TOTAL OR PARTIAL REPRODUCTION AND/OR UTILIZATION OF THIS DOCUMENT ARE FORBIDDEN WITHOUT PRIOR WRITTEN
AUTHORIZATION OF PT PERTAMINA EP
In regards with fax of President Director of PT. Pertamina (Persero), No.147/C00000/2021-SO, dated 07
April 2021, regarding the requirement to increase safety awareness, operation excellence, application of
standards and best practice, in Pertamina’s storage tanks infrastructure following the fire incident in
Storage Tank RU VI Balongan.
Also, following the Letter of Directorate of Development & Production sub holding Upstream No.
004/PHE2000/2021-SO, dated 2 July 2021, regarding the Implementation Team to Increase Awareness
of Safety and Operational Aspects in the storage tanks infrastructure in Pertamina's Upstream Sector.
Both letters became the basis for Pertamina sub holding upstream (SHU) team to conduct self-
assessment on some of the storage tanks infrastructure in the upstream sector.
The results of self-assessment show that there is a need for improvement of safety aspects in the
infrastructure. The determination of the priority scale of implementation of improving safety and operational
aspects in the storage tanks infrastructure in the Upstream – Pertamina sector has been carried out on 7
important elements, namely lightning protection system installation, overflow prevention, CCTV online
surveillance installation, availability of alarms or hazard sirens, early detection and firefighting systems,
external audits and improvement of operator competence.
PT. Pertamina EP Region 4 Zona 14 has conducted voluntary inspection and survey for area of SP
Klamumuk, SP-1 Klamono, SP-2 Klamono, SP-3 Klamono, SP-4 Klamono, SPU Klamono, SP Linda, SP
Sele, Salawati, SPU Salawati, Terminal Sorong & Walio Pump Station. Based on the results of voluntary
inspection and survey there are 40 tanks that need to be further improved.
Figure 1.1 Work Locations of PT Pertamina EP Region 4 Zona 14, Papua Field
In the first priority of handling and improving safety aspects in the storage tanks infra-structure in PT
Pertamina EP Field Papua area focused on 4 aspects:
Lightning Protection System & Grounding System;
Installation CCTV;
Alarm System & Public Announcer (Siren Hazard);
Overfill Protection;
The main result of the deliverable FEED Study Enhanced Tank Safety Protection (40 Units) is that the
design of tank protection against fire and overflow events will be able to be monitored by CCTV in real
monitoring and besides that, handling fire and overflow events is no longer manually, but has been
integrated into a system prevention and emergency response.
PEP-SP-SAL-CV-CAL-201 – Rev- 0 Page 6 of 21
PT PERTAMINA EP REGION 4 ZONA 14
The purpose of this document is to provide engineering design calculation related to the foundation of
Produced Water/Wash Tank within Produced Water Tank Salawati Project located in PT Pertamina
EP Zone 14.
3. DEFINITION
A Area
c Soil Cohesion
LC Load Combinations
Unit weight
μ Friction Coefficients
σ Stress
ϕ Friction Angle
DL Dead Load
L Live Load
S Seismic Load
SF Safety Factor
5. REFERENCE
Design basis and other specifications used in this document are in line with PT Pertamina EP Asset 5
Project documents.
No. Document Number Document Title
1. PEP-00-A0-SP-0001 Civil and Structural Design Basis
1. PEP-00-A3-SP-0001 Specification for Foundation
1. PEP-00-A5-SP-0001 Specification for Steel Structure
6.1. Material
Material used for this project calculation as follows in table below:
Table 6.1 Material Unit Weight
7.1. General
This chapter presents foundation calculation for produced water tank. The detailed calculation is presented
in Attachment A.
Soil data used in this document are derived from CPT Tests performed by UPTD Laboratory Sorong in
2017.
Figure 7.1 Response Spectrum Graph Salawati Area for Soft Soil
LC Description
111 DL + E(E) + WX
112 DL + E(E) + WY
121 DL + E(O) + L
122 DL + E(O) + 0.75L + 0.75WX
123 DL + E(O) + 0.75L + 0.75WY
124 DL + E(O) + WX
125 DL + E(O) + WY
126 DL + E(O) + 0.75L + 0.525S
127 DL + E(O) + 0.7S
131 DL + E(T) + L
132 DL + E(T) + 0.75L + 0,25WX
133 DL + E(T) + 0.75L + 0,25WY
LC Description
211 0.9DL + 0.9E(E) + S
212 0.9DL + 0.9E(E) + 0.8WX
213 0.9DL + 0.9E(E) + 0.8WY
221 1.2DL + 1.2E(O) + 1.6L
222 1.2DL + 1.2E(O) + L + 1.6WX
223 1.2DL + 1.2E(O) + L + 1.6WY
224 1,2DL + 1.2E(O) + L + S
231 1.2DL + 1.2E(T) + 1.6L
232 1.2DL + 1.2E(T) + L + 0,8WX
233 1.2DL + 1.2E(T) + L + 0,8WY
- Qb = qu. Ap (ton)
- qu = 15Np (t/m2) for Bored piles, = 0.5
- qu = 30Np (t/m2) for driven piles
- Qs = fs. As (ton)
- fs = Ns/5 (t/m2) for Sand
- fs = Ns/2 (t/m2) for Clay
V M * PCD1
- Maximum pile reactions =
np 2 * Ip
Where:
H = yo * kh * D / [ 2 * * ( e * + 1 ) ]
= [ kh * D / ( 4 * Ec * Ic ) ]0.25
Where:
The following Table shows the results of Pile Reactions and Bearing Capacity checks
Allowable Pile
Reaction per Pile( tons ) Capacity Result
Load Combinations (tons)
Vmax Vmin Hmax V(comp) H(lateral)
Design
Parameter Condition Limit Remarks
Results
Pile Settlement Elastic 0.81mm 25.40mm Ok
Structural Description
Unit Design
Element
Pile Cap Slab Length per m mm 1000
Thickness mm 450
Reinforcement - D16-150
2 layers both ways
: 25-Apr-20
JASA FEED & DED PERTAMINA EP (BLANKET ORDER) Date
2. EXTERNAL LOAD
qz = velocitiy pressure evaluated at height z of the centroid of area Af above the ground
qz = 0.613 Kz Kzt Kd V2 (N / m2)
Cf = force coefficient from fig. 6-21 through 6-23 of ASCE-7
Kd = The wind directionallity factor = 0.95 table 6-4 ASCE-7
Kz = The velocity presure exposure coeficien, from table 6-3 Exposure C of ASCE-7
Kzt = 1.0 The topographic factor
V= 24 m/s Basic wind speed
G = Gust effect factor
Height
above
Exposure C
ground
level, z
m Case 1 & 2
0 - 4.6 0.85
6.1 0.90
7.6 0.94
9.1 0.98
12.2 1.04
15.2 1.09
18 1.13
CALCULATION SHEET OF FOUNDATION
FOR T101 TANK SALAWATI
Revision : A
: 25-Apr-20
JASA FEED & DED PERTAMINA EP (BLANKET ORDER) Date
Height
above
ground
level, z qz = qh
m N / m2
0 - 4.6 285.12
6.1 301.89
7.6 315.31
9.1 328.72
12.2 348.85
15.2 365.62
18 379.04
m m
: 25-Apr-20
JASA FEED & DED PERTAMINA EP (BLANKET ORDER) Date
Pdesign = qz G Cf (N / m2)
Pdesign
Height
h/D h/D = 0.933 h/D = 7 h/D = 25 h/D = 1 h/D = 7 h/D = 25
(m) 1.249 7 25 N / m2 N / m2 N / m2 kg / m2 kg / m2 kg / m2
0 4.6 0.504 0.6 0.7 128.03 152.37 177.76836 13.05 15.53 18.12
4.6 6.1 0.504 0.6 0.7 135.44 161.19 188.053857 13.81 16.43 19.17
6.1 7.6 0.504 0.6 0.7 141.31 168.18 196.210292 14.41 17.14 20.00
- h/D = 1.249
- Cf = 0.504
Equipment Data :
OD = 6096 mm
H1 = 7315 mm
Hs = 300 mm
Ht = 7615 mm
C.o.G = 3657.5 mm
CALCULATION SHEET OF FOUNDATION
FOR T101 TANK SALAWATI
Revision : A
: 25-Apr-20
JASA FEED & DED PERTAMINA EP (BLANKET ORDER) Date
H1 Ht
ID
TOP OF
FOUNDATION Hs
Seismic load from equipment derived from mechanical laoding data. Seismic load from selfweight of structure shall be calculated in
accordance with design spesification with reference to SNI-03-1726-2019.
CALCULATION SHEET OF FOUNDATION
FOR T101 TANK SALAWATI
Revision : A
: 25-Apr-20
JASA FEED & DED PERTAMINA EP (BLANKET ORDER) Date
Equipment Unit
Using SNI 03-1726-2012 for calculate seismic load for equipment, which have parameter :
Cs = SDS x Ie
R
where ;
Importance Factor Ie = 1.25
Reduction factor R = 2.50
Acceleration respons spectrum SDS = 0.487
Coefficient of seismic Cs = 0.24
Lateral Forces
He1 = Cs.EO = 51.18 tonne
Moment at bottom of Foundation
Me1 = He1* H1/2 = 195 ton.m
Foundation
Using SNI 03-1726-2012 for calculate seismic load for foundation, which have parameter :
Cs = SDS x Ie
R
where ; Ie = 1.25
Importance Factor R = 2.00
Reduction factor SDS = 0.487
Acceleration respons spectrum Cs = 0.30
Coefficient of seismic
Lateral Forces He2= Cs.Wc = 19.20 tonne
: 25-Apr-20
JASA FEED & DED PERTAMINA EP (BLANKET ORDER) Date
: 25-Apr-20
JASA FEED & DED PERTAMINA EP (BLANKET ORDER) Date
CL
D1
D2
GL
h3 h4
h2
hf
3.2. Pile Arrangement.
h1
- TYPE = corner
- Diameter of pile : p = 0.4 m
- Length of pile : L = 4.4 m Pile Arrangement Ilustration
- Dist. between PCD = 6.75
: 25-Apr-20
JASA FEED & DED PERTAMINA EP (BLANKET ORDER) Date
Loading Combinations V H M
( Tons ) ( tons ) ( tm )
Hp = H / np
CALCULATION SHEET OF FOUNDATION
FOR T101 TANK SALAWATI
Revision : A
: 25-Apr-20
JASA FEED & DED PERTAMINA EP (BLANKET ORDER) Date
Allowable Pile
Reaction per Pile( tons ) Result
Load Combinations Capacity (tons)
5. REINFORCEMENT OF FOUNDATION.
5.1. Factored Loading Combination at Bottom of Footing.
Loading Combinations V H M
( kN ) ( kN ) ( kNm )
: 25-Apr-20
JASA FEED & DED PERTAMINA EP (BLANKET ORDER) Date
Re-bar arrangement
m = fy / (0.85 x fc') = 24.72
Rn = Mu / (0.9 x Df x deff2) = 0.892 N/mm2
0.5
= {1 -(1 - 2 x m x Rn / fy) } / m = 0.00230
4/3 = 0.00306108
req. = 0.00306108
2
Asmin. = D1 x h1 x min/2 = 3240.00 mm ,(for shrinkage reinforcement)
2
Asreq. = D1 x deff x req. = 9183.24 mm ,(governed)
Use rebar Dia. = 16 mm
No. of rebar = 46
Rebar spacing (s) = 170 mm
Rebar spacing prov'd = 150 mm
No. of rebar prov'd = 54
As provided = 10857.34 mm2
L1 = p + deff
= 0.775 m
L2 = (D1 - Pcd1) * 0.5
= 2.75 m
bo = 2*L2 + 0.5 * * L1
= 6.72 m
0.5
Vppc = 0.85 x 1/3 x fc x bo x deff = 3114.31 kN > Vupp......OK..!
The following anchor bolt design was found to be satiesfied all design requirement
Concrete Grade
K-225 equivalent with f c' = 186.75 kg/cm2
where,
fc' = Specified compressive strength of concrete
A = Embedment length/depth of anchor bolt
D = Projection length
Tb = Anchor bolt nut thickness
e = edge distance
L = Total anchor bolt length
d = Anchor bolt diameter
Description UC
Shear capacity due to anchor bolt material 0.228
Shear capacity due to concrete breakout strength 0.123
Shear capacity due to concrete pryout strength 0.012
Hence,
a single 20 mm diameter anchor at 200 embedment depth is adequate to resist the applied
service tension and shear loads of 35265 kg and 9296 kg, respectively.
ANCHOR BOLT DESIGN CALCULATION
T101 SALAWATI
Figure 1
H W dcg MT
kg kg m kgm
74369.00 386268.00 3.66 246510.00
where,
H = Maximum horizontal force, in this case, seismic is the governing condition
W = Gravity load
dcg = Distance from T.O.S base plate to the CoG of equipment
MT = Moment for anchor bolt design
1.2 Tension & Shear Forces Design at The Most Critical Anchor Bolt
Elastic stress distribution at the base plate can be calculated using the following formula:
(stress due to combined axial and moment)
W MT c
σ (Refer Roark's Formula for Stress and Strain, page 153, (8.7-1))
A bp I
where,
= Elastic stress at base plate
Abp = Area of base plate
c = Outer fiber location of base plate
I = Base plate moment of inertia
CL
1236
2983
Figure 2
W Abp MT c I C T e
kg mm2 kgm mm mm4 kgm kgm mm
386268.00 3.09E+07 246510.00 3134.00 7.98E+12 0.109 -0.084 405.32
Tension stress is occured
Where :
C = Maximum compression stress at base plate
T = Maximum tension stress at base plate
e = Neutral axis distance from ref. point
FT = Tension force which will be transferred to all bolts in the tension region
L = Distance from CoG of FT to neutral axis
M = FT.L ex
T
FT C
N/A CL
As a concervative approach for calculating maximum tension force in the most critical bolt
"M=FT*L" was considered as "MT" (Note: without any effect of "W"; MT will always > M=FT*L),
this moment shall be transferred to all bolts in the tension region
ANCHOR BOLT DESIGN CALCULATION
T101 SALAWATI
From Figure 2 above, it is found that the most critical bolts are:
Bolt No 2 & 3
di di2
i
mm mm2
1 1236.00 1.53E+06
2 2983.00 8.90E+06
3 2983.00 8.90E+06
4 1236.00 1.53E+06
5 0.00 0.00E+00
6 0.00 0.00E+00
2.09E+07
d i
2
MT d3 Σdi2 c T3 H n V
kgm mm mm2 mm kg kg nos kg
246510.00 2.98E+03 2.09E+07 3134.00 35264.74 74369.00 8.000 9296.125
Hence, the following tension and shear forces shall be considered for anchor bolt design
T V Comp/bolt
kg kg kg
35264.74 9296.125 48283.5 No Tension occurs
M di
Ti k
T
d
2
i
1
Where :
T = Maximum tension force on Anchor Bolt
MT = Moment for anchor bolt design
di = Location of anchor bolt w.r.t center line
H
V
n
Where :
V = Maximum shear force at Anchor Bolt
n = Number of bolts (all bolts were considered can take shear forces effectively)
le do f'c ca1 Vb
mm mm kg/mm2 mm kg
200.00 20.00 1.87 771.00 108246
Vb = 124416.5 kg
Vb = 108246.4 kg
Vcb Vua
Avc
Vcb ed ,V c ,v Vb
Avco
where,
Avc = 2(1.5ca1)(1.5ca1)
Avco = 4.5 ca12
Ψed,v = 1.0 since ca2 > 1.5 ca1
Ψc,v = 1.0 assuming cracking at service loads ( ft > fr ) D.6.2.7
Ф = 0.7 for condition B
(no supplementary reinforcement provided)
UC = Ratio between concrete breakout capacity under shear loading and shear design loads
ANCHOR BOLT DESIGN CALCULATION
T101 SALAWATI
2.3. Concrete pryout strength : D.6.3
Vcp kcp N cb
where,
Vcp = Concrete pryout strength of anchor in shear
UC = Ratio between concrete pryout capacity under shear loading and shear design loads
kc f'c hef Nb
kg/mm2 mm kg
7.00 1.87 200.00 27057
where,
kc = koefficient
f'c = compressive strength
hef = Distance from T.O.S base plate to the end of anchor bolt
Nb = basic concrete breakout strength in tension in cracked concrete
Ncb Ф ФNcb UC
kg kg
71043 0.65 46178 0.76
Ca ,min
ed . N 0.7 0.3 when ca,min <1.5 hef D.5.2.7
1.5 hef
ANC
N cb ed , N c , N cp , N N b
ANCO
ANC
N cb ed , N c , N cp , N kc f 'c hef 1.5
ANCO
where,
ca1 = distance between bolt center diameter and edge of concrete
Anco = 9 hef 2
Depth (m)
Qall vs depth
Np = Average Nspt within 4Dia above pile tip & 1dia below the pile tip, max=50
-2.5
Ns = Average Nspt along the shaft Nspt vs depth
-3
SF1 = 3
-3.5
Boring No. BH4
-4
Pile size D Area (m2) Perimeter (m) D = Driven piles
Square 0 0 0 B = Bored piles -4.5
others
0.125663706 1.256637061
Soil Profile Bearing capacity (ton) Negative skin friction, Garlanger 1973 (empirical)
Depth Soil type Nspt h Ns fs Qs Np fb Qb Qall (ton) Qall (ton)GWL (m) Depth s Soil type 'v Coeff. NSFLocal Qall (ton)
17.8 kN/m3
PT PERTAMINA EP REGION 4 ZONA 14
6. FOUNDATION SETTLEMENT
Width of foundation, B= 8 m
Depth of embedment, D= 0.5 m
Groundwater table correction, C = 1