1 Event Menu
In order to simplify installation and maintenance the DCSS records all unusual events as a
persistent logging. The events are classified using the following convention:
Example: E39
Event Class:
I : Information only:
Results from normal operation. For example logging of
power up events, reversal operation etc.
E: Maintenance request:
Serious event, performance degradation expected. Maintenance required. For example:
3WireComFail.
History:
Shows the events in the order of their appearance. An included logging time stamp gives
the relation to the present time.
Actual:
Non persistent logging of up to 16 very last events, starting with the oldest event, logging
time stamp included. Additional information can be displayed on the SVTOOL by pressing
key: shift 3
EvLog:
Amount of occurrences of each event - logging time stamp included. Representation equals
to DCSS 1-4 loggings.
Del:
Deletes the logged events - clear memory for new logging period.
No.: :GAA30328BAA_REF
OTIS Software Basic Data
SCN. :GAA30328BAA
2 Event Description
Class No. Event name Event Description
I 01 Start of Log Entry indicating a new Log-Start after deleting the previous log-
ging
W 02 Logging Full Event logging memory full
- delete logging to free memory
E 03 Inverter Prot Peak output current greater than 7 A. If this event occurs 3 times
within 120 sec, the DCSS switches into locked mode.
E 04 Motor Protect Motor current was for 10 sec higher than setup limit. If this event
occurs 3 times within 120 sec, the DCSS switches to lock mode.
I 05 ObstaclDetec Door was stalled during closing, the stalled door protection has
been activated more than 10 times in series.
E 06 Encoder Err One or two tracks of the encoder are damaged. DCSS switches
into INI mode. Please check encoder counting in Monitor –
Status menu. Sometimes an error can be logged by blocking the
door run obviously encoder is ok.
Attention:
During INI/Nudg profiles and while the door is creeping before
and after a main profile, encoder errors are not detectable
W 07 Overvoltage DC-Link maximum voltage (450Vdc) exceeded – risk of damage
or lifetime reduction of DCSS package
W 08 Undervoltage Power supply voltage is less than 180Vac – risk of performance
degration
I 09 Power Up Indicates that the DCSS is booting after power down –
power up sequence
E 13 3wireComFail Indicates that the check sequence for the discrete interface failed
three times.
DCSS is set into locked mode – Maintenance required
I 15 Position Err Door runs out of the tolerated end-position range after reaching []
or ][.
I 17 Start Inst Automatic installation started
I 18 Stop Inst Automatic installation stopped by user request
I 20 InstSuccess Automatic installation successful finalized
W 21 Inst failed Automatic installation terminated with error
I 22 New Profiles Indicates that profile setup was modified
I 23 100xReversal X x 100 reversals occurred. Use this information as door mecha-
nism stress indicator
E 24 System Locked DCSS out of order, serious event occurred – maintenance
required. DCSS is de-energized and does not react on com-
mands. Root cause could be:
Motor Protect, InverterProt or 3wireComFail events.
Unlock DCSS performimg power down – power up sequence or
SVTOOL key-sequence ‘shift 5’
W 25 Stalled Door Door stalled during opening operation,
Dcss switches to Ini mode
I 26 OpenTimeout DCSS was not able to open the door within 15 sec
I 27 CloseTimeout DCSS was not able to close the door within 15 sec
I 28 3wireCom Indicates successful discrete I/O check sequence initiated by
Service Tool
I 29 Set Defaults parameters have been reset to the default values
No.: :GAA30328BAA_REF
OTIS Software Basic Data
SCN. :GAA30328BAA
3 Set Up Parameter
Px:OpenRunTime 1500..... ms 3500 To change the open speed only this parameter must
8000 be modified. There is no impact on other parameters.
Px: StartOpnDist 1...150 mm 10 Distance from closed door to startpoint of accel.
Px: StartOpnSpeed 2...10 Hz 4 Speed at the begin of opening run
Px: OpenCrpDist 1...150 mm 20 Creep distance after main profile
Px: OpenCrpSpeed 2...15 Hz 4 Creep speed at end of opening run
Px: ClsRunTime 2500..... ms 3500 To change the close speed only this parameter must
8000 be modified. There is no impact on other parameters.
Px: StartClsDist 1...150 mm 20 Distance from opened door to startpoint of accel.
Px: StartClsSpeed 2...10 Hz 6 Speed at the begin of closing run
Px: ClsCrpDist 1...150 mm 50 Creep distance after main profile
Px: ClsCrpSpeed 2...15 Hz 3 Creep speed at end of closing run
Ix:OpnRunTime 5000 ms 6000* To change the Ini open speed
12000
Ix:ClsRunTime 5000 ms 6000* To change the Ini close speed
12000
Px: NdgClsRunTime 5000...... ms 6000* To change the close nudging speed profile
12000
Px: ClsIdleTorque 10...200 N 50 Force in [N] to hold the door closed at idle state
Px: OpnIdleTorque 10...200 N 60 Force in [N] to hold the door closed at idle state
Profile
2 3 4
1 5
t
Start Creep Main Profile Stop Idle
Creep CLS
Idle OPN
Velocity
Torque
note:
A detailed description of all profile types will be find in the Field Component Manual -
Guidelines
No.: :GAA30328BAA_REF
OTIS Software Basic Data
SCN. :GAA30328BAA
maxMotorCurrent 800....... mA 5000 limit of max. motor current. if limit exceeded 3 times for
6000 more than 10 sec DCSS shuts down and is locked
PassProt Limit 0...100 % 4 sensitivity of stalled door protection in %
StopDistance 30...150 mm 60 reversal stop distance in mm
EndPosRange 10..100 mm 20 tolerated derivation from [] or ][ position in mm
GSM Position 50...500 mm 150 GSM active before ][ in mm
Px:Lock Distance 0...150 mm 50* Position were car & landing doors are closed, but the
lock is still open
Opn Lock Speed 0...10 Hz 5 In order to speed up the unlocking phase set parameter
higher than OpenCreepSpeed
Cls Lock Speed 0...10 Hz 8 In order to speed up the locking phase set parameter
higher than CloseCreepSpeed.
DisabRevDistOpn 0...200 mm 30 reversal is disabled if:
position > doorwidth-DisabRevDistOpn
DisabRevDistCls 20...200 mm 0 reversal is disabled if landing door is less than
DisabRevDistCls before fully closed
* set by automatic learn run
No.: :GAA30328BAA_REF
OTIS Software Basic Data
SCN. :GAA30328BAA
The inputs for the SGS, 2nd PROF and NDG signal can be programmed either as 'high' active or 'low'
active input in the Setup menu ‘ENG’.
No.: :GAA30328BAA_REF
OTIS Software Basic Data
SCN. :GAA30328BAA
note1) SGS function only available with DCSS5 SW Version GAA30328AAE or higher
No.: :GAA30328BAA_REF
OTIS Software Basic Data
SCN. :GAA30328BAA
7 Abbreviations
2/S Telescope Door ( Two Speed Door )
C/O Central Opening Door
DCSS Door Control Subsystem
HSDS High Speed Door System
MCSS Motion Control SubSystem
OCSS Operational Control SubSystem
RAM Random Access Memory
No.: :GAA30328BAA_REF
OTIS Software Basic Data
SCN. :GAA30328BAA
DCSS Mode:
SERVICE DCSS is in Service mode (TCI active), setup and test runs are permitted. The
DCSS executes SVT door commands only.
WORKING DCSS is in normal mode (TCI & TES inactive) and the system is installed. All func-
tionality is available.
Door States
DCSS Inputs
ST1 control signal 1
ST2 control signal 2
ST3 control signal 3
REV Reversal signal, can be EDP or LRD
DOB Door Open Button (only extended 3-Wire interface)
SGS Safety Gate Shoe
TDOB Top of Car Door Open Button
TDCB Top of Car Door Close Button
SO Safe to Open
LRD Light Ray Device
EDP Electronic Door Protector
DCSS Outputs
DOL Door Open Limit Switch
DOS Door (Re-)Opening Signal (due to Passenger Protection)
General:
TCI Top of Car Inspection
EDS Emergency Door Stop
No.: :GAA30328BAA_REF
OTIS Software Basic Data
SCN. :GAA30328BAA
Appendix :
Field-Prof1 (3-3-3-1)
name range Unit Actual description
P1:OpenRunTime 1500..... ms To change the open speed only this parameter must
8000 be modified. There is no impact on other parameters.
P1: StartOpnDist 1...150 mm Distance from closed door to startpoint of accel.
P1: StartOpnSpeed 2...10 Hz Speed at the begin of opening run
P1: OpenCrpDist 1...150 mm Creep distance after main profile
P1: OpenCrpSpeed 2...15 Hz Creep speed at end of opening run
P1: ClsRunTime 2500..... ms To change the close speed only this parameter must
8000 be modified. There is no impact on other parameters.
P1: StartClsDist 1...150 mm Distance from opened door to startpoint of accel.
P1: StartClsSpeed 2...10 Hz Speed at the begin of closing run
P1: ClsCrpDist 1...150 mm Creep distance after main profile
P1: ClsCrpSpeed 2...15 Hz Creep speed at end of closing run
I1:OpnRunTime 5000 ms To change the Ini open speed
12000
I1:ClsRunTime 5000 ms To change the Ini close speed
12000
P1: NdgClsRunTime 5000...... ms To change the close nudging speed profile
12000
P1: ClsIdleTorque 10...200 N Force to hold the door closed at idle state
P1: OpnIdleTorque 10...200 N Force to hold the door closed at idle state
Field-Prof2 (3-3-3-2)
name range Unit Actual description
P2:OpenRunTime 1500..... ms To change the open speed only this parameter must
8000 be modified. There is no impact on other parameters.
P2: StartOpnDist 1...150 mm Distance from closed door to startpoint of accel.
P2: StartOpnSpeed 2...10 Hz Speed at the begin of opening run
P2: OpenCrpDist 1...150 mm Creep distance after main profile
P2: OpenCrpSpeed 2...15 Hz Creep speed at end of opening run
P2: ClsRunTime 2500..... ms To change the close speed only this parameter must
8000 be modified. There is no impact on other parameters.
P2: StartClsDist 1...150 mm Distance from opened door to startpoint of accel.
P2: StartClsSpeed 2...10 Hz Speed at the begin of closing run
P2: ClsCrpDist 1...150 mm Creep distance after main profile
P2: ClsCrpSpeed 2...15 Hz Creep speed at end of closing run
I2:OpnRunTime 5000 ms To change the Ini open speed
12000
I2:ClsRunTime 5000 ms To change the Ini close speed
12000
P2: NdgClsRunTime 5000...... ms To change the close nudging speed profile
12000
P2: ClsIdleTorque 10...200 N Force to hold the door closed at idle state
P2: OpnIdleTorque 10...200 N Force to hold the door closed at idle state
Eng-Prof1 (3-3-4-1)
No.: :GAA30328BAA_REF
OTIS Software Basic Data
SCN. :GAA30328BAA
Eng-Prof2 (3-3-4-2)
name range unit Actual description
Eng-Contrl (3-3-4-3)
name range unit Actual description
Eng-Other (3-3-4-4)
name range unit Actual description
maxMotorCurrent 800....... mA limit of max. motor current. if limit exceeded 3 times for
5000 more than 10 sec DCSS shuts down and is locked
PassProt Limit 0...100 % sensitivity of stalled door protection in %
StopDistance 30...150 mm reversal stop distance in mm
EndPosRange 10..100 mm tolerated derivation from [] or ][ position in mm
GSM Position 50...500 mm GSM active before ][ in mm
P1:Lock Distance 0...150 mm Position where car & landing doors are closed, but the
lock is still open
Opn Lock Speed 0...10 Hz In order to speed up the locking phase set parameter
higher than OpenCreepSpeed
Cls Lock Speed 0...10 Hz In order to speed up the locking phase set parameter
higher than CloseCreepSpeed. To reduce the overall
close time you can increase the parameter up to 8Hz if
the mechanic makes no additional noises
DisabRevDistOpn 0...200 mm reversal is disabled if:
position > doorwidth-DisabRevDistOpn
DisabRevDistCls 20...200 mm reversal is disabled if landing door is less than
DisabRevDistCls before fully closed
No.: :GAA30328BAA_REF
OTIS Software Basic Data
SCN. :GAA30328BAA
Relay (3-3-4-5)
name range unit Acutal description
This table should give a general installation suggestion to help adjusting heavy glass
door types driven with a 200W motor.
1) Fine-adjusting of the torques, which are learned during the installation, to re-
duce the forces at the door panel during closing and to avoid overcurrents.
With reduced forces the Passenger Protection will react much better.