Sanitary Pipe Sizing to BS5572

Location: Level 2, 3, 4, 5, 6, 7, 8 & 9


Project : : Putrajaya Lot 4C11 Stack: ST
Type : Branch Waste Pipe Date : 12-Oct-22

Node No of Fittings Discharge Unit Minimum Proposed Remarks


No No FV FV SDU sink basin taps At each Cumulative Pipe Size pipe size
WC urinal Node mm mm
Discharge Unit per fitting 14 1 1 13 3 1

Female Toilet 1
1 Xb 01 to Xb 00 1 14 70 75 90
2 Xb 02 to Xb 01 1 14 56 75 90
3 Xb 03 to Xb 02 1 14 42 75 90
4 Xb 04 to Xb 03 1 14 28 65 75
5 Xb 05 to Xb 04 1 14 14 50 65

Minimum stack pipe size shall be accordance to BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : WASTE FT1(TYP 2 to 9) - by Tzelin Lee


Sanitary Pipe Sizing to BS5572
Location: Level 2, 3, 4, 5, 6, 7, 8 & 9
Project : : Putrajaya Lot 4C11 Stack: ST
Type : Branch Waste Pipe Date : 12-Oct-22

Node No of Fittings Discharge Unit Minimum Proposed Remarks


No No FV FV SDU sink basin taps At each Cumulative Pipe Size pipe size
WC urinal Node mm mm
Discharge Unit per fitting 14 1 1 13 3 1

Male Toilet 1
1 Xb 01 to Xb 00 4 4 60 75 90
2 Xb 02 to Xb 01 1 14 56 75 90
3 Xb 03 to Xb 02 1 14 42 75 90
4 Xb 04 to Xb 03 1 14 28 65 75
5 Xb 05 to Xb 04 1 14 14 50 65

Minimum stack pipe size shall be accordance to BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : WASTE MT1(TYP 2 to 9) - by Tzelin Lee


Sanitary Pipe Sizing to BS5572
Location: Level 2, 3, 4, 5, 6, 7, 8 & 9
Project : : Putrajaya Lot 4C11 Stack: ST
Type : Branch Soil Pipe Date : 12-Oct-22

Node No of Fittings Discharge Unit Minimum Proposed Remarks


No No Ablution Shower Long sink basin taps At each Cumulative Pipe Size pipe size
Tap bath Node mm mm
Discharge Unit per fitting 3 1 17 13 3 1

Female Toilet 1
1 Xa 01 to Xa 00 5 5 26 50 65
2 Xa 02 to Xa 01 2 6 21 50 65
3 Xa 03 to Xa 02 1 3 15 50 65
4 Xa 04 to Xa 03 1 3 12 50 65
5 Xa 05 to Xa 04 1 3 9 50 65
6 Xa 06 to Xa 05 1 3 6 40 50
7 Xa 07 to Xa 06 1 3 3 40 50

Minimum soil/waste pipe size shall be accordance to Table 8 : BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : SOIL FT1(TYP 2 to 9) - by Tzelin Lee


Sanitary Pipe Sizing to BS5572
Location: Level 2, 3, 4, 5, 6, 7, 8 & 9
Project : : Putrajaya Lot 4C11 Stack: ST
Type : Branch Soil Pipe Date : 12-Oct-22

Node No of Fittings Discharge Unit Minimum Proposed Remarks


No No Ablution Shower Long sink basin taps At each Cumulative Pipe Size pipe size
Tap bath Node mm mm
Discharge Unit per fitting 3 1 17 13 3 1

Male Toilet 1
1 Xa 01 to Xa 00 1 1 4 26 50 65
2 Xa 02 to Xa 01 1 1 22 50 65
3 Xa 03 to Xa 02 1 1 21 50 65
4 Xa 04 to Xa 03 1 1 20 50 65
5 Xa 05 to Xa 04 1 1 19 50 65
6 Xa 06 to Xa 05 2 6 18 50 65
7 Xa 07 to Xa 06 1 3 12 50 65
8 Xa 08 to Xa 07 1 3 9 50 65
9 Xa 09 to Xa 08 1 3 6 40 50
10 Xa 10 to Xa 09 1 3 3 40 50

Minimum soil/waste pipe size shall be accordance to Table 8 : BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : SOIL MT1(TYP 2 to 9) - by Tzelin Lee


Sanitary Pipe Sizing to BS5572
Location: Level Ground & Level 1
Project : : Putrajaya Lot 4C11 Stack: ST
Type : Branch Waste Pipe Date : 12-Oct-22

Node No of Fittings Discharge Unit Minimum Proposed Remarks


No No FV FV SDU sink basin taps At each Cumulative Pipe Size pipe size
WC urinal Node mm mm
Discharge Unit per fitting 14 1 1 13 3 1

Female Toilet 2
1 Xb 01 to Xb 00 1 14 98 75 90
2 Xb 02 to Xb 01 1 14 84 75 90
3 Xb 03 to Xb 02 1 14 70 75 90
4 Xb 04 to Xb 03 1 14 56 75 90
5 Xb 05 to Xb 04 1 14 42 75 90
6 Xb 06 to Xb 05 1 14 28 65 75
7 Xb 07 to Xb 06 1 14 14 50 65

Minimum stack pipe size shall be accordance to BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : WASTE FT2(GRD-1) - by Tzelin Lee


Sanitary Pipe Sizing to BS5572
Location: Level Ground & Level 1
Project : : Putrajaya Lot 4C11 Stack: ST
Type : Branch Waste Pipe Date : 12-Oct-22

Node No of Fittings Discharge Unit Minimum Proposed Remarks


No No FV FV SDU sink basin taps At each Cumulative Pipe Size pipe size
WC urinal Node mm mm
Discharge Unit per fitting 14 1 1 13 3 1

Male Toilet 2
1 Xb 01 to Xb 00 1 14 75 75 90
2 Xb 02 to Xb 01 1 14 61 75 90
3 Xb 03 to Xb 02 1 14 47 75 90
4 Xb 04 to Xb 03 1 14 33 65 75
5 Xb 05 to Xb 04 5 5 19 50 65
6 Xb 06 to Xb 05 1 14 14 50 65

Minimum stack pipe size shall be accordance to BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : WASTE MT2(GRD-1) - by Tzelin Lee


Sanitary Pipe Sizing to BS5572
Location: Level Ground & Level 1
Project : : Putrajaya Lot 4C11 Stack: ST
Type : Branch Soil Pipe Date : 12-Oct-22

Node No of Fittings Discharge Unit Minimum Proposed Remarks


No No Ablution Shower Long sink basin taps At each Cumulative Pipe Size pipe size
Tap bath Node mm mm
Discharge Unit per fitting 3 1 17 13 3 1

Female Toilet 2
1 Xa 01 to Xa 00 1 1 25 50 65
2 Xa 02 to Xa 01 1 1 24 50 65
3 Xa 03 to Xa 02 1 1 23 50 65
4 Xa 04 to Xa 03 1 1 22 50 65
5 Xa 05 to Xa 04 1 1 21 50 65
6 Xa 06 to Xa 05 1 1 20 50 65
7 Xa 07 to Xa 06 1 1 19 50 65
8 Xa 08 to Xa 07 1 3 18 50 65
9 Xa 09 to Xa 08 1 3 15 50 65
10 Xa 10 to Xa 09 1 3 12 50 65
11 Xa 11 to Xa 10 1 3 9 50 65
12 Xa 12 to Xa 11 1 3 6 40 50
13 Xa 13 to Xa 12 1 3 3 40 50

Minimum soil/waste pipe size shall be accordance to Table 8 : BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : SOIL FT2(GRD-1) - by Tzelin Lee


Sanitary Pipe Sizing to BS5572
Location: Level Ground & Level 1
Project : : Putrajaya Lot 4C11 Stack: ST
Type : Branch Soil Pipe Date : 12-Oct-22

Node No of Fittings Discharge Unit Minimum Proposed Remarks


No No Ablution Shower Long sink basin taps At each Cumulative Pipe Size pipe size
Tap bath Node mm mm
Discharge Unit per fitting 3 1 17 13 3 1

Male Toilet 2
1 Xa 01 to Xa 00 1 1 17 50 65
2 Xa 02 to Xa 01 1 1 16 50 65
3 Xa 03 to Xa 02 1 1 15 50 65
4 Xa 04 to Xa 03 1 1 14 50 65
5 Xa 05 to Xa 04 1 1 13 50 65
6 Xa 06 to Xa 05 1 3 12 50 65
7 Xa 07 to Xa 06 1 3 9 50 65
8 Xa 08 to Xa 07 1 3 6 40 50
9 Xa 09 to Xa 08 1 3 3 40 50

Minimum soil/waste pipe size shall be accordance to Table 8 : BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : SOIL MT2(GRD-1) - by Tzelin Lee


Sanitary Pipe Sizing to BS5572
Location: Level 2, 3, 4, 5, 6 & 7
Project : : Putrajaya Lot 4C11 Stack: ST
Type : Branch Waste Pipe Date : 12-Oct-22

Node No of Fittings Discharge Unit Minimum Proposed Remarks


No No FV FV SDU sink basin taps At each Cumulative Pipe Size pipe size
WC urinal Node mm mm
Discharge Unit per fitting 14 1 1 13 3 1

Female Toilet 2
1 Xb 01 to Xb 00 1 14 56 75 90
2 Xb 02 to Xb 01 1 14 42 75 90
3 Xb 03 to Xb 02 1 14 28 65 75
4 Xb 04 to Xb 03 1 14 14 50 65

Minimum stack pipe size shall be accordance to BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : WASTE FT2(TYP 2 to 7) - by Tzelin Lee


Sanitary Pipe Sizing to BS5572
Location: Level 2, 3, 4, 5, 6 & 7
Project : : Putrajaya Lot 4C11 Stack: ST
Type : Branch Waste Pipe Date : 12-Oct-22

Node No of Fittings Discharge Unit Minimum Proposed Remarks


No No FV FV SDU sink basin taps At each Cumulative Pipe Size pipe size
WC urinal Node mm mm
Discharge Unit per fitting 14 1 1 13 3 1

Male Toilet 2
1 Xb 01 to Xb 00 1 14 45 75 90
2 Xb 02 to Xb 01 1 14 31 65 75
3 Xb 03 to Xb 02 1 14 17 50 65
4 Xb 04 to Xb 03 1 1 3 40 50
5 Xb 05 to Xb 04 1 1 2 40 50
6 Xb 06 to Xb 05 1 1 1 32 40

Minimum stack pipe size shall be accordance to BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : WASTE MT2(TYP 2 to 7) - by Tzelin Lee


Sanitary Pipe Sizing to BS5572
Location: Level 2, 3, 4, 5, 6 & 7
Project : : Putrajaya Lot 4C11 Stack: ST
Type : Branch Soil Pipe Date : 12-Oct-22

Node No of Fittings Discharge Unit Minimum Proposed Remarks


No No Ablution Shower Long sink basin taps At each Cumulative Pipe Size pipe size
Tap bath Node mm mm
Discharge Unit per fitting 3 1 17 13 3 1

Female Toilet 2
1 Xa 01 to Xa 00 1 1 16 50 65
2 Xa 02 to Xa 01 1 1 15 50 65
3 Xa 03 to Xa 02 1 1 14 50 65
4 Xa 04 to Xa 03 1 1 13 50 65
5 Xa 05 to Xa 04 1 3 12 50 65
6 Xa 06 to Xa 05 1 3 9 50 65
7 Xa 07 to Xa 06 1 3 6 40 65
8 Xa 08 to Xa 07 1 3 3 40 65

Minimum soil/waste pipe size shall be accordance to Table 8 : BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : SOIL FT2(TYP 2 to 7) - by Tzelin Lee


Sanitary Pipe Sizing to BS5572
Location: Level 2, 3, 4, 5, 6 & 7
Project : : Putrajaya Lot 4C11 Stack: ST
Type : Branch Soil Pipe Date : 12-Oct-22

Node No of Fittings Discharge Unit Minimum Proposed Remarks


No No Ablution Shower Long sink basin taps At each Cumulative Pipe Size pipe size
Tap bath Node mm mm
Discharge Unit per fitting 3 1 17 13 3 1

Male Toilet 2
1 Xa 01 to Xa 00 1 1 21 50 65
2 Xa 02 to Xa 01 1 1 20 50 65
3 Xa 03 to Xa 02 2 1 7 19 50 65
4 Xa 04 to Xa 03 1 3 12 50 65
5 Xa 05 to Xa 04 1 3 9 50 65
6 Xa 06 to Xa 05 1 3 6 40 65
7 Xa 07 to Xa 06 1 3 3 40 65

Minimum soil/waste pipe size shall be accordance to Table 8 : BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : SOIL MT2(TYP 2 to 7) - by Tzelin Lee


Sanitary Pipe Sizing to BS5572

Project : : Putrajaya Lot 4C11 Location: Business Suite


Type : Branch Waste Pipe Date : 12-Oct-22

Node Floor FV basin ablution sink Discharge Unit discharge Flow 1 FV SDU taps Flow 2 Total
No No Level WC tap Cumulative flowrate urinal Cumulative Flow 1& 2
l/s l/s l/s l/s l/s
Discharge unit / Flowrate 14 3 3 13 0.002505 0.002505 0.001002

1 S 00 to S 01 All 1 13 13 4.21 0 0.000 4.21

Total: 0 0 0 1 0 0 0

Minimum stack pipe size shall be accordance to BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : B.SUITE&RETAIL - by Tzelin Lee


Sanitary Pipe Sizing to BS5572
Location: (Hose Reel Riser)
Project : : Putrajaya Lot 4C11 Stack: STACK 01
Type : Vertical Stack Pipe (Stack 01 to Scupper Drain) Date : 12-Oct-22

Node Floor FV SDU taps Flow 1 Total Pipe Proposed


No No Level urinal Cumulative Flow 1& 2 Size pipe size
l/s l/s l/s mm mm
Discharge unit / Flowrate 0.002505 0.002505 0.167000

1 F 01 to F 00 to Scupper Drain 0 1.837 1.84 65 80


2 F 02 to F 01 Level B3 1 0.167 1.837 1.84 65 80
3 F 03 to F 02 Level B2 1 0.167 1.670 1.67 65 80
4 F 04 to F 03 Level B1 1 0.167 1.503 1.50 65 80
5 F 05 to F 04 Level G 1 0.167 1.336 1.34 65 80
6 F 06 to F 05 Level 1 1 0.167 1.169 1.17 50 80
7 F 07 to F 06 Level 2 1 0.167 1.002 1.00 50 80
8 F 08 to F 07 Level 3 1 0.167 0.835 0.84 50 80
9 F 09 to F 08 Level 4 1 0.167 0.668 0.67 50 80
10 F 10 to F 09 Level 5 1 0.167 0.501 0.50 50 80
11 F 11 to F 10 Level 6 1 0.167 0.334 0.33 50 80
12 F 12 to F 11 Level 7 1 0.167 0.167 0.17 50 80

Total: 0 0 11

Minimum stack pipe size shall be accordance to BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : STACK 01 - by Tzelin Lee


Sanitary Pipe Sizing to BS5572
Location: (Hose Reel & Wet Riser)
Project : : Putrajaya Lot 4C11 Stack: STACK 02
Type : Vertical Stack Pipe (Stack 02 to Scupper Drain) Date : 12-Oct-22

Node Floor FV SDU taps Flow 1 Total Pipe Proposed


No No Level urinal Cumulative Flow 1& 2 Size pipe size
l/s l/s l/s mm mm
Discharge unit / Flowrate 0.002505 0.002505 0.167000

1 F 01 to F 00 to Scupper Drain 0 0.501 0.50 50 80


2 F 02 to F 01 Level B3 1 0.167 0.501 0.50 50 80
3 F 03 to F 02 Level B2 1 0.167 0.334 0.33 50 80
4 F 04 to F 03 Level B1 1 0.167 0.167 0.17 50 80

1 F 04 to F 03 to External 0 1.670 1.67 65 80


2 F 05 to F 04 Level G 1 0.167 1.670 1.67 65 80
3 F 06 to F 05 Level 1 1 0.167 1.503 1.50 65 80
4 F 07 to F 06 Level 2 1 0.167 1.336 1.34 65 80
5 F 08 to F 07 Level 3 1 0.167 1.169 1.17 50 80
6 F 09 to F 08 Level 4 1 0.167 1.002 1.00 50 80
7 F 10 to F 09 Level 5 1 0.167 0.835 0.84 50 80
8 F 11 to F 10 Level 6 1 0.167 0.668 0.67 50 80
9 F 12 to F 11 Level 7 1 0.167 0.501 0.50 50 80
10 F 13 to F 12 Level 8 2 0.334 0.334 0.33 50 80

Total: 0 0 13

Minimum stack pipe size shall be accordance to BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : STACK 02 - by Tzelin Lee


Sanitary Pipe Sizing to BS5572
Location: (Hose Reel Riser)
Project : : Putrajaya Lot 4C11 Stack: STACK 03
Type : Vertical Stack Pipe (Stack 03 to Scupper Drain) Date : 12-Oct-22

Node Floor FV SDU taps Flow 1 Total Pipe Proposed


No No Level urinal Cumulative Flow 1& 2 Size pipe size
l/s l/s l/s mm mm
Discharge unit / Flowrate 0.002505 0.002505 0.167000

1 F 01 to F 00 to Scupper Drain 0 0.501 0.50 50 80


2 F 02 to F 01 Level B3 1 0.167 0.501 0.50 50 80
3 F 03 to F 02 Level B2 1 0.167 0.334 0.33 50 80
4 F 04 to F 03 Level B1 1 0.167 0.167 0.17 50 80

1 F 04 to F 03 to External 0 1.837 1.84 65 80


2 F 05 to F 04 Level G 1 0.167 1.837 1.84 65 80
3 F 06 to F 05 Level 1 1 0.167 1.670 1.67 65 80
4 F 07 to F 06 Level 2 1 0.167 1.503 1.50 65 80
5 F 08 to F 07 Level 3 1 0.167 1.336 1.34 65 80
6 F 09 to F 08 Level 4 1 0.167 1.169 1.17 50 80
7 F 10 to F 09 Level 5 1 0.167 1.002 1.00 50 80
8 F 11 to F 10 Level 6 1 0.167 0.835 0.84 50 80
9 F 12 to F 11 Level 7 1 0.167 0.668 0.67 50 80
10 F 13 to F 12 Level 8 1 0.167 0.501 0.50 50 80
11 F 14 to F 13 Level 9 1 0.167 0.334 0.33 50 80
12 F 15 to F 14 Roof Level 1 0.167 0.167 0.17 50 80

Total: 0 0 14

Minimum stack pipe size shall be accordance to BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : STACK 03 - by Tzelin Lee


Sanitary Pipe Sizing to BS5572
Location: (Hose Reel Riser)
Project : : Putrajaya Lot 4C11 Stack: STACK 04
Type : Vertical Stack Pipe (Stack 04 to Scupper Drain) Date : 12-Oct-22

Node Floor FV SDU taps Flow 1 Total Pipe Proposed


No No Level urinal Cumulative Flow 1& 2 Size pipe size
l/s l/s l/s mm mm
Discharge unit / Flowrate 0.002505 0.002505 0.167000

1 F 01 to F 00 to Scupper Drain 0 1.837 1.84 65 80


2 F 02 to F 01 Level B3 1 0.167 1.837 1.84 65 80
3 F 03 to F 02 Level B2 1 0.167 1.670 1.67 65 80
4 F 04 to F 03 Level B1 1 0.167 1.503 1.50 65 80
5 F 05 to F 04 Level G 1 0.167 1.336 1.34 65 80
6 F 06 to F 05 Level 1 1 0.167 1.169 1.17 50 80
7 F 07 to F 06 Level 2 1 0.167 1.002 1.00 50 80
8 F 08 to F 07 Level 3 1 0.167 0.835 0.84 50 80
9 F 09 to F 08 Level 4 1 0.167 0.668 0.67 50 80
10 F 10 to F 09 Level 5 1 0.167 0.501 0.50 50 80
11 F 11 to F 10 Level 6 1 0.167 0.334 0.33 50 80
12 F 12 to F 11 Level 7 1 0.167 0.167 0.17 50 80

Total: 0 0 11

Minimum stack pipe size shall be accordance to BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : STACK 04 - by Tzelin Lee


Sanitary Pipe Sizing to BS5572
Location: (Hose Reel & Wet Riser)
Project : : Putrajaya Lot 4C11 Stack: STACK 05
Type : Vertical Stack Pipe (Stack 05 to Scupper Drain) Date : 12-Oct-22

Node Floor FV SDU taps Flow 1 Total Pipe Proposed


No No Level urinal Cumulative Flow 1& 2 Size pipe size
l/s l/s l/s mm mm
Discharge unit / Flowrate 0.002505 0.002505 0.167000

1 F 01 to F 00 to Scupper Drain 0 0.501 0.50 50 80


2 F 02 to F 01 Level B3 1 0.167 0.501 0.50 50 80
3 F 03 to F 02 Level B2 1 0.167 0.334 0.33 50 80
4 F 04 to F 03 Level B1 1 0.167 0.167 0.17 50 80

1 F 04 to F 03 to External 0 1.837 1.84 65 80


2 F 05 to F 04 Level G 1 0.167 1.837 1.84 65 80
3 F 06 to F 05 Level 1 1 0.167 1.670 1.67 65 80
4 F 07 to F 06 Level 2 1 0.167 1.503 1.50 65 80
5 F 08 to F 07 Level 3 1 0.167 1.336 1.34 65 80
6 F 09 to F 08 Level 4 1 0.167 1.169 1.17 50 80
7 F 10 to F 09 Level 5 1 0.167 1.002 1.00 50 80
8 F 11 to F 10 Level 6 1 0.167 0.835 0.84 50 80
9 F 12 to F 11 Level 7 1 0.167 0.668 0.67 50 80
10 F 13 to F 12 Level 8 1 0.167 0.501 0.50 50 80
11 F 14 to F 13 Level 9 1 0.167 0.334 0.33 50 80
12 F 15 to F 14 Roof Level 1 0.167 0.167 0.17 50 80

Total: 0 0 14

Minimum stack pipe size shall be accordance to BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : STACK 05 - by Tzelin Lee


Sanitary Pipe Sizing to BS5572
Location: (Hose Reel Riser)
Project : : Putrajaya Lot 4C11 Stack: STACK 06
Type : Vertical Stack Pipe (Stack 06 to Scupper Drain) Date : 12-Oct-22

Node Floor FV SDU taps Flow 1 Total Pipe Proposed


No No Level urinal Cumulative Flow 1& 2 Size pipe size
l/s l/s l/s mm mm
Discharge unit / Flowrate 0.002505 0.002505 0.167000

1 F 01 to F 00 to Scupper Drain 0 2.338 2.34 75 80


2 F 02 to F 01 Level B3 1 0.167 2.338 2.34 75 80
3 F 03 to F 02 Level B2 1 0.167 2.171 2.17 75 80
4 F 04 to F 03 Level B1 1 0.167 2.004 2.00 65 80
5 F 05 to F 04 Level G 1 0.167 1.837 1.84 65 80
6 F 06 to F 05 Level 1 1 0.167 1.670 1.67 65 80
7 F 07 to F 06 Level 2 1 0.167 1.503 1.50 65 80
8 F 08 to F 07 Level 3 1 0.167 1.336 1.34 65 80
9 F 09 to F 08 Level 4 1 0.167 1.169 1.17 50 80
10 F 10 to F 09 Level 5 1 0.167 1.002 1.00 50 80
11 F 11 to F 10 Level 6 1 0.167 0.835 0.84 50 80
12 F 12 to F 11 Level 7 1 0.167 0.668 0.67 50 80
13 F 13 to F 12 Level 8 1 0.167 0.501 0.50 50 80
14 F 14 to F 13 Level 9 1 0.167 0.334 0.33 50 80
15 F 15 to F 14 Roof Level 1 0.167 0.167 0.17 50 80

Total: 0 0 14

Minimum stack pipe size shall be accordance to BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : STACK 06 - by Tzelin Lee


Sanitary Pipe Sizing to BS5572

Project : : Putrajaya Lot 4C11 Stack: STACK 07


Type : Vertical Stack Pipe (Stack 07 to Manhole 1) Date : 12-Oct-22

Node Floor FV basin ablution sink Discharge Unit Flow 1 FV SDU taps Flow 2 Total Pipe Proposed
No No Level WC tap Cumulative urinal Cumulative Flow 1& 2 Size pipe size
l/s l/s l/s l/s mm mm
Discharge unit / Flowrate 14 3 3 13 0.002505 0.002505 0.001002

1 S 01 to S 00 Manhole1=> 0 768 6.81 0 0.105 6.92 100 150


2 S 02 to S 01 Level G 0 768 6.81 0 0.105 6.92 100 150
3 S 03 to S 02 Level 1 0 768 6.81 0 0.105 6.92 100 150
4 S 04 to S 03 Level 2 7 8 2 128 768 6.81 3 10 0.01754 0.105 6.92 100 150
5 S 05 to S 04 Level 3 7 8 2 128 640 6.38 3 10 0.01754 0.088 6.47 100 150
6 S 06 to S 05 Level 4 7 8 2 128 512 5.94 3 10 0.01754 0.070 6.01 100 150
7 S 07 to S 06 Level 5 7 8 2 128 384 5.50 3 10 0.01754 0.053 5.55 100 150
8 S 08 to S 07 Level 6 7 8 2 128 256 5.05 3 10 0.01754 0.035 5.09 90 150
9 S 09 to S 08 Level 7 7 8 2 128 128 4.61 3 10 0.01754 0.018 4.63 90 150

Total: 42 48 12 0 18 0 60

Minimum stack pipe size shall be accordance to BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : STACK 07 - by Tzelin Lee


Sanitary Pipe Sizing to BS5572

Project : : Putrajaya Lot 4C11 Stack: STACK 08


Type : Vertical Stack Pipe (Stack 08 to Manhole 1) Date : 12-Oct-22

Node Floor FV basin ablution sink Discharge Unit Flow 1 FV SDU taps Flow 2 Total Pipe Proposed
No No Level WC tap Cumulative urinal Cumulative Flow 1& 2 Size pipe size
l/s l/s l/s l/s mm mm
Discharge unit / Flowrate 14 3 3 13 0.002505 0.002505 0.001002

1 S 01 to S 00 Manhole1=> 0 1408 8.97 0 0.184 9.16 125 150


1 S 01 to S 00 Level G 0 1408 8.97 0 0.184 9.16 125 150
2 S 01 to S 00 Level 1 0 1408 8.97 0 0.184 9.16 125 150
3 S 02 to S 01 Level 2 10 10 2 176 1408 8.97 4 13 0.02305 0.184 9.16 125 150
4 S 03 to S 02 Level 3 10 10 2 176 1232 8.38 4 13 0.02305 0.161 8.54 125 150
5 S 04 to S 03 Level 4 10 10 2 176 1056 7.79 4 13 0.02305 0.138 7.93 125 150
6 S 05 to S 04 Level 5 10 10 2 176 880 7.20 4 13 0.02305 0.115 7.31 125 150
7 S 06 to S 05 Level 6 10 10 2 176 704 6.60 4 13 0.02305 0.092 6.69 100 150
8 S 07 to S 06 Level 7 10 10 2 176 528 5.99 4 13 0.02305 0.069 6.06 100 150
9 S 08 to S 07 Level 8 10 10 2 176 352 5.39 4 13 0.02305 0.046 5.43 100 150
10 S 09 to S 08 Level 9 10 10 2 176 176 4.78 4 13 0.02305 0.023 4.80 90 150

Total: 80 80 16 0 32 0 104

Minimum stack pipe size shall be accordance to BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : STACK 08 - by Tzelin Lee


Sanitary Pipe Sizing to BS5572
Location: (Cold Water Riser)
Project : : Putrajaya Lot 4C11 Stack: STACK 09
Type : Vertical Stack Pipe (Stack 09 to SP-B3/2/a&b) Date : 12-Oct-22

Node Floor FV SDU taps Flow 1 Total Pipe Proposed


No No Level urinal Cumulative Flow 1& 2 Size pipe size
l/s l/s l/s mm mm
Discharge unit / Flowrate 0.002505 0.002505 0.167000

1 C 01 to C 00 to SP-B3/2/a&b 0 2.171 2.17 75 80


2 C 02 to C 01 Level B3 1 0.167 2.171 2.17 75 80
3 C 03 to C 02 Level B2 1 0.167 2.004 2.00 65 80
4 C 04 to C 03 Level B1 1 0.167 1.837 1.84 65 80
5 C 05 to C 04 Level G 1 0.167 1.670 1.67 65 80
6 C 06 to C 05 Level 1 1 0.167 1.503 1.50 65 80
7 C 07 to C 06 Level 2 1 0.167 1.336 1.34 65 80
8 C 08 to C 07 Level 3 1 0.167 1.169 1.17 50 80
9 C 09 to C 08 Level 4 1 0.167 1.002 1.00 50 80
10 C 10 to C 09 Level 5 1 0.167 0.835 0.84 50 80
11 C 11 to C 10 Level 6 1 0.167 0.668 0.67 50 80
12 C 12 to C 11 Level 7 1 0.167 0.501 0.50 50 80
13 C 13 to C 12 Level 8 1 0.167 0.334 0.33 50 80
14 C 14 to C 13 Level 9 1 0.167 0.167 0.17 50 80

Total: 0 0 13

Minimum stack pipe size shall be accordance to BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : STACK 09 - by Tzelin Lee


Sanitary Pipe Sizing to BS5572
Location: (AHU 3)
Project : : Putrajaya Lot 4C11 Stack: STACK 10
Type : Vertical Stack Pipe (Stack 10 to Ext. Drain) Date : 12-Oct-22

Node Floor FV SDU taps Flow 1 Total Pipe Proposed


No No Level urinal Cumulative Flow 1& 2 Size pipe size
l/s l/s l/s mm mm
Discharge unit / Flowrate 0.002505 0.002505 0.167000

1 A 01 to A 00 to External 0 1.837 1.84 65 80


2 A 02 to A 01 Level B3 1 0.167 1.837 1.84 65 80
3 A 03 to A 02 Level B2 1 0.167 1.670 1.67 65 80
4 A 04 to A 03 Level B1 1 0.167 1.503 1.50 65 80
5 A 05 to A 04 Level G 1 0.167 1.336 1.34 65 80
6 A 06 to A 05 Level 1 1 0.167 1.169 1.17 50 80
7 A 07 to A 06 Level 2 1 0.167 1.002 1.00 50 80
8 A 08 to A 07 Level 3 1 0.167 0.835 0.84 50 80
9 A 09 to A 08 Level 4 1 0.167 0.668 0.67 50 80
10 A 10 to A 09 Level 5 1 0.167 0.501 0.50 50 80
11 A 11 to A 10 Level 6 1 0.167 0.334 0.33 50 80
12 A 12 to A 11 Level 7 1 0.167 0.167 0.17 50 80

Total: 0 0 11

Minimum stack pipe size shall be accordance to BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : STACK 10 - by Tzelin Lee


Sanitary Pipe Sizing to BS5572
Location: (AHU 4)
Project : : Putrajaya Lot 4C11 Stack: STACK 11
Type : Vertical Stack Pipe (Stack 11 to Ext. Drain) Date : 12-Oct-22

Node Floor FV SDU taps Flow 1 Total Pipe Proposed


No No Level urinal Cumulative Flow 1& 2 Size pipe size
l/s l/s l/s mm mm
Discharge unit / Flowrate 0.002505 0.002505 0.167000

1 A 01 to A 00 to External 0 1.837 1.84 65 80


2 A 02 to A 01 Level B3 1 0.167 1.837 1.84 65 80
3 A 03 to A 02 Level B2 1 0.167 1.670 1.67 65 80
4 A 04 to A 03 Level B1 1 0.167 1.503 1.50 65 80
5 A 05 to A 04 Level G 1 0.167 1.336 1.34 65 80
6 A 06 to A 05 Level 1 1 0.167 1.169 1.17 50 80
7 A 07 to A 06 Level 2 1 0.167 1.002 1.00 50 80
8 A 08 to A 07 Level 3 1 0.167 0.835 0.84 50 80
9 A 09 to A 08 Level 4 1 0.167 0.668 0.67 50 80
10 A 10 to A 09 Level 5 1 0.167 0.501 0.50 50 80
11 A 11 to A 10 Level 6 1 0.167 0.334 0.33 50 80
12 A 12 to A 11 Level 7 1 0.167 0.167 0.17 50 80

Total: 0 0 11

Minimum stack pipe size shall be accordance to BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : STACK 11 - by Tzelin Lee


Sanitary Pipe Sizing to BS5572
Location: (AHU 1)
Project : : Putrajaya Lot 4C11 Stack: STACK 12
Type : Vertical Stack Pipe (Stack 12 to Ext. Drain) Date : 12-Oct-22

Node Floor FV SDU taps Flow 1 Total Pipe Proposed


No No Level urinal Cumulative Flow 1& 2 Size pipe size
l/s l/s l/s mm mm
Discharge unit / Flowrate 0.002505 0.002505 0.167000

1 A 01 to A 00 to External 0 2.171 2.17 75 80


2 A 02 to A 01 Level B3 1 0.167 2.171 2.17 75 80
3 A 03 to A 02 Level B2 1 0.167 2.004 2.00 65 80
4 A 04 to A 03 Level B1 1 0.167 1.837 1.84 65 80
5 A 05 to A 04 Level G 1 0.167 1.670 1.67 65 80
6 A 06 to A 05 Level 1 1 0.167 1.503 1.50 65 80
7 A 07 to A 06 Level 2 1 0.167 1.336 1.34 65 80
8 A 08 to A 07 Level 3 1 0.167 1.169 1.17 50 80
9 A 09 to A 08 Level 4 1 0.167 1.002 1.00 50 80
10 A 10 to A 09 Level 5 1 0.167 0.835 0.84 50 80
11 A 11 to A 10 Level 6 1 0.167 0.668 0.67 50 80
12 A 12 to A 11 Level 7 1 0.167 0.501 0.50 50 80
13 A 13 to A 12 Level 8 1 0.167 0.334 0.33 50 80
14 A 14 to A 13 Level 9 1 0.167 0.167 0.17 50 80

Total: 0 0 13

Minimum stack pipe size shall be accordance to BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : STACK 12 - by Tzelin Lee


Sanitary Pipe Sizing to BS5572
Location: (AHU 2)
Project : : Putrajaya Lot 4C11 Stack: STACK 13
Type : Vertical Stack Pipe (Stack 13 to Ext. Drain) Date : 12-Oct-22

Node Floor FV SDU taps Flow 1 Total Pipe Proposed


No No Level urinal Cumulative Flow 1& 2 Size pipe size
l/s l/s l/s mm mm
Discharge unit / Flowrate 0.002505 0.002505 0.167000

1 A 01 to A 00 to External 0 2.171 2.17 75 80


2 A 02 to A 01 Level B3 1 0.167 2.171 2.17 75 80
3 A 03 to A 02 Level B2 1 0.167 2.004 2.00 65 80
4 A 04 to A 03 Level B1 1 0.167 1.837 1.84 65 80
5 A 05 to A 04 Level G 1 0.167 1.670 1.67 65 80
6 A 06 to A 05 Level 1 1 0.167 1.503 1.50 65 80
7 A 07 to A 06 Level 2 1 0.167 1.336 1.34 65 80
8 A 08 to A 07 Level 3 1 0.167 1.169 1.17 50 80
9 A 09 to A 08 Level 4 1 0.167 1.002 1.00 50 80
10 A 10 to A 09 Level 5 1 0.167 0.835 0.84 50 80
11 A 11 to A 10 Level 6 1 0.167 0.668 0.67 50 80
12 A 12 to A 11 Level 7 1 0.167 0.501 0.50 50 80
13 A 13 to A 12 Level 8 1 0.167 0.334 0.33 50 80
14 A 14 to A 13 Level 9 1 0.167 0.167 0.17 50 80

Total: 0 0 13

Minimum stack pipe size shall be accordance to BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : STACK 13 - by Tzelin Lee


Sanitary Pipe Sizing to BS5572

Project : : Putrajaya Lot 4C11 Stack: STACK 14


Type : Vertical Stack Pipe for Pantry 1 Date : 12-Oct-22

Node Floor FV basin ablution sink Discharge Unit Flow 1 FV SDU taps Flow 2 Total Pipe Proposed
No No Level WC tap Cumulative urinal Cumulative Flow 1& 2 Size pipe size
l/s l/s l/s l/s mm mm
Discharge unit / Flowrate 14 3 3 13 0.002505 0.002505 0.001002

1 P 00 to P 01 2 1 13 78 4.43 0 0.000 4.43 90 100


2 P 01 to P 02 3 1 13 65 4.39 0 0.000 4.39 90 100
3 P 02 to P 03 4 1 13 52 4.34 0 0.000 4.34 90 100
4 P 03 to P 04 5 1 13 39 4.30 0 0.000 4.30 90 100
5 P 04 to P 05 6 1 13 26 4.25 0 0.000 4.25 90 100
6 P 05 to P 06 7 1 13 13 4.21 0 0.000 4.21 90 100

Total: 0 0 0 6 0 0 0 25.93

Minimum stack pipe size shall be accordance to BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : STACK 14 (Pantry1) - by Tzelin Lee


Sanitary Pipe Sizing to BS5572

Project : : Putrajaya Lot 4C11 Stack: STACK 15


Type : Vertical Stack Pipe for Pantry 2 Date : 12-Oct-22

Node Floor FV basin ablution sink Discharge Unit Flow 1 FV SDU taps Flow 2 Total Pipe Proposed
No No Level WC tap Cumulative urinal Cumulative Flow 1& 2 Size pipe size
l/s l/s l/s l/s mm mm
Discharge unit / Flowrate 14 3 3 13 0.002505 0.002505 0.001002

1 P 00 to P 01 2 1 13 104 4.53 0 0.000 4.53 90 100


2 P 01 to P 02 3 1 13 91 4.48 0 0.000 4.48 90 100
3 P 02 to P 03 4 1 13 78 4.43 0 0.000 4.43 90 100
4 P 03 to P 04 5 1 13 65 4.39 0 0.000 4.39 90 100
5 P 04 to P 05 6 1 13 52 4.34 0 0.000 4.34 90 100
6 P 05 to P 06 7 1 13 39 4.30 0 0.000 4.30 90 100
7 P 06 to P 07 8 1 13 26 4.25 0 0.000 4.25 90 100
8 P 07 to P 08 9 1 13 13 4.21 0 0.000 4.21 90 100

Total: 0 0 0 8 0 0 0 34.93

Minimum stack pipe size shall be accordance to BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : STACK 15 (Pantry2) - by Tzelin Lee


Sanitary Pipe Sizing to BS5572

Project : : Putrajaya Lot 4C11 Stack: STACK 16


Type : Vertical Stack Pipe (Stack 14/15 to Manhole 1) Date : 12-Oct-22

Node Floor FV basin ablution sink Discharge Unit Flow 1 FV SDU taps Flow 2 Total Pipe Proposed
No No Level WC tap Cumulative urinal Cumulative Flow 1& 2 Size pipe size
l/s l/s l/s l/s mm mm
Discharge unit / Flowrate 14 3 3 13 0.002505 0.002505 0.001002

1 S 01 to S 00 Manhole 1 0 182 4.80 0 0.105 4.90 90 100


2 S 02 to S 01 =>Stack 15 8 104 182 4.80 0 0.105 4.90 90 100
3 S 03 to S 02 Stack 14 6 78 78 4.43 18 0 60 0.10521 0.105 4.54 90 100

Total: 0 0 0 14 18 0 60

Minimum stack pipe size shall be accordance to BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : STACK 16 - by Tzelin Lee


Sanitary Pipe Sizing to BS5572

Project : : Putrajaya Lot 4C11 Stack: STACK 17


Type : Vertical Stack Pipe (Stack 17) Date : 12-Oct-22

Node Floor FV basin ablution sink Discharge Unit Flow 1 FV SDU taps Flow 2 Total Pipe Proposed
No No Level WC tap Cumulative urinal Cumulative Flow 1& 2 Size pipe size
l/s l/s l/s l/s mm mm
Discharge unit / Flowrate 14 3 3 13 0.002505 0.002505 0.001002

1 S 01 to S 00 Manhole 1 0 310 5.24 0 0.014 5.26 90 150


2 S 02 to S 01 Sewer 0 310 5.24 0 0.014 5.26 90 150
3 S 03 to S 02 =>Retail/Kiosk 6 7 109 310 5.24 1 0.001 0.014 5.26 90 150
4 S 04 to S 03 Ground 12 11 201 201 4.86 5 0.01253 0.013 4.88 90 150

Total: 12 17 0 7 5 0 1

Minimum stack pipe size shall be accordance to BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : STACK 17 - by Tzelin Lee


Sanitary Pipe Sizing to BS5572

Project : : Putrajaya Lot 4C11 Stack: STACK 18


Type : Vertical Stack Pipe (Stack 18) Date : 12-Oct-22

Node Floor basin ablution shower sink Discharge Unit Flow 1 FV SDU taps Flow 2 Total Pipe Proposed
No No Level tap Cumulative urinal Cumulative Flow 1& 2 Size pipe size
l/s l/s l/s l/s mm mm
Discharge unit / Flowrate 3 3 1 13 0.002505 0.002505 0.001002

1 S 01 to S 00 Stack 20 0 61 4.38 0 0.000 4.38 90 100


2 S 02 to S 01 Basement 1 0 61 4.38 0 0.000 4.38 90 100
3 S 03 to S 02 F&B15/café 3 3 48 61 4.38 0 0.000 4.38 90 100
4 S 04 to S 03 B. Suite 3 1 13 13 4.21 0 0.000 4.21 90 100

Total: 3 0 0 4 0 0 0

Minimum stack pipe size shall be accordance to BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : STACK 18 - by Tzelin Lee


Sanitary Pipe Sizing to BS5572

Project : : Putrajaya Lot 4C11 Stack: STACK 19


Type : Vertical Stack Pipe (Stack 19) Date : 12-Oct-22

Node Floor basin ablution shower sink Discharge Unit Flow 1 FV SDU taps Flow 2 Total Pipe Proposed
No No Level tap Cumulative urinal Cumulative Flow 1& 2 Size pipe size
l/s l/s l/s l/s mm mm
Discharge unit / Flowrate 3 3 1 13 0.002505 0.002505 0.001002

1 S 01 to S 00 Sewer 0 74 4.42 0 0.000 4.42 90 100


2 S 02 to S 01 =>Refuse 0 74 4.42 0 0.000 4.42 90 100
3 S 03 to S 02 =>Stack 18 3 0 0 4 61 74 4.42 0 0.000 4.42 90 100
4 S 04 to S 03 Basement 1 0 13 4.21 0 0.000 4.21 90 100
5 S 05 to S 04 F&B17 1 13 13 4.21 0 0.000 4.21 90 100

Total: 3 0 0 5 0 0 0

Minimum stack pipe size shall be accordance to BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : STACK 19 - by Tzelin Lee


Sanitary Pipe Sizing to BS5572

Project : : Putrajaya Lot 4C11 Stack: STACK 20


Type : Vertical Stack Pipe (Stack 20) Date : 12-Oct-22

Node Floor basin ablution shower sink Discharge Unit Flow 1 FV SDU taps Flow 2 Total Pipe Proposed
No No Level tap Cumulative urinal Cumulative Flow 1& 2 Size pipe size
l/s l/s l/s l/s mm mm
Discharge unit / Flowrate 3 3 1 13 0.002505 0.002505 0.001002

1 S 01 to S 00 Sewer 0 87 4.47 0 0.000 4.47 90 100


2 S 02 to S 01 =>Stack 19/18 3 0 0 5 74 87 4.47 0 0.000 4.47 90 100
3 S 03 to S 02 Basement 1 0 13 4.21 0 0.000 4.21 90 100
4 S 04 to S 03 F&B12 1 13 13 4.21 0 0.000 4.21 90 100

Total: 3 0 0 6 0 0 0

Minimum stack pipe size shall be accordance to BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : STACK 20 - by Tzelin Lee


Sanitary Pipe Sizing to BS5572

Project : : Putrajaya Lot 4C11 Stack: STACK 21


Type : Vertical Stack Pipe (Stack 21) Date : 12-Oct-22

Node Floor FV basin ablution sink Discharge Unit Flow 1 FV SDU taps Flow 2 Total Pipe Proposed
No No Level WC tap Cumulative urinal Cumulative Flow 1& 2 Size pipe size
l/s l/s l/s l/s mm mm
Discharge unit / Flowrate 14 3 3 13 0.002505 0.002505 0.001002

1 S 01 to S 00 Manhole 1 0 415 5.60 0 0.040 5.64 100 150


2 S 02 to S 01 Ground 12 11 201 415 5.60 5 0.01253 0.040 5.64 100 150
3 S 03 to S 02 Level 1 12 11 201 214 4.91 5 15 0.02756 0.028 4.94 90 150
4 S 04 to S 03 B. Suite 13 1 13 13 4.21 0 0.000 4.21 90 150

Total: 24 22 0 1 10 0 15

Minimum stack pipe size shall be accordance to BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : STACK 21 - by Tzelin Lee


Sanitary Pipe Sizing to BS5572

Project : : Putrajaya Lot 4C11 Stack: STACK 21


Type : Vertical Stack Pipe (Stack 21) Date : 12-Oct-22

Node Floor FV basin ablution sink Discharge Unit Flow 1 FV SDU taps Flow 2 Total Pipe Proposed
No No Level WC tap Cumulative urinal Cumulative Flow 1& 2 Size pipe size
l/s l/s l/s l/s mm mm
Discharge unit / Flowrate 14 3 3 13 0.002505 0.002505 0.001002

1 S 01 to S 00 Ground 1 13 35 4.28 0 0.000 4.28 90 150


2 S 02 to S 01 Ground 1 13 22 4.24 0 0.000 4.24 90 150
3 S 03 to S 02 Ground 1 3 9 4.19 0 0.000 4.19 90 150
4 S 04 to S 03 Ground 1 3 6 4.18 0 0.000 4.18 90 150
5 S 05 to S 04 Ground 1 3 3 4.17 0 0.000 4.17 90 150

Total: 0 3 0 2 0 0 0

Minimum stack pipe size shall be accordance to BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : Cafeteria - by Tzelin Lee


Sanitary Pipe Sizing to BS5572

Project : : Putrajaya Lot 4C11 Stack: STACK F&B


Type : Vertical Stack Pipe for F&B Date : 12-Oct-22

Node Floor FV basin ablution sink Discharge Unit Flow 1 FV SDU taps Flow 2 Total Pipe Proposed
No No Level WC tap Cumulative urinal Cumulative Flow 1& 2 Size pipe size
l/s l/s l/s l/s mm mm
Discharge unit / Flowrate 14 3 3 13 0.002505 0.002505 0.001002

1 P 00 to P 01 1 1 13 13 4.21 0 0.000 4.21 90 100

Total: 0 0 0 1 0 0 0 4.21

Minimum stack pipe size shall be accordance to BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : F&B - by Tzelin Lee


Sanitary Pipe Sizing to BS5572

Project : : Putrajaya Lot 3C4 Stack: STACK 02


Type : Vertical Stack Pipe (STACK 02 to MH17a) Date : 12-Oct-22

Node Floor FV basin ablution shower sink Discharge Unit Flow 1 FV SDU tap Flow 2 Total Pipe Proposed
No No Level WC tap Cumulative urinal Cumulative Flow 1& 2 Size pipe size
l/s l/s l/s l/s mm mm
Discharge unit / Flowrate 14 3 3 1 13 0.002505 0.002505 0.001002

1 S 01 to S 00 G (B) #VALUE! #VALUE! 0.000 0.000 #VALUE! #VALUE! 150


2 S 02 to S 01 STACK 0910 0 0 4.16 0.000 0.000 4.16 90 150
3 S 03 to S 02 1 (B) 0 0 4.16 0.000 0.000 4.16 90 150
4 S 04 to S 03 2 (B) 0 0 4.16 0.000 0.000 4.16 90 150
5 S 05 to S 04 3 (B) 0 0 4.16 0.000 0.000 4.16 90 150
6 S 06 to S 05 4 (B) 0 0 4.16 0.000 0.000 4.16 90 150
7 S 07 to S 06 5 (B) 0 0 4.16 0.000 0.000 4.16 90 150
8 S 08 to S 07 6 (B) 0 0 4.16 0.000 0.000 4.16 90 150
9 S 09 to S 08 7 (B) 0 0 4.16 0.000 0.000 4.16 90 150
10 S 10 to S 09 8 (B) 0 0 4.16 0.000 0.000 4.16 90 150
11 S 11 to S 10 9 (B) 0 0 4.16 0.000 0.000 4.16 90 150

Minimum stack pipe size shall be accordance to BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : (SampleSTACK XX) - by Tzelin Lee


Sanitary Pipe Sizing to BS5572

Project : : Putrajaya Lot 3C4 Location:


Type : Branch Waste Pipe Date : 12-Oct-22

Node No of Fittings Discharge Unit Minimum Proposed Remarks


No No Shower Long sink basin taps At each Cumulative Pipe Size pipe size
bath Node mm mm
Discharge Unit per fitting 1 17 13 3 1

Stalls
1 Xa 01 to Xa 00 1 13 78 75 75
2 Xa 02 to Xa 01 1 13 65 75 75
3 Xa 03 to Xa 02 1 13 52 75 75
4 Xa 04 to Xa 03 1 13 39 75 75
5 Xa 05 to Xa 04 1 13 26 50 50
6 Xa 06 to Xa 05 1 13 13 50 50

Minimum soil/waste pipe size shall be accordance to Table 8 : BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : (Sample)Stall - by Tzelin Lee


Sanitary Pipe Sizing to BS5572
Location: Level 1 (A)
Project : : Putrajaya Lot 3C4 Stack: ST
Type : Branch Waste Pipe Date : 12-Oct-22

Node No of Fittings Discharge Unit Minimum Proposed Remarks


No No Shower Long sink basin taps At each Cumulative Pipe Size pipe size
bath Node mm mm
Discharge Unit per fitting 1 17 13 3 1

L1A Male & Female


1 Xa 01 to Xa 00 1 1 24 50 50
2 Xa 02 to Xa 01 1 1 23 50 50
3 Xa 03 to Xa 02 1 1 22 50 50
4 Xa 04 to Xa 03 1 1 21 50 50
5 Xa 05 to Xa 04 1 1 20 50 50
6 Xa 06 to Xa 05 1 1 19 50 50
7 Xa 07 to Xa 06 3 9 18 50 50
8 Xa 08 to Xa 07 1 3 9 50 50
9 Xa 09 to Xa 08 1 3 6 40 40
10 Xa 10 to Xa 09 1 3 3 40 40

Minimum soil/waste pipe size shall be accordance to Table 8 : BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : (Sample)1A W - by Tzelin Lee


Sanitary Pipe Sizing to BS5572
Location: Level 1 (A)
Project : : Putrajaya 3C4 Stack: ST
Type : Branch Soil Pipe Date : 12-Oct-22

Node No of Fittings Discharge Unit Minimum Proposed Remarks


No No FV FV SDU sink basin taps At each Cuulative Pipe Size pipe size
WC urinal Node mm mm
Discharge Unit per fitting 14 1 1 13 3 1

L1A Male & Female


1 Xb 01 to Xb 00 1 14 86 75 75
2 Xb 02 to Xb 01 1 14 72 75 75
3 Xb 03 to Xb 02 2 2 58 75 75
4 Xb 04 to Xb 03 1 14 56 75 75
5 Xb 05 to Xb 04 1 14 42 75 75
6 Xb 06 to Xb 05 1 14 28 65 65
7 Xb 07 to Xb 06 1 14 14 50 50

Minimum stack pipe size shall be accordance to BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : (Sample)1A S - by Tzelin Lee


Sanitary Pipe Sizing to BS5572
Location: Level 2, 4, 6, 8 (A)
Project : : Putrajaya Lot 3C4 Stack: ST
Type : Branch Waste Pipe Date : 12-Oct-22

Node No of Fittings Discharge Unit Minimum Proposed Remarks


No No Ablution Shower Long sink basin taps At each Cumulative Pipe Size pipe size
Tap bath Node mm mm
Discharge Unit per fitting 3 1 17 13 3 1

L2,4,6,8A Male & Female


1 Xa 01 to Xa 00 6 18 49 75 75
2 Xa 02 to Xa 01 1 1 31 65 65
3 Xa 03 to Xa 02 1 1 30 65 65
4 Xa 04 to Xa 03 1 1 29 65 65
5 Xa 05 to Xa 04 1 1 28 65 65
6 Xa 06 to Xa 05 1 1 27 65 65
7 Xa 07 to Xa 06 1 1 26 50 50
8 Xa 08 to Xa 07 4 12 25 50 50
9 Xa 09 to Xa 08 3 9 13 50 50
10 Xa 10 to Xa 09 1 1 4 40 40
11 Xa 11 to Xa 10 1 3 3 40 40

Minimum soil/waste pipe size shall be accordance to Table 8 : BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : (Sample)2468A W - by Tzelin Lee


Sanitary Pipe Sizing to BS5572
Location: Level 2, 4, 6, 8 (A)
Project : : Putrajaya 3C4 Stack: ST
Type : Branch Soil Pipe Date : 12-Oct-22

Node No of Fittings Discharge Unit Minimum Proposed Remarks


No No FV FV SDU sink basin taps At each Cuulative Pipe Size pipe size
WC urinal Node mm mm
Discharge Unit per fitting 14 1 1 13 3 1

L2,4,6,8A Male and Female


1 Xb 01 to Xb 00 1 14 116 90 90
2 Xb 02 to Xb 01 1 14 102 90 90
3 Xb 03 to Xb 02 3 3 88 75 75
4 Xb 04 to Xb 03 1 14 85 75 75
5 Xb 05 to Xb 04 1 14 71 75 75
6 Xb 06 to Xb 05 1 1 57 75 75
7 Xb 07 to Xb 06 1 14 56 75 75
8 Xb 08 to Xb 07 1 14 42 75 75
9 Xb 09 to Xb 08 1 14 28 65 65
10 Xb 10 to Xb 09 1 14 14 50 50

Minimum stack pipe size shall be accordance to BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : |(Sample)2468A S - by Tzelin Lee


Sanitary Pipe Sizing to BS5572

Project : : Putrajaya 3C4 Stack: ST


Type : Branch Soil Pipe Date : 12-Oct-22

Node No of Fittings Discharge Unit Minimum Proposed Remarks


No No FV FV SDU sink basin taps At each Cuulative Pipe Size pipe size
WC urinal Node mm mm
Discharge Unit per fitting 14 1 1 13 3 1

Calculate
1 Yb 01 to Yb 00 0 130 100 90
2 Yb 02 to Yb 01 0 130 100 75
3 Yb 03 to Yb 02 0 130 100 75
4 Yb 04 to Yb 03 5 65 130 100 75
5 Yb 05 to Yb 04 1 13 65 75 75
6 Yb 06 to Yb 05 1 13 52 75 75
7 Yb 07 to Yb 06 1 13 39 75 65
8 Yb 08 to Yb 07 1 13 26 50 50
9 Yb 09 to Yb 08 1 13 13 50 32

Minimum stack pipe size shall be accordance to BS5572 : 1994


All fittings discharge units <1 in BS5572 : 1994 shall be taken as 1

618570549.xls : Calculate - by Tzelin Lee


mix curve
no wc w wc
lu l/s lu l/s
10 1.2 100 4
53 2 260 5
90 2.28 900 8
400 5 5000 20
20000 49
Design flow(l/sec)

Chart Title

60

50
f(x) = − 6.37048590602527E-08 x² + 0.00351559098368233 x + 4.16233806040226
40
w WC
30 Polynomial (w
WC)

20

10

0
0 5000 10000 15000 20000 25000
loading( in discharge units)
Design flow(l/sec)

Chart Title

5
f(x) = − 1.35790431331787E-05 x² + 0.0151686411550744 x + 1.1034700071014
4
No WC
3 Polynomial (No
WC)

0
0 50 100 150 200 250 300 350 400 450
loading( in discharge units)

618570549.xls : Equation - by Tzelin Lee


sdu capacity = 1.98igpm as per supplier catalogue
= 0.15 l/s < 1 LU
Use 1 LU
Supplier catalogue pipe size = 32m

Assumption : bidet and ablution taps same as spray tap basin discharge

Size Gradient angle Nearest


angle
32 1 20 2.86 2.5
40 1 20 2.86 2.5
50 1 20 2.86 2.5
75 1 30 1.91 1.25
90 1 40 1.43 1.25
100 1 40 1.43 1.25
150 1 60 0.95 0.5
200 1 100 0.57 0.5

No Fittings BS5572 VyC Proposal Probability Remarks


MID Discharge MID Discharge of discharge
min unit min unit

1 9 litre WC 10 14 10 14
2 Urinal Add 0.15 l/s x prob. Add 0.15 l/s x prob. 0.0167
3 SDU none Add 0.15 l/s x prob. 0.0167
4 Sink 10 13 10 13
5 Basin 10 13 10 3
6 Ab tap none 10 3
7 Bidet tap not required Add 0.06 l/s x prob. 0.0167 all WC comes with a built in Bidet, hence bidet taps are redundant
Maximum number of discharge units allowed
on branch discharge pipes

Size Gradient Discharge units


mm degree
32 2.5 1
40 2.5 8
50 2.5 26
65 1.25 35
75 1.25 100
90 0.5 120
100 0.5 230
125 0.5 780
150 0.5 2000