmitters  Check the transmitters through parameter trending. If found erratic,
mmH20 Call assistance of I&C for troubleshooting

12.0 IDF STOPPED

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 MFT will be triggered  Electric trouble  Check IDF first out link on DCS
 IDF local stop Push Button (PB)  Have it check by Electrical team for main breaker and soft starter
 IDF stop command  Check local push button (PB) status
 IDF trip command  Check oil levels of motor bearing, fan bearing and hydraulic
 IDF hydraulic coupling working oil coupling
pressure low low  Check hydraulic coupling working oil strainer differential pressure
 IDF hydraulic coupling working oil  Check cooling water supply to IDF hydraulic oil cooler and ID fan
temperature high high bearing.
 IDF Bearing vibration high high  Check GAH status.
 IDF motor winding temperature high high  Check the reliability of the instrument.
 IDF bearing temperature high high  Restart the Unit when repair is done and no major damages on the
 IDF motor bearing vibration high high equipment
 GAH stop

13.0 IDF BEARING TEMP HI/HI-HI

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 TI-FG10561/ TI-FG10562  Insufficient oil level on the IDF motor DE  Top up oil for fan bearing
and TI-FG20561/ TI- or NDE side.  Check the reliability of the instrument
FG20562  Abnormal indication/signal from its  Check cooling water supply to IDF bearing DE and NDE side.
 Temp HI > 80 ◦C instrument.  For Bearing Temp HI-HI, Restart the unit when the repair is done
 Temp HI-HI > 90◦C  Not enough supply of cooling water for and no major damages on the equipment
 For Bearing Temp HI-HI, the IDF bearing NDE or DE side
MFT will be triggered

14.0 PAF STOPPED


ARP RESPONSE PROCEDURE

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 MFT will be triggered  Any of draft fan stopped (FAB-A&B, SAF,  Check PAF first out link on DCS
IDF & GAH)  Have it check by Electrical team for main breaker and soft starter
 PAF lube oil pressure low  Check local push button (PB) status
 All PAF lube oil pump stopped  Check oil level of PAF lube oil tank
 Electrical trouble  Check PAF lube oil strainer differential pressure
 Drum level low low  Check cooling water supply to PAF lube oil cooler
 Furnace pressure HHH  Check the reliability of the instrument
 Motor bearing temperature > 95 deg. C  Restart Unit when repair is done and no major damages on the
 Fan bearing temperature > 80 deg. C equipment
 Motor winding temperature > 180 deg. C
 Fan and Motor vibration HH > 15.6 mm/s
 PAF local stop Push Button (PB)
 PAF stop command

15.0 PAF BEARING TEMP HI/HI-HI

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 TI-FA10531/ TI-FA10532  Instantaneous occurrence due to faulty  Check the transmitters through parameter trending. If found erratic,
and TI-FA20531/ TI- transmitter Call assistance of I&C for troubleshooting.
FA20532  Lubrication failure  Visual checking of the equipment
 Temp HI > 90 ◦C  Cooling water failure  Check the lube oil system
 Temp HI-HI > 95◦C  Excessive vibration  Check the Cooling water supply
 For Bearing Temp HI-HI,  Check valve line up and valve throttling for lube oil to bearing
MFT will be triggered should supply > 1.0 ksc but < 1.6 ksc
 For Bearing Temp HI-HI, Restart the unit when the repair is done
and no major damages on the equipment

16.0 PRIMARY AIR FLOW LO-LO

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 FIFA1071/FIFA2071  Faulty transmitter  Faulty transmitter & DCS glitch. Check through DCS and Call
 Flow LO-LO < 200 T/H  PAF damper abnormal opening attention of I&C engineer for calibration and glitch tracing.
 Visual inspection for local if damper has mechanical failure and
have it repair or replace by mechanical team.
ARP RESPONSE PROCEDURE

17.0 SAF STOPPED

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 MFT will be triggered  Furnace pressure HI-HI  Check PAF first out link on DCS
 R/H temp. > 568 deg. C  Have it check by Electrical team for main breaker and soft starter
 Electrical trouble  Check local push button (PB) status
 Motor bearing temperature > 95 deg. C  Check oil level of PAF lube oil tank
 Fan bearing temperature > 80 deg. C  Check PAF lube oil strainer differential pressure
 Motor winding temperature > 180 deg. C  Check cooling water supply to PAF lube oil cooler
 Fan and Motor vibration HH > 15.6 mm/s  Check the reliability of the instrument
 SAF local stop Push Button (PB) Restart Unit when repair is done and no major damages on the
 SAF stop command equipment

18.0 SAF BEARING TEMP HI/HI-HI

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 TI-FA10541/ TI-FA10542  Instantaneous occurrence due to faulty  Check the transmitters through parameter trending. If found erratic,
and TI-FA20541/ TI- transmitter Call assistance of I&C for troubleshooting.
FA20542  Lubrication failure  Visual checking of the equipment
 Temp HI > 90 ◦C  Cooling water failure  Check the Cooling water supply
 Temp HI-HI > 95◦C  Excessive vibration  Check valve line up and valve throttling for lube oil to bearing
 For Bearing Temp HI-HI, should supply > 1.0 ksc but < 1.6 ksc
MFT will be triggered  For Bearing Temp HI-HI, Restart the unit when the repair is done
and no major damages on the equipment

19.0 DEAERATOR LEVEL LO/LO-LO

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 For D/A Level LO-LO, LSLL-  Stuck Up Deaerator Level Control Valve  For D/A Level LO-LO, immediately reduce load, then Reset the
CD11044 or LT-CD1104  Faulty Level Transmitters at Deaerator BFP breaker at MV MCC. For recovery of D/A level, increase the
1/2/3 (AVERAGE) < -2174  Sudden Opening of Emergency Drain to MV of D/A Level Control Valve or set it to manual. After level
mm {BFP TRIP COMMAND} Condenser recovers, restart the pump.
 Check the control valve and assess, apply troubleshooting if
 For D/A Level LO, LT- needed
ARP RESPONSE PROCEDURE

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


CD1104-1/2/3 (AVERAGE)  Verify the level transmitter with the local level gauge
< -150 mm  D/A LCV may be set on manual or increase MV of valve, Call
attention of I&C for troubleshooting
 For sudden opening of emergency drain to condenser, Close the
emergency drain to condenser

20.0 DEAERATOR LEVEL ABNORMAL

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 Any of the following is  Stuck Up Deaerator Level Control Valve  For D/A Level LO-LO, immediately reduce load for recuperation of
triggered:  Faulty Level Transmitters at Deaerator drum level, Reset the BFP breaker at MV MCC then restart the
- LSLL-CD11044  Sudden Opening of Emergency Drain to pump
- LT-CD1104 1/2/3 Condenser  Check the control valve and assess, apply troubleshooting if
(AVERAGE) : needed
LO-LO < -2174 mm  Verify the level transmitter with the local level gauge
LO< -150 mm  D/A LCV may be set on manually set or increase MV of valve, Call
HI > 200 mm attention of I&C for troubleshooting
HI-HI > 300 mm  For sudden opening of emergency drain to condenser, Close the
emergency drain to condenser

21.0 BFP AUTO START

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


CONDITIONS ON RUNNING BFP:  Check if the standby pump will Auto Cut in, check the parameters if
 BFP Electrical trouble in stable condition
 BFP lube oil pressure LO-LO < 1.0 ksc  Check the troubled BFP stop first out link
 Motor bearing temperature > 100 deg. C  For Electrical Trouble, call attention of Electrical maintenance
 Pump bearing temperature > 100 deg. C  Check the lube oil level at local and check for possible oil line
 Motor winding temperature > 150 deg. C leakage
 Pump vibration HH > 16.4 mm/s  Check the transmitter/s that cause tripping of BFP for possible
 Motor vibration HH > 14.1 mm/s erratic signal call attention of I&C
 BFP Suction DP HH≥ 1.0 ksc  For D/A Level LO-LO, increase the MV of the D/A Level Control
 BFP Outlet Pressure LL < 155 ksc Valve or have it manual
 For Suction DP HH, replace the strainer
ARP RESPONSE PROCEDURE

22.0 BFP A/B STOPPED

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 See “BFP AUTO START” possible causes  Check if the standby pump will Auto Cut in, check the parameters if
(except BFP pressure LL) in stable condition
 D/A Storage Level LO-LO  Check the troubled BFP stop first out link
 BFP Manual stop  For Electrical Trouble, call attention of Electrical maintenance
 Check the lube oil level at local and check for possible oil line
leakage
 Check the transmitter/s that cause tripping of BFP for possible
erratic signal call attention of I&C
 For D/A Level LO-LO, increase the MV of the D/A Level Control
Valve or have it manual.
 For Suction DP HH, replace the strainer

23.0 DRUM LEVEL HI/HI-HI

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 LIBR*001/2/3  Faulty Level transmitters  Check the reliability of the level transmitter, call attention of I&C
 Level: HI > 127 mm  Sudden opening of Drum Level control personnel for troubleshooting
HI-HI > 254 mm (MFT) valve (FCVFW*130-1) or start up valve  For Control valves sudden opening, check the DCS through
{ 2 out of 3 } ((FCVFW*130-2) parameter trending, Check the actual status of the valve locally and
 Passing bypass valve (V-FW*017) troubleshoot (communicate with CRO). If still exist, Call attention of
 Sudden opening of Blow-off valve maintenance for rectification
 Sudden opening of HP bypass valve  Retighten the bypass valve in close position
during normal operation  For Drum Level HI-HI, after repair or troubleshooting is done,
 Sudden Decrease of Load (Droop) Restart the unit
 House mode operations  For Housemode operation, Follow SOP for Housemode Operations

24.0 DRUM LEVEL LO/LO-LO


ARP RESPONSE PROCEDURE

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 LIBR*001/2/3  Faulty Level transmitters  Check the reliability of the level transmitter, call attention of I&C
 Level: LO < -178 mm  Sudden closing of Drum Level control personnel for troubleshooting
LO-LO< - 254 mm valve (FCVFW*130-1) or start up valve  For Control valves sudden closing, check the DCS through
(MFT) { 2 out of 3 } ((FCVFW*130-2) parameter trending, Check the actual status of the valve locally and
 Passing MBD or CBD troubleshoot (communicate with CRO). If still exist, Coordinate with
 Sudden increase of Load (Droop) AO to Open bypass line with close coordination with CRO to
 Closing of Mains steam Valves (CV or monitor flow and opening. Call attention of maintenance for
MSV) rectification
 Boiler Tube Leak  For passing valves, try to retighten in close position
 For Main Steam Valves, check for any valves for abnormal
opening, Check for flow demand and actual opening difference
must be <2% and maintain load
 For Drum Level LO-LO, after repair or troubleshooting is done,
Restart the unit
 For Boiler Tube Leak, See SOP for Boiler Tube Leak

25.0 COAL FEEDER OUTLET TEMPERATURE HI

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 TS-CL1061 > 70 ⁰C (varying  Sponcom of coal inside the coal  Check the alarm if exist at local and DCS. Assess the area and
per coal feeder) feeder remove possible source of heat and conduct housekeeping, if the
 LOGIC:  Erratic temperature switch/faulty physical conditions were at low risk, wait for the temperature switch
- If activated, the coal sensor to be reset. Then start again the coal feeder.
discharge valve will be close  External source of heat that hit the  Inspect the local for possible fire. If sponcom exist, manual
sensor/switch override the discharge valve of the coal feeder by: (For emergency
 Burned coal feeder discharge bellow only, call assistance of I&C immediately)
 Sealing Valve flow shortage *Removing the electrical actuation of the solenoid valve then
 Coal quality (wet coal) at discharge override the solenoid valve using screwdriver to open the position
plenum of coal feeder discharge valve and start the coal feeder
*Reassign the instrument tubing of the solenoid valve (instrument
tube of open position interchange with the outlet port of close
position and vice versa), Open the air supply to open the discharge
valve of the troubled coal feeder, then start the coal feeder {Note:
Make sure that the air supply must be close during the reassigning}
 If above mitigation is not effective, ask the CRO to stop the coal
feeder, open the covers and manually remove the sponcom.
ARP RESPONSE PROCEDURE

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 Check accuracy of transmitters. Verify using thermal gun or other
temperature measuring devices and immediately report to I&C
maintenance for corrective actions.
 For Burned Coal at Discharge Bellow:
*Verify the flow of the purging and sweeping valves. Adjust if
necessary
*Open the PA purging valve to scrape the burned coal into the
furnace.
*Increase the opening of the staging damper near the troubled coal
feeder to help sweep the coal.
*Immediately inform the CRO to stop the coal feeder and increase
the furnace draft to -25mmAq or more
 For Sealing Valve Shortage: Check sealing valve to its minimum
flow range, increase if necessary.
 For coal quality (wet), Increase sealing, purging and sweeping air.
Verify with the auxiliary operator for possible water ingression on
coal silo (if other coal silos were ok)

26.0 COAL SILO A/B/C/ ABNORMAL

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 Any of the following is  Coal silo level high sensor/transmitter  Verify actual level at coal silo by visual checking
triggered: activated.  If found overflow, contact MAH MCC to immediately stop the coal
-LSH-CL1008-A/B/C  Coal silo level low sensor/transmitter forwarding or ask permission to pull the cord.
-LSL-CL1008-A/B/C activated  Conduct purging of level transmitter. If level still high after a series
of purging, issue SR for checking of I&C maintenance.
L: 2.0 H : 7.0  Report to MAH MCC or inform your superior to ask their supervisor
LL: 1.0 HH: 7.5 for the next loading

27.0 COAL FEEDER A/B/C STOPPED


ARP RESPONSE PROCEDURE

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 Any of the following is  Coal feeder switched from remote to local  Confirm with other coal feeders if it compensates prior to the
triggered: (manual intervention) stoppage of the troubled coal feeder. (CRE).
-LSH-CL1008-A/B/C  Coal feeder discharge valve not open  Reduce load if necessary
-LSL-CL1008-A/B/C indication  Verify the Coal Feeder status in local if it is stopped and check the
 Motor &Gearbox problem selector at local panel if its on remote or local. If found local mode,
L: 2.0 H : 7.0  Signal fault from DCS to Field transmitter switch to remote and start the CF at DCS. (AO)
LL: 1.0 HH: 7.5 (busted fuses/relay)  For discharge valve not open indication,
-Mitigate by adjusting the open limit switch using the Allen
wrench
-Open the drain port of the valve and drain-out the accumulated
coal dust
-Open the top cover of the valve and remove the accumulated
coal dust
 If motor and gearbox problem, report to MMD&EMD
 Call I&C for assistance, bias the other coal feeder for coal flow

28.0 FURNACE PRESSURE HI/HI-HI

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 Furnace Pressure HI:  Pressure switch/ transmitters faulty/erratic  Manual control of IDF, PAF, SAF to maintain adequate furnace
PT-FG1085/1086/1087  Coal feeder belt slippage or coal feeder pressure. Report to IMD if confirm erratic.
AVERAGE > 30 mmH2O stoppage  Verify the status of IDF and hydraulic coupling in its parameters
 IDF and hydraulic coupling problem trend. Check the status of scoop tube and manually open if found
 PSHH-FG1085/1086/1087  Furnace Explosion/secondary combustion at fault. Call immediately maintenance for rectification
Furnace pressure is higher  Loss of all fuel/MFT  Check the reliability of the level transmitter, call attention of I&C
than 267 mmH2O, 5  Damper Problem (PAF, SAF, FAB) personnel for troubleshooting
Seconds delay (PAF stop,  Sudden drop of coal to the furnace (due  For furnace explosion, reduce coal and air
to accumulation after coal stoppage)  For Furnace pressure HI-HI, after repair or troubleshooting is done,
MFT TRIGGERED)
 Boiler Tube leak (Backpass Area) Restart the unit
 For Boiler Tube Leak, See SOP for Boiler Tube Leak
ARP RESPONSE PROCEDURE

29.0 FURNACE PRESSURE LO/LO-LO

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 Furnace Pressure LO:  Pressure switch/ transmitters faulty/erratic  Manually control of IDF, PAF, SAF to maintain adequate furnace
PT-FG1085/1086/1087  Coal feeder belt slippage pressure. Report to IMD if confirm erratic.
AVERAGE < -50 mmH2O  Boiler Tube leak  Verify the status of IDF and hydraulic coupling in its parameters
 Coal Feeder Stop trend. Check the status of scoop tube and manually close if found
 PSLL-FG1085/1086/1087  IDF Damper/Hydraulic Coupling Problem at fault. Call immediately maintenance for rectification.
Furnace pressure is lower  Check the reliability of the pressure transmitter/switch, call attention
than -267 mmH2O, 5 of I&C personnel for troubleshooting.
Seconds delay (PAF stop,  For belt slippage, locally check the status of coal feeder and adjust
the belt, accordingly, Reduce the Load if necessary.
MFT TRIGGERED)
 For Coal Feeder Stop, see “Coal Feeder Stopped” Remedial Action
 For Furnace pressure LO-LO, after repair or troubleshooting is
done, Restart the unit
 For Boiler Tube Leak, See SOP for Boiler Tube Leak

30.0 GAH STOPPED

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 If GAH speed low low  GAH motor/gear box problem  Confirm if SV-PA2052 (automatic supply air valve) will
occurs, 30 seconds timer will  Emergency stop push button triggered automatically open to drive the air preheater. If fail to open, put it in
activate before it signals IDF manual mode and open it as soon as possible.
to shut down.  Immediately verify in the local area if the motor really on stop
condition and air drive motor kick-in.
 If APH/GAH motor tripped condition occurred, contact EMD for
reset of breaker in the inverter panel
 If no tripping indication occurred or breaker finished to reset,
proceed to APH/GAH motor restart.
 Assign AO’s for manipulation of PA supply isolation valve of air
driven motor and for checking the pressure regulator.
 AO will close MIV slowly until approaching close and will closely
monitor the dropping of pressure at pressure regulator. Also check
the speed of the motor if it decreases.
 If the pressure drops approaching 0psi and speed of the motor
decreases, communicate to CRE. At DCS wait for the speed low
ARP RESPONSE PROCEDURE

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


indication activate
 If speed low indication activates, start immediately the APH/GAH
motor at DCS.
Note: Do not wait for the speed low low indication to occur before
starting. But if speed low low occurs, 30 seconds timer will activate
before it signals IDF to shut down.
 When APH motor successfully started, normalize the MIV for its
protection.

31.0 B/A SCREW COOLER STOPPED

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 Stop command  Verify the actual status in the local
 Electric trouble/tripped due to overload  Report to EMD and ask assistance for the restoration of the
 Clogged up at BASC Cooler equipment then restart the unit
 Unclog the BASC cooler if found clogged

32.0 IRP POWER SUPPLY FAULT / ARP SYSTEM ALARM

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 Check the PDP and IRP/ARP Panel breaker status
 Call I&C for assistance

33.0 MAKE UP WATER PUMP STOP


ARP RESPONSE PROCEDURE

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 MWP differential pressure > 1.0 ksc  Verify and check at DCS if stand by pump starts automatically. If
 Demi water tank level low @<0.2m not, start it manually or locally.
 Faulty transmitter/s  Verify and check actual status of the pump on local
 Electrical trouble/motor problem/pump  Check and verify accuracy of DP transmitters and level transmitters
problem in its parameters trend at DCS. Report to Maintenance team if
necessary
 For motor or pump problem, Report to MMD/EMD for checking
and troubleshooting

34.0 MAKE UP WATER AUTO START

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 MWP common pressure low< 5.6 ksc  Verify and check at DCS if stand by pump starts automatically. If
 Running make up water pump stopped not, start it manually or locally.
 Verify and check at DCS if other MWP stopped.
 Check if MVMU1001(motorized valve make up)has an opening

35.0 FEEDWATER HEATER LEVEL ABNORMAL

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 HPH-1, HPH-2, LPH-1,  Stuck up/clog up level control valves  Switch level control valve to manual mode, then try to give open
LPH-2, LPH-3 (alternating and cascading) of the troubled command to LCV to confirm if the valve stuck.
 Any of the following heater  Open cascading drain bypass valve (if level high) by AO
transmitter or switch can  Faulty Level transmitter/switch If low, check for possible line leakage
trigger level abnormal  Possible tube leak if level keeps increasing  For faulty switch/ transmitter, Check and verify parameters trend in
 For HPH-1: and uncontrollable DCS. Verify level thru level gauge at the local field.
LS-HD1105 ,LICHD1105  Safety valve and drain valves passing  For Tube leak,
 Passing alternating drain control valve -Check the difference between pressure at inlet and outlet of
 For HPH-2: heater versus previous readings
LS-HD1106 ,LICHD1106 -Check the cascading drain opening during specific load vs
previous reading
 For LPH-1: - Isolate the trouble feedwater heater if deemed necessary
LS-HD1101 ,LICHD1101

 For LPH-2:
LS-HD1102 ,LICHD1102
ARP RESPONSE PROCEDURE

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 For LPH-3:
LS-HD1103 ,LICHD1103

36.0 COOLING WATER PRESSURE ABNORMAL

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 PT-CW1156  Faulty transmitter  Verify and check at DCS if the pressure at the discharge of ACWP
H: > 7ksc L: < 5ksc  Closed Cooling System line leakage and discharge of CCWHE is below 3.5 ksc
 ACWP pump stopped  Verify if standby pump starts automatically. If not, check the status
 ACWP discharge pressure low of pressure transmitters at BASC with verification with other local
 ACWP Strainer with high DP pressure gauges.
 Expansion tank level low  For ACWP stopped, check the status at local and verify the cause
of stoppage/trip
 For Strainer at high DP, Conduct servicing of strainer
 For expansion tank level low, Check make up water supply to
expansion tank in auto, If not, manually open the valve to achieve
optimum/normal level

37.0 PLANT AIR COMPRESSOR A/B/C

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 Motor Bearing Temperature High - High  Verify if standby pump starts automatically. If not, locally start
 Main Motor Fault (Winding Temperature standby air compressor. Make sure that the system pressure is
High-High stabilized.
 Final Stage Air Inlet Temperature High-  For motor bearing fault, Visual checking of motor bearing condition
High and conduct thermal gun scanning for temperature high-high
 Lube Oil Level Low-Low verification
 Lube Oil Temperature High-High  Check air ejector for lube oil if pressure is on range
 Compressor 2nd and 3rd vibration high-  Check Cooling water supply
high  Check for lubricating oil filter DP or possible leaks in the line
 Lube Oil Pressure Low-Low  Coordinate to Electrical team Compressor Motor

38.0 INSTRUMENT AIR COMPRESSOR A/B/C


ARP RESPONSE PROCEDURE

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 Motor Bearing Temperature High - High  Verify if standby pump starts automatically. If not, locally start
 Main Motor Fault (Winding Temperature standby air compressor. Make sure that the system pressure is
High-High stabilized.
 Final Stage Air Inlet Temperature High-  For motor bearing fault, Visual checking of motor bearing condition
High and conduct thermal gun scanning for temperature high-high
 Lube Oil Level Low-Low verification.
 Lube Oil Temperature High-High  Check air ejector for lube oil if pressure is on range
 Compressor 2nd and 3rd vibration high-  Check Cooling water supply
high  Check for lubricating oil filter DP or possible leaks in the line
 Lube Oil Pressure Low-Low  Coordinate to Electrical team Compressor Motor

39.0 INSTRUMENT PRESSURE LOW-LOW

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 All Instrument air compressor stopped  Check if Standby IA Compressor Auto Cut In, If not manually start
 TRANSMITTERS: (AND  Possible Severe Leak on Instrument Air standby IA Compressor c/o Auxiliary
SIGNAL) Piping  If leak is verified, check for possible isolation and checking of
-PT-IA1706 < 3.5ksc  Instrument Failure (Transmitters/Indicators) affected instrument.
-PSL-IA1706  For faulty transmitter or switch, immediately call I&C team for
 MFT will be triggered rectification/bypass.
 If the repair/ troubleshooting is done. Restart the unit.

40.0 DIESEL OIL PUMP A/B STOPPED

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 Motor Electrical Fault  Check for standby pump to auto cut In, If not manually start the
 Motor Bearing Failure pump at DCS or in Local.
 Immediately call Electrical Team for Motor Check

41.0 DIESEL OIL PUMP OUTLET PRESSURE LOW


ARP RESPONSE PROCEDURE

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 Motor Suction Filter High DP  Check for standby pump to auto cut In, If not manually start the
 TRANSMITTERS:  Pump Stopped pump at DCS or in Local.
* PT-DO0005  Unit Start Up (or other unit start up)  Changeover Duplex Oil filter
L : 5 ksc ANN(OPC)  Diesel Leakage at pipeline, Relief valve  Supply valve must be throttled to 50%
LL: 3 ksc ANN(CRT) passing  Check the line for leakages, if found, retighten if able to. If its
 Oil return line control valve stuck severe, file SR for maintenance rectification
up/actuator problem  For control valve problems, check the parameters at DCS.
Troubleshoot at local if able to. If not, call attention of maintenance
personnel

42.0 HOT REHEAT STEAM PRESSURE HIGH

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 HPH 2 Level High at Full Load  Check if Reheater Blow off valve open. Manually control if needed
 TRANSMITTERS:  HP Bypass Valve passing to. Stabilize reheater line.
* PI-HR1003-1/2  Sudden Increase in R/H desuperheater  For HPH-2 high level, Check level or in Auto Mode. and used
H : > 39 ksc spray emergency drain to condenser if necessary.
 SH2 – Reheater Motorized Valve sudden  For HP Bypass Valve passing:
opening *Check the PV vs MV of control valve (CRE)
*Verify the opening at local (AO)
*Command close position to the valve (CRE)
*If abnormal position still exist, call attention of the I&C
maintenance
 For sudden increase of reheater desuperheater, Check for biasing
damper/temperature signal abnormal. If normal status, check the
reheater desup control valve status, then troubleshoot if needed.
Call attention of I&C if problem still exist.
 For SH-2 to Reheater motorized valve, close the motorized valve
and call attention of EMD
ARP RESPONSE PROCEDURE

43.0 HOT REHEAT STEAM PRESSURE LOW

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 LP turbine bypass valve passing/ or Open  For start up and house mode operation, check for LP bypass valve
 TRANSMITTERS:  RH Blow Off valve passing auto set value (>7.5 ksc) and LP bypass valve opening for manual
* PI-HR1003-1/2  Sudden opening of C/R to auxiliary control operation.
L: < 7 ksc valve  For RH Blow off passing, Manually close BOV.
 Faulty transmitter/s  For sudden opening of C/R to aux, Check PV vs MV of C/r to Aux
valve with verification at local then check the equipment supplied
by the auxiliary steam line.
 Check reliability of transmitter/s. If found erratic, call attention of
I&C personnel.

44.0 REHEATER OUTLET TEMP HIGH

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 Unequal opening of biasing damper  Check for biasing damper stuck up and conduct venting on its IA
 TRANSMITTERS:  Abnormal Operation of desuperheater or supply to restore back to its auto position.
* TT-HR1002-1/2 (AVE) valve hunting.  Open bypass of desuperheater at local with precaution and close
H: > 548 ⁰C  Faulty transmitter/s coordination with the CRE
 Check reliability of transmitter/s. If found erratic, call attention of
I&C personnel.

45.0 CONDENSER VACUUM LOW

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 Auxiliary Steam Pressure Low (<7 ksc) at  Manually operate if necessary at 9-10 ksc.
 TRANSMITTERS: auxiliary header  Check if the Cold R/H supply pressure less than 9.5 ksc which
PT-ST1110-1/2/3 > 0.14 causes supply valve to Auxiliary steam to closed
kscA
 LP Exhaust Hood Temperature High  Manual open if LP exhaust hood spray if necessary

 Gland Steam Pressure abnormal  Check for setting and pressure transmitter abnormal reading.
 Call I&C Team for rectification of transmitters

 Insufficient Cooling water supply to  Check the condenser inlet and outlet pressure. If not enough
condenser (Sea Water) pressure, check the status of the seawater line for possibles leaks.
Run the other seawater if deemed necessary.
ARP RESPONSE PROCEDURE

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 Conduct venting of condenser outlet and inlet for possible air
intrusion at waterbox.

 Passing control or motorized valves  Check the activity prior to worsening of vacuum.
connected to flash chamber (heater  Double check at local and provide checklist (extraction, pressure
drains, extraction line, drain pots) heaters and drains connected to flash chamber)
 Check the temperature of flash chamber if it increases versus
previous readings. Call attention of NDT for verification of valves
for possible passing

 Air leaks ( LP Exhaust Hood , Vacuum  Check the activity prior to the worsening of vacuum. Double check
Breaker, CEP Canister pinhole or sealing the sealing of vacuum related valves and equipment
problems)  Check the U-seals at gland steam condenser, fill if necessary

 Main air ejector auxiliary steam Y-strainer  Check the pressure of auxiliary steam at inter condenser and after
clogged or stem trap passing condenser if it is in range. If not, check the valves at local and
reliability of pressure gauge.
 Call attention of NDT for verification of clogged up and passing
steam trap

 Condenser Hotwell Level High  Open the condenser to ditch drain valve

46.0 LP EXHAUST STEAM TEMP HIGH

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 Condenser Vacuum Low  Check if the LP exhaust hood spray will open. Manually open the
 TRANSMITTERS:  Low load Operation valve.
* TE-ST1110-1/2/3 >80 DEG  House Mode Operation  For Condenser Vacuum Low, see “Condenser Vacuum Low
CELCIUS - ALARM  Faulty transmitter/s Remedial Action”
 For Low load Operation, Follow Start up Procedure
 For House Mode Operation, follow WI for House Mode Operation
 Check the reliability of transmitter/s. If found erratic, call attention of
I&C for troubleshooting

47.0 HP EXHAUST STEAM TEMP HIGH


ARP RESPONSE PROCEDURE

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 Low load Operation  Decease the Main Steam Temperature
 TRANSMITTERS:  House Mode Operation  Attain Transfer Region Completed
* TE-ST1003-1/2/3 >400 DEG  Faulty transmitter/s  Increase MW loading
CELCIUS - ALARM  Ventilator Valve Fault  For Low load Operation, Follow Start up Procedure
 Certain Opening of CV  For House Mode Operation, follow WI for House Mode Operation
 Check the reliability of transmitter/s. If found erratic, call attention of
I&C for troubleshooting
 For Ventilator valve fault, check status at local. Manually open if
found at close position

48.0 BEARING OIL PRESSURE LOW

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 Faulty transmitters  Check if the standby pump will auto cut in at DCS and at local.
 TRANSMITTERS:  Leak at discharge line (Flange)  Check the reliability of transmitter/s. If found erratic, call attention of
* PT-LO1003-1/2/3 < 1.3 ksc  Low Level in the main Oil tank I&C for troubleshooting
 Duplex Oil Filter High DP  For low level, call attention of MMD for refilling of main oil tank
 MOP/Motor Problem  For Duplex high DP, changeover the filter
 Defective PRV  For MOP problem, check for unusual sound and bearing status
 Clogged Lube oil heat exchanger through thermal gun scanning. Call attention of performance for
status check and maintenance for rectification
 For Lube oil heat exchanger, changeover the heat exchanger, then
call attention of MMD for rectification.

49.0 CONTROL OIL PRESSURE LOW

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 Faulty transmitters  Check for standby pump to auto cut in and check If pressure
 TRANSMITTERS:  Leak at control oil dowstream line (relay stabilized.
* PT-LO1006-1/2/3 > 133 ksc dump valve/fast acting solenoid valve  Check for any valves for abnormal opening
passing)  Check for flow demand and actual opening difference must be <2%
 Control Oil Filter High DP  Maintain load
 COP Motor/ Pump problem  For Duplex high DP, changeover the filter
 For COP problem, check for unusual sound and bearing status
through thermal gun scanning. Call attention of performance for
status check and maintenance for rectification
ARP RESPONSE PROCEDURE

50.0 NO. 1/2 TURBINE SHAFT VIBRATION HIGH

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 Faulty transmitters  Check the reliability of transmitter/s. If found erratic, call attention of
 TRANSMITTERS:  Critical Speed (Start UP) I&C for troubleshooting
* VE-ST1001-1/2 > .125mm  Sudden Change in Load (Droop)  Follow start up curve
 Bearing temperature high  Check Grid Disturbance Emergency procedure
 Uneven expansion  Check Lube Oil Cooling water supply and TCV SV (46 deg. C)
 Early Steam Admission  Turning Gear Operation at least 24 hrs (prior to steam admission)

51.0 NO. 3/4 GENERATOR VIBRATION HIGH

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 Faulty transmitters  Check the reliability of transmitter/s. If found erratic, call attention of
 TRANSMITTERS:  Critical Speed (Start UP) I&C for troubleshooting
* VE-GE1001-1/2 > .125mm  Sudden Change in Load (Droop)  Follow start up curve
 Bearing temperature high  Check Grid Disturbance Emergency procedure
 Uneven expansion  Check Lube Oil Cooling water supply and TCV SV (46 deg. C)
 Early Steam Admission  Turning Gear Operation at least 24 hrs (prior to steam admission)
 Generator Cooling water supply low  For the generator cooling water supply low, check the flow through
the sight glass verification at temperature gauges. If air bubbles are
seen, provide venting.

51.0 GCB OPEN

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 MFT Activated  See “ Boiler MFT Remedial Action”
 Turbine trip Activated
 Generator Trip Activated
ARP RESPONSE PROCEDURE

52.0 COAL MASTER FORCE MANUAL

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 Any Coal Feeder Demand > 83.3%  Check the coal feeder status at local, if no abnormalities seen
 Any Fuel Flow Signal Abnormal REMOTE back the coal master
 Any Fans Flow Control Not In Remote  Check the status of fan dampers at DCS and at local
 All Coal Feeders In Manual

53.0 BFP DISCHARGE PRESSURE LOW

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 ARCV/ Check Valve of Discharge valve  Verify at DCS through parameter trending. Call assistance of
passing NDT for the passing valves verification.

 BFP STOPPED  See “BFP STOPPED Possible Cause and Remedial Action”
 Hunting Of Desuperheater Valves During  Check Desuperheater valves at DCS and at local if hunting is
Load Up/Down observed. If found erratic, Call attention of I&C for troubleshooting

 Boiler Tube leak  Follow SOP for Boiler Tube Leak

 Faulty Transmitter  Check the reliability of transmitter/s. If found erratic, call attention
of I&C for troubleshooting
 HP Bypass/Reheater Desuperheater  Verify at DCS through parameter trending. Check locally the
Check Valve Passing valve. Call assistance of NDT for the passing valves verification.

 Sudden opening/closing of Valves or  For Control valves sudden opening, check the DCS through
passing valves on Boiler Steam, Main parameter trending, Check the actual status of the valve locally
Steam System (Main FCV, MBD, CBD, and troubleshoot (communicate with CRO). If still exist, Call
Blow off, Bypass system) attention of maintenance for rectification

54.0 TURNING GEAR FAILURE

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 Turning Gear Motor Failure  Check the turning gear at local, try to reset and start again
 Permissive not comply.  Check the MSV and ICV if full close, bearing pressure at normal
and hand turning solenoid valve not triggered
ARP RESPONSE PROCEDURE

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 Immediately call assistance of Electrical Maintenance if it fails
again.
 Proceed with Hand Turning

54.0 SINGLE ELEMENT SELECTED

CONDITIONS POSSIBLE CAUSE REMEDIAL ACTION


 Faulty/ Erratic Flow, Temp Transmitters  Check the reliability of transmitter/s. If found erratic, call attention of
(Eco Inlet, Main Steam) I&C for troubleshooting
 Boiler Main Steam Flow < 100t/H  Check at DCS and at local the status of Boiler Water System.
 Manually Select Single Element Report any abnormalities found.