HORIZONTAL WASTE PIPE (comfort room 1)

TYPE OF TOTAL FIXTURE


NO. OF FIXTURES FIXTURE UNIT
FIXTURES UNIT

lavatory 1 1 1

Floor drain 1 1 1

Bathtub 1 2 2

TOTAL 4

The required diameter of pipe is 50mm under one horizontal branch

HORIZONTAL WASTE PIPE (Bathroom 2)

TYPE OF TOTAL FIXTURE


NO. OF FIXTURES FIXTURE UNIT
FIXTURES UNIT

lavatory 1 1 1

Bathtub 1 2 2

Floor drain 1 1 1

TOTAL 4

The required diameter of pipe is 50mm under one horizontal branch

HORIZONTAL WASTE PIPE (comfort room 3)

TYPE OF TOTAL FIXTURE


NO. OF FIXTURES FIXTURE UNIT
FIXTURES UNIT

lavatory 1 1 1

Floor drain 1 1 1

Bathtub 1 2 2

TOTAL 4

The required diameter of pipe is 50mm under one horizontal branch


HORIZONTAL WASTE PIPE (laundry room)

TYPE OF TOTAL FIXTURE


NO. OF FIXTURES FIXTURE UNIT
FIXTURES UNIT

Laundry tub 2 2 4

Floor drain 1 1 1

TOTAL 5

The required diameter of pipe is 50mm under one horizontal branch

HORIZONTAL WASTE PIPE (kitchen area)

TYPE OF TOTAL FIXTURE


NO. OF FIXTURES FIXTURE UNIT
FIXTURES UNIT

Kitchen sink 2 2 4

TOTAL 4

The required diameter of pipe is 50mm under one horizontal branch

SOIL PIPE/BRANCH

TYPE OF TOTAL FIXTURE


NO. OF FIXTURES FIXTURE UNIT
FIXTURES UNIT

Water closet 3 6 18

Urinal 1 5 5

TOTAL 23

“no water closet shall be discharge into a drain less than 75mm dia. Pipe.” Therefore, a 100 mm pipe
diameter will be specified.
HOUSE DRAIN (2% SLOPE)-TO SEPTIC TANK

TYPE OF TOTAL FIXTURE


NO. OF FIXTURES FIXTURE UNIT
FIXTURES UNIT

Water closet 3 6 18

Urinal 1 5 5

TOTAL 23

The required diameter of pipe is 100mm under 2% slope.

HOUSE DRAIN (2% slope)-TO STREET CANAL

TYPE OF TOTAL FIXTURE


NO. OF FIXTURES FIXTURE UNIT
FIXTURES UNIT

lavatory 3 1 3

Floor drain 7 1 7

Bathtub 2 2 2

TOTAL 12 units

The required diameter of pipe is 63mm under 2% slope.


WATER SUPPLY

TYPE OF TOTAL FIXTURE


NO. OF FIXTURES FIXTURE UNIT
FIXTURES UNIT

lavatory 3 1 3

Shower 3 1 3

Bathtub 3 2 6

Laundry tub 2 2 4

Kitchen sink 2 2 4

Water closet 3 6 18

Urinal 1 5 5

TOTAL 43 units

Total number of fixture unit = 43 units


One-unit fixture = 8 gallons

Max demand of water= total fixture unit X 8


= 43x8
= 344 gallons

Probable demand of water is max demand subtracted by reduced demand of 25%-50%. Assume
reduction of 30%

344 x 0.40 = 137.6 gallons = reduction

Probable demand of water = max demand – reduction


= 344 – 137.6 = 206.4 gallons

CALCULATE PRESSURE (p)

P = P(ave.) – P (static)
• Assuming the water district of city is 40 PSI
• 1 ft of water column 0.43 psi
• Length of second floor = 10ft

10 x 0.43 = 4.3 psi up feed needed in second floor

P = 40 psi – 4.3 psi = 35.7 psi (water pressure tank for up feed)
Determining the pipe size and meter size
-from RNPCP table 6.6

-40psi, Max length = 35.3 m


• Water meter size = 25 mm dia
• Service pipe size = 32 mmdia
• Branch pipe size = 32 mm dia
STORM DRAIN (2% SLOPE)

ROOF WIDTH OF ROOF LENGTH OF ROOF AREA OF ROOF


DIMENSIONS (W) (L) (L X W) sq. meters

AREA 1 8.2 9.37 76.834

AREA 2 10.11 19.96 201.7956

AREA 3 1.98 4.51 8.9298

AREA 4 6.85 8.48 58.088

TOTAL 345.6474 sq. m

PIPE SIZE = 125 mm diameter

In reference to table 9-1 in the “plumbing design and estimate textbook by M.B. Fajardo Jr.”, under
the column of 2% slope, a 125 mm (5 inches) pipe will be needed for a roof with 345.6474 sq. m.

STORM DRAIN (2% SLOPE) - GUTTER IN REFERENCE TO TABLE 9-2

GUTTER
WIDTH LENGTH AREA OF GUTTER TOP
GUTTER LEADER
OF ROOF OF ROOF ROOF (L X DIMENSION
DIMENSIONS DIMENSION
(W) (L) W) sq. meters (mm)
(mm)
GUTTER 1 8.2 9.37 76.834 125 90
GUTTER 2 10.11 9.98 100.8978 125 90
GUTTER 3 10.11 9.98 100.8978 125 90
GUTTER 4 4.51 12.99 25.7202 100 75
GUTTER 5 4.87 8.48 41.2976 100 75
TOTAL 345.6474 sq.m

In reference to table 9-2 in the “plumbing design and estimate textbook by M.B. Fajardo Jr.”, we can
determine the gutter top sizes and gutter leader sizes using the gutter areas of the roof.
TECHNICAL DATA IN DETERMINING VOLUME OF SEPTIC TANK

Minimum width 90 cm
Minimum length 150 cm
Minimum depth 120 cm

SEPTIC TANK VOLUME

NUMBER OF CU. FT. PER TOTAL


FORMULA TOTAL CU. FT.
PERSONS (N) PERSON (X) GALLONS

7 2 N*X 14 cu. ft. 104. 73 gal

Using technical data in page 92 of “plumbing design and estimate textbook by M.B. Fajardo Jr.”, the
volume of the septic tank should not have liquid content more than 2.0 cu.meters.

For small residential house to serve up to 12 persons, the chamber should have a liquid content of
not more than- 2.0 cu.meters

7 persons * 2 cu. Meter= 14 cu.meter or 104.73 gal

WIDTH OF SEPTIC TANK

NUMBER OF M. PER PERSON (X)


FORMULA TOTAL (METER)
PERSONS (N)

7 .75 N*X 5.25 meters

LENGTH OF SEPTIC TANK

MAX. DEPTH OF
VOLUME (V) WIDTH (W) FORMULA LENGTH
S.T. WATER (Y)

14 5.25 1.5 m L=V/W(Y) 1.78 m

TOTAL LENGTH OF SEPTIC TANK

LENGTH (L) FORMULA TOTAL LENGTH

1.78 m TOTAL LENGTH= L/2 + L 2.67 m