Professional Documents
Culture Documents
Electric Malfunction
Protective Relays
1. Defects in electrical systems are bound to occur at some point of time. However
when a failure occurs it must be quickly detected & disconnected from the system.
► Disconnecting and isolating faulty equipment in time in order to protect and
maintain the power supply to the remaining healthy circuits in the system
► Limit the amount of damage
► Protecting personnel from electric shock
2. Detection and Disconnection can be achieved using
► Fuses or
► Relays in conjunction with Circuit Breakers
3. (a) FUSES - Performs both detection and interruption function automatically but its
use is limited for protection of LOW Voltage circuits only
(b) RELAYS & CIRCUIT BREAKERS - for HIGH Voltage circuits
► The Relays detect the fault and
► Circuit Breaker performs the disconnection
Protective Relays – Principle of Operation
A protective relay is a device that detects the fault and initiates the breaking
operation of the circuit breaker to isolate the defective element from the
circuit
1. The relay circuit connection can be divided into 3
parts
● the primary winding of a current
transformer (CT) which is connected in
series with the line to be protected
● the secondary winding of CT and the relay
operating coil
● the tripping circuit. It consists of a source
of supply, the trip coil of the circuit breaker
and the relay stationary contacts
► Electromagnetic attraction
► Electromagnetic induction
d1 d d 2
i1 α (1max sin t ) and i2 2 max sin (t )
dt dt dt
1max cos t 2 max cos t
Electromagnetic Induction Type
Also F1 1 i2 and F2 2 i1
From the diagram it can be seen that the two forces F1 and F2 are in opposition
Therefore the resultant force F is
F = F2 - F1
2 i1 - 1 i2
2max sin (t + ) 1max cos t - 1max sin t 2max cos (t + )
1max 2max [ sin (t + ) cos t - sin t cos (t + ) ]
1max 2max sin …… [sin (A-B) = sinAcosB – cosAsinB]
F 1 2 sin
where 1 and 2 are the r.m.s. values of the fluxes.
Electromagnetic Induction Type
F 1 2 sin
(a) Greater the phase angle between the fluxes, greater is the resultant force applied
to the disc. The maximum force will be produced when the two fluxes are 900 out of
phase
(b) The direction of the resultant force and hence the direction of motion of the disc,
depends upon which flux is leading.
The following three types of structures are commonly used for obtaining the phase
difference in the fluxes and hence the operating torque in induction relay:
(i) Shaded pole structure
(ii) Watthour-meter or double winding structure
(iii) induction cup structure
T 1 2 sin
Induction Cup Structure
10. Under normal operating condition, restraining torque is greater than driving torque
produced by the relay coil current. Therefore the aluminium disc is stationary.
11. If the current in the protected circuit exceeds the preset value, the driving torque
becomes greater than the restraining torque. Consequently, the disc rotates and
moving contact bridges the fixed contacts when the disc has rotated through a pre
set angle. The trip circuit operates the circuit breaker which isolates the faulty
section.
Operation of Reverse Power Relay
T α Φ1 Φ2 sinα
Since Φ1 V ; Φ2 I and α = (90 - ɵ)
T V I sin (90 - ɵ)
T V I cos ɵ
T α power in the circuit
Cont…..
Operation of Reverse Power Relay (Cont…..)
4. The direction of driving torque on the disc depends on the direction of power flow
in the circuit.
5. When the power in the circuit, flows in the normal direction, the driving torque and
the restraining torque (due to spring) help each other to turn the moving contact
away from the fixed contacts and the relay remains inoperative.
6. When the direction of power reverses the driving torque reverses. When the driving
torque is large enough the disc rotates in reverse direction and the moving contact
closes the trip circuit and the circuit breaker contacts open. A time delay
of 5 seconds is also provided so as to prevent tripping during synchronizing
process. The general reverse power settings are 2 to 6% for turbine power movers
and 8 to 15% for diesel engines.
Induction Type Power Relay
4. The scheme comprises three current line transformers, one mounted in each
phase having their secondaries connected in parallel.
5. A relay is connected is connected in parallel across the transformer secondaries
6. Under normal conditions, equal currents flow through the different phases of the
alternator and their algebric sum is zero and no current flows through the operating
coil of the relay.
7. When imbalance occurs, the currents induced in the secondaries will not be zero
and the resultant current will flow through the relay coil.
8. The operation of the relay will trip the circuit breaker.
Protection Discrimination
3. If the inverse time current curves (trip curves) of the Main Breaker X, Feeder Breaker Y
and Branch Breaker Z are placed on the same graph, there should not be any
overlapping of the curves, which indicates that the breakers are coordinated.
Instrument Transformers
3. For measurement of power of a high voltage circuit, a wattmeter of low rating can be
used where the current coil and potential coil of the wattmeter are connected to the HV
circuit through a Current Transformer and Potential Transformer respectively.
Current Transformer
5. The secondaries of all current transformers are rated at 5A, irrespective of the
primary current rating.
Current Transformer
6. A 1000A current transformer has a ratio of 200 : 1. The ratio of primary and
secondary turns will be 1 : 200.
7. The primary of a CT may be of the form of a bar as shown above. The secondary is
insulated from the primary and is assembled on a core.
8. The main difference between a CT and a two winding power transformer is that the
PRIMARY CURRENT of a CT is determined by the load on the system and not the
load on its secondary.
9. If by chance the secondary is open-circuited, the whole of the primary current (load
on the system) will work as a magnetising current. A dangerously high voltage will
be induced in the secondary winding (Ns > NP). This high voltage can cause damage
to the insulation and also give a fatal shock to the operator, hence the secondary of
a current transformer must always be earthed
Potential Transformer
1. Potential transformers (PT) are similar to power transformers except that their
power rating is considerably low.
2. The primary of a PT has more number of turns compared to its secondary turns.
3. The primary winding is connected across the high voltage system whose voltage is
to be measured.
4. The secondary winding is usually rated for 110V irrespective of the primary voltage
rating. With the secondary winding wound for 110V, the primary is wound for the
voltage which is to be measured
eg. If a voltage of 6.6 KV is to be measured, the PT will have a turns ratio of
6.6x1000 /110 ie. 60 : 1
5. To ensure safety of the operator, the secondary of the PT should be earthed